Más contenido relacionado
ASME_Water Tube Boilers_Feed Water Quality.pdf
- 1. Drum pressure (psi)
0-300
301-450
451-600
601-750
751-900
901-1000
1001-1500
1501-2000
Iron (ppm Fe)
0.100
0.050
0.030
0.025
0.020
0.020
0.010
0.010
Copper (ppm Cu)
0.050
0.025
0.020
0.020
0.015
0.015
0.010
0.010
Total hardness (ppm
CaCO3)
0.300
0.300
0.200
0.200
0.100
0.050
0.0
0.0
Silica (ppm SiO2)
150
90
40
30
20
8
2
1
Total alkalinity (ppm
CaCO3)
700
600
500
400
300
200
0
0
Specific conductance
(micro-ohms/cm) (un-
neutralized)
7000
6000
5000
4000
3000
2000
150
100
Boiler feed water
ASME Guidelines for Water Quality in Modern Industrial Water Tube Boilers for Reliable Continuous Operation