What is Electricity Meter?
 A device to record
Electrical Energy
consumption/
delivery .
3
Programmable Digital Energy Meter
4
Programmable Digital Energy Meter
Meter Terminology:
Starting Current
Current Range
Influence parameters
Specifications of Energy Meter:
 Rating :
In : 3x5; Vn : 3x110V(L-L),
In : 3x30(100); Vn : 3x230/400V(L-L),
 Starting Current :0.2%
 Kwh, KVARH and MD in KW
 TOU, 6 Tariff and 6 time zone
 6 Month Billing data
 RS232C
Why Mechanical meters read less?
 Influence Parameters
 Age
 Wear and Tear
 Narrow Range
 Mounting
 Dust and Oil effect
 Mechanical Counters
Why electronic meters are preferred ?
 Wide Range
 Low starting current
 Less effect of Influence
parameters
 More accurate
 Tamper proof
ROLE OF LED:
CAL. LED
REV. LED
N-CUT
EL
REV LED
*Indicates reverse flow of Energy
•Reasons :
*Incorrect wiring
*Use of un isolated
*Generator/ Inverters
CAL LED
High resolution
out put device for
meter checking
EL
•Due to ‘unbalanced’ Current.
• Needs Attention
•Neutral is touching the earth
.
N- Cut
•Indicates current without voltage
on Meter.
• Contact discom immediately.
* In general Phase, current is
used for measurement. However
if neutral Current varies by more
than 10~ 12 % then Neutral
current selected
 Good electronic meters have
Current sensors in both the
 Phase path, and Neutral path
 For Measurement, it chooses
higher * of the two current.
 Electro-mechanical Meter has
Current sensor only on one wire
 All Measurement based on
phase wire current even when
connected to neutral.
1.L and N swapped, load to
Earth
2. L and N swapped, load
partially connected to Earth
3.Load connected to Earth
4. Load partially connected to
Earth
3.L and N swapped, l/O swapped,
Load connected to Earth
4.L and N swapped, l/O swapped,
Load partially connected to Earth
 Wrong wiring, among others things can
result in:
Safety hazards (wires are still live, even
when the main switch is off).
Cause fire (if by mistake, phase and
neutral wires get interchanged)
Wrong Current flow (neighbours current
can flow through your meter)
21
Connection Arrangement of Programmable Digital
Energy Meter
1 2 3 4 1 5 6 7 8 9 10 11
LOAD
R
Y
B
N
WHOLE CURRENT METERING
Figure-1
N
Y
B
R
4
K L
k
1 2
i
3
K L K
6
k l
5
k
7
L
l
8 9 11
LT CT METERING
LOAD
Figure -2
Figure-3
Vector diagram of Figure-1 & 2
3
I
V 3
1
I
3

 1
V 1
 2
I2
2
V
Here
P= Total Power
P1= Power for phase-1
P2= Power for phase-2
P3= Power for phase-3
Balance Condition :
Voltage V1-n=V2-n=V3-n = V (P-n)
Current I1=I2=I3 = I
Phase Angle 1=23 
P= P1+P2+P3
= V1.I1.Cos1V2.I2.Cos2V3.I3.Cos3
= 3 V.I.Cos
22
Connection Diagram of Whole Current & LT CT
Energy Meter
Wiring Diagram of Polyphase Direct
Connected Meter
3-Element 4-Wire
Figure-3.1
3
1 2
N
R
Y
B
v
V
u
v
u
U V U
v
u k
U V K L
l
11
8 9
6 7
4 5
LOAD
k
l
k
K L K L
l
CT & PT OPERATED (HT METERING) METER CONNECTION
3-Element 4-Wire
Figure-3.2
3
1 2
N
R
Y
B
v
u
U V
v
u k
U V K L
l
11
8 9
6 7
4 5
LOAD
k
l
k
K L K L
l
Y
B
R
2
v
u
v
u k
U V U V K
1
k l
i
L K L
7
5
3 8 9
LOAD
Figure-3.3
2-Element 3-Wire
Y
B
R
2
k
K
1
k l
i
L K L
7
5
3 8 9
LOAD
Figure-3.4
2-Element 3-Wire
v
V
u
v
u
U V U
v
u
U V
24
Connection Diagram of 3-Element 4-Wire & 2-Element 3-Wire
Energy Meter
Wiring Diagram of Polyphase CT Connected
Meter
Wiring Diagram of Polyphase Instrument TR.
Connected Meter
27
Phasor Diagram Analysis
EDMI
Elster
Proper connection of 3-Element 4-Wire Energy Meter
R
B
N
Y
2
1
LOAD
5
3 4 7
6 9
8 11
k l k l k l
K L K L K L
U V
u v
U V
u v
U V
u v
CONNECTION CIRCUIT OF METER VECTOR DIAGRAM
Fig.-5-1
Voltage RED Phase open circuited
B
N
Y
R
U
u
V
v
U
u
V
v
LOAD
2
U
u
V
v
K
k
1
L
l
3
K
k
4 5 9
7
L
l k
6
K L
l
8 11
B
N
Y
R
U
u
V
v
U
u
V
v
LOAD
2
U
u
V
v
K
k
1
L
l
3
K
k
4 5 9
7
L
l k
6
K L
l
8 11
V 3
3
I
 3
1
I
2

V
2
I
2
Similar for Yellow & Blue phase
V 3
3
I
 3
1
V
2

V
2
I
2
Current RED Phase open circuited
V 3
3
I
 3
1
I
 1
1
V
2

V
2
I
2
CALCULATION
P= P1+P2+P3
= V1.I1.Cos1V2.I2.Cos2V3.I3.Cos3
= 3 V.I.Cos
Here
P= Total Power
P1= Power for phase-1
P2= Power for phase-2
P3=Power for phase-3
V1-n,V2-n ,V3-n = Phase voltage
1,2,3 = Phase angle between V & I
Balance Condition :
V1-n=V2-n =V3-n =V (p-n)
I1=I2 =I3 =I
1 =2 =3 =
P= 3.V.I. Cos
PF=2.V.I. Cos
CF=1.5
PF= P1+P2+P3
= 0V2.I2.Cos2V3.I3.Cos3
= 2 V.I.Cos
PF=2.V.I. Cos
CF=1.5
PF= P1+P2+P3
= 0V2.I2.Cos2V3.I3.Cos3
= 2 V.I.Cos
Balance Condition :
V1=V2 =V3 =V
I1=I2 =I3 =I
1 =2 =3 =
Balance Condition :
V1=V2 =V3 =V
I1=I2 =I3 =I
1 =2 =3 =
Similar for Yellow & Blue phase
Fig.-5-2
Fig.-5-3
FAULT ANALYSIS OF 3-ELEMENT 4-WIRE METERING
P= Total power in proper connection
= 3 V.I.Cos
PF=2 V.I.Cos
Correction Factor(CF)= P
PF
CF= 3 V.I.Cos2 V.I.Cos

28
Faulty Connection Analysis of 3-Element 4-Wire Energy Meter
Fig.-5-6
V
Fig.-5-5
Fig.-5-4
V
V
B
N
R
Y
U
u
Y
N
B
R
U
u
Y
N
B
R
U
u
Voltage Red and Blue Phase exchanged
V
v
v v
V
u
U
u
U
k
l
k
K L K
1 2 3 4
l
k
l
K
L L
6
5 7 8 9
LOAD
11
Current Red Phase incorrectly poled
Voltage Red Phase incorrectly poled
V
v
V
v
U
u
U
u v k
K L
l
K
k
1 2 3 4
V
v
V
v
U
u
U
u v k
K L
l
K
k
1 2 3 4
K
L
l k
L
l
6
5 7 8 9
LOAD
11
K
L
l k
L
l
6
5 7 8 9
LOAD
11
PF =P1+P2+P3
= V3.I1.Cos(120°+1)+V2.I2.Cos2
V1.I3.Cos(120°-3)
= V.I Cos(120°+)+Cos
Cos(120°-)
= 0
Similar for Yellow & Blue phase
Similar for Yellow & Blue phase
PF =P2+P3-P1
= V2.I2.Cos2V3.I3.Cos3
-V1.I1.Cos(180°+1)
= V2.I2.Cos2V3.I3.Cos3-V1.I1.Cos1
= V.I.Cos
PF =P2+P3-P1
= V2.I2.Cos2V3.I3.Cos3
-V1.I1.Cos(180°+1)
= V2.I2.Cos2V3.I3.Cos3-V1.I1.Cos1
= V.I.Cos
PF =V.I. Cos

I3
V 3
 3
3
V 1
2

CF=
PF =0

1
1
I
I2
2
V
PF =V.I. Cos
CF=3
CF=3
-V
I3
3
V
 3
1
1
I
 2

3
I
3
V
 3
1
V

-I1
2
1
1
I2
V2
I2
V2
CONNECTION CIRCUIT OF METER VECTOR DIAGRAM CALCULATION
Balance Condition :
V1=V2 =V3 =V
I1=I2 =I3 =I
1 =2 =3 =
Balance Condition :
V1=V2 =V3 =V
I1=I2 =I3 =I
1 =2 =3 =
Balance Condition :
V1=V2 =V3 =V
I1=I2 =I3 =I
1 =2 =3 =
FAULT ANALYSIS OF 3-ELEMENT 4-WIRE METERING
29
Faulty Connection Analysis of 3-Element 4-Wire Energy Meter
Tools Testing:
 Clamp on tester
 Bulb tester
 Electric Meter testing Kit.
Typical Pts. Where Earth gets common with neutral
 Metallic body Appliances.
 Appliances connected with metal pipe line.
 Building RCC.
Wiring Defect:
 If number of meters in one premise is only one,
then there is no common Neutral problem.
33
Step-2. Load On
Check I phase & I neutral
If I neutral = 0
Earth is used.
Phase
Neutral
METER
EARTH
EL NE
Common
Neutral
10A
0A
34
Phase
Neutral
EARTH
Phase
Neutral
EARTH
35
Different Type of Current Transformers (CT)
36
Different Type of Potential Transformers (PT)
History of Energy Meter:
 The first accurate, recording electricity
consumption meter was a D.C(Direct Current).
 Dr. Hermann Aron, who patented it in 1883 in the
General Electric Company.
 It is commercially introduced into Great Britain from
1888.
 Aron's meter recorded the total energy used over
time, and showed it on a series of clock dials.
History of Energy Meter:
 The first specimen of the AC kilowatt-hour meter produced
on the basis of Hungarian Ottó Bláthy's patent and named
after him was presented by the Ganz Works at the
Frankfurt Fair in the autumn of 1889, and the first
induction kilowatt-hour meter was already marketed by the
factory at the end of the same year. These were the first
alternating-current wattmeters, known by the name of
Bláthy-meters.
History of Electromechanical Energy Meter:
 The most common type of electricity meter is the Thomson
or electromechanical induction watt-hour meter, invented
by Elihu Thomson in 1888.
 The electromechanical induction meter operates by
counting the revolutions of an aluminum disc which is
made to rotate at a speed proportional to the power. The
number of revolutions is thus proportional to the energy
usage.
 It consumes a small amount of power, typically around 2
watts
Classification of energy meter:
According to their Specification:
Energy Meter
Single phase Three phase and
three wire
Three phase and
four wire
1.Single phase: reference voltage: 220V
2. Three phase and three wire: reference voltage: 3X100/110V
3. Three phase and four wire: reference voltage:
3X57.7V/100/110V, 3X220V/380/415V
Classification of energy meter:
According to their connection:
Energy Meter
Connection through
transformers
Direct connection
1.Current from connection through transformers: 3X0.3 (1.2) A,
3X0.5 (2) A, 3X1.5 (6) A, and 3X5 (6) A, etc.
2. Current from direct connection: 3X5 (20) A, 3X10 (40) A, and
3X30 (100) A, etc
Classification of energy meter:
According to their Measuring Accuracy:
Energy Meter
Watt-hour Var-hour
1.Watt-hour accuracy class: 0.2S, 0.5S, 0.5, 1.0,2.0.
2.Var-hour accuracy class: 0.2S, 0.5S, 0.5, 1.0,2.0.
Classification of energy meter:
According to purposes, energy meters can be divided
into:
 Single phase energy meter
 Three-phase watt-hour energy meter
 Three-phase var-hour energy meter
 Maximum demand meter
 Multi-rate energy meter (time-based)
 Multifunctional watthour meter
 Copper loss meter
 Iron loss meter
 Prepayment energy meter
What is power?
 Electric power is the rate at which electrical energy is
transferred by an electric circuit. That means
Power = Energy(Work done) / Time
 The SI unit of power is the watt(named after the
scientist James Watt) that means one joule per second.
1 Watt = 1 Joule / Second.
 A 100 watt light bulb is a device that converts 100 joules of
electrical energy into 100 joules of electromagnetic
radiation (light) every second.
What is power?
The electric power in watts produced by an electric
current I consisting of a charge of Q coulombs every t
seconds passing through an electric potential (voltage)
difference of V is
where
Q is electric charge in coulombs
t is time in seconds
I is electric current in amperes
V is electric potential or voltage in volts
What is Energy?
 The term energy defines the amount of power consumed
/delivered over the period. That means..
Energy = Power x Time.
 1 kilo-watt hour = the energy delivered by 1000 watts of
power over over a one hour time period. That means…
Energy = Power x Time
= (1000 Joules/Second) x (3600 Seconds)
= 3,600,000 Joules = 3.6 million Joules!
That's a lot of Joules! So you see that kilo-watt hours is a
much better unit for large amounts of energy a one hour
time period.
Formula of power in various circuit:
Different Measurement Data in Displayedin Energy meter :
49
In EDMI Meter
In L&G Meter
In Elster Meter
In Elster Meter
Default Display Sample of Digital
Meter
Phasor Representation:
 Phasor Diagram
 Sine Wave
Phase Rotation:
Positive Phase Rotation
Positive Phase Rotation
Benefits of Phasor Analysis:
 Provide visual verification of errors in service
wiring
 Minimize or eliminate the need to use instrument
meters (volt, amp, phase angle)
 Facilitate the detection and trouble-shooting of:
 Cross-phased wires
 Wrong application
 Wrong CT and PT polarity
Energy meter testing Procedure:
1.First Process:
 With the help of a duly calibrated standard lamp of 1000 watt:-
A 1000-watt lamp if energized for one hour would consume one
unit of electrical energy.
 Switch off all electrical lamps/appliances, etc., in your house.
 Percentage error =
(energy registered by the meter – true energy) × 100
true energy
Energy meter testing Procedure:
2.Second Process:
 With the help of Meter constant which is indicated in the Meter
Body. e.g. X impulses /kWh i.e. X impulses per unit i.e. X times
blinking of LED installed on meter for 1 unit consumption of
electrical energy.
 We may cross check this meter constant by actually counting the
blinking of LED e.g. one unit should be registered by the meter in
3200 impulses i.e. 3200 times blinking of LED or ½ unit should be
registered in 1600 impulses or ¼ unit should be registered in 800
impulses and so on. If meter constant indicated on the meter
matches with your actual impulse count/number of blinks of LED, it
means that the meter is running ok.
Energy meter testing Procedure:
3.Third Process:
 With the help of a Voltmeter, Ammeter, Switch and a Stop
Watch:- Connect the Switch (SW), Voltmeter (V) and Ammeter
(A) as shown in the following circuit diagram:
S.L
N.O
Energy Meter
Initial Reading
(kWh) (X)
Energy
Meter
Final
Reading
(kWh) (Y)
V
(Volts)
I
(Amps)
T
(Seconds)
Energy by
calculation =
Vlt/1000x3600
(kWh)
Energy Meter
Reading (X)-(Y)
(kWh)
Energy meter testing Procedure:
4.Fourth Process:
With the help of a Meter Testing Set:
 PWS-2.3,
 PEWM-3CF,
 PRS-1.3,
 EDI
IEC Standards for meter testing:
S.L
N.O
IEC Standard N.O. Purpose
01. IEC 62053-11 For electromechanical meters
02. IEC 62053-21 For electronic meters
03. IEC 62052-11 For general requirements, tests & test conditions of
metering equipments.
Balanced Load?
Load/Unit Calculation:
S. L.
No
Appliance
used in
house
No. (A) Wattage per
appliance
(watts) (B)
Appliance use per
day (hours) (C)
Units consumed per month (30
days) (kWH) (AxBxCx30) /
1000
01. Fluorescent
Tube
2 40 6 14.40
02. Television 1 150 5 22.50
03. Refrigerator 1 150 16 72.50
04. Ceiling Fans 2 60 16 57.60
05. Lamps 2 100 10 60.00
06. Electric Iron 1 1500 0.5 22.50
07. Mixer 1 200 0.5 3.00
08. Air conditioner 1 2500 6 450
09. Geyser 1 2000 2 120.00
10. Water pump 1 550 1 16.50
11. Cooler 1 180 8 43.20
Total 881.70
AMR/SMART Metering System:
 AMR (Automated Meter Reading) and RMR
(Remote Meter Reading)
`
MD Manager
`
MD Manager
`
Web Browser
`
Web Browser
MultiDrive Servers
PowerSignature
Servers
MultiDrive
Comm. Servers
MD COM API
RADIO
DIRECT
P
L
C
/
D
L
C
G
P
R
S
/
E
D
G
E
/
3
G
GSM
Database Servers
PLC / DLC
Concentrator
RS232 / RS485
Convertor
TCP/UDP
Total Connectivity
Local
BTS
MTS
GP
Central
Server
Connecting Root of AMR Meter
Modem,
Antenna &
GPRS SIM
Server
In
GMCO
optical
fiber
GPRS/GSM Modem Used in AMR System
Frequently Answer Question:
Q. Why are electricity bills getting inflated after replacement of old
electromechanical meters by new electronic meters by the utilities?
A : 01: Energy consumed by the consumer is actually high.
02. New meter is working satisfactorily but the wiring to meter,
which was done earlier as per old electromechanical meter was
not correct.
Presented By –
Tanvir Ahmed
A.E, Energy Auditing Unit ,
BPDB,Dhaka

Más contenido relacionado

La actualidad más candente

prepaid energy meter using gsm
prepaid energy meter using gsm prepaid energy meter using gsm
prepaid energy meter using gsm
udaypallyreddy
 

La actualidad más candente (20)

Design & Building Smart Energy Meter
Design & Building Smart Energy MeterDesign & Building Smart Energy Meter
Design & Building Smart Energy Meter
 
Smart meter
Smart meterSmart meter
Smart meter
 
Advance Metering Infrastructure: Smart Meter
Advance Metering Infrastructure: Smart MeterAdvance Metering Infrastructure: Smart Meter
Advance Metering Infrastructure: Smart Meter
 
measurement of high voltage and high currents
 measurement of high voltage and high currents  measurement of high voltage and high currents
measurement of high voltage and high currents
 
prepaid energy meter using gsm
prepaid energy meter using gsm prepaid energy meter using gsm
prepaid energy meter using gsm
 
An approach to smart energy meter
An approach to smart energy meterAn approach to smart energy meter
An approach to smart energy meter
 
Electrical Energy Meter
Electrical Energy Meter Electrical Energy Meter
Electrical Energy Meter
 
AUTOMATIC ENERGY METER READING SYSTEM FOR BILLING PURPOSE
AUTOMATIC ENERGY METER READING SYSTEM FOR BILLING PURPOSEAUTOMATIC ENERGY METER READING SYSTEM FOR BILLING PURPOSE
AUTOMATIC ENERGY METER READING SYSTEM FOR BILLING PURPOSE
 
Smart Grid & WAMS
Smart Grid & WAMSSmart Grid & WAMS
Smart Grid & WAMS
 
Energy meter
Energy meterEnergy meter
Energy meter
 
SMART METER ppt
SMART METER pptSMART METER ppt
SMART METER ppt
 
Smart energy meter ppt
Smart energy meter   pptSmart energy meter   ppt
Smart energy meter ppt
 
Phasor Measurement Unit (PMU)
 Phasor Measurement Unit (PMU) Phasor Measurement Unit (PMU)
Phasor Measurement Unit (PMU)
 
Wide area network in smart grid kundan
Wide area network in smart grid kundanWide area network in smart grid kundan
Wide area network in smart grid kundan
 
Smart energy meter (Updated)
Smart energy meter (Updated)Smart energy meter (Updated)
Smart energy meter (Updated)
 
Advanced Metering Infrastructure (AMI)
Advanced Metering Infrastructure (AMI)Advanced Metering Infrastructure (AMI)
Advanced Metering Infrastructure (AMI)
 
Automatic meter reading nnb ppt
Automatic meter reading  nnb pptAutomatic meter reading  nnb ppt
Automatic meter reading nnb ppt
 
Calibration & Testing of Electronic Meters
Calibration & Testing of Electronic MetersCalibration & Testing of Electronic Meters
Calibration & Testing of Electronic Meters
 
energy theft detection
energy theft detectionenergy theft detection
energy theft detection
 
REPORT ON 33/11KV SUBSTATION
REPORT ON 33/11KV SUBSTATION REPORT ON 33/11KV SUBSTATION
REPORT ON 33/11KV SUBSTATION
 

Similar a meter.pptx

Basic electrical lab manual
Basic electrical lab manualBasic electrical lab manual
Basic electrical lab manual
Devashish Meena
 
Bai thi nghiem_linear_circuit_cttt
Bai thi nghiem_linear_circuit_ctttBai thi nghiem_linear_circuit_cttt
Bai thi nghiem_linear_circuit_cttt
kutyonljne
 
2426Lab7Series&ParallelCircuits
2426Lab7Series&ParallelCircuits2426Lab7Series&ParallelCircuits
2426Lab7Series&ParallelCircuits
Taylor Huston
 

Similar a meter.pptx (20)

Lab report 2
Lab report 2Lab report 2
Lab report 2
 
Basic electrical lab manual
Basic electrical lab manualBasic electrical lab manual
Basic electrical lab manual
 
Measuremnt of Power and Energy
Measuremnt of Power and EnergyMeasuremnt of Power and Energy
Measuremnt of Power and Energy
 
Unit 03 Construction & Operation of Watt meter & Energy meter
Unit   03 Construction & Operation of Watt meter & Energy meterUnit   03 Construction & Operation of Watt meter & Energy meter
Unit 03 Construction & Operation of Watt meter & Energy meter
 
eem-2020309.pdf
eem-2020309.pdfeem-2020309.pdf
eem-2020309.pdf
 
Bai thi nghiem_linear_circuit_cttt
Bai thi nghiem_linear_circuit_ctttBai thi nghiem_linear_circuit_cttt
Bai thi nghiem_linear_circuit_cttt
 
Lab 07 voltage_current_divider
Lab 07 voltage_current_dividerLab 07 voltage_current_divider
Lab 07 voltage_current_divider
 
Electronics AC Voltmeter & probes
Electronics AC Voltmeter & probesElectronics AC Voltmeter & probes
Electronics AC Voltmeter & probes
 
Electrical Machines
Electrical MachinesElectrical Machines
Electrical Machines
 
1 phase energy meter
1 phase energy meter1 phase energy meter
1 phase energy meter
 
2426Lab7Series&ParallelCircuits
2426Lab7Series&ParallelCircuits2426Lab7Series&ParallelCircuits
2426Lab7Series&ParallelCircuits
 
Engr2200 lab manual_lab2_
Engr2200 lab manual_lab2_Engr2200 lab manual_lab2_
Engr2200 lab manual_lab2_
 
Ect2
Ect2Ect2
Ect2
 
Testing of power_transformers_kt_80_gb_2
Testing of power_transformers_kt_80_gb_2Testing of power_transformers_kt_80_gb_2
Testing of power_transformers_kt_80_gb_2
 
IEMCON-2015
IEMCON-2015IEMCON-2015
IEMCON-2015
 
Single phase transformer
Single phase transformerSingle phase transformer
Single phase transformer
 
Power converter lab manual by chaturvedula
Power converter lab manual by chaturvedulaPower converter lab manual by chaturvedula
Power converter lab manual by chaturvedula
 
Introduction to Transformer Rated Metering
Introduction to Transformer Rated MeteringIntroduction to Transformer Rated Metering
Introduction to Transformer Rated Metering
 
Measurement of 3 phase power by two watt-meter method
Measurement of 3 phase power by two watt-meter methodMeasurement of 3 phase power by two watt-meter method
Measurement of 3 phase power by two watt-meter method
 
Npc informe final
Npc informe finalNpc informe final
Npc informe final
 

Último

Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Dr.Costas Sachpazis
 
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and workingUNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
rknatarajan
 
result management system report for college project
result management system report for college projectresult management system report for college project
result management system report for college project
Tonystark477637
 

Último (20)

(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
 
Introduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxIntroduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptx
 
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINEDJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
 
Introduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxIntroduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptx
 
University management System project report..pdf
University management System project report..pdfUniversity management System project report..pdf
University management System project report..pdf
 
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
 
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINEMANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
 
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
 
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdfONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
 
Russian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur Escorts
Russian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur EscortsRussian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur Escorts
Russian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur Escorts
 
Online banking management system project.pdf
Online banking management system project.pdfOnline banking management system project.pdf
Online banking management system project.pdf
 
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and workingUNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
 
Roadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and RoutesRoadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and Routes
 
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordCCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
 
result management system report for college project
result management system report for college projectresult management system report for college project
result management system report for college project
 
Glass Ceramics: Processing and Properties
Glass Ceramics: Processing and PropertiesGlass Ceramics: Processing and Properties
Glass Ceramics: Processing and Properties
 
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...
 

meter.pptx

  • 1. Presented By – Tanvir Ahmed A.E, Energy Auditing Unit , BPDB,Dhaka
  • 2. What is Electricity Meter?  A device to record Electrical Energy consumption/ delivery .
  • 5. Meter Terminology: Starting Current Current Range Influence parameters
  • 6. Specifications of Energy Meter:  Rating : In : 3x5; Vn : 3x110V(L-L), In : 3x30(100); Vn : 3x230/400V(L-L),  Starting Current :0.2%  Kwh, KVARH and MD in KW  TOU, 6 Tariff and 6 time zone  6 Month Billing data  RS232C
  • 7. Why Mechanical meters read less?  Influence Parameters  Age  Wear and Tear  Narrow Range  Mounting  Dust and Oil effect  Mechanical Counters
  • 8. Why electronic meters are preferred ?  Wide Range  Low starting current  Less effect of Influence parameters  More accurate  Tamper proof
  • 9. ROLE OF LED: CAL. LED REV. LED N-CUT EL
  • 10. REV LED *Indicates reverse flow of Energy •Reasons : *Incorrect wiring *Use of un isolated *Generator/ Inverters
  • 11. CAL LED High resolution out put device for meter checking
  • 12. EL •Due to ‘unbalanced’ Current. • Needs Attention •Neutral is touching the earth .
  • 13. N- Cut •Indicates current without voltage on Meter. • Contact discom immediately.
  • 14. * In general Phase, current is used for measurement. However if neutral Current varies by more than 10~ 12 % then Neutral current selected  Good electronic meters have Current sensors in both the  Phase path, and Neutral path  For Measurement, it chooses higher * of the two current.
  • 15.  Electro-mechanical Meter has Current sensor only on one wire  All Measurement based on phase wire current even when connected to neutral.
  • 16.
  • 17. 1.L and N swapped, load to Earth 2. L and N swapped, load partially connected to Earth
  • 18. 3.Load connected to Earth 4. Load partially connected to Earth
  • 19. 3.L and N swapped, l/O swapped, Load connected to Earth 4.L and N swapped, l/O swapped, Load partially connected to Earth
  • 20.  Wrong wiring, among others things can result in: Safety hazards (wires are still live, even when the main switch is off). Cause fire (if by mistake, phase and neutral wires get interchanged) Wrong Current flow (neighbours current can flow through your meter)
  • 21. 21 Connection Arrangement of Programmable Digital Energy Meter
  • 22. 1 2 3 4 1 5 6 7 8 9 10 11 LOAD R Y B N WHOLE CURRENT METERING Figure-1 N Y B R 4 K L k 1 2 i 3 K L K 6 k l 5 k 7 L l 8 9 11 LT CT METERING LOAD Figure -2 Figure-3 Vector diagram of Figure-1 & 2 3 I V 3 1 I 3   1 V 1  2 I2 2 V Here P= Total Power P1= Power for phase-1 P2= Power for phase-2 P3= Power for phase-3 Balance Condition : Voltage V1-n=V2-n=V3-n = V (P-n) Current I1=I2=I3 = I Phase Angle 1=23  P= P1+P2+P3 = V1.I1.Cos1V2.I2.Cos2V3.I3.Cos3 = 3 V.I.Cos 22 Connection Diagram of Whole Current & LT CT Energy Meter
  • 23. Wiring Diagram of Polyphase Direct Connected Meter
  • 24. 3-Element 4-Wire Figure-3.1 3 1 2 N R Y B v V u v u U V U v u k U V K L l 11 8 9 6 7 4 5 LOAD k l k K L K L l CT & PT OPERATED (HT METERING) METER CONNECTION 3-Element 4-Wire Figure-3.2 3 1 2 N R Y B v u U V v u k U V K L l 11 8 9 6 7 4 5 LOAD k l k K L K L l Y B R 2 v u v u k U V U V K 1 k l i L K L 7 5 3 8 9 LOAD Figure-3.3 2-Element 3-Wire Y B R 2 k K 1 k l i L K L 7 5 3 8 9 LOAD Figure-3.4 2-Element 3-Wire v V u v u U V U v u U V 24 Connection Diagram of 3-Element 4-Wire & 2-Element 3-Wire Energy Meter
  • 25. Wiring Diagram of Polyphase CT Connected Meter
  • 26. Wiring Diagram of Polyphase Instrument TR. Connected Meter
  • 28. Proper connection of 3-Element 4-Wire Energy Meter R B N Y 2 1 LOAD 5 3 4 7 6 9 8 11 k l k l k l K L K L K L U V u v U V u v U V u v CONNECTION CIRCUIT OF METER VECTOR DIAGRAM Fig.-5-1 Voltage RED Phase open circuited B N Y R U u V v U u V v LOAD 2 U u V v K k 1 L l 3 K k 4 5 9 7 L l k 6 K L l 8 11 B N Y R U u V v U u V v LOAD 2 U u V v K k 1 L l 3 K k 4 5 9 7 L l k 6 K L l 8 11 V 3 3 I  3 1 I 2  V 2 I 2 Similar for Yellow & Blue phase V 3 3 I  3 1 V 2  V 2 I 2 Current RED Phase open circuited V 3 3 I  3 1 I  1 1 V 2  V 2 I 2 CALCULATION P= P1+P2+P3 = V1.I1.Cos1V2.I2.Cos2V3.I3.Cos3 = 3 V.I.Cos Here P= Total Power P1= Power for phase-1 P2= Power for phase-2 P3=Power for phase-3 V1-n,V2-n ,V3-n = Phase voltage 1,2,3 = Phase angle between V & I Balance Condition : V1-n=V2-n =V3-n =V (p-n) I1=I2 =I3 =I 1 =2 =3 = P= 3.V.I. Cos PF=2.V.I. Cos CF=1.5 PF= P1+P2+P3 = 0V2.I2.Cos2V3.I3.Cos3 = 2 V.I.Cos PF=2.V.I. Cos CF=1.5 PF= P1+P2+P3 = 0V2.I2.Cos2V3.I3.Cos3 = 2 V.I.Cos Balance Condition : V1=V2 =V3 =V I1=I2 =I3 =I 1 =2 =3 = Balance Condition : V1=V2 =V3 =V I1=I2 =I3 =I 1 =2 =3 = Similar for Yellow & Blue phase Fig.-5-2 Fig.-5-3 FAULT ANALYSIS OF 3-ELEMENT 4-WIRE METERING P= Total power in proper connection = 3 V.I.Cos PF=2 V.I.Cos Correction Factor(CF)= P PF CF= 3 V.I.Cos2 V.I.Cos  28 Faulty Connection Analysis of 3-Element 4-Wire Energy Meter
  • 29. Fig.-5-6 V Fig.-5-5 Fig.-5-4 V V B N R Y U u Y N B R U u Y N B R U u Voltage Red and Blue Phase exchanged V v v v V u U u U k l k K L K 1 2 3 4 l k l K L L 6 5 7 8 9 LOAD 11 Current Red Phase incorrectly poled Voltage Red Phase incorrectly poled V v V v U u U u v k K L l K k 1 2 3 4 V v V v U u U u v k K L l K k 1 2 3 4 K L l k L l 6 5 7 8 9 LOAD 11 K L l k L l 6 5 7 8 9 LOAD 11 PF =P1+P2+P3 = V3.I1.Cos(120°+1)+V2.I2.Cos2 V1.I3.Cos(120°-3) = V.I Cos(120°+)+Cos Cos(120°-) = 0 Similar for Yellow & Blue phase Similar for Yellow & Blue phase PF =P2+P3-P1 = V2.I2.Cos2V3.I3.Cos3 -V1.I1.Cos(180°+1) = V2.I2.Cos2V3.I3.Cos3-V1.I1.Cos1 = V.I.Cos PF =P2+P3-P1 = V2.I2.Cos2V3.I3.Cos3 -V1.I1.Cos(180°+1) = V2.I2.Cos2V3.I3.Cos3-V1.I1.Cos1 = V.I.Cos PF =V.I. Cos  I3 V 3  3 3 V 1 2  CF= PF =0  1 1 I I2 2 V PF =V.I. Cos CF=3 CF=3 -V I3 3 V  3 1 1 I  2  3 I 3 V  3 1 V  -I1 2 1 1 I2 V2 I2 V2 CONNECTION CIRCUIT OF METER VECTOR DIAGRAM CALCULATION Balance Condition : V1=V2 =V3 =V I1=I2 =I3 =I 1 =2 =3 = Balance Condition : V1=V2 =V3 =V I1=I2 =I3 =I 1 =2 =3 = Balance Condition : V1=V2 =V3 =V I1=I2 =I3 =I 1 =2 =3 = FAULT ANALYSIS OF 3-ELEMENT 4-WIRE METERING 29 Faulty Connection Analysis of 3-Element 4-Wire Energy Meter
  • 30. Tools Testing:  Clamp on tester  Bulb tester  Electric Meter testing Kit.
  • 31. Typical Pts. Where Earth gets common with neutral  Metallic body Appliances.  Appliances connected with metal pipe line.  Building RCC.
  • 32. Wiring Defect:  If number of meters in one premise is only one, then there is no common Neutral problem.
  • 33. 33 Step-2. Load On Check I phase & I neutral If I neutral = 0 Earth is used. Phase Neutral METER EARTH EL NE Common Neutral 10A 0A
  • 35. 35 Different Type of Current Transformers (CT)
  • 36. 36 Different Type of Potential Transformers (PT)
  • 37. History of Energy Meter:  The first accurate, recording electricity consumption meter was a D.C(Direct Current).  Dr. Hermann Aron, who patented it in 1883 in the General Electric Company.  It is commercially introduced into Great Britain from 1888.  Aron's meter recorded the total energy used over time, and showed it on a series of clock dials.
  • 38. History of Energy Meter:  The first specimen of the AC kilowatt-hour meter produced on the basis of Hungarian Ottó Bláthy's patent and named after him was presented by the Ganz Works at the Frankfurt Fair in the autumn of 1889, and the first induction kilowatt-hour meter was already marketed by the factory at the end of the same year. These were the first alternating-current wattmeters, known by the name of Bláthy-meters.
  • 39. History of Electromechanical Energy Meter:  The most common type of electricity meter is the Thomson or electromechanical induction watt-hour meter, invented by Elihu Thomson in 1888.  The electromechanical induction meter operates by counting the revolutions of an aluminum disc which is made to rotate at a speed proportional to the power. The number of revolutions is thus proportional to the energy usage.  It consumes a small amount of power, typically around 2 watts
  • 40. Classification of energy meter: According to their Specification: Energy Meter Single phase Three phase and three wire Three phase and four wire 1.Single phase: reference voltage: 220V 2. Three phase and three wire: reference voltage: 3X100/110V 3. Three phase and four wire: reference voltage: 3X57.7V/100/110V, 3X220V/380/415V
  • 41. Classification of energy meter: According to their connection: Energy Meter Connection through transformers Direct connection 1.Current from connection through transformers: 3X0.3 (1.2) A, 3X0.5 (2) A, 3X1.5 (6) A, and 3X5 (6) A, etc. 2. Current from direct connection: 3X5 (20) A, 3X10 (40) A, and 3X30 (100) A, etc
  • 42. Classification of energy meter: According to their Measuring Accuracy: Energy Meter Watt-hour Var-hour 1.Watt-hour accuracy class: 0.2S, 0.5S, 0.5, 1.0,2.0. 2.Var-hour accuracy class: 0.2S, 0.5S, 0.5, 1.0,2.0.
  • 43. Classification of energy meter: According to purposes, energy meters can be divided into:  Single phase energy meter  Three-phase watt-hour energy meter  Three-phase var-hour energy meter  Maximum demand meter  Multi-rate energy meter (time-based)  Multifunctional watthour meter  Copper loss meter  Iron loss meter  Prepayment energy meter
  • 44. What is power?  Electric power is the rate at which electrical energy is transferred by an electric circuit. That means Power = Energy(Work done) / Time  The SI unit of power is the watt(named after the scientist James Watt) that means one joule per second. 1 Watt = 1 Joule / Second.  A 100 watt light bulb is a device that converts 100 joules of electrical energy into 100 joules of electromagnetic radiation (light) every second.
  • 45. What is power? The electric power in watts produced by an electric current I consisting of a charge of Q coulombs every t seconds passing through an electric potential (voltage) difference of V is where Q is electric charge in coulombs t is time in seconds I is electric current in amperes V is electric potential or voltage in volts
  • 46. What is Energy?  The term energy defines the amount of power consumed /delivered over the period. That means.. Energy = Power x Time.  1 kilo-watt hour = the energy delivered by 1000 watts of power over over a one hour time period. That means… Energy = Power x Time = (1000 Joules/Second) x (3600 Seconds) = 3,600,000 Joules = 3.6 million Joules! That's a lot of Joules! So you see that kilo-watt hours is a much better unit for large amounts of energy a one hour time period.
  • 47. Formula of power in various circuit:
  • 48. Different Measurement Data in Displayedin Energy meter :
  • 49. 49 In EDMI Meter In L&G Meter In Elster Meter In Elster Meter Default Display Sample of Digital Meter
  • 50. Phasor Representation:  Phasor Diagram  Sine Wave
  • 51. Phase Rotation: Positive Phase Rotation Positive Phase Rotation
  • 52. Benefits of Phasor Analysis:  Provide visual verification of errors in service wiring  Minimize or eliminate the need to use instrument meters (volt, amp, phase angle)  Facilitate the detection and trouble-shooting of:  Cross-phased wires  Wrong application  Wrong CT and PT polarity
  • 53. Energy meter testing Procedure: 1.First Process:  With the help of a duly calibrated standard lamp of 1000 watt:- A 1000-watt lamp if energized for one hour would consume one unit of electrical energy.  Switch off all electrical lamps/appliances, etc., in your house.  Percentage error = (energy registered by the meter – true energy) × 100 true energy
  • 54. Energy meter testing Procedure: 2.Second Process:  With the help of Meter constant which is indicated in the Meter Body. e.g. X impulses /kWh i.e. X impulses per unit i.e. X times blinking of LED installed on meter for 1 unit consumption of electrical energy.  We may cross check this meter constant by actually counting the blinking of LED e.g. one unit should be registered by the meter in 3200 impulses i.e. 3200 times blinking of LED or ½ unit should be registered in 1600 impulses or ¼ unit should be registered in 800 impulses and so on. If meter constant indicated on the meter matches with your actual impulse count/number of blinks of LED, it means that the meter is running ok.
  • 55. Energy meter testing Procedure: 3.Third Process:  With the help of a Voltmeter, Ammeter, Switch and a Stop Watch:- Connect the Switch (SW), Voltmeter (V) and Ammeter (A) as shown in the following circuit diagram: S.L N.O Energy Meter Initial Reading (kWh) (X) Energy Meter Final Reading (kWh) (Y) V (Volts) I (Amps) T (Seconds) Energy by calculation = Vlt/1000x3600 (kWh) Energy Meter Reading (X)-(Y) (kWh)
  • 56. Energy meter testing Procedure: 4.Fourth Process: With the help of a Meter Testing Set:  PWS-2.3,  PEWM-3CF,  PRS-1.3,  EDI
  • 57. IEC Standards for meter testing: S.L N.O IEC Standard N.O. Purpose 01. IEC 62053-11 For electromechanical meters 02. IEC 62053-21 For electronic meters 03. IEC 62052-11 For general requirements, tests & test conditions of metering equipments.
  • 59. Load/Unit Calculation: S. L. No Appliance used in house No. (A) Wattage per appliance (watts) (B) Appliance use per day (hours) (C) Units consumed per month (30 days) (kWH) (AxBxCx30) / 1000 01. Fluorescent Tube 2 40 6 14.40 02. Television 1 150 5 22.50 03. Refrigerator 1 150 16 72.50 04. Ceiling Fans 2 60 16 57.60 05. Lamps 2 100 10 60.00 06. Electric Iron 1 1500 0.5 22.50 07. Mixer 1 200 0.5 3.00 08. Air conditioner 1 2500 6 450 09. Geyser 1 2000 2 120.00 10. Water pump 1 550 1 16.50 11. Cooler 1 180 8 43.20 Total 881.70
  • 60. AMR/SMART Metering System:  AMR (Automated Meter Reading) and RMR (Remote Meter Reading)
  • 61. ` MD Manager ` MD Manager ` Web Browser ` Web Browser MultiDrive Servers PowerSignature Servers MultiDrive Comm. Servers MD COM API RADIO DIRECT P L C / D L C G P R S / E D G E / 3 G GSM Database Servers PLC / DLC Concentrator RS232 / RS485 Convertor TCP/UDP Total Connectivity
  • 62. Local BTS MTS GP Central Server Connecting Root of AMR Meter Modem, Antenna & GPRS SIM Server In GMCO optical fiber
  • 63. GPRS/GSM Modem Used in AMR System
  • 64. Frequently Answer Question: Q. Why are electricity bills getting inflated after replacement of old electromechanical meters by new electronic meters by the utilities? A : 01: Energy consumed by the consumer is actually high. 02. New meter is working satisfactorily but the wiring to meter, which was done earlier as per old electromechanical meter was not correct.
  • 65.