Fault-
Any defect in the electrical circuit or network which deviates the
current paths from its intended path is called “FAULT”.
The fault which results into symmetrical currents (Three line
currents of equal magnitude with 120ᵒ displacement) is called
symmetrical Faults (5%).
1. Three Phase to ground fault
2. Three Phase fault
Type of Fault Type
Reasons of Faults in Electrical Power System-
Failure of Insulation
Mechanical Failure
Excessive Internal and External Electric Stress
Heavy winds
Lightning Strokes
Falling of Trees on the line
Over voltage or under voltage due to switching surges
Vehicle accidents due to pole, towers etc
Three phase short circuit Analysis of Unloaded
Alternator-
The flux linkages in the armature circuits and the field
circuit can not changed suddenly by the application of short
circuit to the armature winding.
For maintaining these flux linkages constant large changes
of current may take place in both of the windings, when
short circuit occurs in order to keep their respective flux
linkages constant.
Direct-Axis Subtransient Reactance, 𝑋 𝑑
𝑖𝑖
𝑋 𝑑
𝑖𝑖
=𝑋𝑙 +
1
1
𝑋 𝑎
+
1
𝑋 𝑓
+
1
𝑋 𝑑𝑤
… … … . Ohm
Direct-Axis Transient Reactance, 𝑋 𝑑
𝑖
𝑋 𝑑
𝑖
=𝑋𝑙 +
1
1
𝑋 𝑎
+
1
𝑋 𝑓
… … … . Ohm
Direct-Axis Steady State Reactance, 𝑋 𝑑
𝑋 𝑑=𝑋𝑙 + 𝑋 𝑎 … … … . Ohm
𝑋 𝑑
𝑖𝑖
<𝑋 𝑑
𝑖
<𝑋 𝑑
Relation between direct axis
Reactance
3-Phase fault current transients in synchronous
generators
The current can be
represented as a transient
DC component added on top
of a symmetrical AC
component.
Before the fault, only AC
voltages and currents are
present, but immediately
after the fault, both AC and
DC currents are present.
Symmetrical AC component of the fault current:
There are three periods of time:
 Sub-transient period: first cycle or so after
the fault – AC current is very large and falls
rapidly;
 Transient period: current falls at a slower
rate;
 Steady-state period: current reaches its
steady value.
Some Important Formulae-
Isc Per Unit =
𝑃𝑒𝑟 𝑈𝑛𝑖𝑡 𝑣𝑜𝑙𝑡𝑎𝑔𝑒 𝑎𝑡 𝑓𝑎𝑢𝑙𝑡 𝑝𝑜𝑖𝑛𝑡
𝑃𝑒𝑟 𝑈𝑛𝑖𝑡 𝐸𝑞𝑢𝑖𝑣𝑎𝑙𝑒𝑛𝑡 𝑅𝑒𝑎𝑐𝑡𝑎𝑛𝑐𝑒
Per Unit Fault MVA = 3 × 𝑃𝑒𝑟 𝑈𝑛𝑖𝑡 𝐹𝑎𝑢𝑙𝑡 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 × Per Unit Source Voltage
Fault MVA =
𝐵𝑎𝑠𝑒 𝑀𝑉𝐴
𝑃𝑈 𝐸𝑞𝑢𝑖𝑣𝑎𝑙𝑒𝑛𝑡 𝑅𝑒𝑎𝑐𝑡𝑎𝑛𝑐𝑒
(𝑀𝑉𝐴 𝐿𝑎𝑔𝑔𝑖𝑛𝑔)
Fault Current Isc =
𝐹𝑎𝑢𝑙𝑡 𝑀𝑉𝐴 × 103
3 ×𝐵𝑎𝑠𝑒 𝑘𝑉
𝐴
Fault MVA = 3 × Fault Current × Base Voltage × 10−6
Example -1 A 3 phase – 10000 KVA , 11kv
alternator has a subtransient reactance of 8% . A
three phase short circuit occurs at its terminals.
Determine fault current and fault MVA.
 Base MVA for Complete Section-10 MVA
 Base kV for Generator Section-11 kV
Fault Current Isc =𝑃𝑒𝑟 𝑈𝑛𝑖𝑡 𝑆ℎ𝑜𝑟𝑡 𝐶𝑖𝑟𝑐𝑢𝑖𝑡 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 × 𝐵𝑎𝑠𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡
Solution :
Base Current,
Base Current =
Base MVA
3 Base kV
=
10
√3×11
= 0.525kA
Isc Per Unit =
𝑷𝒆𝒓 𝑼𝒏𝒊𝒕 𝑽𝒐𝒍𝒕𝒂𝒈𝒆
𝑷𝒆𝒓 𝑼𝒏𝒊𝒕 𝑹𝒆𝒂𝒄𝒕𝒂𝒏𝒄𝒆
=
𝟏
𝒋𝟎.𝟎𝟖
=12.5 < −900 Ampere
Fault Current Isc =𝑃𝑒𝑟 𝑈𝑛𝑖𝑡 𝑆ℎ𝑜𝑟𝑡 𝐶𝑖𝑟𝑐𝑢𝑖𝑡 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 × 𝐵𝑎𝑠𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡
=12.5 × 525
=6562 A
Fault Power (MVA) = 𝟑 × 𝑰𝒔𝒄 × 𝑺𝒐𝒖𝒓𝒄𝒆 𝑽𝒐𝒍𝒕𝒂𝒈𝒆 × 𝟏𝟎−𝟔 𝑴𝑽𝑨
=√𝟑 × 𝟔𝟓𝟔𝟐 × 𝟏𝟏𝟎𝟎𝟎 × 𝟏𝟎−𝟔
=125 MVA
Example-2 A three phase 5 MVA, 6.6 kV Alternator with a
reactance of 8% is connected to a feeder of series
impedance of (0.12+0.48j) Ohms/Phase/Km. The
transformer is rated at 3 MVA, 6.6 /33 kV and has a
reactance of 5 %. Determine fault current supplied by
the generator operating under no load with a voltage a
voltage of 6.9 kV, When a three phase symmetrical fault
occurs at a point 15 KM along the feeder.
 Base MVA for Complete Section-5 MVA
 Base kV for Generator Section-6.6 kV
Example-2 A three phase 5 MVA, 6.6 kV Alternator with a reactance of 8% is
connected to a feeder of series impedance of (0.12+0.48j) Ohms/Phase/Km.
The transformer is rated at 3 MVA, 6.6 /33 kV and has a reactance of 5 %.
Determine fault current supplied by the generator operating under no load with
a voltage a voltage of 6.9 kV, When a three phase symmetrical fault occurs at a
point 15 KM along the feeder.
BASE MVA= 5 MVA FOR ENTIRE SECTION
Core of Transformer
Base KV=6.6 kV up to the
Primary of Transformer
Base KV=33 kV from the Secondary of
Transformer----Along the Feeder
Example-2 A three phase 5 MVA, 6.6 kV Alternator with a reactance of 8% is
connected to a feeder of series impedance of (0.12+0.48j) Ohms/Phase/Km.
The transformer is rated at 3 MVA, 6.6 /33 kV and has a reactance of 5 %.
Determine fault current supplied by the generator operating under no load with
a voltage a voltage of 6.9 kV, When a three phase symmetrical fault occurs at a
point 15 KM along the feeder.
𝑋 𝑛𝑒𝑤 𝑝𝑒𝑟 𝑢𝑛𝑖𝑡 = 𝑋 𝑜𝑙𝑑 𝑝𝑒𝑟 𝑢𝑛𝑖𝑡 ∗
𝑀𝑉𝐴 𝑏𝑎𝑠𝑒 𝑛𝑒𝑤
𝑀𝑉𝐴 𝑏𝑎𝑠𝑒 𝑜𝑙𝑑
∗
𝑘𝑉 𝑏𝑎𝑠𝑒 𝑜𝑙𝑑
𝑘𝑉𝑏𝑎𝑠𝑒 𝑛𝑒𝑤
2
Using Above formula calculate new values of per unit reactance for all the
components of given power system by referring the kV base and MVA base.
𝑋 𝑛𝑒𝑤 𝑝𝑒𝑟 𝑢𝑛𝑖𝑡 for Alternator=0.08*(
5
5
)*(
6.6
6.6
)2
=0.08 PU
𝑋 𝑛𝑒𝑤 𝑝𝑒𝑟 𝑢𝑛𝑖𝑡 for Transformer=0.05*(
5
3
)*(
6.6
6.6
)2------------------Referring to Primary
=0.0833 PU
Example-2 A three phase 5 MVA, 6.6 kV Alternator with a reactance of 8% is
connected to a feeder of series impedance of (0.12+0.48j) Ohms/Phase/Km.
The transformer is rated at 3 MVA, 6.6 /33 kV and has a reactance of 5 %.
Determine fault current supplied by the generator operating under no load with
a voltage a voltage of 6.9 kV, When a three phase symmetrical fault occurs at a
point 15 KM along the feeder.
𝑋 𝑝𝑒𝑟 𝑢𝑛𝑖𝑡 = 𝑋 𝑎𝑐𝑡𝑢𝑎𝑙 ∗
𝑀𝑉𝐴 𝑏𝑎𝑠𝑒 𝑛𝑒𝑤
(𝑘𝑉𝑏𝑎𝑠𝑒 𝑛𝑒𝑤)2
Using Above formula calculate the per unit reactance for the components,
whose actual values are given. In this case impedance of feeder is given as
0.12+0.48j ohms/phase/Km & total distance given as 15 KM.
𝑍 𝑝𝑒𝑟 𝑢𝑛𝑖𝑡 =(1.8+7.2j)*(
5
332)
=0.008+0.033j PU
𝑍 𝐴𝑐𝑡𝑢𝑎𝑙 𝑓𝑜𝑟 𝑓𝑒𝑒𝑑𝑒𝑟 𝑜𝑓 𝑙𝑒𝑛𝑔𝑡ℎ 15 𝑘𝑚 = 0.12 + 0.48𝑗 ∗ 15
=1.8+7.2j-----Ohm/phase
Example-2 A three phase 5 MVA, 6.6 kV Alternator with a reactance of 8% is
connected to a feeder of series impedance of (0.12+0.48j) Ohms/Phase/Km.
The transformer is rated at 3 MVA, 6.6 /33 kV and has a reactance of 5 %.
Determine fault current supplied by the generator operating under no load
with a voltage a voltage of 6.9 kV, When a three phase symmetrical fault occurs
at a point 15 KM along the feeder.
Total Per Unit impedance up to fault= X per unit of Alternator+ X
per unit of transformer+ Per unit impedance of Feeder up to fault
point
Total Per Unit impedance up to fault= 0.008+0.196j
Per Unit Fault Current=
Actual Fault Current
𝐵𝑎𝑠𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡
Per Unit Fault Current=
Per unit Voltage
𝑷𝒆𝒓 𝑼𝒏𝒊𝒕 𝑰𝒎𝒑𝒆𝒅𝒂𝒏𝒄𝒆 𝒖𝒑 𝒕𝒐 𝒇𝒂𝒖𝒍𝒕 𝒑𝒐𝒊𝒏𝒕
Per Unit Fault Current=
6.9
6.6
0.008+0.196𝑗
=5.3282<-87.66 PU
Example-2 A three phase 5 MVA, 6.6 kV Alternator with a reactance of 8% is
connected to a feeder of series impedance of (0.12+0.48j) Ohms/Phase/Km.
The transformer is rated at 3 MVA, 6.6 /33 kV and has a reactance of 5 %.
Determine fault current supplied by the generator operating under no load
with a voltage a voltage of 6.9 kV, When a three phase symmetrical fault occurs
at a point 15 KM along the feeder.
Per Unit Fault Current=
Actual Fault Current
𝐵𝑎𝑠𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡
Per Unit Fault Current=
6.9
6.6
0.008+0.196𝑗
=5.3282<-87.66 PU
Base Fault Current=
𝐵𝑎𝑠𝑒 𝑀𝑉𝐴
3 ∗𝐵𝑎𝑠𝑒 𝑘𝑉
=
𝟓
𝟑∗𝟑𝟑
= 𝟎. 𝟎𝟖𝟕𝟒𝟕 𝑲𝑨
Actual Fault Current=Base Current∗ Per Unit Fault Current
=5.3282*87.47
=466 Ampere
Example-3 Two three phase, 11kV Alternators of
capacities 8 MVA & 4 MVA and Substransient reactance
of 8% and 4% respectively operate in parallel. The
generating station is connected to a transmission line of
200 Km length through a step up transformer of capacity
4 MVA, having percentage reactance of 3.5 %. The
impedance ohm per phase per km of its is 0.025+0.1j
and it operates at 66 kV. Calculate the short circuit MVA
for a phase to phase faults at receiving end of the
transmission line and at the sending end.
 Base MVA for Complete Section- 8 MVA
 Base kV for Generator Section- 11 kV
Example-3 Two three phase, 11kV Alternators of capacities 8 MVA & 4 MVA and
Substransient reactance of 8% and 4% respectively operate in parallel. The
generating station is connected to a transmission line of 200 Km length through
a step up transformer of capacity 4 MVA, having percentage reactance of 3.5 %.
The impedance ohm per phase per km of its is 0.025+0.1j and it operates at 66
kV. Calculate the short circuit MVA for a phase to phase faults at receiving end
of the transmission line and at the sending end.
G1
BASE MVA= 8 MVA FOR ENTIRE SECTION
Transformer
Base KV=11 kV up to the
Primary of Transformer
Base KV=66 kV from the Secondary of
Transformer----Along the Feeder
(0.025+0.1j)*200 Km=5+20j ohm
G2
8 MVA, 11 kV, 8%
4 MVA, 11 kV, 4%
4 MVA, 11/66 kV, 3.5%
Transmission line operates at 66 kV
F1 F2
Example-3 Two three phase, 11kV Alternators of capacities 8 MVA & 4 MVA and
Substransient reactance of 8% and 4% respectively operate in parallel. The generating
station is connected to a transmission line of 200 Km length through a step up
transformer of capacity 4 MVA, having percentage reactance of 3.5 %. The impedance
ohm per phase per km of its is 0.025+0.1j and it operates at 66 kV. Calculate the short
circuit MVA for a phase to phase faults at receiving end of the transmission line and at
the sending end.
𝑋 𝑛𝑒𝑤 𝑝𝑒𝑟 𝑢𝑛𝑖𝑡 = 𝑋 𝑜𝑙𝑑 𝑝𝑒𝑟 𝑢𝑛𝑖𝑡 ∗
𝑀𝑉𝐴 𝑏𝑎𝑠𝑒 𝑛𝑒𝑤
𝑀𝑉𝐴 𝑏𝑎𝑠𝑒 𝑜𝑙𝑑
∗
𝑘𝑉 𝑏𝑎𝑠𝑒 𝑜𝑙𝑑
𝑘𝑉𝑏𝑎𝑠𝑒 𝑛𝑒𝑤
2
𝑋 𝑛𝑒𝑤 𝑝𝑒𝑟 𝑢𝑛𝑖𝑡 for Alternator 1 =0.08*(
8
8
)*(
11
11
)2
=0.08 PU
𝑋 𝑛𝑒𝑤 𝑝𝑒𝑟 𝑢𝑛𝑖𝑡 for Transformer=0.035*(
8
4
)*(
11
11
)2------------------Referring to Primary
=0.07 PU
𝑋 𝑛𝑒𝑤 𝑝𝑒𝑟 𝑢𝑛𝑖𝑡 for Alternator 2 =0.04*(
8
4
)*(
11
11
)2
=0.08 PU
Example-3 Two three phase, 11kV Alternators of capacities 8 MVA & 4 MVA and
Substransient reactance of 8% and 4% respectively operate in parallel. The generating
station is connected to a transmission line of 200 Km length through a step up
transformer of capacity 4 MVA, having percentage reactance of 3.5 %. The impedance
ohm per phase per km of its is 0.025+0.1j and it operates at 66 kV. Calculate the short
circuit MVA for a phase to phase faults at receiving end of the transmission line and at
the sending end.
𝑋 𝑝𝑒𝑟 𝑢𝑛𝑖𝑡 = 𝑋 𝑎𝑐𝑡𝑢𝑎𝑙 ∗
𝑀𝑉𝐴 𝑏𝑎𝑠𝑒 𝑛𝑒𝑤
(𝑘𝑉𝑏𝑎𝑠𝑒 𝑛𝑒𝑤)2
Using Above formula calculate the per unit reactance for the components,
whose actual values are given. In this case impedance of feeder is given as
0.025+0.1j ohms/phase/Km & total distance given as 200 KM.
𝑍 𝑝𝑒𝑟 𝑢𝑛𝑖𝑡 =(5+20j)*(
8
662)
=0.0092+0.0368j PU
𝑍 𝐴𝑐𝑡𝑢𝑎𝑙 𝑓𝑜𝑟 𝑓𝑒𝑒𝑑𝑒𝑟 𝑜𝑓 𝑙𝑒𝑛𝑔𝑡ℎ 200 𝑘𝑚 = 0.025 + 0.1𝑗 ∗200
=5+20j-----Ohm/phase
Example-3 Two three phase, 11kV Alternators of capacities 8 MVA & 4 MVA and
Substransient reactance of 8% and 4% respectively operate in parallel. The generating
station is connected to a transmission line of 200 Km length through a step up
transformer of capacity 4 MVA, having percentage reactance of 3.5 %. The impedance
ohm per phase per km of its is 0.025+0.1j and it operates at 66 kV. Calculate the short
circuit MVA for a phase to phase faults at receiving end of the transmission line and at
the sending end.
G1
G2
0.08 PU
Transmission line operates at 66 kV0.08 PU
0.07 PU 0.0092+0.0368j PU
E1=1 PU
E2=1 PU
G
Transmission line operates at 66 kV
0.04 PU 0.07 PU 0.0092+0.0368j PU
E=1 PU
F1 F2
F1 F2
Example-3 Two three phase, 11kV Alternators of capacities 8 MVA & 4 MVA and
Substransient reactance of 8% and 4% respectively operate in parallel. The generating
station is connected to a transmission line of 200 Km length through a step up
transformer of capacity 4 MVA, having percentage reactance of 3.5 %. The impedance
ohm per phase per km of its is 0.025+0.1j and it operates at 66 kV. Calculate the short
circuit MVA for a phase to phase faults at receiving end of the transmission line and
at the sending end.
Fault MVA =
𝑩𝒂𝒔𝒆 𝑴𝑽𝑨
𝑷𝑼 𝑬𝒒𝒖𝒊𝒗𝒂𝒍𝒆𝒏𝒕 𝑹𝒆𝒂𝒄𝒕𝒂𝒏𝒄𝒆
G
Transmission line operates at 66 kV
0.04 PU 0.07 PU 0.0092+0.0368j PU
E=1 PU
F1 F2
Fault MVA at F1=
8
0.04+0.07 𝑗
=72.72 MVA Lagging
Fault MVA at F2=
8
0.04+0.07 𝑗+(0.0092+0.0368𝑗)
=54.38 MVA Lagging
Example-4 Two three phase, 11kV Alternators of
capacities 10 MVA and transient reactance of 20% at
their own MVA base. The two transformer are also
identical and are rated 5MVA, 11/66 kV and have a
reactance of 5% at their own MVA base. The tie line is
100 Km and has a reactance of 0.1 ohm/Km. A three
phase fault occurs at a distance of 25 Km from one end
of line when the system is on no load but at rated
voltage. Calculate fault MVA and fault current.
 Base MVA for Complete Section- 10 MVA
 Base kV for Generator Section- 11 kV
Example-4 Two three phase, 11kV Alternators of capacities 10 MVA and
transient reactance of 20% at their own MVA base. The two transformer are
also identical and are rated 5MVA, 11/66 kV and have a reactance of 5% at their
own MVA base. The tie line is 100 Km and has a reactance of 0.1 ohm/Km. A
three phase fault occurs at a distance of 25 Km from one end of line when the
system is on no load but at rated voltage. Calculate fault MVA and fault current.
G1
BASE MVA= 10 MVA FOR ENTIRE SECTION
Transformer
Base KV=11 kV up to the
Primary of Transformer
Base KV=66 kV from the Secondary
of Transformer----Along the Feeder
G2
10 MVA, 11 kV, 20% 10 MVA, 11 kV, 20%
5 MVA, 11/66 kV, 5%
Transmission line operates at 66 kV
F1
5 MVA, 66/11 kV, 5%
25 Km 75 Km
Transformer
Base KV=11 kV
X1 X2
Example-4 Two three phase, 11kV Alternators of capacities 10 MVA and transient
reactance of 20% at their own MVA base. The two transformer are also identical and
are rated 5MVA, 11/66 kV and have a reactance of 5% at their own MVA base. The tie
line is 100 Km and has a reactance of 0.1 ohm/Km. A three phase fault occurs at a
distance of 25 Km from one end of line when the system is on no load but at rated
voltage. Calculate fault MVA and fault current.
𝑋 𝑛𝑒𝑤 𝑝𝑒𝑟 𝑢𝑛𝑖𝑡 = 𝑋 𝑜𝑙𝑑 𝑝𝑒𝑟 𝑢𝑛𝑖𝑡 ∗
𝑀𝑉𝐴 𝑏𝑎𝑠𝑒 𝑛𝑒𝑤
𝑀𝑉𝐴 𝑏𝑎𝑠𝑒 𝑜𝑙𝑑
∗
𝑘𝑉 𝑏𝑎𝑠𝑒 𝑜𝑙𝑑
𝑘𝑉𝑏𝑎𝑠𝑒 𝑛𝑒𝑤
2
𝑋 𝑛𝑒𝑤 𝑝𝑒𝑟 𝑢𝑛𝑖𝑡 for Alternator 1 & 2 =0.2*(
10
10
)*(
11
11
)2
=0.2 PU
𝑋 𝑛𝑒𝑤 𝑝𝑒𝑟 𝑢𝑛𝑖𝑡 for Transformer 1 & 2=0.05*(
10
5
)*(
11
11
)2------------------Referring to
Primary for 1st transformer and Referring Secondary for 2nd transformer
=0.1 PU
As Rating of Alternator 1 & 2 and Transformer 1 & 2 are same
Example-4 Two three phase, 11kV Alternators of capacities 10 MVA and transient
reactance of 20% at their own MVA base. The two transformer are also identical and
are rated 5MVA, 11/66 kV and have a reactance of 5% at their own MVA base. The tie
line is 100 Km and has a reactance of 0.1 ohm/Km. A three phase fault occurs at a
distance of 25 Km from one end of line when the system is on no load but at rated
voltage. Calculate fault MVA and fault current.
𝑋 𝑝𝑒𝑟 𝑢𝑛𝑖𝑡 = 𝑋 𝑎𝑐𝑡𝑢𝑎𝑙 ∗
𝑀𝑉𝐴 𝑏𝑎𝑠𝑒 𝑛𝑒𝑤
(𝑘𝑉𝑏𝑎𝑠𝑒 𝑛𝑒𝑤)2
0.1j ohms/phase/Km & total distance given as 100 KM.
X1=0.1j*25=2.5j Ohm/phase
X2=0.1j*75=7.5j Ohm/phase
𝑋1 𝑝𝑒𝑟 𝑢𝑛𝑖𝑡 𝑢𝑝 𝑡𝑜 𝑙𝑒𝑛𝑔𝑡ℎ 25 𝑘𝑚 =(2.5j)*(
10
662)
=0.00574 PU
𝑋2 𝑝𝑒𝑟 𝑢𝑛𝑖𝑡 𝑢𝑝 𝑡𝑜 𝑙𝑒𝑛𝑔𝑡ℎ 75 𝑘𝑚 =(7.5j)*(
10
662)
=0.01722 PU
Example-4 Two three phase, 11kV Alternators of capacities 10 MVA and transient
reactance of 20% at their own MVA base. The two transformer are also identical and
are rated 5MVA, 11/66 kV and have a reactance of 5% at their own MVA base. The tie
line is 100 Km and has a reactance of 0.1 ohm/Km. A three phase fault occurs at a
distance of 25 Km from one end of line when the system is on no load but at rated
voltage. Calculate fault MVA and fault current.
0.2 PU
0.2 PU
0.1 PU
E1=1 PU
E2=1 PU
0.1 PU
𝑿 𝟏 =0.00574 PU
𝑿 𝟐 = 0.01722 PU
G1
G2
0.30574 PU
E1=1 PU
E2=1 PU
0.31722 PU
G
E1=1 PU
0.1557 PU
G2
G1
F1
Example-4 Two three phase, 11kV Alternators of capacities 10 MVA and transient
reactance of 20% at their own MVA base. The two transformer are also identical and
are rated 5MVA, 11/66 kV and have a reactance of 5% at their own MVA base. The tie
line is 100 Km and has a reactance of 0.1 ohm/Km. A three phase fault occurs at a
distance of 25 Km from one end of line when the system is on no load but at rated
voltage. Calculate fault MVA and fault current.
Fault MVA =
𝑩𝒂𝒔𝒆 𝑴𝑽𝑨
𝑷𝑼 𝑬𝒒𝒖𝒊𝒗𝒂𝒍𝒆𝒏𝒕 𝑹𝒆𝒂𝒄𝒕𝒂𝒏𝒄𝒆
Fault MVA =
10
0.1557𝑗
=64.3 MVA Lagging
G1
E1=1 PU
0.1557 PU
Fault Current Isc =
𝐹𝑎𝑢𝑙𝑡 𝑀𝑉𝐴 × 103
3 ×𝐵𝑎𝑠𝑒 𝑘𝑉
𝐴 Fault Current Isc =
64.3 × 103
3 ×66
𝐴
=562 Ampere
Example-5 Determine the required MVA rating of the circuit breaker CB for the system
shown in fig. Consider the grid as infinite bus. Choose 6 MVA as base.
Grid CB Load
6 MVA, 33/11 kV,
0.01+0.08j PU
3 Phase, 11 kV, 5800
kVA, 0.8 Lag, 0.02j PU
9+18j
9+18j
BASE MVA= 6 MVA FOR ENTIRE SECTION
Transformer
Base KV=33 kV up to the
Primary of Transformer
Base KV=11 kV from the Secondary
of Transformer----Along the Feeder
Example-5 Determine the required MVA rating of the circuit breaker CB for the system
shown in fig. Consider the grid as infinite bus. Choose 6 MVA as base.
Grid CB Load
6 MVA, 33/11 kV,
0.01+0.08j PU
3 Phase, 11 kV, 5800
kVA, 0.8 Lag, 0.02j PU
9+18j
9+18j
𝑋 𝑛𝑒𝑤 𝑝𝑒𝑟 𝑢𝑛𝑖𝑡 = 𝑋 𝑜𝑙𝑑 𝑝𝑒𝑟 𝑢𝑛𝑖𝑡 ∗
𝑀𝑉𝐴 𝑏𝑎𝑠𝑒 𝑛𝑒𝑤
𝑀𝑉𝐴 𝑏𝑎𝑠𝑒 𝑜𝑙𝑑
∗
𝑘𝑉 𝑏𝑎𝑠𝑒 𝑜𝑙𝑑
𝑘𝑉𝑏𝑎𝑠𝑒 𝑛𝑒𝑤
2
𝑋 𝑛𝑒𝑤 𝑝𝑒𝑟 𝑢𝑛𝑖𝑡 for Transformer =(0.01+0.08j)*(
6
6
)*(
33
33
)2
------------------Referring to
Primary
=0.01+0.08j PU
𝑋 𝑛𝑒𝑤 𝑝𝑒𝑟 𝑢𝑛𝑖𝑡 for Load =(0.02j)*(
6
5.8
)*(
11
11
)2
=0.207j PU
Example-5 Determine the required MVA rating of the circuit breaker CB for the system
shown in fig. Consider the grid as infinite bus. Choose 6 MVA as base.
Grid CB Load
6 MVA, 33/11 kV,
0.01+0.08j PU
3 Phase, 11 kV, 5800
kVA, 0.8 Lag, 0.02j PU
9+18j
9+18j
𝑋 𝑝𝑒𝑟 𝑢𝑛𝑖𝑡 = 𝑋 𝑎𝑐𝑡𝑢𝑎𝑙 ∗
𝑀𝑉𝐴 𝑏𝑎𝑠𝑒 𝑛𝑒𝑤
(𝑘𝑉𝑏𝑎𝑠𝑒 𝑛𝑒𝑤)2
Z 𝑝𝑒𝑟 𝑢𝑛𝑖𝑡 𝑓𝑜𝑟 𝐹𝑒𝑒𝑑𝑒𝑟 =(9+18j)*(
6
332)
=0.04958+j0.09916 PU
Example-5 Determine the required MVA rating of the circuit breaker CB for the system
shown in fig. Consider the grid as infinite bus. Choose 6 MVA as base.
Grid CB Load
6 MVA, 33/11 kV,
0.01+0.08j PU
3 Phase, 11 kV, 5800
kVA, 0.8 Lag, 0.02j PU
9+18j
9+18j
G CB
0.04958+j0.09916 PU
0.04958+j0.09916 PU
0.01+0.08j PU 0.207j PU
Equivalent impedance from grid to fault point, 𝑍 𝑒𝑞 = 0.13417 < 74.97° Ohm
Fault MVA =
𝑩𝒂𝒔𝒆 𝑴𝑽𝑨
𝑷𝑼 𝑬𝒒𝒖𝒊𝒗𝒂𝒍𝒆𝒏𝒕 𝑹𝒆𝒂𝒄𝒕𝒂𝒏𝒄𝒆
=
𝟔
𝟎.𝟏𝟑𝟒𝟏𝟕
= 𝟒𝟒. 𝟕𝟐 𝑴𝑽𝑨
Current Limiting Reactors-
A current limiting reactor, also sometimes called a series reactor, is an
inductive coil having a large inductive reactance in comparison to its
reactance and is used for limiting short circuit currents during fault
conditions.
Functions-
 Protective reactors are used to reduce flow of current in to a short
circuit.
 It is used to reduce the magnitude of voltage disturbances caused by
short circuit.
 They also localize the fault by limiting the current that flows into the
fault from other healthy feeders or part of the system.
 They reduce the duty imposed on switching equipment during short
circuits to be within economical ratings.
Types of Current Limiting Reactors-
1. Generator Reactor-
in series with the generators
2. Feeder Reactor-
in series with the feeder
2. Busbar Reactor-
a. Ring type
b. Tie bar type
G1
G2
Feeder
Busbar
Feeder
Busbar
G2
G1
Any Questions
?????????
Thank You

Más contenido relacionado

La actualidad más candente

Basic types of facts controllers
Basic types of facts controllersBasic types of facts controllers
Basic types of facts controllers
Ayyarao T S L V
 

La actualidad más candente (20)

Hvdc transmission seminar
Hvdc transmission seminar Hvdc transmission seminar
Hvdc transmission seminar
 
Symmetrical and un-symmetrical fault
Symmetrical and un-symmetrical faultSymmetrical and un-symmetrical fault
Symmetrical and un-symmetrical fault
 
Economic load dispatch(with and without losses)
Economic load dispatch(with and without losses)Economic load dispatch(with and without losses)
Economic load dispatch(with and without losses)
 
Two area system
Two area systemTwo area system
Two area system
 
Power system stability
Power system stabilityPower system stability
Power system stability
 
FACTS DEVICES AND POWER SYSTEM STABILITY ppt
FACTS DEVICES AND POWER SYSTEM STABILITY pptFACTS DEVICES AND POWER SYSTEM STABILITY ppt
FACTS DEVICES AND POWER SYSTEM STABILITY ppt
 
Electric power system
Electric power systemElectric power system
Electric power system
 
Alternator protection
Alternator protectionAlternator protection
Alternator protection
 
Power system fault analysis ppt
Power system fault analysis pptPower system fault analysis ppt
Power system fault analysis ppt
 
Hvdc transmission & its applications
Hvdc transmission & its applicationsHvdc transmission & its applications
Hvdc transmission & its applications
 
Exp 3 (1)3. To Formulate YBUS Matrix By Singular Transformation.
Exp 3 (1)3.	To Formulate YBUS Matrix By Singular Transformation.Exp 3 (1)3.	To Formulate YBUS Matrix By Singular Transformation.
Exp 3 (1)3. To Formulate YBUS Matrix By Singular Transformation.
 
Load dispatch center
Load dispatch centerLoad dispatch center
Load dispatch center
 
Synchronous machines
Synchronous machinesSynchronous machines
Synchronous machines
 
Basic types of facts controllers
Basic types of facts controllersBasic types of facts controllers
Basic types of facts controllers
 
VSC based HVDC system
VSC based HVDC systemVSC based HVDC system
VSC based HVDC system
 
Protective relay
Protective relay Protective relay
Protective relay
 
Unit 2.Converter and Chopper fed Dc drives
Unit 2.Converter and Chopper fed Dc drivesUnit 2.Converter and Chopper fed Dc drives
Unit 2.Converter and Chopper fed Dc drives
 
Transient in Power system
Transient in Power systemTransient in Power system
Transient in Power system
 
Power electronics Phase Controlled Rectifiers - SCR
Power electronics   Phase Controlled Rectifiers - SCRPower electronics   Phase Controlled Rectifiers - SCR
Power electronics Phase Controlled Rectifiers - SCR
 
Synchronous motor
Synchronous motorSynchronous motor
Synchronous motor
 

Similar a Symmetrical Fault Analysis

FAULT Analysis presentation Armstrong
FAULT Analysis presentation ArmstrongFAULT Analysis presentation Armstrong
FAULT Analysis presentation Armstrong
Armstrong Okai Ababio
 
Alternating Current Machines-Synchronous Machines
Alternating Current Machines-Synchronous MachinesAlternating Current Machines-Synchronous Machines
Alternating Current Machines-Synchronous Machines
Talia Carbis
 
ECNG 3015 - PU system and 3Phase Fault calculation
ECNG 3015 - PU system and 3Phase Fault calculation ECNG 3015 - PU system and 3Phase Fault calculation
ECNG 3015 - PU system and 3Phase Fault calculation
Chandrabhan Sharma
 
Emec 1 bank nee 301
Emec 1 bank nee 301Emec 1 bank nee 301
Emec 1 bank nee 301
Ravi Anand
 

Similar a Symmetrical Fault Analysis (20)

Lecture 02.pptx
Lecture 02.pptxLecture 02.pptx
Lecture 02.pptx
 
FAULT Analysis presentation Armstrong
FAULT Analysis presentation ArmstrongFAULT Analysis presentation Armstrong
FAULT Analysis presentation Armstrong
 
Synchronous machines
Synchronous machinesSynchronous machines
Synchronous machines
 
Section 7 Fault Analysis.pdf
Section 7 Fault Analysis.pdfSection 7 Fault Analysis.pdf
Section 7 Fault Analysis.pdf
 
Alternating Current Machines-Synchronous Machines
Alternating Current Machines-Synchronous MachinesAlternating Current Machines-Synchronous Machines
Alternating Current Machines-Synchronous Machines
 
Cahpter_7_Symmetrical_Fault_Analysis.pptx
Cahpter_7_Symmetrical_Fault_Analysis.pptxCahpter_7_Symmetrical_Fault_Analysis.pptx
Cahpter_7_Symmetrical_Fault_Analysis.pptx
 
overvoltage in distribution network
overvoltage in distribution networkovervoltage in distribution network
overvoltage in distribution network
 
CHAPTER 3 Voltage Drop and Short Circuit Analysis.pptx
CHAPTER 3 Voltage Drop and Short Circuit Analysis.pptxCHAPTER 3 Voltage Drop and Short Circuit Analysis.pptx
CHAPTER 3 Voltage Drop and Short Circuit Analysis.pptx
 
presentation_transformers_1489551826_236516.ppt
presentation_transformers_1489551826_236516.pptpresentation_transformers_1489551826_236516.ppt
presentation_transformers_1489551826_236516.ppt
 
Three phase transformers
Three phase transformersThree phase transformers
Three phase transformers
 
per_unit_system.pptx
per_unit_system.pptxper_unit_system.pptx
per_unit_system.pptx
 
Power-System-Slide-1.pptx
Power-System-Slide-1.pptxPower-System-Slide-1.pptx
Power-System-Slide-1.pptx
 
CHAPTER 3 - Three Phase Network.ppt
CHAPTER 3 - Three Phase Network.pptCHAPTER 3 - Three Phase Network.ppt
CHAPTER 3 - Three Phase Network.ppt
 
EMEC-II, unit 1
EMEC-II, unit 1EMEC-II, unit 1
EMEC-II, unit 1
 
8925273.ppt
8925273.ppt8925273.ppt
8925273.ppt
 
Power system safety and protection
Power system safety and protectionPower system safety and protection
Power system safety and protection
 
Chapter 3 Generation of high voltages and current
Chapter 3 Generation of high voltages and currentChapter 3 Generation of high voltages and current
Chapter 3 Generation of high voltages and current
 
ECNG 3015 - PU system and 3Phase Fault calculation
ECNG 3015 - PU system and 3Phase Fault calculation ECNG 3015 - PU system and 3Phase Fault calculation
ECNG 3015 - PU system and 3Phase Fault calculation
 
Emec 1 bank nee 301
Emec 1 bank nee 301Emec 1 bank nee 301
Emec 1 bank nee 301
 
An Improved Single Phase Transformer less Inverter Topology for Cost Effecti...
An Improved Single Phase Transformer less Inverter Topology  for Cost Effecti...An Improved Single Phase Transformer less Inverter Topology  for Cost Effecti...
An Improved Single Phase Transformer less Inverter Topology for Cost Effecti...
 

Más de SANTOSH GADEKAR (9)

Unit 5 Economic Load Dispatch and Unit Commitment
Unit 5 Economic Load Dispatch and Unit CommitmentUnit 5 Economic Load Dispatch and Unit Commitment
Unit 5 Economic Load Dispatch and Unit Commitment
 
Unit 4 Automatic Generation Control
Unit 4 Automatic Generation ControlUnit 4 Automatic Generation Control
Unit 4 Automatic Generation Control
 
Unit 2 Reactive Power Management
Unit 2 Reactive Power ManagementUnit 2 Reactive Power Management
Unit 2 Reactive Power Management
 
Unit 1 Power System Stability
Unit 1 Power System Stability Unit 1 Power System Stability
Unit 1 Power System Stability
 
Unit 3 FACTS Technology
Unit 3 FACTS TechnologyUnit 3 FACTS Technology
Unit 3 FACTS Technology
 
HVDC System
HVDC SystemHVDC System
HVDC System
 
Traction Motors and Control
Traction Motors and ControlTraction Motors and Control
Traction Motors and Control
 
Unsymmetrical Fault Analysis
Unsymmetrical Fault AnalysisUnsymmetrical Fault Analysis
Unsymmetrical Fault Analysis
 
Traction Mechanics
Traction MechanicsTraction Mechanics
Traction Mechanics
 

Último

Integrated Test Rig For HTFE-25 - Neometrix
Integrated Test Rig For HTFE-25 - NeometrixIntegrated Test Rig For HTFE-25 - Neometrix
Integrated Test Rig For HTFE-25 - Neometrix
Neometrix_Engineering_Pvt_Ltd
 
Verification of thevenin's theorem for BEEE Lab (1).pptx
Verification of thevenin's theorem for BEEE Lab (1).pptxVerification of thevenin's theorem for BEEE Lab (1).pptx
Verification of thevenin's theorem for BEEE Lab (1).pptx
chumtiyababu
 
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak HamilCara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Kandungan 087776558899
 
Hospital management system project report.pdf
Hospital management system project report.pdfHospital management system project report.pdf
Hospital management system project report.pdf
Kamal Acharya
 

Último (20)

Double Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torqueDouble Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torque
 
Computer Networks Basics of Network Devices
Computer Networks  Basics of Network DevicesComputer Networks  Basics of Network Devices
Computer Networks Basics of Network Devices
 
data_management_and _data_science_cheat_sheet.pdf
data_management_and _data_science_cheat_sheet.pdfdata_management_and _data_science_cheat_sheet.pdf
data_management_and _data_science_cheat_sheet.pdf
 
HAND TOOLS USED AT ELECTRONICS WORK PRESENTED BY KOUSTAV SARKAR
HAND TOOLS USED AT ELECTRONICS WORK PRESENTED BY KOUSTAV SARKARHAND TOOLS USED AT ELECTRONICS WORK PRESENTED BY KOUSTAV SARKAR
HAND TOOLS USED AT ELECTRONICS WORK PRESENTED BY KOUSTAV SARKAR
 
Integrated Test Rig For HTFE-25 - Neometrix
Integrated Test Rig For HTFE-25 - NeometrixIntegrated Test Rig For HTFE-25 - Neometrix
Integrated Test Rig For HTFE-25 - Neometrix
 
Computer Lecture 01.pptxIntroduction to Computers
Computer Lecture 01.pptxIntroduction to ComputersComputer Lecture 01.pptxIntroduction to Computers
Computer Lecture 01.pptxIntroduction to Computers
 
Hostel management system project report..pdf
Hostel management system project report..pdfHostel management system project report..pdf
Hostel management system project report..pdf
 
Block diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.pptBlock diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.ppt
 
Introduction to Serverless with AWS Lambda
Introduction to Serverless with AWS LambdaIntroduction to Serverless with AWS Lambda
Introduction to Serverless with AWS Lambda
 
Verification of thevenin's theorem for BEEE Lab (1).pptx
Verification of thevenin's theorem for BEEE Lab (1).pptxVerification of thevenin's theorem for BEEE Lab (1).pptx
Verification of thevenin's theorem for BEEE Lab (1).pptx
 
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak HamilCara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
 
kiln thermal load.pptx kiln tgermal load
kiln thermal load.pptx kiln tgermal loadkiln thermal load.pptx kiln tgermal load
kiln thermal load.pptx kiln tgermal load
 
Tamil Call Girls Bhayandar WhatsApp +91-9930687706, Best Service
Tamil Call Girls Bhayandar WhatsApp +91-9930687706, Best ServiceTamil Call Girls Bhayandar WhatsApp +91-9930687706, Best Service
Tamil Call Girls Bhayandar WhatsApp +91-9930687706, Best Service
 
Generative AI or GenAI technology based PPT
Generative AI or GenAI technology based PPTGenerative AI or GenAI technology based PPT
Generative AI or GenAI technology based PPT
 
Hospital management system project report.pdf
Hospital management system project report.pdfHospital management system project report.pdf
Hospital management system project report.pdf
 
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
 
School management system project Report.pdf
School management system project Report.pdfSchool management system project Report.pdf
School management system project Report.pdf
 
PE 459 LECTURE 2- natural gas basic concepts and properties
PE 459 LECTURE 2- natural gas basic concepts and propertiesPE 459 LECTURE 2- natural gas basic concepts and properties
PE 459 LECTURE 2- natural gas basic concepts and properties
 
AIRCANVAS[1].pdf mini project for btech students
AIRCANVAS[1].pdf mini project for btech studentsAIRCANVAS[1].pdf mini project for btech students
AIRCANVAS[1].pdf mini project for btech students
 
Online food ordering system project report.pdf
Online food ordering system project report.pdfOnline food ordering system project report.pdf
Online food ordering system project report.pdf
 

Symmetrical Fault Analysis

  • 1. DEPARTMENT OF ELECTRICAL ENGINEERING JSPMS BHIVARABAISAWANTINSTITUTEOFTECHNOLOGYANDRESEARCH, WAGHOLI,PUNE A.Y. 2019-20 (SEM-II) Class: T.E. Subject: Power System-II Prepared by Prof. S. D. Gadekar Santoshgadekar.919@gmail.com Mob. No-9130827661
  • 2. Fault- Any defect in the electrical circuit or network which deviates the current paths from its intended path is called “FAULT”. The fault which results into symmetrical currents (Three line currents of equal magnitude with 120ᵒ displacement) is called symmetrical Faults (5%). 1. Three Phase to ground fault 2. Three Phase fault
  • 4. Reasons of Faults in Electrical Power System- Failure of Insulation Mechanical Failure Excessive Internal and External Electric Stress Heavy winds Lightning Strokes Falling of Trees on the line Over voltage or under voltage due to switching surges Vehicle accidents due to pole, towers etc
  • 5. Three phase short circuit Analysis of Unloaded Alternator- The flux linkages in the armature circuits and the field circuit can not changed suddenly by the application of short circuit to the armature winding. For maintaining these flux linkages constant large changes of current may take place in both of the windings, when short circuit occurs in order to keep their respective flux linkages constant.
  • 6. Direct-Axis Subtransient Reactance, 𝑋 𝑑 𝑖𝑖 𝑋 𝑑 𝑖𝑖 =𝑋𝑙 + 1 1 𝑋 𝑎 + 1 𝑋 𝑓 + 1 𝑋 𝑑𝑤 … … … . Ohm
  • 7. Direct-Axis Transient Reactance, 𝑋 𝑑 𝑖 𝑋 𝑑 𝑖 =𝑋𝑙 + 1 1 𝑋 𝑎 + 1 𝑋 𝑓 … … … . Ohm
  • 8. Direct-Axis Steady State Reactance, 𝑋 𝑑 𝑋 𝑑=𝑋𝑙 + 𝑋 𝑎 … … … . Ohm
  • 9. 𝑋 𝑑 𝑖𝑖 <𝑋 𝑑 𝑖 <𝑋 𝑑 Relation between direct axis Reactance
  • 10. 3-Phase fault current transients in synchronous generators The current can be represented as a transient DC component added on top of a symmetrical AC component. Before the fault, only AC voltages and currents are present, but immediately after the fault, both AC and DC currents are present.
  • 11. Symmetrical AC component of the fault current: There are three periods of time:  Sub-transient period: first cycle or so after the fault – AC current is very large and falls rapidly;  Transient period: current falls at a slower rate;  Steady-state period: current reaches its steady value.
  • 12. Some Important Formulae- Isc Per Unit = 𝑃𝑒𝑟 𝑈𝑛𝑖𝑡 𝑣𝑜𝑙𝑡𝑎𝑔𝑒 𝑎𝑡 𝑓𝑎𝑢𝑙𝑡 𝑝𝑜𝑖𝑛𝑡 𝑃𝑒𝑟 𝑈𝑛𝑖𝑡 𝐸𝑞𝑢𝑖𝑣𝑎𝑙𝑒𝑛𝑡 𝑅𝑒𝑎𝑐𝑡𝑎𝑛𝑐𝑒 Per Unit Fault MVA = 3 × 𝑃𝑒𝑟 𝑈𝑛𝑖𝑡 𝐹𝑎𝑢𝑙𝑡 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 × Per Unit Source Voltage Fault MVA = 𝐵𝑎𝑠𝑒 𝑀𝑉𝐴 𝑃𝑈 𝐸𝑞𝑢𝑖𝑣𝑎𝑙𝑒𝑛𝑡 𝑅𝑒𝑎𝑐𝑡𝑎𝑛𝑐𝑒 (𝑀𝑉𝐴 𝐿𝑎𝑔𝑔𝑖𝑛𝑔) Fault Current Isc = 𝐹𝑎𝑢𝑙𝑡 𝑀𝑉𝐴 × 103 3 ×𝐵𝑎𝑠𝑒 𝑘𝑉 𝐴 Fault MVA = 3 × Fault Current × Base Voltage × 10−6
  • 13. Example -1 A 3 phase – 10000 KVA , 11kv alternator has a subtransient reactance of 8% . A three phase short circuit occurs at its terminals. Determine fault current and fault MVA.  Base MVA for Complete Section-10 MVA  Base kV for Generator Section-11 kV Fault Current Isc =𝑃𝑒𝑟 𝑈𝑛𝑖𝑡 𝑆ℎ𝑜𝑟𝑡 𝐶𝑖𝑟𝑐𝑢𝑖𝑡 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 × 𝐵𝑎𝑠𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡
  • 14. Solution : Base Current, Base Current = Base MVA 3 Base kV = 10 √3×11 = 0.525kA Isc Per Unit = 𝑷𝒆𝒓 𝑼𝒏𝒊𝒕 𝑽𝒐𝒍𝒕𝒂𝒈𝒆 𝑷𝒆𝒓 𝑼𝒏𝒊𝒕 𝑹𝒆𝒂𝒄𝒕𝒂𝒏𝒄𝒆 = 𝟏 𝒋𝟎.𝟎𝟖 =12.5 < −900 Ampere Fault Current Isc =𝑃𝑒𝑟 𝑈𝑛𝑖𝑡 𝑆ℎ𝑜𝑟𝑡 𝐶𝑖𝑟𝑐𝑢𝑖𝑡 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 × 𝐵𝑎𝑠𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 =12.5 × 525 =6562 A
  • 15. Fault Power (MVA) = 𝟑 × 𝑰𝒔𝒄 × 𝑺𝒐𝒖𝒓𝒄𝒆 𝑽𝒐𝒍𝒕𝒂𝒈𝒆 × 𝟏𝟎−𝟔 𝑴𝑽𝑨 =√𝟑 × 𝟔𝟓𝟔𝟐 × 𝟏𝟏𝟎𝟎𝟎 × 𝟏𝟎−𝟔 =125 MVA
  • 16. Example-2 A three phase 5 MVA, 6.6 kV Alternator with a reactance of 8% is connected to a feeder of series impedance of (0.12+0.48j) Ohms/Phase/Km. The transformer is rated at 3 MVA, 6.6 /33 kV and has a reactance of 5 %. Determine fault current supplied by the generator operating under no load with a voltage a voltage of 6.9 kV, When a three phase symmetrical fault occurs at a point 15 KM along the feeder.  Base MVA for Complete Section-5 MVA  Base kV for Generator Section-6.6 kV
  • 17. Example-2 A three phase 5 MVA, 6.6 kV Alternator with a reactance of 8% is connected to a feeder of series impedance of (0.12+0.48j) Ohms/Phase/Km. The transformer is rated at 3 MVA, 6.6 /33 kV and has a reactance of 5 %. Determine fault current supplied by the generator operating under no load with a voltage a voltage of 6.9 kV, When a three phase symmetrical fault occurs at a point 15 KM along the feeder. BASE MVA= 5 MVA FOR ENTIRE SECTION Core of Transformer Base KV=6.6 kV up to the Primary of Transformer Base KV=33 kV from the Secondary of Transformer----Along the Feeder
  • 18. Example-2 A three phase 5 MVA, 6.6 kV Alternator with a reactance of 8% is connected to a feeder of series impedance of (0.12+0.48j) Ohms/Phase/Km. The transformer is rated at 3 MVA, 6.6 /33 kV and has a reactance of 5 %. Determine fault current supplied by the generator operating under no load with a voltage a voltage of 6.9 kV, When a three phase symmetrical fault occurs at a point 15 KM along the feeder. 𝑋 𝑛𝑒𝑤 𝑝𝑒𝑟 𝑢𝑛𝑖𝑡 = 𝑋 𝑜𝑙𝑑 𝑝𝑒𝑟 𝑢𝑛𝑖𝑡 ∗ 𝑀𝑉𝐴 𝑏𝑎𝑠𝑒 𝑛𝑒𝑤 𝑀𝑉𝐴 𝑏𝑎𝑠𝑒 𝑜𝑙𝑑 ∗ 𝑘𝑉 𝑏𝑎𝑠𝑒 𝑜𝑙𝑑 𝑘𝑉𝑏𝑎𝑠𝑒 𝑛𝑒𝑤 2 Using Above formula calculate new values of per unit reactance for all the components of given power system by referring the kV base and MVA base. 𝑋 𝑛𝑒𝑤 𝑝𝑒𝑟 𝑢𝑛𝑖𝑡 for Alternator=0.08*( 5 5 )*( 6.6 6.6 )2 =0.08 PU 𝑋 𝑛𝑒𝑤 𝑝𝑒𝑟 𝑢𝑛𝑖𝑡 for Transformer=0.05*( 5 3 )*( 6.6 6.6 )2------------------Referring to Primary =0.0833 PU
  • 19. Example-2 A three phase 5 MVA, 6.6 kV Alternator with a reactance of 8% is connected to a feeder of series impedance of (0.12+0.48j) Ohms/Phase/Km. The transformer is rated at 3 MVA, 6.6 /33 kV and has a reactance of 5 %. Determine fault current supplied by the generator operating under no load with a voltage a voltage of 6.9 kV, When a three phase symmetrical fault occurs at a point 15 KM along the feeder. 𝑋 𝑝𝑒𝑟 𝑢𝑛𝑖𝑡 = 𝑋 𝑎𝑐𝑡𝑢𝑎𝑙 ∗ 𝑀𝑉𝐴 𝑏𝑎𝑠𝑒 𝑛𝑒𝑤 (𝑘𝑉𝑏𝑎𝑠𝑒 𝑛𝑒𝑤)2 Using Above formula calculate the per unit reactance for the components, whose actual values are given. In this case impedance of feeder is given as 0.12+0.48j ohms/phase/Km & total distance given as 15 KM. 𝑍 𝑝𝑒𝑟 𝑢𝑛𝑖𝑡 =(1.8+7.2j)*( 5 332) =0.008+0.033j PU 𝑍 𝐴𝑐𝑡𝑢𝑎𝑙 𝑓𝑜𝑟 𝑓𝑒𝑒𝑑𝑒𝑟 𝑜𝑓 𝑙𝑒𝑛𝑔𝑡ℎ 15 𝑘𝑚 = 0.12 + 0.48𝑗 ∗ 15 =1.8+7.2j-----Ohm/phase
  • 20. Example-2 A three phase 5 MVA, 6.6 kV Alternator with a reactance of 8% is connected to a feeder of series impedance of (0.12+0.48j) Ohms/Phase/Km. The transformer is rated at 3 MVA, 6.6 /33 kV and has a reactance of 5 %. Determine fault current supplied by the generator operating under no load with a voltage a voltage of 6.9 kV, When a three phase symmetrical fault occurs at a point 15 KM along the feeder. Total Per Unit impedance up to fault= X per unit of Alternator+ X per unit of transformer+ Per unit impedance of Feeder up to fault point Total Per Unit impedance up to fault= 0.008+0.196j Per Unit Fault Current= Actual Fault Current 𝐵𝑎𝑠𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 Per Unit Fault Current= Per unit Voltage 𝑷𝒆𝒓 𝑼𝒏𝒊𝒕 𝑰𝒎𝒑𝒆𝒅𝒂𝒏𝒄𝒆 𝒖𝒑 𝒕𝒐 𝒇𝒂𝒖𝒍𝒕 𝒑𝒐𝒊𝒏𝒕 Per Unit Fault Current= 6.9 6.6 0.008+0.196𝑗 =5.3282<-87.66 PU
  • 21. Example-2 A three phase 5 MVA, 6.6 kV Alternator with a reactance of 8% is connected to a feeder of series impedance of (0.12+0.48j) Ohms/Phase/Km. The transformer is rated at 3 MVA, 6.6 /33 kV and has a reactance of 5 %. Determine fault current supplied by the generator operating under no load with a voltage a voltage of 6.9 kV, When a three phase symmetrical fault occurs at a point 15 KM along the feeder. Per Unit Fault Current= Actual Fault Current 𝐵𝑎𝑠𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 Per Unit Fault Current= 6.9 6.6 0.008+0.196𝑗 =5.3282<-87.66 PU Base Fault Current= 𝐵𝑎𝑠𝑒 𝑀𝑉𝐴 3 ∗𝐵𝑎𝑠𝑒 𝑘𝑉 = 𝟓 𝟑∗𝟑𝟑 = 𝟎. 𝟎𝟖𝟕𝟒𝟕 𝑲𝑨 Actual Fault Current=Base Current∗ Per Unit Fault Current =5.3282*87.47 =466 Ampere
  • 22. Example-3 Two three phase, 11kV Alternators of capacities 8 MVA & 4 MVA and Substransient reactance of 8% and 4% respectively operate in parallel. The generating station is connected to a transmission line of 200 Km length through a step up transformer of capacity 4 MVA, having percentage reactance of 3.5 %. The impedance ohm per phase per km of its is 0.025+0.1j and it operates at 66 kV. Calculate the short circuit MVA for a phase to phase faults at receiving end of the transmission line and at the sending end.  Base MVA for Complete Section- 8 MVA  Base kV for Generator Section- 11 kV
  • 23. Example-3 Two three phase, 11kV Alternators of capacities 8 MVA & 4 MVA and Substransient reactance of 8% and 4% respectively operate in parallel. The generating station is connected to a transmission line of 200 Km length through a step up transformer of capacity 4 MVA, having percentage reactance of 3.5 %. The impedance ohm per phase per km of its is 0.025+0.1j and it operates at 66 kV. Calculate the short circuit MVA for a phase to phase faults at receiving end of the transmission line and at the sending end. G1 BASE MVA= 8 MVA FOR ENTIRE SECTION Transformer Base KV=11 kV up to the Primary of Transformer Base KV=66 kV from the Secondary of Transformer----Along the Feeder (0.025+0.1j)*200 Km=5+20j ohm G2 8 MVA, 11 kV, 8% 4 MVA, 11 kV, 4% 4 MVA, 11/66 kV, 3.5% Transmission line operates at 66 kV F1 F2
  • 24. Example-3 Two three phase, 11kV Alternators of capacities 8 MVA & 4 MVA and Substransient reactance of 8% and 4% respectively operate in parallel. The generating station is connected to a transmission line of 200 Km length through a step up transformer of capacity 4 MVA, having percentage reactance of 3.5 %. The impedance ohm per phase per km of its is 0.025+0.1j and it operates at 66 kV. Calculate the short circuit MVA for a phase to phase faults at receiving end of the transmission line and at the sending end. 𝑋 𝑛𝑒𝑤 𝑝𝑒𝑟 𝑢𝑛𝑖𝑡 = 𝑋 𝑜𝑙𝑑 𝑝𝑒𝑟 𝑢𝑛𝑖𝑡 ∗ 𝑀𝑉𝐴 𝑏𝑎𝑠𝑒 𝑛𝑒𝑤 𝑀𝑉𝐴 𝑏𝑎𝑠𝑒 𝑜𝑙𝑑 ∗ 𝑘𝑉 𝑏𝑎𝑠𝑒 𝑜𝑙𝑑 𝑘𝑉𝑏𝑎𝑠𝑒 𝑛𝑒𝑤 2 𝑋 𝑛𝑒𝑤 𝑝𝑒𝑟 𝑢𝑛𝑖𝑡 for Alternator 1 =0.08*( 8 8 )*( 11 11 )2 =0.08 PU 𝑋 𝑛𝑒𝑤 𝑝𝑒𝑟 𝑢𝑛𝑖𝑡 for Transformer=0.035*( 8 4 )*( 11 11 )2------------------Referring to Primary =0.07 PU 𝑋 𝑛𝑒𝑤 𝑝𝑒𝑟 𝑢𝑛𝑖𝑡 for Alternator 2 =0.04*( 8 4 )*( 11 11 )2 =0.08 PU
  • 25. Example-3 Two three phase, 11kV Alternators of capacities 8 MVA & 4 MVA and Substransient reactance of 8% and 4% respectively operate in parallel. The generating station is connected to a transmission line of 200 Km length through a step up transformer of capacity 4 MVA, having percentage reactance of 3.5 %. The impedance ohm per phase per km of its is 0.025+0.1j and it operates at 66 kV. Calculate the short circuit MVA for a phase to phase faults at receiving end of the transmission line and at the sending end. 𝑋 𝑝𝑒𝑟 𝑢𝑛𝑖𝑡 = 𝑋 𝑎𝑐𝑡𝑢𝑎𝑙 ∗ 𝑀𝑉𝐴 𝑏𝑎𝑠𝑒 𝑛𝑒𝑤 (𝑘𝑉𝑏𝑎𝑠𝑒 𝑛𝑒𝑤)2 Using Above formula calculate the per unit reactance for the components, whose actual values are given. In this case impedance of feeder is given as 0.025+0.1j ohms/phase/Km & total distance given as 200 KM. 𝑍 𝑝𝑒𝑟 𝑢𝑛𝑖𝑡 =(5+20j)*( 8 662) =0.0092+0.0368j PU 𝑍 𝐴𝑐𝑡𝑢𝑎𝑙 𝑓𝑜𝑟 𝑓𝑒𝑒𝑑𝑒𝑟 𝑜𝑓 𝑙𝑒𝑛𝑔𝑡ℎ 200 𝑘𝑚 = 0.025 + 0.1𝑗 ∗200 =5+20j-----Ohm/phase
  • 26. Example-3 Two three phase, 11kV Alternators of capacities 8 MVA & 4 MVA and Substransient reactance of 8% and 4% respectively operate in parallel. The generating station is connected to a transmission line of 200 Km length through a step up transformer of capacity 4 MVA, having percentage reactance of 3.5 %. The impedance ohm per phase per km of its is 0.025+0.1j and it operates at 66 kV. Calculate the short circuit MVA for a phase to phase faults at receiving end of the transmission line and at the sending end. G1 G2 0.08 PU Transmission line operates at 66 kV0.08 PU 0.07 PU 0.0092+0.0368j PU E1=1 PU E2=1 PU G Transmission line operates at 66 kV 0.04 PU 0.07 PU 0.0092+0.0368j PU E=1 PU F1 F2 F1 F2
  • 27. Example-3 Two three phase, 11kV Alternators of capacities 8 MVA & 4 MVA and Substransient reactance of 8% and 4% respectively operate in parallel. The generating station is connected to a transmission line of 200 Km length through a step up transformer of capacity 4 MVA, having percentage reactance of 3.5 %. The impedance ohm per phase per km of its is 0.025+0.1j and it operates at 66 kV. Calculate the short circuit MVA for a phase to phase faults at receiving end of the transmission line and at the sending end. Fault MVA = 𝑩𝒂𝒔𝒆 𝑴𝑽𝑨 𝑷𝑼 𝑬𝒒𝒖𝒊𝒗𝒂𝒍𝒆𝒏𝒕 𝑹𝒆𝒂𝒄𝒕𝒂𝒏𝒄𝒆 G Transmission line operates at 66 kV 0.04 PU 0.07 PU 0.0092+0.0368j PU E=1 PU F1 F2 Fault MVA at F1= 8 0.04+0.07 𝑗 =72.72 MVA Lagging Fault MVA at F2= 8 0.04+0.07 𝑗+(0.0092+0.0368𝑗) =54.38 MVA Lagging
  • 28. Example-4 Two three phase, 11kV Alternators of capacities 10 MVA and transient reactance of 20% at their own MVA base. The two transformer are also identical and are rated 5MVA, 11/66 kV and have a reactance of 5% at their own MVA base. The tie line is 100 Km and has a reactance of 0.1 ohm/Km. A three phase fault occurs at a distance of 25 Km from one end of line when the system is on no load but at rated voltage. Calculate fault MVA and fault current.  Base MVA for Complete Section- 10 MVA  Base kV for Generator Section- 11 kV
  • 29. Example-4 Two three phase, 11kV Alternators of capacities 10 MVA and transient reactance of 20% at their own MVA base. The two transformer are also identical and are rated 5MVA, 11/66 kV and have a reactance of 5% at their own MVA base. The tie line is 100 Km and has a reactance of 0.1 ohm/Km. A three phase fault occurs at a distance of 25 Km from one end of line when the system is on no load but at rated voltage. Calculate fault MVA and fault current. G1 BASE MVA= 10 MVA FOR ENTIRE SECTION Transformer Base KV=11 kV up to the Primary of Transformer Base KV=66 kV from the Secondary of Transformer----Along the Feeder G2 10 MVA, 11 kV, 20% 10 MVA, 11 kV, 20% 5 MVA, 11/66 kV, 5% Transmission line operates at 66 kV F1 5 MVA, 66/11 kV, 5% 25 Km 75 Km Transformer Base KV=11 kV X1 X2
  • 30. Example-4 Two three phase, 11kV Alternators of capacities 10 MVA and transient reactance of 20% at their own MVA base. The two transformer are also identical and are rated 5MVA, 11/66 kV and have a reactance of 5% at their own MVA base. The tie line is 100 Km and has a reactance of 0.1 ohm/Km. A three phase fault occurs at a distance of 25 Km from one end of line when the system is on no load but at rated voltage. Calculate fault MVA and fault current. 𝑋 𝑛𝑒𝑤 𝑝𝑒𝑟 𝑢𝑛𝑖𝑡 = 𝑋 𝑜𝑙𝑑 𝑝𝑒𝑟 𝑢𝑛𝑖𝑡 ∗ 𝑀𝑉𝐴 𝑏𝑎𝑠𝑒 𝑛𝑒𝑤 𝑀𝑉𝐴 𝑏𝑎𝑠𝑒 𝑜𝑙𝑑 ∗ 𝑘𝑉 𝑏𝑎𝑠𝑒 𝑜𝑙𝑑 𝑘𝑉𝑏𝑎𝑠𝑒 𝑛𝑒𝑤 2 𝑋 𝑛𝑒𝑤 𝑝𝑒𝑟 𝑢𝑛𝑖𝑡 for Alternator 1 & 2 =0.2*( 10 10 )*( 11 11 )2 =0.2 PU 𝑋 𝑛𝑒𝑤 𝑝𝑒𝑟 𝑢𝑛𝑖𝑡 for Transformer 1 & 2=0.05*( 10 5 )*( 11 11 )2------------------Referring to Primary for 1st transformer and Referring Secondary for 2nd transformer =0.1 PU As Rating of Alternator 1 & 2 and Transformer 1 & 2 are same
  • 31. Example-4 Two three phase, 11kV Alternators of capacities 10 MVA and transient reactance of 20% at their own MVA base. The two transformer are also identical and are rated 5MVA, 11/66 kV and have a reactance of 5% at their own MVA base. The tie line is 100 Km and has a reactance of 0.1 ohm/Km. A three phase fault occurs at a distance of 25 Km from one end of line when the system is on no load but at rated voltage. Calculate fault MVA and fault current. 𝑋 𝑝𝑒𝑟 𝑢𝑛𝑖𝑡 = 𝑋 𝑎𝑐𝑡𝑢𝑎𝑙 ∗ 𝑀𝑉𝐴 𝑏𝑎𝑠𝑒 𝑛𝑒𝑤 (𝑘𝑉𝑏𝑎𝑠𝑒 𝑛𝑒𝑤)2 0.1j ohms/phase/Km & total distance given as 100 KM. X1=0.1j*25=2.5j Ohm/phase X2=0.1j*75=7.5j Ohm/phase 𝑋1 𝑝𝑒𝑟 𝑢𝑛𝑖𝑡 𝑢𝑝 𝑡𝑜 𝑙𝑒𝑛𝑔𝑡ℎ 25 𝑘𝑚 =(2.5j)*( 10 662) =0.00574 PU 𝑋2 𝑝𝑒𝑟 𝑢𝑛𝑖𝑡 𝑢𝑝 𝑡𝑜 𝑙𝑒𝑛𝑔𝑡ℎ 75 𝑘𝑚 =(7.5j)*( 10 662) =0.01722 PU
  • 32. Example-4 Two three phase, 11kV Alternators of capacities 10 MVA and transient reactance of 20% at their own MVA base. The two transformer are also identical and are rated 5MVA, 11/66 kV and have a reactance of 5% at their own MVA base. The tie line is 100 Km and has a reactance of 0.1 ohm/Km. A three phase fault occurs at a distance of 25 Km from one end of line when the system is on no load but at rated voltage. Calculate fault MVA and fault current. 0.2 PU 0.2 PU 0.1 PU E1=1 PU E2=1 PU 0.1 PU 𝑿 𝟏 =0.00574 PU 𝑿 𝟐 = 0.01722 PU G1 G2 0.30574 PU E1=1 PU E2=1 PU 0.31722 PU G E1=1 PU 0.1557 PU G2 G1 F1
  • 33. Example-4 Two three phase, 11kV Alternators of capacities 10 MVA and transient reactance of 20% at their own MVA base. The two transformer are also identical and are rated 5MVA, 11/66 kV and have a reactance of 5% at their own MVA base. The tie line is 100 Km and has a reactance of 0.1 ohm/Km. A three phase fault occurs at a distance of 25 Km from one end of line when the system is on no load but at rated voltage. Calculate fault MVA and fault current. Fault MVA = 𝑩𝒂𝒔𝒆 𝑴𝑽𝑨 𝑷𝑼 𝑬𝒒𝒖𝒊𝒗𝒂𝒍𝒆𝒏𝒕 𝑹𝒆𝒂𝒄𝒕𝒂𝒏𝒄𝒆 Fault MVA = 10 0.1557𝑗 =64.3 MVA Lagging G1 E1=1 PU 0.1557 PU Fault Current Isc = 𝐹𝑎𝑢𝑙𝑡 𝑀𝑉𝐴 × 103 3 ×𝐵𝑎𝑠𝑒 𝑘𝑉 𝐴 Fault Current Isc = 64.3 × 103 3 ×66 𝐴 =562 Ampere
  • 34. Example-5 Determine the required MVA rating of the circuit breaker CB for the system shown in fig. Consider the grid as infinite bus. Choose 6 MVA as base. Grid CB Load 6 MVA, 33/11 kV, 0.01+0.08j PU 3 Phase, 11 kV, 5800 kVA, 0.8 Lag, 0.02j PU 9+18j 9+18j BASE MVA= 6 MVA FOR ENTIRE SECTION Transformer Base KV=33 kV up to the Primary of Transformer Base KV=11 kV from the Secondary of Transformer----Along the Feeder
  • 35. Example-5 Determine the required MVA rating of the circuit breaker CB for the system shown in fig. Consider the grid as infinite bus. Choose 6 MVA as base. Grid CB Load 6 MVA, 33/11 kV, 0.01+0.08j PU 3 Phase, 11 kV, 5800 kVA, 0.8 Lag, 0.02j PU 9+18j 9+18j 𝑋 𝑛𝑒𝑤 𝑝𝑒𝑟 𝑢𝑛𝑖𝑡 = 𝑋 𝑜𝑙𝑑 𝑝𝑒𝑟 𝑢𝑛𝑖𝑡 ∗ 𝑀𝑉𝐴 𝑏𝑎𝑠𝑒 𝑛𝑒𝑤 𝑀𝑉𝐴 𝑏𝑎𝑠𝑒 𝑜𝑙𝑑 ∗ 𝑘𝑉 𝑏𝑎𝑠𝑒 𝑜𝑙𝑑 𝑘𝑉𝑏𝑎𝑠𝑒 𝑛𝑒𝑤 2 𝑋 𝑛𝑒𝑤 𝑝𝑒𝑟 𝑢𝑛𝑖𝑡 for Transformer =(0.01+0.08j)*( 6 6 )*( 33 33 )2 ------------------Referring to Primary =0.01+0.08j PU 𝑋 𝑛𝑒𝑤 𝑝𝑒𝑟 𝑢𝑛𝑖𝑡 for Load =(0.02j)*( 6 5.8 )*( 11 11 )2 =0.207j PU
  • 36. Example-5 Determine the required MVA rating of the circuit breaker CB for the system shown in fig. Consider the grid as infinite bus. Choose 6 MVA as base. Grid CB Load 6 MVA, 33/11 kV, 0.01+0.08j PU 3 Phase, 11 kV, 5800 kVA, 0.8 Lag, 0.02j PU 9+18j 9+18j 𝑋 𝑝𝑒𝑟 𝑢𝑛𝑖𝑡 = 𝑋 𝑎𝑐𝑡𝑢𝑎𝑙 ∗ 𝑀𝑉𝐴 𝑏𝑎𝑠𝑒 𝑛𝑒𝑤 (𝑘𝑉𝑏𝑎𝑠𝑒 𝑛𝑒𝑤)2 Z 𝑝𝑒𝑟 𝑢𝑛𝑖𝑡 𝑓𝑜𝑟 𝐹𝑒𝑒𝑑𝑒𝑟 =(9+18j)*( 6 332) =0.04958+j0.09916 PU
  • 37. Example-5 Determine the required MVA rating of the circuit breaker CB for the system shown in fig. Consider the grid as infinite bus. Choose 6 MVA as base. Grid CB Load 6 MVA, 33/11 kV, 0.01+0.08j PU 3 Phase, 11 kV, 5800 kVA, 0.8 Lag, 0.02j PU 9+18j 9+18j G CB 0.04958+j0.09916 PU 0.04958+j0.09916 PU 0.01+0.08j PU 0.207j PU Equivalent impedance from grid to fault point, 𝑍 𝑒𝑞 = 0.13417 < 74.97° Ohm Fault MVA = 𝑩𝒂𝒔𝒆 𝑴𝑽𝑨 𝑷𝑼 𝑬𝒒𝒖𝒊𝒗𝒂𝒍𝒆𝒏𝒕 𝑹𝒆𝒂𝒄𝒕𝒂𝒏𝒄𝒆 = 𝟔 𝟎.𝟏𝟑𝟒𝟏𝟕 = 𝟒𝟒. 𝟕𝟐 𝑴𝑽𝑨
  • 38. Current Limiting Reactors- A current limiting reactor, also sometimes called a series reactor, is an inductive coil having a large inductive reactance in comparison to its reactance and is used for limiting short circuit currents during fault conditions. Functions-  Protective reactors are used to reduce flow of current in to a short circuit.  It is used to reduce the magnitude of voltage disturbances caused by short circuit.  They also localize the fault by limiting the current that flows into the fault from other healthy feeders or part of the system.  They reduce the duty imposed on switching equipment during short circuits to be within economical ratings.
  • 39. Types of Current Limiting Reactors- 1. Generator Reactor- in series with the generators 2. Feeder Reactor- in series with the feeder 2. Busbar Reactor- a. Ring type b. Tie bar type G1 G2 Feeder Busbar Feeder Busbar G2 G1