150mm AV / DATA CABLE TRAY.
TRUNKINGS RISE TO SOFFIT
DB L
18CHANNEL
6A DIMMABLE POWER UNIT
TIGER MODE TP-06-18
MODE REMOTE TIMER
RT-00-10
2" GAS TO KITCHEN
SOLENOID VALVE CONTROLLED
BY MERLIN CT1200S GAS SAFETY SYSTEM
2" GAS SPLITS
1) RISES IN
CEILING TO PLANTROOM
2)RISES TO GROUND CEILING TO KITCHEN
300MM CABLE TRAYS
15mm CWS
15mm CWS TO DISHWASHER
DHW DROP FROM ABOVE
28mm FLOW
DHW RISES TO ABOVE
15mm RETURN
2" GAS DROPS IN
SERVICES COLUMN
5"EV
6L/S
15mmCWS
RISES TO ABOVE
1050x360x1338
22mm CWS RISES TO SOFFIT
22mm DHW F&R RISE TO SOFFIT
28MM CWS IN CEILING
WCs & BAR
28MM CWS IN CEILING VOID
TO SERVE BOH
15mm CWS TO ICE MACHINES
WC FAN
150mm /
66L/S@70Pa
5" EV
6L/S
GROUND LEVEL
22mm CWS,22mmDHW F&15mmR, 2"DRAIN
POP UP
No.1
POP UP
No.2
POP UP
No.3
POP UP
No.6
POP UP
No.5
POP UP
No.4
Soil Manifold Gradient = 1deg(18mm/m)
Air admittance valve before last connection
AIR ADMITTANCE VALE
IT DB
14W SPN
2" GAS SOLENOID
DRAIN MAJOR
400mmH
DRAIN MAJOR
400mmH
RETURN AIR LOUVER
1580
BAR WASTE 50MM SS Europipe
VCD
FA SG13 -
PREP AREA FRESH AIR
SUPPLY100L/s
VCD
FA SG14 -
PREP AREA FRESH AIR
SUPPLY 100L/s
2" DRAINMAJOR DISCHARGE PIPES
403
302
690
82mm BLUCHER
50mm BLUCHER
50mm BLUCHER
FA SG15 -
WASHUP AREA FRESH AIR
SUPPLY250L/s
EG14 -
220L/s
EG13 -
220L/s
FA SG16 -
SUPPLY 250L/s
POP UP
No.1
POP UP
No.2
POP UP
No.3
POP UP
No.6
POP UP
No.5
POP UP
No.4
CLEANERS'
SINK
E E
E E
E E
E E
E E
2820(STAINLESSGANTRY)
3235 (STAINLESS GANTRY)
800
4235 (STAINLESS GANTRY)
400 400
2920(TIMBERBULKHEAD)
7920 (STAINLESS GANTRY)
8020 (TIMBER BULKHEAD)
500
400
8020 (TIMBER BULKHEAD)
450
2820(STAINLESSGANTRY)
2920(TIMBERBULKHEAD)
400
500
400
500
400
500
GAS
METER
TEAM
ROOM
300L DHW
CALORIFIER
2046mmH
C13 TYPE FLUES
5" EV
6L/S
5" EV
6L/S
MITSUBISHI
(20.25kW)
40mm DRAIN DROPS TO POP UP NO3 BELOW
WC FAN
100MM /
12L/S@30Pa
C13 TYPE FLUES
DHW DROP TO BELOW
28mm FLOW
DHW RISES FROM BELOW
15mm RETURN
15mmCWS
RISES TO ABOVE
MEZZANINE LEVEL
3000.0000
3850.0000
3 X MITSUBISHI PUHZ-P250YHA3
FAN COIL CONDENSERS
MITSUBISHI
(20.25kW)
FREEZER
LPHC068
16ATPN
CHILLER
MPHC026
16ATPN
CELLAR
MPHC034
20ATPN
LPHW EXPANSION VESSEL
LOWLOSS HEADER
8-AC-0.195m3/S
14-AC-0.18m3/S
5-AC-0.195m3/S 6-AC-0.195m3/S
15-AC-0.195m3/S
17-AC-0.195m3/S18-AC-0.195m3/S 16-FA-0.144m3/S
800x800mm KITCHEN EXTRACT DUCT
DISCHARGE NOZZLE 0.55m2 / 15m/s.
DUCT RUNS VERTICAL TO 1m ABOVE
PARAPIT
SUPPLY AIR CONNECTIONS
DUCT RISES TO MEZZ LEVEL
AND ENTERS PLANTROOM
0.88m3/s0.88m3/s
0.88m3/s 0.88m3/s
0.76m3/s
0.76m3/s 0.76m3/s
VCD
F/D
F/D
12-AC-0.18m3/S
11-AC-0.18m3/S
2-AC-0.195m3/S 3-AC-0.195m3/S
20-AC-0.195m3/S21-AC-0.195m3/S22-FA-0.144m3/S 19-FA-0.144m3/S
1-FA-0.144m3/S 4-FA-0.144m3/S
1.12m3/s
1.12m3/s
7-FA-0.144m3/S
SUPPLY DUCTS RISES TO HL
AND RUNS ALONG SOFFIT
0.76m3/s
0.76m3/s 0.76m3/s
800Wx400H
1000X400
VCD
VCD VCD
1000Wx400H - 2416L/s@6m/s
KITCHEN SUPPLY
SET UP
OVER EXTRACT
AIRTEMPERINGCONDENSER
20KW.1540X900X320
AIRTEMPERINGCONDENSER
20KW.1540X900X320
AIRTEMPERINGCONDENSER
20KW.1540X900X320
2" GAS SOLENOID
SYSTEM PUMP
MAGNA3 D40-100F
GLYCOL
UNIT
13A SPN
GLYCOL
UNIT
13A SPN
GLYCOL
UNIT
13A SPN
GLYCOL
UNIT
13A SPN
22mm CWS FOR COKE
VCD
IT CONDENSERS
23-RETURNAIR
500
1200Wx600H
5.8m3/s@8m/s
1200Wx600H
8m/s
1200Wx600H
8m/s
TRANSITION
1100 x 800H TO
800 x 500H
800x500H
9504m3/hR 6m/s
WASHUP/ICE MACHINE EXTRACT 0.64m3/S
PREP AREA FRESH AIR
SUPPLY150L/s
654
614
700
1004
754
548
596
793 377
POP UP
No.1
RELIEF VALVE PIPEWORK RATED TO 110degC
50mm BLUCHER
50mm BLUCHER
WASHUPSUPPLY 0.25m3/S
FA SG11 -
SUPPLY 24L/s
2 PERSON BANQUETTE SEATS x 11 = 22 No. COVERS
TOTAL RESTAURANT DINING COVERS = 248 No. COVERS
6 & OVER 58 No. COVERS 23%
4 & 5 144 No. COVERS 58%
2 46 No. COVERS 19%
WITH 'ZONE A' CLOSED = 226 No. COVERS
WITH 'ZONE B' CLOSED = 228 No. COVERS
WITH 'ZONES A & B' CLOSED = 206 No. COVERS
PINK DOTTED LINE INDICATES WALL TO BE
TAKEN FULL HEIGHT - 6500mm
SEALS
ELECTRICS
ALL ELECTRICAL WORKS TO BE CARRIED OUT IN ACCORDANCE WITH
PHDD DRAWINGS
FIRE ALARM SYSTEM
THE PROPOSED FIRE ALARM WILL BE INSTALLED TO BS 5839 : PART 1
: 2002 TO L2 STANDARD. THIS WILL BE CONNECTED TO THE
LANDLORD'S SYSTEM IN ACCORDANCE WITH THEIR INSTRUCTION.
SMOKE DETECTION TO CEILING VOIDS TO BE INCLUDED
EMERGENCY LIGHTING
EMERGENCY LIGHTING SYSTEM TO BE PROVIDED IN ACCORDANCE
WITH BS 5266 : PART 1 : 2005
FIRE STOPPING
FIRE STOPPING TO BE INSERTED INTO CEILING AS REQUIRED.
ALL DUCTWORK PASSING THROUGH COMPARTMENT FLOORS AND
WALLS TO BE PROTECTED BY FIRE COLLARS
NOTICES
NOTICES WITH THE WORDS 'PUSH BAR TO OPEN' TO BE DISPLAYED
ON ALL DOORS FITTED WITH PANIC BOLTS
ALL FIRE RESISTING SELF CLOSING DOORS TO BE PERMANENTLY
MARKED ON EACH SIDE AT EYE LEVEL WITH A BLUE CIRCULAR
NOTICE BEARING THE WORDS 'FIRE DOOR - KEEP SHUT' IN WHICH
LETTERS ARE NOT TO BE LESS THAN 5mm IN HEIGHT
PLANT
ROOM
TEAM
ROOM
OFFICE
STORE
800x800mm KITCHEN
EXTRACT DUCT
E E
STORE
FA-0.576m3/S
34-FA-0.266m3/S
500 x 200 BELLMOUTH
30-AC-0.22m3/S 25-AC-0.22m3/S
29-AC-0.22m3/S 26-AC-0.22m3/S
28-AC-0.22m3/S 27-AC-0.22m3/S
MULTI-CONE DIFFUSERS C/W
TWIN BLADE TYPE (R) DAMPER
3No: 450 X 200 DOUBLE
DEFLECTION SIDE WALL
GRILLE.
31-FA- 0.19m3s
32-FA- 0.19m3s
500
30mm external Mezz
flanges on MMF casing.
30mm external Mezz
flanges on MMF casing.
Side Elevation of ESPs, UVO and MMF
PUHZ-P250YHA3
PUHZ-P250YHA3
PUHZ-P250YHA3
PEA-RP250GAQ
PEA-RP250GAQ
PEA-RP250GAQ
300L
EXPANSION
VESSEL
MIKROFILL
SOLENOID VALVE
FUSIBLE
LINK
DHW SCHEMATIC
GAS
CWS
2" 11
2"
11
2"1"
1"11
2"
11
4"
11
4"
1"
1"
MULTI-CONE DIFFUSERS
C/W TWIN BLADE TYPE (R)
DAMPER
3No: 450 X 200 DOUBLE
DEFLECTION SIDE WALL
GRILLE.
500 x 200 BELLMOUTH
HVAC
TGI FRIDAYS STAINES
C2 1of1
1:50@A019/10/2015NJH
Project
PH Design & Deliver Ltd, Park Holland Building
Sampson Street, Stoke on Trent, ST1 5EZPHDD

Más contenido relacionado

La actualidad más candente (10)

Td90 straddle mount
Td90 straddle mountTd90 straddle mount
Td90 straddle mount
 
Fae Interruptores valvulas.pdf
Fae Interruptores valvulas.pdfFae Interruptores valvulas.pdf
Fae Interruptores valvulas.pdf
 
New holland w50 tc compact wheel loader parts catalogue manual instant download
New holland w50 tc compact wheel loader parts catalogue manual instant downloadNew holland w50 tc compact wheel loader parts catalogue manual instant download
New holland w50 tc compact wheel loader parts catalogue manual instant download
 
632 Lagina Trl - Sheet - A1-00 - FLOOR PLAN
632 Lagina Trl - Sheet - A1-00 - FLOOR PLAN632 Lagina Trl - Sheet - A1-00 - FLOOR PLAN
632 Lagina Trl - Sheet - A1-00 - FLOOR PLAN
 
Corpo de borboleta fiat
Corpo de borboleta fiatCorpo de borboleta fiat
Corpo de borboleta fiat
 
Fc 450 2018 moteur
Fc 450 2018 moteurFc 450 2018 moteur
Fc 450 2018 moteur
 
John deere maximizer combine 9400 parts catalog
John deere maximizer combine 9400 parts catalogJohn deere maximizer combine 9400 parts catalog
John deere maximizer combine 9400 parts catalog
 
Te 250i 2018 chassis
Te 250i 2018 chassisTe 250i 2018 chassis
Te 250i 2018 chassis
 
SULION Lámparas e Iluminación para casa
SULION Lámparas e Iluminación para casaSULION Lámparas e Iluminación para casa
SULION Lámparas e Iluminación para casa
 
Lot 280 Bogdanich way
Lot 280 Bogdanich wayLot 280 Bogdanich way
Lot 280 Bogdanich way
 

Destacado

BIM COORDINATION PORTOFOLIOOO
BIM COORDINATION PORTOFOLIOOOBIM COORDINATION PORTOFOLIOOO
BIM COORDINATION PORTOFOLIOOO
Mohab Magdy,PMP
 
Combined BIM & Design Coordination Workflow-r01
Combined BIM & Design Coordination Workflow-r01Combined BIM & Design Coordination Workflow-r01
Combined BIM & Design Coordination Workflow-r01
saed saffarini
 
BIM & Coordination Work Process Presentation
BIM & Coordination Work Process PresentationBIM & Coordination Work Process Presentation
BIM & Coordination Work Process Presentation
Indranath Sinha
 

Destacado (17)

Ablution Power feeding & calculations
Ablution Power feeding & calculationsAblution Power feeding & calculations
Ablution Power feeding & calculations
 
3D Renderings
3D Renderings3D Renderings
3D Renderings
 
Haram Expansion cables arrangement, MEP coordination and cable trays maneuver
Haram Expansion cables arrangement, MEP coordination and cable trays maneuverHaram Expansion cables arrangement, MEP coordination and cable trays maneuver
Haram Expansion cables arrangement, MEP coordination and cable trays maneuver
 
Haram Expansion M.V substations diversified feeding sources Scenrio
Haram Expansion M.V substations diversified feeding sources ScenrioHaram Expansion M.V substations diversified feeding sources Scenrio
Haram Expansion M.V substations diversified feeding sources Scenrio
 
1 Generral Layout
1 Generral Layout1 Generral Layout
1 Generral Layout
 
Haram complementary projects temporary feeding proposals
Haram complementary projects temporary feeding proposalsHaram complementary projects temporary feeding proposals
Haram complementary projects temporary feeding proposals
 
Pinnacle Infotech partaking at 2017 PCI Convention
 Pinnacle Infotech partaking at 2017 PCI Convention  Pinnacle Infotech partaking at 2017 PCI Convention
Pinnacle Infotech partaking at 2017 PCI Convention
 
BIM COORDINATION PORTOFOLIOOO
BIM COORDINATION PORTOFOLIOOOBIM COORDINATION PORTOFOLIOOO
BIM COORDINATION PORTOFOLIOOO
 
Diversifying source feeding loads for chiller Ajyad Haram
Diversifying source feeding loads for chiller Ajyad HaramDiversifying source feeding loads for chiller Ajyad Haram
Diversifying source feeding loads for chiller Ajyad Haram
 
Construction Coordination Underground M.V Relocation works
Construction Coordination Underground M.V Relocation worksConstruction Coordination Underground M.V Relocation works
Construction Coordination Underground M.V Relocation works
 
Temp. Relocation of Electrical utilities @ Lowering Of Jabal Al-Kabaa Project
Temp. Relocation of Electrical utilities @ Lowering Of Jabal Al-Kabaa ProjectTemp. Relocation of Electrical utilities @ Lowering Of Jabal Al-Kabaa Project
Temp. Relocation of Electrical utilities @ Lowering Of Jabal Al-Kabaa Project
 
110 K.V SIEMENS TRANSFORMER JACKING AND SLIDING SCENARIO
110 K.V SIEMENS TRANSFORMER JACKING AND SLIDING SCENARIO110 K.V SIEMENS TRANSFORMER JACKING AND SLIDING SCENARIO
110 K.V SIEMENS TRANSFORMER JACKING AND SLIDING SCENARIO
 
M.V/H.V Cable trays earthing systems
M.V/H.V Cable trays earthing systemsM.V/H.V Cable trays earthing systems
M.V/H.V Cable trays earthing systems
 
Combined BIM & Design Coordination Workflow-r01
Combined BIM & Design Coordination Workflow-r01Combined BIM & Design Coordination Workflow-r01
Combined BIM & Design Coordination Workflow-r01
 
BIM & Coordination Work Process Presentation
BIM & Coordination Work Process PresentationBIM & Coordination Work Process Presentation
BIM & Coordination Work Process Presentation
 
Honeymoon suite bedroom tutorial ferry
Honeymoon suite bedroom tutorial ferryHoneymoon suite bedroom tutorial ferry
Honeymoon suite bedroom tutorial ferry
 
How to write a good business letter
How to write a good business letter   How to write a good business letter
How to write a good business letter
 

Similar a STAINES AP-PLANS PHDD C2-A0 HVAC MECH

STAINES AP-PLANS PHDD C5 4 11 15-AO FIRE GROUND
STAINES AP-PLANS PHDD C5 4 11 15-AO FIRE GROUNDSTAINES AP-PLANS PHDD C5 4 11 15-AO FIRE GROUND
STAINES AP-PLANS PHDD C5 4 11 15-AO FIRE GROUND
Nick Hyde CEng MIMechE
 

Similar a STAINES AP-PLANS PHDD C2-A0 HVAC MECH (20)

STAINES AP-PLANS PHDD C5 4 11 15-AO FIRE GROUND
STAINES AP-PLANS PHDD C5 4 11 15-AO FIRE GROUNDSTAINES AP-PLANS PHDD C5 4 11 15-AO FIRE GROUND
STAINES AP-PLANS PHDD C5 4 11 15-AO FIRE GROUND
 
heat exchangers | column components | couplings
heat exchangers | column components | couplingsheat exchangers | column components | couplings
heat exchangers | column components | couplings
 
Bombas Dosadoras Williams
Bombas Dosadoras WilliamsBombas Dosadoras Williams
Bombas Dosadoras Williams
 
Catálogo Geral Williams
Catálogo Geral WilliamsCatálogo Geral Williams
Catálogo Geral Williams
 
Jual ariston 082113812149
Jual ariston 082113812149Jual ariston 082113812149
Jual ariston 082113812149
 
Pasang ariston water heater 082122541663
Pasang ariston water heater 082122541663Pasang ariston water heater 082122541663
Pasang ariston water heater 082122541663
 
Gauges Transmitters Switches Product guide 2016
Gauges Transmitters Switches Product guide 2016Gauges Transmitters Switches Product guide 2016
Gauges Transmitters Switches Product guide 2016
 
Modelo 1
Modelo 1Modelo 1
Modelo 1
 
Blow-Tech Engineers, Mumbai, Direct Drive Blowers
Blow-Tech Engineers, Mumbai, Direct Drive BlowersBlow-Tech Engineers, Mumbai, Direct Drive Blowers
Blow-Tech Engineers, Mumbai, Direct Drive Blowers
 
Blow Tech Engineers, Mumbai, Ventilation Systems
Blow Tech Engineers, Mumbai, Ventilation SystemsBlow Tech Engineers, Mumbai, Ventilation Systems
Blow Tech Engineers, Mumbai, Ventilation Systems
 
Rte 1 en
Rte 1 enRte 1 en
Rte 1 en
 
Niva Hava Perdesi Katolog 2021
Niva Hava Perdesi Katolog 2021Niva Hava Perdesi Katolog 2021
Niva Hava Perdesi Katolog 2021
 
hvac refragration Pipes size and table
hvac refragration Pipes size and tablehvac refragration Pipes size and table
hvac refragration Pipes size and table
 
Continental Industrie
Continental IndustrieContinental Industrie
Continental Industrie
 
Hs29 6 20-ton_ehb_hs29_072to240_0706
Hs29 6 20-ton_ehb_hs29_072to240_0706Hs29 6 20-ton_ehb_hs29_072to240_0706
Hs29 6 20-ton_ehb_hs29_072to240_0706
 
Catálogo Williams _ Vdual seal plunger
Catálogo Williams _ Vdual seal plunger   Catálogo Williams _ Vdual seal plunger
Catálogo Williams _ Vdual seal plunger
 
Catálogo Williams _ V series
Catálogo Williams _ V series Catálogo Williams _ V series
Catálogo Williams _ V series
 
Sb ls screw-fixed-speed_ver.3.0_en
Sb ls screw-fixed-speed_ver.3.0_enSb ls screw-fixed-speed_ver.3.0_en
Sb ls screw-fixed-speed_ver.3.0_en
 
Misting pumps catalogue
Misting pumps catalogueMisting pumps catalogue
Misting pumps catalogue
 
7311032-ELE.09-20.lr.pdf
7311032-ELE.09-20.lr.pdf7311032-ELE.09-20.lr.pdf
7311032-ELE.09-20.lr.pdf
 

STAINES AP-PLANS PHDD C2-A0 HVAC MECH

  • 1. 150mm AV / DATA CABLE TRAY. TRUNKINGS RISE TO SOFFIT DB L 18CHANNEL 6A DIMMABLE POWER UNIT TIGER MODE TP-06-18 MODE REMOTE TIMER RT-00-10 2" GAS TO KITCHEN SOLENOID VALVE CONTROLLED BY MERLIN CT1200S GAS SAFETY SYSTEM 2" GAS SPLITS 1) RISES IN CEILING TO PLANTROOM 2)RISES TO GROUND CEILING TO KITCHEN 300MM CABLE TRAYS 15mm CWS 15mm CWS TO DISHWASHER DHW DROP FROM ABOVE 28mm FLOW DHW RISES TO ABOVE 15mm RETURN 2" GAS DROPS IN SERVICES COLUMN 5"EV 6L/S 15mmCWS RISES TO ABOVE 1050x360x1338 22mm CWS RISES TO SOFFIT 22mm DHW F&R RISE TO SOFFIT 28MM CWS IN CEILING WCs & BAR 28MM CWS IN CEILING VOID TO SERVE BOH 15mm CWS TO ICE MACHINES WC FAN 150mm / 66L/S@70Pa 5" EV 6L/S GROUND LEVEL 22mm CWS,22mmDHW F&15mmR, 2"DRAIN POP UP No.1 POP UP No.2 POP UP No.3 POP UP No.6 POP UP No.5 POP UP No.4 Soil Manifold Gradient = 1deg(18mm/m) Air admittance valve before last connection AIR ADMITTANCE VALE IT DB 14W SPN 2" GAS SOLENOID DRAIN MAJOR 400mmH DRAIN MAJOR 400mmH RETURN AIR LOUVER 1580 BAR WASTE 50MM SS Europipe VCD FA SG13 - PREP AREA FRESH AIR SUPPLY100L/s VCD FA SG14 - PREP AREA FRESH AIR SUPPLY 100L/s 2" DRAINMAJOR DISCHARGE PIPES 403 302 690 82mm BLUCHER 50mm BLUCHER 50mm BLUCHER FA SG15 - WASHUP AREA FRESH AIR SUPPLY250L/s EG14 - 220L/s EG13 - 220L/s FA SG16 - SUPPLY 250L/s POP UP No.1 POP UP No.2 POP UP No.3 POP UP No.6 POP UP No.5 POP UP No.4 CLEANERS' SINK E E E E E E E E E E 2820(STAINLESSGANTRY) 3235 (STAINLESS GANTRY) 800 4235 (STAINLESS GANTRY) 400 400 2920(TIMBERBULKHEAD) 7920 (STAINLESS GANTRY) 8020 (TIMBER BULKHEAD) 500 400 8020 (TIMBER BULKHEAD) 450 2820(STAINLESSGANTRY) 2920(TIMBERBULKHEAD) 400 500 400 500 400 500 GAS METER TEAM ROOM 300L DHW CALORIFIER 2046mmH C13 TYPE FLUES 5" EV 6L/S 5" EV 6L/S MITSUBISHI (20.25kW) 40mm DRAIN DROPS TO POP UP NO3 BELOW WC FAN 100MM / 12L/S@30Pa C13 TYPE FLUES DHW DROP TO BELOW 28mm FLOW DHW RISES FROM BELOW 15mm RETURN 15mmCWS RISES TO ABOVE MEZZANINE LEVEL 3000.0000 3850.0000 3 X MITSUBISHI PUHZ-P250YHA3 FAN COIL CONDENSERS MITSUBISHI (20.25kW) FREEZER LPHC068 16ATPN CHILLER MPHC026 16ATPN CELLAR MPHC034 20ATPN LPHW EXPANSION VESSEL LOWLOSS HEADER 8-AC-0.195m3/S 14-AC-0.18m3/S 5-AC-0.195m3/S 6-AC-0.195m3/S 15-AC-0.195m3/S 17-AC-0.195m3/S18-AC-0.195m3/S 16-FA-0.144m3/S 800x800mm KITCHEN EXTRACT DUCT DISCHARGE NOZZLE 0.55m2 / 15m/s. DUCT RUNS VERTICAL TO 1m ABOVE PARAPIT SUPPLY AIR CONNECTIONS DUCT RISES TO MEZZ LEVEL AND ENTERS PLANTROOM 0.88m3/s0.88m3/s 0.88m3/s 0.88m3/s 0.76m3/s 0.76m3/s 0.76m3/s VCD F/D F/D 12-AC-0.18m3/S 11-AC-0.18m3/S 2-AC-0.195m3/S 3-AC-0.195m3/S 20-AC-0.195m3/S21-AC-0.195m3/S22-FA-0.144m3/S 19-FA-0.144m3/S 1-FA-0.144m3/S 4-FA-0.144m3/S 1.12m3/s 1.12m3/s 7-FA-0.144m3/S SUPPLY DUCTS RISES TO HL AND RUNS ALONG SOFFIT 0.76m3/s 0.76m3/s 0.76m3/s 800Wx400H 1000X400 VCD VCD VCD 1000Wx400H - 2416L/s@6m/s KITCHEN SUPPLY SET UP OVER EXTRACT AIRTEMPERINGCONDENSER 20KW.1540X900X320 AIRTEMPERINGCONDENSER 20KW.1540X900X320 AIRTEMPERINGCONDENSER 20KW.1540X900X320 2" GAS SOLENOID SYSTEM PUMP MAGNA3 D40-100F GLYCOL UNIT 13A SPN GLYCOL UNIT 13A SPN GLYCOL UNIT 13A SPN GLYCOL UNIT 13A SPN 22mm CWS FOR COKE VCD IT CONDENSERS 23-RETURNAIR 500 1200Wx600H 5.8m3/s@8m/s 1200Wx600H 8m/s 1200Wx600H 8m/s TRANSITION 1100 x 800H TO 800 x 500H 800x500H 9504m3/hR 6m/s WASHUP/ICE MACHINE EXTRACT 0.64m3/S PREP AREA FRESH AIR SUPPLY150L/s 654 614 700 1004 754 548 596 793 377 POP UP No.1 RELIEF VALVE PIPEWORK RATED TO 110degC 50mm BLUCHER 50mm BLUCHER WASHUPSUPPLY 0.25m3/S FA SG11 - SUPPLY 24L/s 2 PERSON BANQUETTE SEATS x 11 = 22 No. COVERS TOTAL RESTAURANT DINING COVERS = 248 No. COVERS 6 & OVER 58 No. COVERS 23% 4 & 5 144 No. COVERS 58% 2 46 No. COVERS 19% WITH 'ZONE A' CLOSED = 226 No. COVERS WITH 'ZONE B' CLOSED = 228 No. COVERS WITH 'ZONES A & B' CLOSED = 206 No. COVERS PINK DOTTED LINE INDICATES WALL TO BE TAKEN FULL HEIGHT - 6500mm SEALS ELECTRICS ALL ELECTRICAL WORKS TO BE CARRIED OUT IN ACCORDANCE WITH PHDD DRAWINGS FIRE ALARM SYSTEM THE PROPOSED FIRE ALARM WILL BE INSTALLED TO BS 5839 : PART 1 : 2002 TO L2 STANDARD. THIS WILL BE CONNECTED TO THE LANDLORD'S SYSTEM IN ACCORDANCE WITH THEIR INSTRUCTION. SMOKE DETECTION TO CEILING VOIDS TO BE INCLUDED EMERGENCY LIGHTING EMERGENCY LIGHTING SYSTEM TO BE PROVIDED IN ACCORDANCE WITH BS 5266 : PART 1 : 2005 FIRE STOPPING FIRE STOPPING TO BE INSERTED INTO CEILING AS REQUIRED. ALL DUCTWORK PASSING THROUGH COMPARTMENT FLOORS AND WALLS TO BE PROTECTED BY FIRE COLLARS NOTICES NOTICES WITH THE WORDS 'PUSH BAR TO OPEN' TO BE DISPLAYED ON ALL DOORS FITTED WITH PANIC BOLTS ALL FIRE RESISTING SELF CLOSING DOORS TO BE PERMANENTLY MARKED ON EACH SIDE AT EYE LEVEL WITH A BLUE CIRCULAR NOTICE BEARING THE WORDS 'FIRE DOOR - KEEP SHUT' IN WHICH LETTERS ARE NOT TO BE LESS THAN 5mm IN HEIGHT PLANT ROOM TEAM ROOM OFFICE STORE 800x800mm KITCHEN EXTRACT DUCT E E STORE FA-0.576m3/S 34-FA-0.266m3/S 500 x 200 BELLMOUTH 30-AC-0.22m3/S 25-AC-0.22m3/S 29-AC-0.22m3/S 26-AC-0.22m3/S 28-AC-0.22m3/S 27-AC-0.22m3/S MULTI-CONE DIFFUSERS C/W TWIN BLADE TYPE (R) DAMPER 3No: 450 X 200 DOUBLE DEFLECTION SIDE WALL GRILLE. 31-FA- 0.19m3s 32-FA- 0.19m3s 500 30mm external Mezz flanges on MMF casing. 30mm external Mezz flanges on MMF casing. Side Elevation of ESPs, UVO and MMF PUHZ-P250YHA3 PUHZ-P250YHA3 PUHZ-P250YHA3 PEA-RP250GAQ PEA-RP250GAQ PEA-RP250GAQ 300L EXPANSION VESSEL MIKROFILL SOLENOID VALVE FUSIBLE LINK DHW SCHEMATIC GAS CWS 2" 11 2" 11 2"1" 1"11 2" 11 4" 11 4" 1" 1" MULTI-CONE DIFFUSERS C/W TWIN BLADE TYPE (R) DAMPER 3No: 450 X 200 DOUBLE DEFLECTION SIDE WALL GRILLE. 500 x 200 BELLMOUTH HVAC TGI FRIDAYS STAINES C2 1of1 1:50@A019/10/2015NJH Project PH Design & Deliver Ltd, Park Holland Building Sampson Street, Stoke on Trent, ST1 5EZPHDD