9. A building has a U-value of 0.5 W/m2
.K and a total exposed surface area of 384
m2
. The building is subjected to an external load (only sensible) of 2 kW and an
internal load of 1.2 kW (sensible). If the required internal temperature is 25o
C, state
-Estimation Of Required
Cooling/Heating Capacity
..Sample Problems
whether a cooling system is required or a heating system is required when the
external temperature is 3o
C. How the results will change, if the U-value of the
building is reduced to 0.36 W/m.K?
Ans.: From energy balance,
C
33
.
8
384
x
5
.
0
1000
x
)
2
.
1
2
(
25
UA
)
Q
Q
(
T
T o
sensible
int
solar
in
bal
,
out =
+
−
=
+
−
=
Since the outdoor temperature at balance point is greater than the external
temperature (Text < Tout,bal);
the building requires heating (Ans.)
When the U-value of the building is reduced to 0.36 W/m.K, the new balanced
outdoor temperature is given by:
C
85
.
1
384
x
36
.
0
1000
x
)
2
.
1
2
(
25
UA
)
Q
Q
(
T
T o
sensible
int
solar
in
bal
,
out =
+
−
=
+
−
=
Since now the outdoor temperature at balance point is smaller than the external
temperature (Text > Tout,bal);
the building now requires cooling (Ans.)
The above example shows that adding more insulation to a building extends the
cooling season and reduces the heating season.
10. An air conditioned room that stands on a well ventilated basement measures 3 m
wide, 3 m high and 6 m deep. One of the two 3 m walls faces west and contains a
double glazed glass window of size 1.5 m by 1.5 m, mounted flush with the wall with
no external shading. There are no heat gains through the walls other than the one
facing west. Calculate the sensible, latent and total heat gains on the room, room
sensible heat factor from the following information. What is the required cooling
capacity?
Inside conditions : 25o
C dry bulb, 50 percent RH
Outside conditions :
U-value for wall :
U-value for roof :
U-value for floor :
Effective Temp. Difference (ETD) for wall:
Effective Temp. Difference (ETD) for roof:
U-value for glass ;
Solar Heat Gain (SHG) of glass ;
43o
C dry bulb, 24o
C wet bulb
1.78 W/m2
.K
1.316 W/m2
.K
1.2 W/m2
.K
25o
C
30o
C
3.12 W/m2
.K
300 W/m2
Internal Shading Coefficient (SC) of glass: 0.86
Occupancy : 4 (90 W sensible heat/person)
Lighting load :
(40 W latent heat/person)
33 W/m2
of floor area
:
:
Appliance load
Infiltration
Barometric pressure
s
600 W (Sensible) + 300 W(latent)
0.5 Air Changes per Hour
s 101 kPa
Ans.: From psychrometric chart,
For the inside conditions of 25o
C dry bulb, 50 percent RH:
Wi = 9,9167 x 10-3
kgw/kgda
For the outside conditions of 43o
C dry bulb, 24o
C wet bulb:
Wo = 0.0107 kgw/kgda, density of dry air = 1.095 kg/m3
External loads:
a) Heat transfer rate through the walls: Since only west wall measuring 3m x 3m with
a glass windows of 1.5m x 1.5m is exposed; the heat transfer rate through this wall is
given by:
Qwall = UwallAwallETDwall = 1.78 x (9-2.25) x 25 = 300.38 W (Sensible)
b) Heat transfer rate through roof:
Qroof = UroofAroofETDroof = 1.316 x 18 x 30 = 710.6 W (Sensible)
c) Heat transfer rate through floor: Since the room stands on a well-ventilated
basement, we can assume the conditions in the basement to be same as that of the
outside (i.e., 43o
C dry bulb and 24o
C wet bulb), since the floor is not exposed to solar
radiation, the driving temperature difference for the roof is the temperature difference
between the outdoor and indoor, hence:
Qfloor = UfloorAfloorETDfloor = 1.2 x 18 x 18 = 388.8 W (Sensible)
d) Heat transfer rate through glass: This consists of the radiative as well as
conductive components. Since no information is available on the value of CLF, it is
taken as 1.0. Hence the total heat transfer rate through the glass window is given by:
Qglass = Aglass [Uglass(To−Ti)+SHGFmaxSC] = 2.25[3.12 x 18 + 300 x 0.86] = 706.9 W
(Sensible)
e) Heat transfer due to infiltration: The infiltration rate is 0.5 ACH, converting this into
mass flow rate, the infiltration rate in kg/s is given by:
minf = density of air x (ACH x volume of the room)/3600 = 1.095 x (0.5 x 3x3x6)/3600
minf = 8.2125 x 10-3
kg/s
Sensible heat transfer rate due to infiltration,Qs,inf;
Qs,inf = minfcpm(To−Ti) = 8.2125 x 10-3
x 1021.6 x (43 – 25) = 151 W (Sensible)
Latent heat transfer rate due to infiltration, Ql,inf:
Ql,inf = minfhfg(Wo−Wi) = 8.8125x10-3
x 2501x103
(0.0107−0.0099)=16.4 W (latent)
Internal loads:
a) Load due to occupants: The sensible and latent load due to occupants are:
Qs,occ = no.of occupants x SHG = 4 x 90 = 360 W
Ql,occ = no.of occupants x LHG = 4 x 40 = 160 W
b) Load due to lighting: Assuming a CLF value of 1.0, the load due to lighting is:
Qlights = 33 x floor area = 33 x 18 = 594 W (Sensible)
c) Load due to appliance:
Qs,app = 600 W (Sensible)
Ql,app = 300 W (Latent)
Total sensible and latent loads are obtained by summing-up all the sensible and
latent load components (both external as well as internal) as:
Qs,total = 300.38+710.6+388.8+706.9+151+360+594+600 = 3811.68 W (Ans.)
Ql,total = 16.4+160+300 = 476.4 W (Ans.)
Total load on the building is:
Qtotal = Qs,total + Ql,total = 3811.68 + 476.4 = 4288.08 W (Ans.)
Room Sensible Heat Factor (RSHF) is given by:
RSHF = Qs,total/Qtotal = 3811.68/4288.08 = 0.889 (Ans.)
To calculate the required cooling capacity, one has to know the losses in return air
ducts. Ventilation may be neglected as the infiltration can take care of the small
ventilation requirement. Hence using a safety factor of 1.25, the required cooling
capacity is:
Required cooling capacity = 4288.08 x 1.25 = 5360.1 W ≈ 1.5 TR (Ans.)

Más contenido relacionado

La actualidad más candente

Cooling Tower & Dryer Fundamentals
Cooling Tower & Dryer FundamentalsCooling Tower & Dryer Fundamentals
Cooling Tower & Dryer FundamentalsYuri Melliza
 
air standard, fuel air and actual cycles
air standard, fuel air and actual cyclesair standard, fuel air and actual cycles
air standard, fuel air and actual cyclesmp poonia
 
Condenser and cooling tower
Condenser and cooling towerCondenser and cooling tower
Condenser and cooling towerYashvir Singh
 
Basics of Refrigerartion
Basics of RefrigerartionBasics of Refrigerartion
Basics of RefrigerartionKonal Singh
 
Insulation materials
Insulation materialsInsulation materials
Insulation materialsSawan Wani
 
Presentation cooling tower
Presentation cooling towerPresentation cooling tower
Presentation cooling towerALOK KUMAR SWAIN
 
Calculation of Turbine Efficiency
Calculation of Turbine EfficiencyCalculation of Turbine Efficiency
Calculation of Turbine EfficiencyJahanzeb Khan
 
Theory of machines by rs. khurmi_ solution manual _ chapter 11
Theory of machines by rs. khurmi_ solution manual _ chapter 11Theory of machines by rs. khurmi_ solution manual _ chapter 11
Theory of machines by rs. khurmi_ solution manual _ chapter 11Darawan Wahid
 
Refrigeration And Air Conditioning
Refrigeration And Air ConditioningRefrigeration And Air Conditioning
Refrigeration And Air ConditioningSaurabh Jain
 
Condenser and Cooling Tower Power Plant Engineering
Condenser and Cooling Tower Power Plant EngineeringCondenser and Cooling Tower Power Plant Engineering
Condenser and Cooling Tower Power Plant EngineeringAjaypalsinh Barad
 
Electronic cooling
Electronic coolingElectronic cooling
Electronic coolingabuamo
 
Air refrigerationsystem
Air refrigerationsystemAir refrigerationsystem
Air refrigerationsystemnaphis ahamad
 
Gas turbine 2 - regeneration and intercooling
Gas turbine   2 - regeneration and intercoolingGas turbine   2 - regeneration and intercooling
Gas turbine 2 - regeneration and intercoolingNihal Senanayake
 
Refrigeration and airconditioning
Refrigeration and airconditioningRefrigeration and airconditioning
Refrigeration and airconditioningHarsh Gandhi
 
REFRIGERATION SYSTEM
REFRIGERATION SYSTEMREFRIGERATION SYSTEM
REFRIGERATION SYSTEMDenny John
 
2. psychrometric chart
2. psychrometric chart2. psychrometric chart
2. psychrometric chartManoj Pj
 

La actualidad más candente (20)

Cooling Tower & Dryer Fundamentals
Cooling Tower & Dryer FundamentalsCooling Tower & Dryer Fundamentals
Cooling Tower & Dryer Fundamentals
 
air standard, fuel air and actual cycles
air standard, fuel air and actual cyclesair standard, fuel air and actual cycles
air standard, fuel air and actual cycles
 
Condenser and cooling tower
Condenser and cooling towerCondenser and cooling tower
Condenser and cooling tower
 
Dryers
DryersDryers
Dryers
 
Hvac duct design
Hvac duct designHvac duct design
Hvac duct design
 
BOILER DRAUGHT
BOILER DRAUGHTBOILER DRAUGHT
BOILER DRAUGHT
 
Basics of Refrigerartion
Basics of RefrigerartionBasics of Refrigerartion
Basics of Refrigerartion
 
Insulation materials
Insulation materialsInsulation materials
Insulation materials
 
Presentation cooling tower
Presentation cooling towerPresentation cooling tower
Presentation cooling tower
 
Calculation of Turbine Efficiency
Calculation of Turbine EfficiencyCalculation of Turbine Efficiency
Calculation of Turbine Efficiency
 
Theory of machines by rs. khurmi_ solution manual _ chapter 11
Theory of machines by rs. khurmi_ solution manual _ chapter 11Theory of machines by rs. khurmi_ solution manual _ chapter 11
Theory of machines by rs. khurmi_ solution manual _ chapter 11
 
Refrigeration And Air Conditioning
Refrigeration And Air ConditioningRefrigeration And Air Conditioning
Refrigeration And Air Conditioning
 
Condenser and Cooling Tower Power Plant Engineering
Condenser and Cooling Tower Power Plant EngineeringCondenser and Cooling Tower Power Plant Engineering
Condenser and Cooling Tower Power Plant Engineering
 
Electronic cooling
Electronic coolingElectronic cooling
Electronic cooling
 
Chapter_3.pdf
Chapter_3.pdfChapter_3.pdf
Chapter_3.pdf
 
Air refrigerationsystem
Air refrigerationsystemAir refrigerationsystem
Air refrigerationsystem
 
Gas turbine 2 - regeneration and intercooling
Gas turbine   2 - regeneration and intercoolingGas turbine   2 - regeneration and intercooling
Gas turbine 2 - regeneration and intercooling
 
Refrigeration and airconditioning
Refrigeration and airconditioningRefrigeration and airconditioning
Refrigeration and airconditioning
 
REFRIGERATION SYSTEM
REFRIGERATION SYSTEMREFRIGERATION SYSTEM
REFRIGERATION SYSTEM
 
2. psychrometric chart
2. psychrometric chart2. psychrometric chart
2. psychrometric chart
 

Similar a Cooling load problems

CH EN 3453 Heat Transfer 2014 Fall Utah Homework HW 04 Solutions
CH EN 3453 Heat Transfer 2014 Fall Utah Homework HW 04 SolutionsCH EN 3453 Heat Transfer 2014 Fall Utah Homework HW 04 Solutions
CH EN 3453 Heat Transfer 2014 Fall Utah Homework HW 04 Solutionssemihypocrite
 
Taller 2 diseno de maquinas termicas 2 p.2021
Taller 2 diseno de maquinas termicas 2 p.2021Taller 2 diseno de maquinas termicas 2 p.2021
Taller 2 diseno de maquinas termicas 2 p.2021jhon alvaro guevara
 
ATI_SDM_2010_Jun
ATI_SDM_2010_JunATI_SDM_2010_Jun
ATI_SDM_2010_JunMDO_Lab
 
Thermodynamics Hw#2
Thermodynamics Hw#2Thermodynamics Hw#2
Thermodynamics Hw#2littlepine13
 
CH EN 3453 Heat Transfer 2014 Fall Utah Homework HW 11 Assignment
CH EN 3453 Heat Transfer 2014 Fall Utah Homework HW 11 AssignmentCH EN 3453 Heat Transfer 2014 Fall Utah Homework HW 11 Assignment
CH EN 3453 Heat Transfer 2014 Fall Utah Homework HW 11 Assignmentsemihypocrite
 
Cold storage design
Cold storage designCold storage design
Cold storage designengrhanif04
 
Problem set 2 4b3
Problem set 2 4b3Problem set 2 4b3
Problem set 2 4b34ChEAB08
 
CH EN 3453 Heat Transfer 2014 Fall Utah Homework HW 03 Assignment
CH EN 3453 Heat Transfer 2014 Fall Utah Homework HW 03 AssignmentCH EN 3453 Heat Transfer 2014 Fall Utah Homework HW 03 Assignment
CH EN 3453 Heat Transfer 2014 Fall Utah Homework HW 03 Assignmentsemihypocrite
 
4B group 4
4B group 44B group 4
4B group 44ChEAB08
 
Group4 4 Ch E B
Group4 4 Ch E BGroup4 4 Ch E B
Group4 4 Ch E B4ChEAB08
 
CH EN 3453 Heat Transfer 2014 Fall Utah Homework HW 01 Assignment
CH EN 3453 Heat Transfer 2014 Fall Utah Homework HW 01 AssignmentCH EN 3453 Heat Transfer 2014 Fall Utah Homework HW 01 Assignment
CH EN 3453 Heat Transfer 2014 Fall Utah Homework HW 01 Assignmentsemihypocrite
 
Latihan soal jawab fentrans
Latihan soal jawab fentransLatihan soal jawab fentrans
Latihan soal jawab fentransWidia Kurnia Adi
 
Latihan soal jawab fentrans
Latihan soal jawab fentransLatihan soal jawab fentrans
Latihan soal jawab fentransWidia Kurnia Adi
 

Similar a Cooling load problems (20)

CH EN 3453 Heat Transfer 2014 Fall Utah Homework HW 04 Solutions
CH EN 3453 Heat Transfer 2014 Fall Utah Homework HW 04 SolutionsCH EN 3453 Heat Transfer 2014 Fall Utah Homework HW 04 Solutions
CH EN 3453 Heat Transfer 2014 Fall Utah Homework HW 04 Solutions
 
No 6 g3 solved problems
No 6 g3  solved problemsNo 6 g3  solved problems
No 6 g3 solved problems
 
Group 2 A
Group 2 AGroup 2 A
Group 2 A
 
Taller 2 diseno de maquinas termicas 2 p.2021
Taller 2 diseno de maquinas termicas 2 p.2021Taller 2 diseno de maquinas termicas 2 p.2021
Taller 2 diseno de maquinas termicas 2 p.2021
 
ATI_SDM_2010_Jun
ATI_SDM_2010_JunATI_SDM_2010_Jun
ATI_SDM_2010_Jun
 
Architectural Engineering Assignment Help
Architectural Engineering Assignment HelpArchitectural Engineering Assignment Help
Architectural Engineering Assignment Help
 
Thermodynamics Hw#2
Thermodynamics Hw#2Thermodynamics Hw#2
Thermodynamics Hw#2
 
Exercise
ExerciseExercise
Exercise
 
CH EN 3453 Heat Transfer 2014 Fall Utah Homework HW 11 Assignment
CH EN 3453 Heat Transfer 2014 Fall Utah Homework HW 11 AssignmentCH EN 3453 Heat Transfer 2014 Fall Utah Homework HW 11 Assignment
CH EN 3453 Heat Transfer 2014 Fall Utah Homework HW 11 Assignment
 
Cold storage design
Cold storage designCold storage design
Cold storage design
 
Thermodynamic, sheet 2
Thermodynamic, sheet 2Thermodynamic, sheet 2
Thermodynamic, sheet 2
 
hvac
hvachvac
hvac
 
Problem set 2 4b3
Problem set 2 4b3Problem set 2 4b3
Problem set 2 4b3
 
CH EN 3453 Heat Transfer 2014 Fall Utah Homework HW 03 Assignment
CH EN 3453 Heat Transfer 2014 Fall Utah Homework HW 03 AssignmentCH EN 3453 Heat Transfer 2014 Fall Utah Homework HW 03 Assignment
CH EN 3453 Heat Transfer 2014 Fall Utah Homework HW 03 Assignment
 
4B group 4
4B group 44B group 4
4B group 4
 
Group4 4 Ch E B
Group4 4 Ch E BGroup4 4 Ch E B
Group4 4 Ch E B
 
L0372066071
L0372066071L0372066071
L0372066071
 
CH EN 3453 Heat Transfer 2014 Fall Utah Homework HW 01 Assignment
CH EN 3453 Heat Transfer 2014 Fall Utah Homework HW 01 AssignmentCH EN 3453 Heat Transfer 2014 Fall Utah Homework HW 01 Assignment
CH EN 3453 Heat Transfer 2014 Fall Utah Homework HW 01 Assignment
 
Latihan soal jawab fentrans
Latihan soal jawab fentransLatihan soal jawab fentrans
Latihan soal jawab fentrans
 
Latihan soal jawab fentrans
Latihan soal jawab fentransLatihan soal jawab fentrans
Latihan soal jawab fentrans
 

Último

Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night StandCall Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Standamitlee9823
 
data_management_and _data_science_cheat_sheet.pdf
data_management_and _data_science_cheat_sheet.pdfdata_management_and _data_science_cheat_sheet.pdf
data_management_and _data_science_cheat_sheet.pdfJiananWang21
 
Hostel management system project report..pdf
Hostel management system project report..pdfHostel management system project report..pdf
Hostel management system project report..pdfKamal Acharya
 
22-prompt engineering noted slide shown.pdf
22-prompt engineering noted slide shown.pdf22-prompt engineering noted slide shown.pdf
22-prompt engineering noted slide shown.pdf203318pmpc
 
Unit 2- Effective stress & Permeability.pdf
Unit 2- Effective stress & Permeability.pdfUnit 2- Effective stress & Permeability.pdf
Unit 2- Effective stress & Permeability.pdfRagavanV2
 
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756dollysharma2066
 
Block diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.pptBlock diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.pptNANDHAKUMARA10
 
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdfONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdfKamal Acharya
 
Hazard Identification (HAZID) vs. Hazard and Operability (HAZOP): A Comparati...
Hazard Identification (HAZID) vs. Hazard and Operability (HAZOP): A Comparati...Hazard Identification (HAZID) vs. Hazard and Operability (HAZOP): A Comparati...
Hazard Identification (HAZID) vs. Hazard and Operability (HAZOP): A Comparati...soginsider
 
notes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.pptnotes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.pptMsecMca
 
University management System project report..pdf
University management System project report..pdfUniversity management System project report..pdf
University management System project report..pdfKamal Acharya
 
Unleashing the Power of the SORA AI lastest leap
Unleashing the Power of the SORA AI lastest leapUnleashing the Power of the SORA AI lastest leap
Unleashing the Power of the SORA AI lastest leapRishantSharmaFr
 
2016EF22_0 solar project report rooftop projects
2016EF22_0 solar project report rooftop projects2016EF22_0 solar project report rooftop projects
2016EF22_0 solar project report rooftop projectssmsksolar
 
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Bookingdharasingh5698
 
DC MACHINE-Motoring and generation, Armature circuit equation
DC MACHINE-Motoring and generation, Armature circuit equationDC MACHINE-Motoring and generation, Armature circuit equation
DC MACHINE-Motoring and generation, Armature circuit equationBhangaleSonal
 
A Study of Urban Area Plan for Pabna Municipality
A Study of Urban Area Plan for Pabna MunicipalityA Study of Urban Area Plan for Pabna Municipality
A Study of Urban Area Plan for Pabna MunicipalityMorshed Ahmed Rahath
 
UNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its PerformanceUNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its Performancesivaprakash250
 
Bhosari ( Call Girls ) Pune 6297143586 Hot Model With Sexy Bhabi Ready For ...
Bhosari ( Call Girls ) Pune  6297143586  Hot Model With Sexy Bhabi Ready For ...Bhosari ( Call Girls ) Pune  6297143586  Hot Model With Sexy Bhabi Ready For ...
Bhosari ( Call Girls ) Pune 6297143586 Hot Model With Sexy Bhabi Ready For ...tanu pandey
 

Último (20)

Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night StandCall Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
 
data_management_and _data_science_cheat_sheet.pdf
data_management_and _data_science_cheat_sheet.pdfdata_management_and _data_science_cheat_sheet.pdf
data_management_and _data_science_cheat_sheet.pdf
 
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort ServiceCall Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
 
Hostel management system project report..pdf
Hostel management system project report..pdfHostel management system project report..pdf
Hostel management system project report..pdf
 
22-prompt engineering noted slide shown.pdf
22-prompt engineering noted slide shown.pdf22-prompt engineering noted slide shown.pdf
22-prompt engineering noted slide shown.pdf
 
Unit 2- Effective stress & Permeability.pdf
Unit 2- Effective stress & Permeability.pdfUnit 2- Effective stress & Permeability.pdf
Unit 2- Effective stress & Permeability.pdf
 
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
 
Block diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.pptBlock diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.ppt
 
FEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced Loads
FEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced LoadsFEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced Loads
FEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced Loads
 
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdfONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
 
Hazard Identification (HAZID) vs. Hazard and Operability (HAZOP): A Comparati...
Hazard Identification (HAZID) vs. Hazard and Operability (HAZOP): A Comparati...Hazard Identification (HAZID) vs. Hazard and Operability (HAZOP): A Comparati...
Hazard Identification (HAZID) vs. Hazard and Operability (HAZOP): A Comparati...
 
notes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.pptnotes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.ppt
 
University management System project report..pdf
University management System project report..pdfUniversity management System project report..pdf
University management System project report..pdf
 
Unleashing the Power of the SORA AI lastest leap
Unleashing the Power of the SORA AI lastest leapUnleashing the Power of the SORA AI lastest leap
Unleashing the Power of the SORA AI lastest leap
 
2016EF22_0 solar project report rooftop projects
2016EF22_0 solar project report rooftop projects2016EF22_0 solar project report rooftop projects
2016EF22_0 solar project report rooftop projects
 
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
 
DC MACHINE-Motoring and generation, Armature circuit equation
DC MACHINE-Motoring and generation, Armature circuit equationDC MACHINE-Motoring and generation, Armature circuit equation
DC MACHINE-Motoring and generation, Armature circuit equation
 
A Study of Urban Area Plan for Pabna Municipality
A Study of Urban Area Plan for Pabna MunicipalityA Study of Urban Area Plan for Pabna Municipality
A Study of Urban Area Plan for Pabna Municipality
 
UNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its PerformanceUNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its Performance
 
Bhosari ( Call Girls ) Pune 6297143586 Hot Model With Sexy Bhabi Ready For ...
Bhosari ( Call Girls ) Pune  6297143586  Hot Model With Sexy Bhabi Ready For ...Bhosari ( Call Girls ) Pune  6297143586  Hot Model With Sexy Bhabi Ready For ...
Bhosari ( Call Girls ) Pune 6297143586 Hot Model With Sexy Bhabi Ready For ...
 

Cooling load problems

  • 1. 9. A building has a U-value of 0.5 W/m2 .K and a total exposed surface area of 384 m2 . The building is subjected to an external load (only sensible) of 2 kW and an internal load of 1.2 kW (sensible). If the required internal temperature is 25o C, state -Estimation Of Required Cooling/Heating Capacity ..Sample Problems whether a cooling system is required or a heating system is required when the external temperature is 3o C. How the results will change, if the U-value of the building is reduced to 0.36 W/m.K?
  • 2. Ans.: From energy balance, C 33 . 8 384 x 5 . 0 1000 x ) 2 . 1 2 ( 25 UA ) Q Q ( T T o sensible int solar in bal , out = + − = + − = Since the outdoor temperature at balance point is greater than the external temperature (Text < Tout,bal); the building requires heating (Ans.) When the U-value of the building is reduced to 0.36 W/m.K, the new balanced outdoor temperature is given by: C 85 . 1 384 x 36 . 0 1000 x ) 2 . 1 2 ( 25 UA ) Q Q ( T T o sensible int solar in bal , out = + − = + − = Since now the outdoor temperature at balance point is smaller than the external temperature (Text > Tout,bal); the building now requires cooling (Ans.) The above example shows that adding more insulation to a building extends the cooling season and reduces the heating season.
  • 3. 10. An air conditioned room that stands on a well ventilated basement measures 3 m wide, 3 m high and 6 m deep. One of the two 3 m walls faces west and contains a double glazed glass window of size 1.5 m by 1.5 m, mounted flush with the wall with no external shading. There are no heat gains through the walls other than the one facing west. Calculate the sensible, latent and total heat gains on the room, room sensible heat factor from the following information. What is the required cooling capacity? Inside conditions : 25o C dry bulb, 50 percent RH Outside conditions : U-value for wall : U-value for roof : U-value for floor : Effective Temp. Difference (ETD) for wall: Effective Temp. Difference (ETD) for roof: U-value for glass ; Solar Heat Gain (SHG) of glass ; 43o C dry bulb, 24o C wet bulb 1.78 W/m2 .K 1.316 W/m2 .K 1.2 W/m2 .K 25o C 30o C 3.12 W/m2 .K 300 W/m2 Internal Shading Coefficient (SC) of glass: 0.86 Occupancy : 4 (90 W sensible heat/person) Lighting load : (40 W latent heat/person) 33 W/m2 of floor area : : Appliance load Infiltration Barometric pressure s 600 W (Sensible) + 300 W(latent) 0.5 Air Changes per Hour s 101 kPa
  • 4. Ans.: From psychrometric chart, For the inside conditions of 25o C dry bulb, 50 percent RH: Wi = 9,9167 x 10-3 kgw/kgda For the outside conditions of 43o C dry bulb, 24o C wet bulb: Wo = 0.0107 kgw/kgda, density of dry air = 1.095 kg/m3 External loads: a) Heat transfer rate through the walls: Since only west wall measuring 3m x 3m with a glass windows of 1.5m x 1.5m is exposed; the heat transfer rate through this wall is given by: Qwall = UwallAwallETDwall = 1.78 x (9-2.25) x 25 = 300.38 W (Sensible) b) Heat transfer rate through roof: Qroof = UroofAroofETDroof = 1.316 x 18 x 30 = 710.6 W (Sensible) c) Heat transfer rate through floor: Since the room stands on a well-ventilated basement, we can assume the conditions in the basement to be same as that of the outside (i.e., 43o C dry bulb and 24o C wet bulb), since the floor is not exposed to solar radiation, the driving temperature difference for the roof is the temperature difference between the outdoor and indoor, hence: Qfloor = UfloorAfloorETDfloor = 1.2 x 18 x 18 = 388.8 W (Sensible) d) Heat transfer rate through glass: This consists of the radiative as well as conductive components. Since no information is available on the value of CLF, it is taken as 1.0. Hence the total heat transfer rate through the glass window is given by: Qglass = Aglass [Uglass(To−Ti)+SHGFmaxSC] = 2.25[3.12 x 18 + 300 x 0.86] = 706.9 W (Sensible) e) Heat transfer due to infiltration: The infiltration rate is 0.5 ACH, converting this into mass flow rate, the infiltration rate in kg/s is given by: minf = density of air x (ACH x volume of the room)/3600 = 1.095 x (0.5 x 3x3x6)/3600 minf = 8.2125 x 10-3 kg/s
  • 5. Sensible heat transfer rate due to infiltration,Qs,inf; Qs,inf = minfcpm(To−Ti) = 8.2125 x 10-3 x 1021.6 x (43 – 25) = 151 W (Sensible) Latent heat transfer rate due to infiltration, Ql,inf: Ql,inf = minfhfg(Wo−Wi) = 8.8125x10-3 x 2501x103 (0.0107−0.0099)=16.4 W (latent) Internal loads: a) Load due to occupants: The sensible and latent load due to occupants are: Qs,occ = no.of occupants x SHG = 4 x 90 = 360 W Ql,occ = no.of occupants x LHG = 4 x 40 = 160 W b) Load due to lighting: Assuming a CLF value of 1.0, the load due to lighting is: Qlights = 33 x floor area = 33 x 18 = 594 W (Sensible) c) Load due to appliance: Qs,app = 600 W (Sensible) Ql,app = 300 W (Latent) Total sensible and latent loads are obtained by summing-up all the sensible and latent load components (both external as well as internal) as: Qs,total = 300.38+710.6+388.8+706.9+151+360+594+600 = 3811.68 W (Ans.) Ql,total = 16.4+160+300 = 476.4 W (Ans.) Total load on the building is: Qtotal = Qs,total + Ql,total = 3811.68 + 476.4 = 4288.08 W (Ans.) Room Sensible Heat Factor (RSHF) is given by: RSHF = Qs,total/Qtotal = 3811.68/4288.08 = 0.889 (Ans.) To calculate the required cooling capacity, one has to know the losses in return air ducts. Ventilation may be neglected as the infiltration can take care of the small ventilation requirement. Hence using a safety factor of 1.25, the required cooling capacity is: Required cooling capacity = 4288.08 x 1.25 = 5360.1 W ≈ 1.5 TR (Ans.)