FIRE RISK ASSESSMENT 
The Fire Risk Assessment is kept at the Head Office of Bluezone Ltd. A duplicate should be available on each site. It should be available for audits undertaken by the appropriate enforcement authority. 
Woodberry Manor 
REGULATORY REFORM (FIRE SAFETY) 2005 
Ray Woodberry 
01268 697815 
Type of Fire Risk Assessment 
Block Risk Assessment 
Sleeping Accommodation 
Full Fire Risk Assessment 
Medium - Renew FRA at least every three years 
21 June 2017
UPRN 
Full Address 
Date 
21 June 2014 
Contents 
1. Introduction 
8. Photographs 
The responsible person must take general fire precautions as will ensure so far as is reasonably practicable the safety of any employees and also in relation to relevant persons who are not in their employ take such general fire precautions as may reasonably be required in the circumstances of the case to ensure that the premises are safe. 
Regulatory Reform (Fire Safety) Order 2005 Article 9 requires that every responsible person must make a suitable and sufficient assessment of the risks to which relevant persons are exposed for the purpose of identifying the general fire precautions needed to take to comply with the requirements and prohibitions imposed by or under the order. 
The responsible person (or other person who has to any extent control of the property) must ensure that the duties imposed by the relevant articles of the Regulatory Reform (Fire Safety) Order 2005 are complied with where the matters relate to items within their control. 
The prescribed information is the significant findings of the assessment including the measures which have or will be taken by the responsible person pursuant to the Regulatory Reform (Fire Safety) Order 2005 and any group of persons identified by the assessment as being especially at risk. 
This includes identification of all current significant fire hazards to which relevant persons and others in the area may be exposed. 
The Risk Assessment will prioritise the level of risk associated with the property incorporating existing controlling measures to mitigate any risk 
The Assessment will also advise upon additional control measures that may me implemented to manage the risk in accordance with Article 10 of the Order. 
a. Measures to control sources of ignition 
0 
0 
1. Introduction 
2. Scope and Methodology of Assessment 
3. Identification of Significant Fire Hazards and People at Risk 
4. Existing Fire Safety Measures and Occupancy 
5. Assessment of Fire Risk 
b. Measures to control sources of fuel 
c. Measures to control sources of oxygen 
d. Measures to assist Fire Service 
e. Measures to assist Fire Fighters 
h. Measures for Signs and Notices 
i. Installation, Testing & Maintenance 
j. Management of Procedures & Information 
2. Scope and Methodology of Assessment 
Statutory Requirement 
6. Fire Risk Rating Matrix 
7. Fire Risk Assessment Action Schedule 
This report has been prepared as the written record of the Fire Risk Assessment carried out to the communal areas of this building on behalf of the Landlord, Bluezone Ltd, in accordance with the requirements of the Regulatory Reform (Fire Safety) Order 2005. 
The objectives of the Fire Risk Assessment are to ensure that a suitable and sufficient assessment of the risks to which relevant persons are exposed for the purpose of identifying the general fire precautions he needs to take to comply with the requirements and prohibitions of the Regulatory Reform (Fire Safety) Order 2005. 
f. Measures for Fire Detection and Warning 
g. Measures to assist Means of escape 
A Bluezone Ltd Fire Risk Assessment is not a one off document and is part of a strategic Fire Safety Strategy and Policy implemented to identify, manage and monitor the risks to Bluezone Ltd properties on a regular basis. 
The Fire Risk Assessment will be reviewed under Article 9 (3) of the Order and in direct accordance with Bluezone Ltd review policy and National guidance documentation; this includes but is not restricted to:- 
(a) there is reason to suspect that the Fire Risk Assessment is no longer valid; 
(b) there has been a significant change to which it relates including when the premises, special, technical or organisational measures undergo significant change, extension or conversion. 
(c) Identification of risk following an actual or near miss incident. 
The report is to provide and assessment of the risk to life from a fire within the building and to make recommendations to ensure compliance with the Regulatory Reform (Fire Safety) Order 2005; it does not address the risk to the property or business continuity from fire.
Information contained within the report is based on observations at the time of inspection and details provided by on site personnel. 
To identify the significant fire hazards within the premises checklists are used which consider the particular fire hazard associated with the building and the nature of the occupancy. 
The hazard will consider the items with regard to existing control measures which are either already inherent within the building or implemented through the management procedures. The answers are either Yes / No or Not Applicable (N/A). 
Each hazard is assessed in accordance with the fire risk rating system. This includes consideration of the hazard in terms of the potential to harm (severity) and their likelihood (probability) of occurring. 
In addition a specific risk rating is applied in consideration of the controlling measures in place and subsequently considers the timescales within which the measures should be implemented. 
The Action plan details the significant findings of both technical and procedural measures that should be considered necessary to address the risk identified. It is a register of the remedial and advisory actions to be carried out in accordance with the priorities defined using the fire risk rating system. 
To reduce the risk to an acceptable level all Action Plan items should be addressed. 
The Fire Risk Assessment information is gathered using non invasive physical inspections of the property. Where floor plans are available these have been used utilised and direct conversation or information has been gathered from on-site staff. Digital photographs have also been taken and included for means of identification of locations and hazards 
The new Regulatory Reform (Fire Safety) Order 2005 requires a fire risk assessment to be carried out and the significant findings recorded. The process followed was as follows: 
The building was inspected, hazards were identified and the fire risk categorised as high, medium or low. The existing measures were recorded as well as any recommended action. Where actions have been recommended these are in line with British Standards. 
Hazards included any sources of ignition (sparks, electrical equipment, heat sources etc), dangerous substances (flammable materials, combustible materials, gases etc) and unsatisfactory structural features (absence of fire stopping, ducts and voids and compromised protected routes). Any areas where evacuation of occupants could be compromised were also classed as hazards. 
A high fire risk was categorised in areas where there is likely to be a large number of people or old, young or disabled people. Areas with flammable processes or large quantities of heat or combustible materials were also categorised high risk as well as any areas where structural features would allow the spread of smoke or fire from one part of the building to another. 
A normal fire risk was categorised where a fire is likely to remain localised or to spread slowly enough to allow people to escape to a place of safety or where there is an effective automatic means of detecting and giving warning of fire. 
A low fire risk was categorised where there is minimal risk to life safety and the risk of fire occurring is negligible and the risk of fire, smoke or fumes spreading is negligible. 
Identification of Fire Hazards 
Assessment of Fire Risk 
The Fire Risk Assessment Action Plan 
Information Source
UPRN 
Full Address 
Date 
21 June 2014 
2 
8 
1 
no 
Staircase (element) 
yes 
no 
yes 
yes 
no 
Sole Leaseholder or post 1991 converted or purpose built property 
Maximum number of occupants / residents 
24 
Maximum number of visitors 
120 
Maximum number of sleeping occupants at any one time 
144 
Maximum number of vulnerable occupants at any one time 
24 
Does the tenure include occupants who are:- 
“Disabled” incl mobility impairment, hearing or vision impairment 
unknown 
“Restricted” parents with children 
unknown 
“Sensory Impaired” due to alcohol, drugs or medication 
unknown 
Maximum number of unaccompanied children at any one time 
unknown 
Maximum occupation in remote areas at any one time 
n/a 
Accessible by lift / s 
Tenure of flats / units 
General tenure / occupancy description 
4. Identification of People at Risk 
Number of Flats within block 
Number of direct staircases from corridors 
Is there a lobby approach from the staircases to the flats or within the flats? 
Fully Enclosed / No Borrowed Light / windows 
Semi Enclosed / some Borrowed Light / windows 
Fully Open / with Borrowed Light / windows 
Fully Enclosed / No Borrowed Light / windows 
Semi Enclosed / some Borrowed Light / windows 
Fully Open / with Borrowed Light / windows 
Number of Storeys (incl basement) 
Date of Construction 
Areas not assessed 
Two storey tradditional build premise comprising eight residential flats accessed by two doors front and rear and 
0 
3. Existing Fire Safety Measures and Occupancy (Static data) 
Brief description of building and its construction 
No communal Corridors (flats direct to staircases) 
Corridors (from the staircases) 
1986 
Roof void area 
0
UPRN 
Full Address 
Date 
21 June 2014 
Risk Level 
1 (Low) 
2 
3 (Medium) 
4 
5 (High) 
Probability Level 
1 (Low) 
2 
3 (Medium) 
4 
5 (High) 
Degree of Risk 
Risk Rating Score 
High 
15 – 25 
Medium High 
08 – 12 
Medium 
02 – 06 
Low Risk 
01 
Continuous review 
00 
A Traffic light approach is made in respect of the degree and level of risk, which is also translated into the priority rating for remedial work or recommendations. Timescales given include consideration for practicality and financial impact to Bluezone Ltd when planning their implementation. In order to reduce the risk to an acceptable level it is recommended that all Action Plan items are implemented 
5. Risk Matrix 
Building / Area should not be occupied until risk is reduced. Fatality or total loss of property 
Exposure 
Improbable – no known instances of occurrence <10% 
Essential that efforts are made to reduce the risk; measures to be implemented within set timescales. Serious damage to property 
Considerable resources may have to be allocated to reduce the risk; where a building is occupied urgent action should be undertaken. Permanent injury; permanent damage to property. 
The following risk matrix has been used to prioritise and quantify the individual fire safety deficiencies identified. 
Action / Consequence 
No Further Action is necessary, detailed records needed. No serious injuries, little or no damage to property. 
No major additional controls needed consideration for improvements which have minor cost incurrence. Some injury, remedial works needed to property 
0 
0 
Unlikely – but still possible 10 -30% 
Likely to occur 30 - 50 % 
Will occur frequently 50 - 90% 
Will occur very frequently unless prevented >90% 
Within three years of notification (programmed work) 
Within five years of notification (programmed work) 
Timescale for action 
Within 28 days of notification 
Within six months of notification 
Within one year of notification
UPRN 
Full Address 
Date 
21 June 2014 
some 
no 
yes 
Zero – 1 fire 
yes 
some 
7. Identification of significant Fire Hazards 
Source & location of Ignition 
1 
2 
3 
4 
5 
6 
7 
8 
9 
10 
Other notes 
Source & location of Fuel 
1 
2 
3 
4 
5 
6 
7 
8 
9 
10 
Other notes 
Source and location of oxygen 
1 
2 
3 
4 
5 
Other notes 
Are Estate Management issues being raised and managed effectively? 
Is there automatic smoke or fire detection present to the building ? 
Fixed lighting equipment 
0 
0 
Have flat / unit own doors been upgraded to 30 min fire rated? 
Is Emergency Lighting installed throughout? 
6. Existing Fire Safety Measures and Occupancy (changeable data) 
Is the Means of Escape kept clear at all times? 
How Many fires have occurred within the block within the past five 
Natural airflow
UPRN 
Full Address 
Date 
21 June 2014 
Item 
Measures to control Source of Ignition 
N/A 
Yes 
No 
Risk Level (1-5) 
Probability Level (1- 
Rating (RLxP) 
Priority 
Comments 
Action Point Ref. 
8.1.1 
Are current arrangements for the control of arson suitable and sufficient? 
r 
a 
r 
0 
1 
0 
Continuous review 
None 
8.1.2 
Is Smoking confined to designated areas and “No Smoking” signs displayed as appropriate? 
r 
a 
r 
0 
1 
0 
Continuous review 
None 
8.1.3 
Are suitable arrangements in place for the disposal of “smoking” materials 
r 
r 
a 
2 
3 
6 
Medium Risk 
Evidence that residents dispose of smoking materials at entrance area. 
8.1.3 
8.1.4 
Is there an adequate system adopted for permitting and monitoring hot works operations by outside contractors? 
a 
r 
r 
0 
0 
0 
Continuous review 
None 
8.1.5 
Are arrangements for managing building work and alterations suitable and sufficient? 
r 
a 
r 
0 
1 
0 
Continuous review 
None 
8.1.6 
Are adequate measures in place to guard against malicious ignition? 
r 
a 
r 
0 
2 
0 
Continuous review 
None 
8.1.7 
Are Access control / security systems In place? 
r 
a 
r 
0 
1 
0 
Continuous review 
door entry system not operational 
None 
8. Assessment of Fire Risk 
The following table details the approach that has been taken to assess the individual risk level for each identified hazard / fire safety deficiency. All hazards have been considered with regard to the specific relevant people affected and the control measures necessary to contend with the risk. 
0 
0
UPRN 
Full Address 
Date 
21 June 2014 
Measures to control Source of Fuel 
N/A 
Yes 
No 
Risk Level (1-5) 
Probability Level (1- 
Rating (RLxP) 
Priority 
Comments 
Action Point Ref. 
8.2.1 
Have all areas of flammable wall and ceiling Linings been removed, covered, or treated to reduce the spread of flame across their 
r 
a 
r 
0 
1 
0 
Continuous review 
None 
8.2.2 
Is the premises free from accumulation of Rubbish, waste paper, and other ignitable materials? 
r 
a 
r 
0 
1 
0 
Continuous review 
None 
8.2.3 
Are adequate arrangements made for the Disposal of waste and rubbish? 
r 
a 
r 
0 
1 
0 
Continuous review 
None 
8.2.4 
Are suitable arrangements in place for storing highly flammable or readily combustible materials not in current use? 
a 
r 
r 
0 
0 
0 
Continuous review 
None 
8.2.5 
Are storage areas for highly flammable and explosive materials identified by hazard warning signs 
a 
r 
r 
0 
0 
0 
Continuous review 
None 
8.2.6 
Are the housekeeping arrangements for communal areas sufficiently controlled? 
r 
a 
r 
0 
1 
0 
Continuous review 
None 
8.2.7 
Are the arrangements for use of equipment and machinery suitable and sufficient? 
a 
r 
r 
0 
0 
0 
Continuous review 
None 
8.2.8 
Is the existing building layout and construction appropriate, suitable and sufficient? 
r 
a 
r 
0 
1 
0 
Continuous review 
None 
8.2.9 
Are areas of high fire risk and loading provided with physical separation from the remainder of the premises? 
r 
a 
r 
0 
2 
0 
Continuous review 
None 
8.2.10 
Is the provision of means for restricting spread of fire and smoke in common areas suitable and sufficient? 
r 
a 
r 
0 
1 
0 
Continuous review 
None 
8.2.11 
Is the provision of means for restricting fire and smoke within access duct /chutes etc. suitable and sufficient? 
a 
r 
r 
0 
0 
0 
Continuous review 
None 
8.2.12 
Is the provision of means for restricting fire and smoke from entering into individual flats / units / areas / linked or attached properties suitable and sufficient? 
r 
a 
r 
0 
1 
0 
Continuous review 
None 
Measures to control Source of Oxygen 
N/A 
Yes 
No 
Risk Level (1-5) 
Probability Level (1- 
Rating (RLxP) 
Priority 
Comments 
Action Point Ref. 
8.3.1 
Are the communal opening windows operational? 
r 
a 
r 
0 
1 
0 
Continuous review 
None 
8.3.2 
Are there smoke vents present – if they are not present are they required / recommended ? 
a 
r 
r 
0 
0 
0 
Continuous review 
None 
8.3.3 
Are air conditioning units present – if they are not present are they required / recommended ? 
a 
r 
r 
0 
0 
0 
Continuous review 
None 
0 
0
UPRN 
Full Address 
Date 
21 June 2014 
Measures to assist fire service 
N/A 
Yes 
No 
Risk Level (1-5) 
Probability Level (1- 
Rating (RLxP) 
Priority 
Comments 
Action Point Ref. 
8.4.1 
Are there suitable access facilities for Fire Service vehicles to access the entire building? 
r 
a 
r 
0 
1 
0 
Continuous review 
None 
8.4.2 
Are Fire Hydrants in suitable proximity of building and clearly visible? 
r 
r 
a 
4 
4 
16 
High Risk 
No visual evidence of hydrants 
8.4.2 
8.4.3 
Does the Emergency Action Plan relate to the Fire & Rescue Service response? 
a 
r 
r 
0 
0 
0 
Continuous review 
None 
8.4.4 
Are the fire fighting lifts clearly identified and appropriate signage fitted? 
a 
r 
r 
0 
0 
0 
Continuous review 
None 
8.4.5 
Are there Dry / Wet Risers present – if they are not present are they required / recommended ? 
a 
r 
r 
0 
0 
0 
Continuous review 
None 
8.4.6 
Are the fire fighting lifts clearly identified and appropriate signage fitted? 
a 
r 
r 
0 
0 
0 
Continuous review 
None 
8.4.7 
Are there sprinklers / suppression systems present – if they are not present are they required / recommended ? 
a 
r 
r 
0 
0 
0 
Continuous review 
None 
8.4.8 
Are there hose reels present – if they are not present are they required / recommended ? 
a 
r 
r 
0 
0 
0 
Continuous review 
None 
8.4.9 
Are fire blankets present – if they are not present are they required / recommended ? 
a 
r 
r 
0 
0 
0 
Continuous review 
None 
8.4.10 
Are there portable fire extinguishers present – if they are not present are they required / recommended ? 
a 
r 
r 
0 
0 
0 
Continuous review 
None 
8.4.11 
Are the portable fire extinguishers clearly visible and accessible with correct signage? 
a 
r 
r 
0 
0 
0 
Continuous review 
None 
8.4.14 
Are the Portable Fire Extinguishers suitable & sufficient for purpose? 
a 
r 
r 
0 
0 
0 
Continuous review 
None 
8.4.15 
Are the Portable Fire Extinguishers clearly visible and accessible? 
a 
r 
r 
0 
0 
0 
Continuous review 
None 
r 
0
UPRN 
Full Address 
Date 
21 June 2014 
Measures for fire detection and warning 
N/A 
Yes 
No 
Risk Level (1-5) 
Probability Level (1- 
Rating (RLxP) 
Priority 
Comments 
Action Point Ref. 
8.4.12 
Is an automatic fire warning system present – or if it is not present is it required or recommended? 
a 
r 
r 
0 
0 
0 
Continuous review 
None 
8.4.13 
Is the property classified as a HMO (House of Multiple Occupancy) within guidelines of Lacors and Housing Act 
a 
r 
r 
0 
0 
0 
Continuous review 
None 
8.5.1 
Does the fire warning system have a named responsible person, who has authority and training to manage the system? 
a 
r 
r 
0 
0 
0 
Continuous review 
None 
8.5.2 
Is the Automatic Fire Detection / warning system suitable and sufficient for the premises? 
a 
r 
r 
0 
0 
0 
Continuous review 
None 
8.5.3 
Are manual call points suitable and sufficiently located and accessible? 
a 
r 
r 
0 
0 
0 
Continuous review 
None 
8.5.3 
Are sounders/klaxons suitable and sufficiently located? 
a 
r 
r 
0 
0 
0 
Continuous review 
None 
8.5.4 
Does the Fire Warning system have a guaranteed power supply? 
a 
r 
r 
0 
0 
0 
Continuous review 
None 
Measures for signs and notices 
N/A 
Yes 
No 
Risk Level (1-5) 
Probability Level (1- 
Rating (RLxP) 
Priority 
Comments 
Action Point Ref. 
8.6.1 
Are all Fire doors fitted with self closing devices suitably and correctly signed 
a 
r 
r 
0 
0 
0 
Continuous review 
None 
8.6.2 
Are all Fire Doors to stores, and cupboards suitably and correctly signed 
r 
a 
r 
0 
1 
0 
Continuous review 
None 
8.6.3 
Are all final exit doors suitably and correctly signed 
r 
a 
r 
0 
1 
0 
Continuous review 
None 
8.6.4 
Are all emergency exits suitably and correctly signed 
r 
a 
r 
0 
1 
0 
Continuous review 
None 
8.6.5 
Are all emergency escape routes suitably and correctly signed? 
r 
a 
r 
0 
1 
0 
Continuous review 
single means of escape from building 
None 
8.6.6 
Are Lifts ( in case of emergency) suitably and correctly signed? 
a 
r 
r 
0 
0 
0 
Continuous review 
None 
8.6.7 
Are Fire Action Notices clearly displayed? 
a 
r 
r 
0 
0 
0 
Continuous review 
None 
8.6.8 
Are electrical warnings clearly displayed 
a 
r 
r 
0 
0 
0 
Continuous review 
None 
0 
0
UPRN 
Full Address 
Date 
21 June 2014 
Measures to assist means of escape 
N/A 
Yes 
No 
Risk Level (1-5) 
Probability Level (1- 
Rating (RLxP) 
Priority 
Comments 
Action Point Ref. 
8.7.1 
Are there a sufficient number of exits from the building, and are they of adequate size for the number of occupants? 
r 
a 
r 
0 
1 
0 
Continuous review 
None 
8.7.2 
Can all emergency / final exit doors be opened easily in single action? 
r 
a 
r 
0 
1 
0 
Continuous review 
None 
8.7.3 
Do means of escape lead directly to a place of safety? 
r 
a 
r 
0 
1 
0 
Continuous review 
None 
8.7.4 
Is the Escape route free from obstructions, slip or trip hazards? 
r 
a 
r 
0 
1 
0 
Continuous review 
None 
8.7.5 
Are the travel distances suitable and sufficient ? 
r 
a 
r 
0 
1 
0 
Continuous review 
None 
8.7.6 
Are the escape routes suitable and sufficient for occupants with impaired mobility ? 
r 
r 
a 
3 
4 
12 
Medium High Risk 
No details provided about private residents with disabilities 
8.7.6 
8.7.7 
Are the escape routes widths and capacities suitable and sufficient ? 
r 
a 
r 
0 
1 
0 
Continuous review 
None 
8.7.8 
Are there alternative exits from inner rooms or basements? 
a 
r 
r 
0 
0 
0 
Continuous review 
None 
8.7.9 
Are the exits from external stairways suitable and sufficient? 
a 
r 
r 
0 
0 
0 
Continuous review 
None 
8.7.10 
Is the means of escape clear of the need to use ladders, hatches or windows? 
r 
a 
r 
0 
1 
0 
Continuous review 
None 
8.7.11 
Is the Means of Escape suitable and sufficient to provide 30 minutes fire resistance? 
r 
a 
r 
0 
1 
0 
Continuous review 
None 
8.7.12 
Is the use of cavity barriers / fire stopping and dampers evident within ducts / suspended ceilings / floors? 
a 
r 
r 
0 
0 
0 
Continuous review 
None 
8.7.13 
Is a suitable and sufficient place of safety (refuge) provided? 
a 
r 
r 
0 
0 
0 
Continuous review 
None 
8.7.14 
Are defined zones on external emergency areas of fire resisting nature, including doors, windows, and walls? 
a 
r 
r 
0 
0 
0 
Continuous review 
None 
8.7.15 
Where roof exits are designated as means of escape is suitable and sufficient access through the door available? 
a 
r 
r 
0 
0 
0 
Continuous review 
None 
8.7.16 
Where roof exits are designated as means of escape is suitable and sufficient lighting / illumination available? 
a 
r 
r 
0 
0 
0 
Continuous review 
None 
8.7.17 
Where roof exits are designated as means of escape is the surface non slip / guarded with a protective barrier? 
a 
r 
r 
0 
0 
0 
Continuous review 
None 
8.7.18 
Are all emergency escape routes suitably illuminated with emergency lighting? 
r 
r 
a 
3 
4 
12 
Medium High Risk 
borrowed lighting available 
8.7.18 
8.7.19 
Does the Emergency Lighting system have a back up power source? 
a 
r 
r 
0 
0 
0 
Continuous review 
None 
8.7.20 
Do all final exit doors open in the direction of escape? 
r 
r 
a 
3 
4 
12 
Medium High Risk 
limited occupation less than 60 persons 
8.7.20 
0 
0
UPRN 
Full Address 
Date 
21 June 2014 
Measures of maintenance for fire safety facilities. Do you regularly inspect, test, report and record in a log book the following? 
N/A 
Yes 
No 
Risk Level (1-5) 
Probability Level (1-5) 
Rating (RLxP) 
Priority 
Comments 
Action Point Ref. 
8.8.1 
All Flat Entrance doors 
a 
r 
r 
0 
0 
0 
Continuous review 
None 
8.8.2 
All Communal doors 
r 
a 
r 
0 
1 
0 
Continuous review 
Doors in poor condition and do not lock securely 
None 
8.8.3 
All Roof Access doors 
a 
r 
r 
0 
0 
0 
Continuous review 
None 
8.8.4 
All intake Cupboard doors 
r 
a 
r 
0 
1 
0 
Continuous review 
None 
8.8.5 
All Store Cupboard doors 
a 
r 
r 
0 
0 
0 
Continuous review 
None 
8.8.6 
Escape Routes 
r 
a 
r 
0 
1 
0 
Continuous review 
None 
8.8.7 
Housekeeping 
r 
a 
r 
0 
1 
0 
Continuous review 
None 
8.8.8 
Compartmentation 
a 
r 
r 
0 
0 
0 
Continuous review 
None 
8.8.9 
Fire Integrity common areas 
r 
a 
r 
0 
1 
0 
Continuous review 
None 
8.8.10 
Emergency Lighting 
a 
r 
r 
0 
0 
0 
Continuous review 
None 
8.8.11 
Fire fighting equipment 
a 
r 
r 
0 
0 
0 
Continuous review 
None 
8.8.12 
Portable Appliances 
a 
r 
r 
0 
0 
0 
Continuous review 
None 
8.8.13 
Electrical installations 
r 
r 
a 
3 
2 
6 
Medium Risk 
no evidence of recent Periodic inspection to electrical system 
8.8.13 
8.8.14 
Fire Alarm / Detection / warning system 
r 
a 
r 
0 
1 
0 
Continuous review 
None 
8.8.15 
Fire Extinguishers 
a 
r 
r 
0 
0 
0 
Continuous review 
None 
8.8.16 
Smoke Vents 
a 
r 
r 
0 
0 
0 
Continuous review 
None 
8.8.17 
Sprinklers / Suppression system 
a 
r 
r 
0 
0 
0 
Continuous review 
None 
8.8.18 
Signs & Notices 
r 
a 
r 
0 
1 
0 
Continuous review 
None 
8.8.19 
Dry / Wet Riser 
a 
r 
r 
0 
0 
0 
Continuous review 
None 
8.8.20 
Lightning Conductors 
a 
r 
r 
0 
0 
0 
Continuous review 
None 
8.8.21 
Access levels 
r 
a 
r 
0 
1 
0 
Continuous review 
None 
8.8.22 
Gas Appliances / systems 
a 
r 
r 
0 
0 
0 
Continuous review 
None 
8.8.23 
Air conditioning units 
a 
r 
r 
0 
0 
0 
Continuous review 
None 
8.8.24 
Hose Reels 
a 
r 
r 
0 
0 
0 
Continuous review 
None 
8.8.25 
Fire Blankets 
a 
r 
r 
0 
0 
0 
Continuous review 
None 
8.8.26 
Presence of a log book 
a 
r 
r 
0 
0 
0 
Continuous review 
None 
0 
0
UPRN 
Full Address 
Date 
21 June 2014 
Item 
Measures for management of information and procedure 
N/A 
Yes 
No 
Risk Level (1-5) 
Probability Level (1- 
Rating (RLxP) 
Priority 
Comments 
Action Point Ref. 
8.9.1 
Is a suitable emergency action plan in place for the purpose of safeguarding residents, occupants and other persons present in the event of a fire? 
r 
r 
a 
5 
4 
20 
High Risk 
No emergency plans on site or issued to occupants 
8.9.1 
8.9.2 
Is the plan premise specific and up to date? 
a 
r 
r 
0 
0 
0 
Continuous review 
None 
8.9.3 
Is there a fully trained and equipped warden nominated to implement the emergency action plan? 
a 
r 
r 
0 
0 
0 
Continuous review 
None 
8.9.4 
Are emergency contacts with external services arranged as necessary with regards to rescue work and fire fighting? 
r 
r 
a 
3 
4 
12 
Medium High Risk 
contact is local fire brigade service 
8.9.4 
8.9.5 
Where two or more organisations share/manage the premise do they cooperate as far as necessary to comply with the RR(FS)O . 
a 
r 
r 
0 
0 
0 
Continuous review 
None 
8.9.6 
Have appropriate procedures been established to evacuate or restrict access to confined spaces or hazardous locations? 
a 
r 
r 
0 
0 
0 
Continuous review 
None 
8.9.7 
Are others who may have caused to visit or work within the property provided with comprehensive information on the measures taken in compliance with the RR(FS)O? 
r 
a 
r 
0 
1 
0 
Continuous review 
None 
8.9.8 
Are occupants on the premise provided with comprehensive and relevant information on the emergency action plan? 
r 
r 
a 
3 
4 
12 
Medium High Risk 
No emergency plans on site or issued to occupants 
8.9.8 
8.9.9 
Do the occupants know the identity of those persons nominated to implement the emergency action plan? 
r 
r 
a 
3 
4 
12 
Medium High Risk 
No emergency plans on site or issued to occupants 
8.9.9 
8.9.10 
Is a record of fire or near misses kept with full details of the occurrence? 
r 
a 
r 
0 
1 
0 
Continuous review 
None 
8.9.11 
Are others who may have caused to visit or work within the property provided with regular fire safety training and details of the training recorded? 
r 
a 
r 
0 
1 
0 
Continuous review 
None 
8.9.12 
Are regular fire evacuation drills undertaken and details of these recorded? 
r 
r 
a 
3 
4 
12 
Medium High Risk 
8.9.12 
0 
0
UPRN 
Full Address 
Date 
21 June 2014 
Responsible Team 
Action to be taken 
Date Completed 
8.1.3 
Are suitable arrangements in place for the disposal of “smoking” materials 
Evidence that residents dispose of smoking materials at entrance area. 
Medium Risk 
1 year 
Landlord / managing agent 
consider installing smokers bin adjacent to the door 
8.4.2 
Are Fire Hydrants in suitable proximity of building and clearly visible? 
No visual evidence of hydrants 
High Risk 
28 days 
Landlord / managing agent 
identify and clearly label the location of local hydrants to the site 
8.7.6 
Are the escape routes suitable and sufficient for occupants with impaired mobility ? 
No details provided about private residents with disabilities 
Medium High Risk 
6 months 
Landlord / managing agent 
consider reviewing occupancy types and include within emergency action plan for the building where necessary 
8.7.18 
Are all emergency escape routes suitably illuminated with emergency lighting? 
borrowed lighting available 
Medium High Risk 
6 months 
Landlord / managing agent 
consider installing emergency lighting to the building 
8.7.20 
Do all final exit doors open in the direction of escape? 
limited occupation less than 60 persons 
Medium High Risk 
6 months 
Landlord / managing agent 
nor requried due to the building capacity 
8.8.13 
Electrical installations 
no evidence of recent Periodic inspection to electrical system 
Medium Risk 
1 year 
Landlord / managing agent 
Arrange for a five yearly inspection of system to be carried out 
0 
0 
Photo Ref. No. 
Action Point 
Assessment Guidance Ref. 
Description of Significant Finding / Item 
Priority 
Target Time 
Comment 
Significant Findings
Responsible Team 
Action to be taken 
Date Completed 
Photo Ref. No. 
Action Point 
Assessment Guidance Ref. 
Description of Significant Finding / Item 
Priority 
Target Time 
Comment 
Significant Findings 
8.9.1 
Is a suitable emergency action plan in place for the purpose of safeguarding residents, occupants and other persons present in the event of a fire? 
No emergency plans on site or issued to occupants 
High Risk 
28 days 
Landlord / managing agent 
create and distibute emergency plan for premise 
8.9.4 
Are emergency contacts with external services arranged as necessary with regards to rescue work and fire fighting? 
contact is local fire brigade service 
Medium High Risk 
6 months 
Landlord / managing agent 
no action needed 
8.9.8 
Are occupants on the premise provided with comprehensive and relevant information on the emergency action plan? 
No emergency plans on site or issued to occupants 
Medium High Risk 
6 months 
Landlord / managing agent 
create and distibute emergency plan for premise 
8.9.9 
Do the occupants know the identity of those persons nominated to implement the emergency action plan? 
No emergency plans on site or issued to occupants 
Medium High Risk 
6 months 
Landlord / managing agent 
create and distibute emergency plan for premise 
8.9.12 
Are regular fire evacuation drills undertaken and details of these recorded? 
0 
Medium High Risk 
6 months 
Landlord / managing agent 
create and distibute emergency plan for premise
Block Fire Risk Assessment Sheet 
The below scoring system will determine the overall fire risk profile and frequency 
of Fire Risk Assessment review. 
Description 
High Risk 
Medium Risk 
Low Risk 
1.0 
Number of Staircases within the building 
One 
Two 
Three + 
1 
0 
0 
2.0 
Is there a lobby approach to the flat front doors? 
No 
Yes 
1 
0 
3.0 
Have ALL doors to the block been upgraded? 
No 
Some 
Yes 
0 
1 
0 
4.0 
Is Emergency Lighting installed throughout? 
No 
Some 
Yes 
1 
0 
0 
5.0 
Is the Means of Escape kept clear at all times? 
No 
Sometimes 
Yes 
0 
0 
0 
6.0 
How Many fires have occurred within the block within the past five years? 
More than 6 
2 – 5 fires 
Zero – 1 fire 
0 
0 
1 
7.0 
Are Estate Management issues raised and managed effectively 
No 
Sometimes 
Yes 
0 
0 
1 
8.0 
What is the general layout or nature of the building and referring to tenancy 
SAS / Community centre / caretaker area 
General Needs / HMO designed building 
General Needs / Leaseholder or converted property 
0 
0 
1 
9.0 
How Many Floors are in the block including basement 
Over 7 
Between 4 - 6 
One - three 
0 
0 
1 
10.0 
Is there automatic smoke or fire detection present to the building 
None at all in building 
Some in communal areas 
Full Fire detection system 
0 
1 
0 
Scoring 
points added from each column 
3 
2 
4 
Multiplication factor 
3 
2 
1 
Sub score 
9 
4 
4 
Total score of all columns 
17 
Findings guide Fire Risk Assessment renewal as follows: 
* between 1 and 10 is classified as a low risk building and will have a full fire risk assessment undertaken every five years. 
All buildings will have their fire risk assessment reviewed prior and post completion of any major works within the block. 
This building has been identified with a block level risk assessment as a building of : 
Medium - Renew FRA at least every three years 
0 
0 
21 June 2014 
* between 20 and 30 is a high risk building and will have a full fire risk assessment undertaken each year. 
* between 10 and 20 is classified as a medium risk building and will have a full fire risk assessment undertaken every three years.

Más contenido relacionado

La actualidad más candente

Basic Fire Fighting Training
Basic Fire Fighting TrainingBasic Fire Fighting Training
Basic Fire Fighting TrainingChristian Escaler
 
Fire Risk Assessment.pdf
Fire Risk Assessment.pdfFire Risk Assessment.pdf
Fire Risk Assessment.pdfHSEXINYIPROJECT
 
Emergency Preparedness and Response Training by BCMSA
Emergency Preparedness and Response Training by BCMSAEmergency Preparedness and Response Training by BCMSA
Emergency Preparedness and Response Training by BCMSAAtlantic Training, LLC.
 
Safe Operation of Machines by WSH Council
Safe Operation of Machines by WSH CouncilSafe Operation of Machines by WSH Council
Safe Operation of Machines by WSH CouncilAtlantic Training, LLC.
 
Emergency Response Planning Training
Emergency Response Planning Training Emergency Response Planning Training
Emergency Response Planning Training Laura Lee
 
Hazard Identification _ Risk Assessment.ppt
Hazard Identification _ Risk Assessment.pptHazard Identification _ Risk Assessment.ppt
Hazard Identification _ Risk Assessment.pptjxuaaaka
 
Highfield Training Presentation HABC Fire Safety Level 02.ppt
Highfield Training Presentation HABC Fire Safety Level 02.pptHighfield Training Presentation HABC Fire Safety Level 02.ppt
Highfield Training Presentation HABC Fire Safety Level 02.pptAkshayG52
 
training near miss program
training near miss programtraining near miss program
training near miss programoscar anell
 
Incident investigation
Incident investigationIncident investigation
Incident investigationaufumy
 
Fire fighting traning 2019
Fire fighting traning 2019Fire fighting traning 2019
Fire fighting traning 2019Nasir Khan
 
Emergency action plan
Emergency action plan   Emergency action plan
Emergency action plan Anand Mishra
 
CONDUCTING AN EFFECTIVE FIRE DRILL
CONDUCTING AN EFFECTIVE FIRE DRILLCONDUCTING AN EFFECTIVE FIRE DRILL
CONDUCTING AN EFFECTIVE FIRE DRILLAmb Steve Mbugua
 

La actualidad más candente (20)

Basic Fire Fighting Training
Basic Fire Fighting TrainingBasic Fire Fighting Training
Basic Fire Fighting Training
 
EMERGENCY RESPONSE PLAN
EMERGENCY RESPONSE PLANEMERGENCY RESPONSE PLAN
EMERGENCY RESPONSE PLAN
 
Fire Risk Assessment.pdf
Fire Risk Assessment.pdfFire Risk Assessment.pdf
Fire Risk Assessment.pdf
 
Emergency Preparedness and Response Training by BCMSA
Emergency Preparedness and Response Training by BCMSAEmergency Preparedness and Response Training by BCMSA
Emergency Preparedness and Response Training by BCMSA
 
Fire Safety Awareness
Fire Safety AwarenessFire Safety Awareness
Fire Safety Awareness
 
Fire warden training
Fire warden trainingFire warden training
Fire warden training
 
Safe Operation of Machines by WSH Council
Safe Operation of Machines by WSH CouncilSafe Operation of Machines by WSH Council
Safe Operation of Machines by WSH Council
 
Emergency Response Planning Training
Emergency Response Planning Training Emergency Response Planning Training
Emergency Response Planning Training
 
Hazard Identification _ Risk Assessment.ppt
Hazard Identification _ Risk Assessment.pptHazard Identification _ Risk Assessment.ppt
Hazard Identification _ Risk Assessment.ppt
 
Highfield Training Presentation HABC Fire Safety Level 02.ppt
Highfield Training Presentation HABC Fire Safety Level 02.pptHighfield Training Presentation HABC Fire Safety Level 02.ppt
Highfield Training Presentation HABC Fire Safety Level 02.ppt
 
Evacuation Plan
Evacuation PlanEvacuation Plan
Evacuation Plan
 
training near miss program
training near miss programtraining near miss program
training near miss program
 
Incident investigation
Incident investigationIncident investigation
Incident investigation
 
Hirarc
HirarcHirarc
Hirarc
 
Risk assessment-training
Risk assessment-trainingRisk assessment-training
Risk assessment-training
 
Fire fighting traning 2019
Fire fighting traning 2019Fire fighting traning 2019
Fire fighting traning 2019
 
fire safety training
 fire safety training fire safety training
fire safety training
 
Emergency action plan
Emergency action plan   Emergency action plan
Emergency action plan
 
Emergency Response Plan
Emergency Response PlanEmergency Response Plan
Emergency Response Plan
 
CONDUCTING AN EFFECTIVE FIRE DRILL
CONDUCTING AN EFFECTIVE FIRE DRILLCONDUCTING AN EFFECTIVE FIRE DRILL
CONDUCTING AN EFFECTIVE FIRE DRILL
 

Destacado

My Fire Risk Assessment Template
My Fire Risk Assessment TemplateMy Fire Risk Assessment Template
My Fire Risk Assessment Templateneiltilley
 
Film production risk assessment form
Film production risk assessment formFilm production risk assessment form
Film production risk assessment formcembitmead
 
Bizsafe Risk Assessment
Bizsafe Risk AssessmentBizsafe Risk Assessment
Bizsafe Risk Assessmentsearchgeeksg
 
Film production risk assessment form
Film production risk assessment formFilm production risk assessment form
Film production risk assessment formGraveney School
 
Risk assessment template
Risk assessment templateRisk assessment template
Risk assessment templatetamz486
 
Risk assessment form
Risk assessment formRisk assessment form
Risk assessment formanthony987
 
Video shoot schedule
Video shoot scheduleVideo shoot schedule
Video shoot scheduleanthony987
 
4.2 Risk assessment project (i)
4.2 Risk assessment project (i)4.2 Risk assessment project (i)
4.2 Risk assessment project (i)Md Farid Talif
 
Smokers risk assessment form v 1.0.docx.docx
Smokers risk assessment form v 1.0.docx.docxSmokers risk assessment form v 1.0.docx.docx
Smokers risk assessment form v 1.0.docx.docxPhoenix STS Ltd
 
Risk assessment
Risk assessmentRisk assessment
Risk assessmentchamahan
 
Bizsafe risk assessment
Bizsafe risk assessmentBizsafe risk assessment
Bizsafe risk assessmentsearchgeeksg
 
Fire safety-log-book-2012
Fire safety-log-book-2012Fire safety-log-book-2012
Fire safety-log-book-2012madanhse
 
Risk Assessment Form
Risk Assessment FormRisk Assessment Form
Risk Assessment FormBrett Tinnion
 
How to carry out fire risk assessments
How to carry out fire risk assessmentsHow to carry out fire risk assessments
How to carry out fire risk assessmentsQuick-Test
 
Risk assessment template media
Risk assessment template mediaRisk assessment template media
Risk assessment template mediaKhem Slawson
 

Destacado (20)

My Fire Risk Assessment Template
My Fire Risk Assessment TemplateMy Fire Risk Assessment Template
My Fire Risk Assessment Template
 
Film production risk assessment form
Film production risk assessment formFilm production risk assessment form
Film production risk assessment form
 
Risk assessment
Risk assessmentRisk assessment
Risk assessment
 
risk assesment SMDB
risk assesment SMDBrisk assesment SMDB
risk assesment SMDB
 
Hazard Communication Training by LAUSD
Hazard Communication Training by LAUSDHazard Communication Training by LAUSD
Hazard Communication Training by LAUSD
 
Bizsafe Risk Assessment
Bizsafe Risk AssessmentBizsafe Risk Assessment
Bizsafe Risk Assessment
 
Film production risk assessment form
Film production risk assessment formFilm production risk assessment form
Film production risk assessment form
 
Risk assessment template
Risk assessment templateRisk assessment template
Risk assessment template
 
Risk assessment form
Risk assessment formRisk assessment form
Risk assessment form
 
Video shoot schedule
Video shoot scheduleVideo shoot schedule
Video shoot schedule
 
4.2 Risk assessment project (i)
4.2 Risk assessment project (i)4.2 Risk assessment project (i)
4.2 Risk assessment project (i)
 
Risk assessment c19
Risk assessment c19Risk assessment c19
Risk assessment c19
 
Smokers risk assessment form v 1.0.docx.docx
Smokers risk assessment form v 1.0.docx.docxSmokers risk assessment form v 1.0.docx.docx
Smokers risk assessment form v 1.0.docx.docx
 
Risk assessment
Risk assessmentRisk assessment
Risk assessment
 
Risk assessment
Risk assessmentRisk assessment
Risk assessment
 
Bizsafe risk assessment
Bizsafe risk assessmentBizsafe risk assessment
Bizsafe risk assessment
 
Fire safety-log-book-2012
Fire safety-log-book-2012Fire safety-log-book-2012
Fire safety-log-book-2012
 
Risk Assessment Form
Risk Assessment FormRisk Assessment Form
Risk Assessment Form
 
How to carry out fire risk assessments
How to carry out fire risk assessmentsHow to carry out fire risk assessments
How to carry out fire risk assessments
 
Risk assessment template media
Risk assessment template mediaRisk assessment template media
Risk assessment template media
 

Similar a Fire Risk Assessment Master ( Flats)

2010 Fsp Overview W Objective Statements
2010 Fsp Overview W Objective Statements2010 Fsp Overview W Objective Statements
2010 Fsp Overview W Objective Statementsandrewwcwong
 
Fire safety plan assembly occupancy
Fire safety plan   assembly occupancyFire safety plan   assembly occupancy
Fire safety plan assembly occupancyRahjuPlapon
 
Fire Risk Assessmen Cornford House Fire Risk Assessment 21-05.pdf
Fire Risk Assessmen Cornford House Fire Risk Assessment 21-05.pdfFire Risk Assessmen Cornford House Fire Risk Assessment 21-05.pdf
Fire Risk Assessmen Cornford House Fire Risk Assessment 21-05.pdfeliasox
 
Mango Webinar - Dealing with Emergencies (ID 389681).pptx
Mango Webinar - Dealing with Emergencies (ID 389681).pptxMango Webinar - Dealing with Emergencies (ID 389681).pptx
Mango Webinar - Dealing with Emergencies (ID 389681).pptxssuser68b89e
 
Fia Best Practice Guide to Fire Safety
Fia Best Practice Guide to Fire SafetyFia Best Practice Guide to Fire Safety
Fia Best Practice Guide to Fire Safetyno suhaila
 
Professionals - Wildfires - Response part 3
Professionals - Wildfires - Response part 3Professionals - Wildfires - Response part 3
Professionals - Wildfires - Response part 3NCC-CCT
 
Fire safety in the workplace
Fire safety in the workplaceFire safety in the workplace
Fire safety in the workplaceAmb Steve Mbugua
 
Fire and Safety Engineering.pptx
Fire and Safety Engineering.pptxFire and Safety Engineering.pptx
Fire and Safety Engineering.pptxZeeshan Yousaf
 
L14 emergency preparednes-industrial facility
L14 emergency preparednes-industrial facilityL14 emergency preparednes-industrial facility
L14 emergency preparednes-industrial facilityMahbubul Hassan
 
Fire Safety Talk
Fire Safety TalkFire Safety Talk
Fire Safety Talkmda03036110
 
Fire Risk Assessment | Fire Prevention | Fire Safety | Fire Safety Audit
Fire Risk Assessment | Fire Prevention | Fire Safety | Fire Safety AuditFire Risk Assessment | Fire Prevention | Fire Safety | Fire Safety Audit
Fire Risk Assessment | Fire Prevention | Fire Safety | Fire Safety Audithimalya sharma
 
Pre Fire Planning.pptx
Pre Fire Planning.pptxPre Fire Planning.pptx
Pre Fire Planning.pptxMarvinCCabral
 
The Fire and Rescue Service Books is a guidance for organize a safe system of...
The Fire and Rescue Service Books is a guidance for organize a safe system of...The Fire and Rescue Service Books is a guidance for organize a safe system of...
The Fire and Rescue Service Books is a guidance for organize a safe system of...Mario Robusti
 
FIRE PREVENTION REQUIREMENTS Form # HSEQ - Rev 2.docx
FIRE PREVENTION REQUIREMENTS Form # HSEQ -  Rev 2.docxFIRE PREVENTION REQUIREMENTS Form # HSEQ -  Rev 2.docx
FIRE PREVENTION REQUIREMENTS Form # HSEQ - Rev 2.docxDwarika Bhushan Sharma
 
Education & Training in the Passive Fire Protection Sector: Towards compete...
Education & Training in the Passive Fire Protection Sector: Towards compete...Education & Training in the Passive Fire Protection Sector: Towards compete...
Education & Training in the Passive Fire Protection Sector: Towards compete...Su Butcher
 
Fso size up03
Fso   size up03Fso   size up03
Fso size up03Kevin C
 
Create a fire prevention plan with a suppression engineer
Create a fire prevention plan with a suppression engineerCreate a fire prevention plan with a suppression engineer
Create a fire prevention plan with a suppression engineerStartech Engineering
 

Similar a Fire Risk Assessment Master ( Flats) (20)

2010 Fsp Overview W Objective Statements
2010 Fsp Overview W Objective Statements2010 Fsp Overview W Objective Statements
2010 Fsp Overview W Objective Statements
 
Fire safety plan assembly occupancy
Fire safety plan   assembly occupancyFire safety plan   assembly occupancy
Fire safety plan assembly occupancy
 
Fire risk assessment
Fire risk assessmentFire risk assessment
Fire risk assessment
 
Fire Risk Assessmen Cornford House Fire Risk Assessment 21-05.pdf
Fire Risk Assessmen Cornford House Fire Risk Assessment 21-05.pdfFire Risk Assessmen Cornford House Fire Risk Assessment 21-05.pdf
Fire Risk Assessmen Cornford House Fire Risk Assessment 21-05.pdf
 
Mango Webinar - Dealing with Emergencies (ID 389681).pptx
Mango Webinar - Dealing with Emergencies (ID 389681).pptxMango Webinar - Dealing with Emergencies (ID 389681).pptx
Mango Webinar - Dealing with Emergencies (ID 389681).pptx
 
Htm 05 01 (1)
Htm 05 01 (1)Htm 05 01 (1)
Htm 05 01 (1)
 
Fia Best Practice Guide to Fire Safety
Fia Best Practice Guide to Fire SafetyFia Best Practice Guide to Fire Safety
Fia Best Practice Guide to Fire Safety
 
Professionals - Wildfires - Response part 3
Professionals - Wildfires - Response part 3Professionals - Wildfires - Response part 3
Professionals - Wildfires - Response part 3
 
Fire safety in the workplace
Fire safety in the workplaceFire safety in the workplace
Fire safety in the workplace
 
8 fire safety
8 fire safety8 fire safety
8 fire safety
 
Fire and Safety Engineering.pptx
Fire and Safety Engineering.pptxFire and Safety Engineering.pptx
Fire and Safety Engineering.pptx
 
L14 emergency preparednes-industrial facility
L14 emergency preparednes-industrial facilityL14 emergency preparednes-industrial facility
L14 emergency preparednes-industrial facility
 
Fire Safety Talk
Fire Safety TalkFire Safety Talk
Fire Safety Talk
 
Fire Risk Assessment | Fire Prevention | Fire Safety | Fire Safety Audit
Fire Risk Assessment | Fire Prevention | Fire Safety | Fire Safety AuditFire Risk Assessment | Fire Prevention | Fire Safety | Fire Safety Audit
Fire Risk Assessment | Fire Prevention | Fire Safety | Fire Safety Audit
 
Pre Fire Planning.pptx
Pre Fire Planning.pptxPre Fire Planning.pptx
Pre Fire Planning.pptx
 
The Fire and Rescue Service Books is a guidance for organize a safe system of...
The Fire and Rescue Service Books is a guidance for organize a safe system of...The Fire and Rescue Service Books is a guidance for organize a safe system of...
The Fire and Rescue Service Books is a guidance for organize a safe system of...
 
FIRE PREVENTION REQUIREMENTS Form # HSEQ - Rev 2.docx
FIRE PREVENTION REQUIREMENTS Form # HSEQ -  Rev 2.docxFIRE PREVENTION REQUIREMENTS Form # HSEQ -  Rev 2.docx
FIRE PREVENTION REQUIREMENTS Form # HSEQ - Rev 2.docx
 
Education & Training in the Passive Fire Protection Sector: Towards compete...
Education & Training in the Passive Fire Protection Sector: Towards compete...Education & Training in the Passive Fire Protection Sector: Towards compete...
Education & Training in the Passive Fire Protection Sector: Towards compete...
 
Fso size up03
Fso   size up03Fso   size up03
Fso size up03
 
Create a fire prevention plan with a suppression engineer
Create a fire prevention plan with a suppression engineerCreate a fire prevention plan with a suppression engineer
Create a fire prevention plan with a suppression engineer
 

Fire Risk Assessment Master ( Flats)

  • 1. UPRN Full Address Prepared by Karen Daykin On date 21 June 2014 For Responsible Person Bluezone Ltd Woodberry Close Canvey Island, SS8 9PP Telephone 01268 697815 Email Website Site Contact name Telephone Date of Review FIRE RISK ASSESSMENT The Fire Risk Assessment is kept at the Head Office of Bluezone Ltd. A duplicate should be available on each site. It should be available for audits undertaken by the appropriate enforcement authority. Woodberry Manor REGULATORY REFORM (FIRE SAFETY) 2005 Ray Woodberry 01268 697815 Type of Fire Risk Assessment Block Risk Assessment Sleeping Accommodation Full Fire Risk Assessment Medium - Renew FRA at least every three years 21 June 2017
  • 2. UPRN Full Address Date 21 June 2014 Contents 1. Introduction 8. Photographs The responsible person must take general fire precautions as will ensure so far as is reasonably practicable the safety of any employees and also in relation to relevant persons who are not in their employ take such general fire precautions as may reasonably be required in the circumstances of the case to ensure that the premises are safe. Regulatory Reform (Fire Safety) Order 2005 Article 9 requires that every responsible person must make a suitable and sufficient assessment of the risks to which relevant persons are exposed for the purpose of identifying the general fire precautions needed to take to comply with the requirements and prohibitions imposed by or under the order. The responsible person (or other person who has to any extent control of the property) must ensure that the duties imposed by the relevant articles of the Regulatory Reform (Fire Safety) Order 2005 are complied with where the matters relate to items within their control. The prescribed information is the significant findings of the assessment including the measures which have or will be taken by the responsible person pursuant to the Regulatory Reform (Fire Safety) Order 2005 and any group of persons identified by the assessment as being especially at risk. This includes identification of all current significant fire hazards to which relevant persons and others in the area may be exposed. The Risk Assessment will prioritise the level of risk associated with the property incorporating existing controlling measures to mitigate any risk The Assessment will also advise upon additional control measures that may me implemented to manage the risk in accordance with Article 10 of the Order. a. Measures to control sources of ignition 0 0 1. Introduction 2. Scope and Methodology of Assessment 3. Identification of Significant Fire Hazards and People at Risk 4. Existing Fire Safety Measures and Occupancy 5. Assessment of Fire Risk b. Measures to control sources of fuel c. Measures to control sources of oxygen d. Measures to assist Fire Service e. Measures to assist Fire Fighters h. Measures for Signs and Notices i. Installation, Testing & Maintenance j. Management of Procedures & Information 2. Scope and Methodology of Assessment Statutory Requirement 6. Fire Risk Rating Matrix 7. Fire Risk Assessment Action Schedule This report has been prepared as the written record of the Fire Risk Assessment carried out to the communal areas of this building on behalf of the Landlord, Bluezone Ltd, in accordance with the requirements of the Regulatory Reform (Fire Safety) Order 2005. The objectives of the Fire Risk Assessment are to ensure that a suitable and sufficient assessment of the risks to which relevant persons are exposed for the purpose of identifying the general fire precautions he needs to take to comply with the requirements and prohibitions of the Regulatory Reform (Fire Safety) Order 2005. f. Measures for Fire Detection and Warning g. Measures to assist Means of escape A Bluezone Ltd Fire Risk Assessment is not a one off document and is part of a strategic Fire Safety Strategy and Policy implemented to identify, manage and monitor the risks to Bluezone Ltd properties on a regular basis. The Fire Risk Assessment will be reviewed under Article 9 (3) of the Order and in direct accordance with Bluezone Ltd review policy and National guidance documentation; this includes but is not restricted to:- (a) there is reason to suspect that the Fire Risk Assessment is no longer valid; (b) there has been a significant change to which it relates including when the premises, special, technical or organisational measures undergo significant change, extension or conversion. (c) Identification of risk following an actual or near miss incident. The report is to provide and assessment of the risk to life from a fire within the building and to make recommendations to ensure compliance with the Regulatory Reform (Fire Safety) Order 2005; it does not address the risk to the property or business continuity from fire.
  • 3. Information contained within the report is based on observations at the time of inspection and details provided by on site personnel. To identify the significant fire hazards within the premises checklists are used which consider the particular fire hazard associated with the building and the nature of the occupancy. The hazard will consider the items with regard to existing control measures which are either already inherent within the building or implemented through the management procedures. The answers are either Yes / No or Not Applicable (N/A). Each hazard is assessed in accordance with the fire risk rating system. This includes consideration of the hazard in terms of the potential to harm (severity) and their likelihood (probability) of occurring. In addition a specific risk rating is applied in consideration of the controlling measures in place and subsequently considers the timescales within which the measures should be implemented. The Action plan details the significant findings of both technical and procedural measures that should be considered necessary to address the risk identified. It is a register of the remedial and advisory actions to be carried out in accordance with the priorities defined using the fire risk rating system. To reduce the risk to an acceptable level all Action Plan items should be addressed. The Fire Risk Assessment information is gathered using non invasive physical inspections of the property. Where floor plans are available these have been used utilised and direct conversation or information has been gathered from on-site staff. Digital photographs have also been taken and included for means of identification of locations and hazards The new Regulatory Reform (Fire Safety) Order 2005 requires a fire risk assessment to be carried out and the significant findings recorded. The process followed was as follows: The building was inspected, hazards were identified and the fire risk categorised as high, medium or low. The existing measures were recorded as well as any recommended action. Where actions have been recommended these are in line with British Standards. Hazards included any sources of ignition (sparks, electrical equipment, heat sources etc), dangerous substances (flammable materials, combustible materials, gases etc) and unsatisfactory structural features (absence of fire stopping, ducts and voids and compromised protected routes). Any areas where evacuation of occupants could be compromised were also classed as hazards. A high fire risk was categorised in areas where there is likely to be a large number of people or old, young or disabled people. Areas with flammable processes or large quantities of heat or combustible materials were also categorised high risk as well as any areas where structural features would allow the spread of smoke or fire from one part of the building to another. A normal fire risk was categorised where a fire is likely to remain localised or to spread slowly enough to allow people to escape to a place of safety or where there is an effective automatic means of detecting and giving warning of fire. A low fire risk was categorised where there is minimal risk to life safety and the risk of fire occurring is negligible and the risk of fire, smoke or fumes spreading is negligible. Identification of Fire Hazards Assessment of Fire Risk The Fire Risk Assessment Action Plan Information Source
  • 4. UPRN Full Address Date 21 June 2014 2 8 1 no Staircase (element) yes no yes yes no Sole Leaseholder or post 1991 converted or purpose built property Maximum number of occupants / residents 24 Maximum number of visitors 120 Maximum number of sleeping occupants at any one time 144 Maximum number of vulnerable occupants at any one time 24 Does the tenure include occupants who are:- “Disabled” incl mobility impairment, hearing or vision impairment unknown “Restricted” parents with children unknown “Sensory Impaired” due to alcohol, drugs or medication unknown Maximum number of unaccompanied children at any one time unknown Maximum occupation in remote areas at any one time n/a Accessible by lift / s Tenure of flats / units General tenure / occupancy description 4. Identification of People at Risk Number of Flats within block Number of direct staircases from corridors Is there a lobby approach from the staircases to the flats or within the flats? Fully Enclosed / No Borrowed Light / windows Semi Enclosed / some Borrowed Light / windows Fully Open / with Borrowed Light / windows Fully Enclosed / No Borrowed Light / windows Semi Enclosed / some Borrowed Light / windows Fully Open / with Borrowed Light / windows Number of Storeys (incl basement) Date of Construction Areas not assessed Two storey tradditional build premise comprising eight residential flats accessed by two doors front and rear and 0 3. Existing Fire Safety Measures and Occupancy (Static data) Brief description of building and its construction No communal Corridors (flats direct to staircases) Corridors (from the staircases) 1986 Roof void area 0
  • 5. UPRN Full Address Date 21 June 2014 Risk Level 1 (Low) 2 3 (Medium) 4 5 (High) Probability Level 1 (Low) 2 3 (Medium) 4 5 (High) Degree of Risk Risk Rating Score High 15 – 25 Medium High 08 – 12 Medium 02 – 06 Low Risk 01 Continuous review 00 A Traffic light approach is made in respect of the degree and level of risk, which is also translated into the priority rating for remedial work or recommendations. Timescales given include consideration for practicality and financial impact to Bluezone Ltd when planning their implementation. In order to reduce the risk to an acceptable level it is recommended that all Action Plan items are implemented 5. Risk Matrix Building / Area should not be occupied until risk is reduced. Fatality or total loss of property Exposure Improbable – no known instances of occurrence <10% Essential that efforts are made to reduce the risk; measures to be implemented within set timescales. Serious damage to property Considerable resources may have to be allocated to reduce the risk; where a building is occupied urgent action should be undertaken. Permanent injury; permanent damage to property. The following risk matrix has been used to prioritise and quantify the individual fire safety deficiencies identified. Action / Consequence No Further Action is necessary, detailed records needed. No serious injuries, little or no damage to property. No major additional controls needed consideration for improvements which have minor cost incurrence. Some injury, remedial works needed to property 0 0 Unlikely – but still possible 10 -30% Likely to occur 30 - 50 % Will occur frequently 50 - 90% Will occur very frequently unless prevented >90% Within three years of notification (programmed work) Within five years of notification (programmed work) Timescale for action Within 28 days of notification Within six months of notification Within one year of notification
  • 6. UPRN Full Address Date 21 June 2014 some no yes Zero – 1 fire yes some 7. Identification of significant Fire Hazards Source & location of Ignition 1 2 3 4 5 6 7 8 9 10 Other notes Source & location of Fuel 1 2 3 4 5 6 7 8 9 10 Other notes Source and location of oxygen 1 2 3 4 5 Other notes Are Estate Management issues being raised and managed effectively? Is there automatic smoke or fire detection present to the building ? Fixed lighting equipment 0 0 Have flat / unit own doors been upgraded to 30 min fire rated? Is Emergency Lighting installed throughout? 6. Existing Fire Safety Measures and Occupancy (changeable data) Is the Means of Escape kept clear at all times? How Many fires have occurred within the block within the past five Natural airflow
  • 7. UPRN Full Address Date 21 June 2014 Item Measures to control Source of Ignition N/A Yes No Risk Level (1-5) Probability Level (1- Rating (RLxP) Priority Comments Action Point Ref. 8.1.1 Are current arrangements for the control of arson suitable and sufficient? r a r 0 1 0 Continuous review None 8.1.2 Is Smoking confined to designated areas and “No Smoking” signs displayed as appropriate? r a r 0 1 0 Continuous review None 8.1.3 Are suitable arrangements in place for the disposal of “smoking” materials r r a 2 3 6 Medium Risk Evidence that residents dispose of smoking materials at entrance area. 8.1.3 8.1.4 Is there an adequate system adopted for permitting and monitoring hot works operations by outside contractors? a r r 0 0 0 Continuous review None 8.1.5 Are arrangements for managing building work and alterations suitable and sufficient? r a r 0 1 0 Continuous review None 8.1.6 Are adequate measures in place to guard against malicious ignition? r a r 0 2 0 Continuous review None 8.1.7 Are Access control / security systems In place? r a r 0 1 0 Continuous review door entry system not operational None 8. Assessment of Fire Risk The following table details the approach that has been taken to assess the individual risk level for each identified hazard / fire safety deficiency. All hazards have been considered with regard to the specific relevant people affected and the control measures necessary to contend with the risk. 0 0
  • 8. UPRN Full Address Date 21 June 2014 Measures to control Source of Fuel N/A Yes No Risk Level (1-5) Probability Level (1- Rating (RLxP) Priority Comments Action Point Ref. 8.2.1 Have all areas of flammable wall and ceiling Linings been removed, covered, or treated to reduce the spread of flame across their r a r 0 1 0 Continuous review None 8.2.2 Is the premises free from accumulation of Rubbish, waste paper, and other ignitable materials? r a r 0 1 0 Continuous review None 8.2.3 Are adequate arrangements made for the Disposal of waste and rubbish? r a r 0 1 0 Continuous review None 8.2.4 Are suitable arrangements in place for storing highly flammable or readily combustible materials not in current use? a r r 0 0 0 Continuous review None 8.2.5 Are storage areas for highly flammable and explosive materials identified by hazard warning signs a r r 0 0 0 Continuous review None 8.2.6 Are the housekeeping arrangements for communal areas sufficiently controlled? r a r 0 1 0 Continuous review None 8.2.7 Are the arrangements for use of equipment and machinery suitable and sufficient? a r r 0 0 0 Continuous review None 8.2.8 Is the existing building layout and construction appropriate, suitable and sufficient? r a r 0 1 0 Continuous review None 8.2.9 Are areas of high fire risk and loading provided with physical separation from the remainder of the premises? r a r 0 2 0 Continuous review None 8.2.10 Is the provision of means for restricting spread of fire and smoke in common areas suitable and sufficient? r a r 0 1 0 Continuous review None 8.2.11 Is the provision of means for restricting fire and smoke within access duct /chutes etc. suitable and sufficient? a r r 0 0 0 Continuous review None 8.2.12 Is the provision of means for restricting fire and smoke from entering into individual flats / units / areas / linked or attached properties suitable and sufficient? r a r 0 1 0 Continuous review None Measures to control Source of Oxygen N/A Yes No Risk Level (1-5) Probability Level (1- Rating (RLxP) Priority Comments Action Point Ref. 8.3.1 Are the communal opening windows operational? r a r 0 1 0 Continuous review None 8.3.2 Are there smoke vents present – if they are not present are they required / recommended ? a r r 0 0 0 Continuous review None 8.3.3 Are air conditioning units present – if they are not present are they required / recommended ? a r r 0 0 0 Continuous review None 0 0
  • 9. UPRN Full Address Date 21 June 2014 Measures to assist fire service N/A Yes No Risk Level (1-5) Probability Level (1- Rating (RLxP) Priority Comments Action Point Ref. 8.4.1 Are there suitable access facilities for Fire Service vehicles to access the entire building? r a r 0 1 0 Continuous review None 8.4.2 Are Fire Hydrants in suitable proximity of building and clearly visible? r r a 4 4 16 High Risk No visual evidence of hydrants 8.4.2 8.4.3 Does the Emergency Action Plan relate to the Fire & Rescue Service response? a r r 0 0 0 Continuous review None 8.4.4 Are the fire fighting lifts clearly identified and appropriate signage fitted? a r r 0 0 0 Continuous review None 8.4.5 Are there Dry / Wet Risers present – if they are not present are they required / recommended ? a r r 0 0 0 Continuous review None 8.4.6 Are the fire fighting lifts clearly identified and appropriate signage fitted? a r r 0 0 0 Continuous review None 8.4.7 Are there sprinklers / suppression systems present – if they are not present are they required / recommended ? a r r 0 0 0 Continuous review None 8.4.8 Are there hose reels present – if they are not present are they required / recommended ? a r r 0 0 0 Continuous review None 8.4.9 Are fire blankets present – if they are not present are they required / recommended ? a r r 0 0 0 Continuous review None 8.4.10 Are there portable fire extinguishers present – if they are not present are they required / recommended ? a r r 0 0 0 Continuous review None 8.4.11 Are the portable fire extinguishers clearly visible and accessible with correct signage? a r r 0 0 0 Continuous review None 8.4.14 Are the Portable Fire Extinguishers suitable & sufficient for purpose? a r r 0 0 0 Continuous review None 8.4.15 Are the Portable Fire Extinguishers clearly visible and accessible? a r r 0 0 0 Continuous review None r 0
  • 10. UPRN Full Address Date 21 June 2014 Measures for fire detection and warning N/A Yes No Risk Level (1-5) Probability Level (1- Rating (RLxP) Priority Comments Action Point Ref. 8.4.12 Is an automatic fire warning system present – or if it is not present is it required or recommended? a r r 0 0 0 Continuous review None 8.4.13 Is the property classified as a HMO (House of Multiple Occupancy) within guidelines of Lacors and Housing Act a r r 0 0 0 Continuous review None 8.5.1 Does the fire warning system have a named responsible person, who has authority and training to manage the system? a r r 0 0 0 Continuous review None 8.5.2 Is the Automatic Fire Detection / warning system suitable and sufficient for the premises? a r r 0 0 0 Continuous review None 8.5.3 Are manual call points suitable and sufficiently located and accessible? a r r 0 0 0 Continuous review None 8.5.3 Are sounders/klaxons suitable and sufficiently located? a r r 0 0 0 Continuous review None 8.5.4 Does the Fire Warning system have a guaranteed power supply? a r r 0 0 0 Continuous review None Measures for signs and notices N/A Yes No Risk Level (1-5) Probability Level (1- Rating (RLxP) Priority Comments Action Point Ref. 8.6.1 Are all Fire doors fitted with self closing devices suitably and correctly signed a r r 0 0 0 Continuous review None 8.6.2 Are all Fire Doors to stores, and cupboards suitably and correctly signed r a r 0 1 0 Continuous review None 8.6.3 Are all final exit doors suitably and correctly signed r a r 0 1 0 Continuous review None 8.6.4 Are all emergency exits suitably and correctly signed r a r 0 1 0 Continuous review None 8.6.5 Are all emergency escape routes suitably and correctly signed? r a r 0 1 0 Continuous review single means of escape from building None 8.6.6 Are Lifts ( in case of emergency) suitably and correctly signed? a r r 0 0 0 Continuous review None 8.6.7 Are Fire Action Notices clearly displayed? a r r 0 0 0 Continuous review None 8.6.8 Are electrical warnings clearly displayed a r r 0 0 0 Continuous review None 0 0
  • 11. UPRN Full Address Date 21 June 2014 Measures to assist means of escape N/A Yes No Risk Level (1-5) Probability Level (1- Rating (RLxP) Priority Comments Action Point Ref. 8.7.1 Are there a sufficient number of exits from the building, and are they of adequate size for the number of occupants? r a r 0 1 0 Continuous review None 8.7.2 Can all emergency / final exit doors be opened easily in single action? r a r 0 1 0 Continuous review None 8.7.3 Do means of escape lead directly to a place of safety? r a r 0 1 0 Continuous review None 8.7.4 Is the Escape route free from obstructions, slip or trip hazards? r a r 0 1 0 Continuous review None 8.7.5 Are the travel distances suitable and sufficient ? r a r 0 1 0 Continuous review None 8.7.6 Are the escape routes suitable and sufficient for occupants with impaired mobility ? r r a 3 4 12 Medium High Risk No details provided about private residents with disabilities 8.7.6 8.7.7 Are the escape routes widths and capacities suitable and sufficient ? r a r 0 1 0 Continuous review None 8.7.8 Are there alternative exits from inner rooms or basements? a r r 0 0 0 Continuous review None 8.7.9 Are the exits from external stairways suitable and sufficient? a r r 0 0 0 Continuous review None 8.7.10 Is the means of escape clear of the need to use ladders, hatches or windows? r a r 0 1 0 Continuous review None 8.7.11 Is the Means of Escape suitable and sufficient to provide 30 minutes fire resistance? r a r 0 1 0 Continuous review None 8.7.12 Is the use of cavity barriers / fire stopping and dampers evident within ducts / suspended ceilings / floors? a r r 0 0 0 Continuous review None 8.7.13 Is a suitable and sufficient place of safety (refuge) provided? a r r 0 0 0 Continuous review None 8.7.14 Are defined zones on external emergency areas of fire resisting nature, including doors, windows, and walls? a r r 0 0 0 Continuous review None 8.7.15 Where roof exits are designated as means of escape is suitable and sufficient access through the door available? a r r 0 0 0 Continuous review None 8.7.16 Where roof exits are designated as means of escape is suitable and sufficient lighting / illumination available? a r r 0 0 0 Continuous review None 8.7.17 Where roof exits are designated as means of escape is the surface non slip / guarded with a protective barrier? a r r 0 0 0 Continuous review None 8.7.18 Are all emergency escape routes suitably illuminated with emergency lighting? r r a 3 4 12 Medium High Risk borrowed lighting available 8.7.18 8.7.19 Does the Emergency Lighting system have a back up power source? a r r 0 0 0 Continuous review None 8.7.20 Do all final exit doors open in the direction of escape? r r a 3 4 12 Medium High Risk limited occupation less than 60 persons 8.7.20 0 0
  • 12. UPRN Full Address Date 21 June 2014 Measures of maintenance for fire safety facilities. Do you regularly inspect, test, report and record in a log book the following? N/A Yes No Risk Level (1-5) Probability Level (1-5) Rating (RLxP) Priority Comments Action Point Ref. 8.8.1 All Flat Entrance doors a r r 0 0 0 Continuous review None 8.8.2 All Communal doors r a r 0 1 0 Continuous review Doors in poor condition and do not lock securely None 8.8.3 All Roof Access doors a r r 0 0 0 Continuous review None 8.8.4 All intake Cupboard doors r a r 0 1 0 Continuous review None 8.8.5 All Store Cupboard doors a r r 0 0 0 Continuous review None 8.8.6 Escape Routes r a r 0 1 0 Continuous review None 8.8.7 Housekeeping r a r 0 1 0 Continuous review None 8.8.8 Compartmentation a r r 0 0 0 Continuous review None 8.8.9 Fire Integrity common areas r a r 0 1 0 Continuous review None 8.8.10 Emergency Lighting a r r 0 0 0 Continuous review None 8.8.11 Fire fighting equipment a r r 0 0 0 Continuous review None 8.8.12 Portable Appliances a r r 0 0 0 Continuous review None 8.8.13 Electrical installations r r a 3 2 6 Medium Risk no evidence of recent Periodic inspection to electrical system 8.8.13 8.8.14 Fire Alarm / Detection / warning system r a r 0 1 0 Continuous review None 8.8.15 Fire Extinguishers a r r 0 0 0 Continuous review None 8.8.16 Smoke Vents a r r 0 0 0 Continuous review None 8.8.17 Sprinklers / Suppression system a r r 0 0 0 Continuous review None 8.8.18 Signs & Notices r a r 0 1 0 Continuous review None 8.8.19 Dry / Wet Riser a r r 0 0 0 Continuous review None 8.8.20 Lightning Conductors a r r 0 0 0 Continuous review None 8.8.21 Access levels r a r 0 1 0 Continuous review None 8.8.22 Gas Appliances / systems a r r 0 0 0 Continuous review None 8.8.23 Air conditioning units a r r 0 0 0 Continuous review None 8.8.24 Hose Reels a r r 0 0 0 Continuous review None 8.8.25 Fire Blankets a r r 0 0 0 Continuous review None 8.8.26 Presence of a log book a r r 0 0 0 Continuous review None 0 0
  • 13. UPRN Full Address Date 21 June 2014 Item Measures for management of information and procedure N/A Yes No Risk Level (1-5) Probability Level (1- Rating (RLxP) Priority Comments Action Point Ref. 8.9.1 Is a suitable emergency action plan in place for the purpose of safeguarding residents, occupants and other persons present in the event of a fire? r r a 5 4 20 High Risk No emergency plans on site or issued to occupants 8.9.1 8.9.2 Is the plan premise specific and up to date? a r r 0 0 0 Continuous review None 8.9.3 Is there a fully trained and equipped warden nominated to implement the emergency action plan? a r r 0 0 0 Continuous review None 8.9.4 Are emergency contacts with external services arranged as necessary with regards to rescue work and fire fighting? r r a 3 4 12 Medium High Risk contact is local fire brigade service 8.9.4 8.9.5 Where two or more organisations share/manage the premise do they cooperate as far as necessary to comply with the RR(FS)O . a r r 0 0 0 Continuous review None 8.9.6 Have appropriate procedures been established to evacuate or restrict access to confined spaces or hazardous locations? a r r 0 0 0 Continuous review None 8.9.7 Are others who may have caused to visit or work within the property provided with comprehensive information on the measures taken in compliance with the RR(FS)O? r a r 0 1 0 Continuous review None 8.9.8 Are occupants on the premise provided with comprehensive and relevant information on the emergency action plan? r r a 3 4 12 Medium High Risk No emergency plans on site or issued to occupants 8.9.8 8.9.9 Do the occupants know the identity of those persons nominated to implement the emergency action plan? r r a 3 4 12 Medium High Risk No emergency plans on site or issued to occupants 8.9.9 8.9.10 Is a record of fire or near misses kept with full details of the occurrence? r a r 0 1 0 Continuous review None 8.9.11 Are others who may have caused to visit or work within the property provided with regular fire safety training and details of the training recorded? r a r 0 1 0 Continuous review None 8.9.12 Are regular fire evacuation drills undertaken and details of these recorded? r r a 3 4 12 Medium High Risk 8.9.12 0 0
  • 14. UPRN Full Address Date 21 June 2014 Responsible Team Action to be taken Date Completed 8.1.3 Are suitable arrangements in place for the disposal of “smoking” materials Evidence that residents dispose of smoking materials at entrance area. Medium Risk 1 year Landlord / managing agent consider installing smokers bin adjacent to the door 8.4.2 Are Fire Hydrants in suitable proximity of building and clearly visible? No visual evidence of hydrants High Risk 28 days Landlord / managing agent identify and clearly label the location of local hydrants to the site 8.7.6 Are the escape routes suitable and sufficient for occupants with impaired mobility ? No details provided about private residents with disabilities Medium High Risk 6 months Landlord / managing agent consider reviewing occupancy types and include within emergency action plan for the building where necessary 8.7.18 Are all emergency escape routes suitably illuminated with emergency lighting? borrowed lighting available Medium High Risk 6 months Landlord / managing agent consider installing emergency lighting to the building 8.7.20 Do all final exit doors open in the direction of escape? limited occupation less than 60 persons Medium High Risk 6 months Landlord / managing agent nor requried due to the building capacity 8.8.13 Electrical installations no evidence of recent Periodic inspection to electrical system Medium Risk 1 year Landlord / managing agent Arrange for a five yearly inspection of system to be carried out 0 0 Photo Ref. No. Action Point Assessment Guidance Ref. Description of Significant Finding / Item Priority Target Time Comment Significant Findings
  • 15. Responsible Team Action to be taken Date Completed Photo Ref. No. Action Point Assessment Guidance Ref. Description of Significant Finding / Item Priority Target Time Comment Significant Findings 8.9.1 Is a suitable emergency action plan in place for the purpose of safeguarding residents, occupants and other persons present in the event of a fire? No emergency plans on site or issued to occupants High Risk 28 days Landlord / managing agent create and distibute emergency plan for premise 8.9.4 Are emergency contacts with external services arranged as necessary with regards to rescue work and fire fighting? contact is local fire brigade service Medium High Risk 6 months Landlord / managing agent no action needed 8.9.8 Are occupants on the premise provided with comprehensive and relevant information on the emergency action plan? No emergency plans on site or issued to occupants Medium High Risk 6 months Landlord / managing agent create and distibute emergency plan for premise 8.9.9 Do the occupants know the identity of those persons nominated to implement the emergency action plan? No emergency plans on site or issued to occupants Medium High Risk 6 months Landlord / managing agent create and distibute emergency plan for premise 8.9.12 Are regular fire evacuation drills undertaken and details of these recorded? 0 Medium High Risk 6 months Landlord / managing agent create and distibute emergency plan for premise
  • 16. Block Fire Risk Assessment Sheet The below scoring system will determine the overall fire risk profile and frequency of Fire Risk Assessment review. Description High Risk Medium Risk Low Risk 1.0 Number of Staircases within the building One Two Three + 1 0 0 2.0 Is there a lobby approach to the flat front doors? No Yes 1 0 3.0 Have ALL doors to the block been upgraded? No Some Yes 0 1 0 4.0 Is Emergency Lighting installed throughout? No Some Yes 1 0 0 5.0 Is the Means of Escape kept clear at all times? No Sometimes Yes 0 0 0 6.0 How Many fires have occurred within the block within the past five years? More than 6 2 – 5 fires Zero – 1 fire 0 0 1 7.0 Are Estate Management issues raised and managed effectively No Sometimes Yes 0 0 1 8.0 What is the general layout or nature of the building and referring to tenancy SAS / Community centre / caretaker area General Needs / HMO designed building General Needs / Leaseholder or converted property 0 0 1 9.0 How Many Floors are in the block including basement Over 7 Between 4 - 6 One - three 0 0 1 10.0 Is there automatic smoke or fire detection present to the building None at all in building Some in communal areas Full Fire detection system 0 1 0 Scoring points added from each column 3 2 4 Multiplication factor 3 2 1 Sub score 9 4 4 Total score of all columns 17 Findings guide Fire Risk Assessment renewal as follows: * between 1 and 10 is classified as a low risk building and will have a full fire risk assessment undertaken every five years. All buildings will have their fire risk assessment reviewed prior and post completion of any major works within the block. This building has been identified with a block level risk assessment as a building of : Medium - Renew FRA at least every three years 0 0 21 June 2014 * between 20 and 30 is a high risk building and will have a full fire risk assessment undertaken each year. * between 10 and 20 is classified as a medium risk building and will have a full fire risk assessment undertaken every three years.