ISKRA Case study - Elektro Gorenjska
1. Energysector
Instruments Remote Monitoring in
Slovenian Electrodistribution Company
Elektro Gorenjska
Input/Output Modules Use
• Published by Iskra, d.d. • Version 1.0 March 2015
Input signals of PLC
Measurement of water, heat, gas etc. consumption
Substation control accessOvervoltage protection
Measurement of solar radiation, transformer
station temperature, wind speed etc.
Control
Auxiliary inputs
Use of Input /Output Modules
Power quality analyser functions also as a secondary protection device
High accurate data about consumption
Up to 32 alarms
Fast notification of faults in a system
Four energy counters for four-quadrant metering
Can be viewed on device or downloaded
Alarm
Energy
About Electrodistribution Company
Facts About Elektro Gorenjska
Elektro Gorenjska is one of the largest Slovenian Electrodistribution
Companies, which operates middle voltage (MV) as well as low voltage
(LV) infrastructure. It owns 1.333 MV/LV transformer stations and 14 HV
(high voltage)/LV transformer stations, mainly in the region of Gorenjska.
Its'customerbaseconsistsofaround87.000customers.
Elektro Gorenjska transformer stations were equipped with approximately 200 Iskra's measuring centres MI 7150, which were installed at the
beginning of this millennium. They were equipped with serial communication RS 232. A few of them were also equipped with new types of Iskra
instruments,namelywith18MC760networkanalyzersand25MC750networkrecorders.Fordatatransferfromtransformerstationsintothe
controlcentre,ElektroGorenjskausedWiMax,GPRSandEthernetcommunication.
www.iskra.eu
Situation before the intrduction of our systemSituation before the introduction of our system
20 kV
0,4 kV
MC MI
MC750
no. 1
MI7150
no. 2
Communication
terminal
WiMAX/GPRS
Ethernet
Offline data
reading from
MMC
Feeders
Substation 400/110 kV
HV 110 kV
Substation 110/20 kV
MV 20 kV
LV 0.4 kV
TS 20/0.4 kV
Distrbution network
2. Energysector
Instruments Remote Monitoring in
Slovenian Electrodistribution Company
Elektro Gorenjska
Input/Output Modules Use
• Published by Iskra, d.d. • Version 1.0 March 2015
Input signals of PLC
Measurement of water, heat, gas etc. consumption
Substation control accessOvervoltage protection
Measurement of solar radiation, transformer
station temperature, wind speed etc.
Control
Auxiliary inputs
Use of Input /Output Modules
Power quality analyser functions also as a secondary protection device
High accurate data about consumption
Up to 32 alarms
Fast notification of faults in a system
Four energy counters for four-quadrant metering
Can be viewed on device or downloaded
Alarm
Energy
About Electrodistribution Company
Facts About Elektro Gorenjska
Elektro Gorenjska is one of the largest Slovenian Electrodistribution
Companies, which operates middle voltage (MV) as well as low voltage
(LV) infrastructure. It owns 1.333 MV/LV transformer stations and 14 HV
(high voltage)/LV transformer stations, mainly in the region of Gorenjska.
Its'customerbaseconsistsofaround87.000customers.
Elektro Gorenjska transformer stations were equipped with approximately 200 Iskra's measuring centres MI 7150, which were installed at the
beginning of this millennium. They were equipped with serial communication RS 232. A few of them were also equipped with new types of Iskra
instruments,namelywith18MC760networkanalyzersand25MC750networkrecorders.Fordatatransferfromtransformerstationsintothe
controlcentre,ElektroGorenjskausedWiMax,GPRSandEthernetcommunication.
www.iskra.eu
Situation before the intrduction of our systemSituation before the introduction of our system
20 kV
0,4 kV
MC MI
MC750
no. 1
MI7150
no. 2
Communication
terminal
WiMAX/GPRS
Ethernet
Offline data
reading from
MMC
Feeders
Substation 400/110 kV
HV 110 kV
Substation 110/20 kV
MV 20 kV
LV 0.4 kV
TS 20/0.4 kV
Distrbution network
3. MC 774
Power Quality Analyser
MC 760
Network Analyser
MC 750
Network Recorder
Our Solution
Our solution
ź
ź
ź
ź
ź
ź
Data aquisition & analysis
Three arch architecture
Real time alarm management
Data access administration
Power quality reports
Graphical monitoring
The management of Elektro Gorenjska wanted to have better insight into power quality related power grid parameters within transformer
stations. For this reason we proposed equipping a majority of their MV/LV transformer stations with network analyzers MC 760, network
recordersMC750andsomepowerqualityanalyzersMC774.Characteristicsofourmeasuringdevicesaredescribedbelow.
Benefits MC 774 Benefits MC 760, MC 750
Key user benefits
ź
ź
ź
ź
ź
ź
ź
ź
ź
ź
ź
ź
ź
ź
ź
ź
EN50160voltagequalityevaluation
Measurementsofinstantaneousvaluesofmorethan140quantitiesincludingharmonics,flicker,powerlinesignallingvoltage,unbalance...
Monitoringdetectionofpowerqualitydeviations(MiSMART,MiQensoftwaresolution)
Widevarietyofrealtimesynchronizationoptions
Webbased3-tiercentraliseddistributedinstrumentdatamonitoringsoftwareMiSMART
Voltageandcurrentautorangemeasurementsupto1000VRMS,12.5A
4voltageand4currentchannelswith32mssamplingtime
Widefrequencymeasurementrange16-400Hz
Up to three independent communication ports (Serial, Ethernet and USB communication)
Support for GPS, IRIG-B and NTP real time synchronisation
Up to 20 I/0 modules (analogue in/out, pulse in/out, digital in/out, alarm/watchdog out, tariff in)
Wide range of input and output modules (competitive products in most cases “only” voltage quality analyzers)
MODBUS and DNP3 communication protocols
Multilingual support (Menus in 15 languages)
User-friendly setting and evaluation software MiQen
Highaccuracy-classA-measurements(certifiedbyPSL-PowerStandardsLab)
.
.
.
.
.
.
.
.
.
ź
ź
ź
ź
ź
ź
ź
ź
ź
ź
ź
ź
ź
Measurementsofinstantaneousvaluesofmorethan140quantities(U,I,P,Q,S,PF,PA,f,ϕ,THD,MD,energy,energycostbytariffs,etc.)
Accuracyclass0.5(optional0.2)
ActiveenergyClass1(optionalClass0.5S)
32adjustablealarms
Frequencyrangefrom16Hzto400Hz
RS232/RS485communicationupto115,200bit/sorEthernet/USBcommunication
MODBUSandDNP3communicationprotocol
Upto4inputsoroutputs(analogue,pulse,relayandwatchdogoutputs,digital,tariff,pulseandanalogueinputs)
Universal or AC power supply
Automatic range of nominal current and voltage (max. 12.5 A and 750 V)
Adjustable tariff clock, display of electric energy consumption in optional currency
Multilingual support User-friendly powerful setting and evaluation software MiQen (freeware)
EvaluationoftheelectricitysupplyqualityincompliancewithEN50160(onlyMC760)
.
.
.
.
.
.
We also had to properly address the problem of data collection from transformer stations. For this purpose we introduced the MiSmart server
for remote monitoring and collecting operational measurements from transformer stations. These recorder measurements were setup to
includeenergycounters,powers,powerfactors,voltages,currentsetc.Recorderevaluationperiodsweresetat1,5or10minutesmeaningthat
all data was sent to the server immediately after evaluation and successful storage into the device recorder. Along with recorded
measurements our system also provided real time alarm information to the electro-distribution company. This was setup by using alarms
about voltage absence, overvoltage undervoltage, overcurrent andfrequency deviations.. Alarms also enable detection of overheating of
interioroftransformerstationsorphysicalintrusion.
Description of MiSmart software
MC 774
Power Quality Analyser
MC 760
Network Analyser
MC 750
Network Recorder ź R
phaseangles,maximalperiodvalues,minimalperiodvalues)
ź Remoteandcentralizedalarmmonitoringinrealtime–alarmsaresentintothesystemuponappearance
ź owerqualityparametermonitoringaccordingtoEN50160on19locations
ź Realtimeinformationontheoperationofinstalledequipment
ź ExcelandPQDIFdataexportcapabilityforregulatorreporting
ź Betterandfastermaintenanceplanningaccordingtohistoricdataofferedbythesystem
ź Quickerresponsetofailuresaswellasfailureanalysis
ź Bettersupervisionoverenergylosseswithinthepowergridbycomparingconsumptiondatawiththeoneofthebillingsystem
.
ź SCADAsystemintegrationovertheIEC60870-5-104protocol
emote and centralized measurement monitoring of different electrical quantities (energy, active power, reactive power, currents, voltages,
P
At the beginning of 2014 our system for electrical quantities recording and power quality monitoring consisted of approximately 260
measuringcentres:MC750,MC760,MC774andsoftwareMiSmart.Thekeyadvantagesafterintroducingthesystemare:Meter
points 5
Web
Clients
Remote
Device
Setting & Monitoring
Local
Device
Setting & Monitoring
System
Server
Meter
points 6
Meter
points 7
Meter
points 1
Meter
points 2
Meter
points 3
Database
Data
Collector
Web
Server
Remote
System
Data
Monitoring
GPRS/UMTS
HSPA/WiMAX
Meter
points 4
4. MC 774
Power Quality Analyser
MC 760
Network Analyser
MC 750
Network Recorder
Our Solution
Our solution
ź
ź
ź
ź
ź
ź
Data aquisition & analysis
Three arch architecture
Real time alarm management
Data access administration
Power quality reports
Graphical monitoring
The management of Elektro Gorenjska wanted to have better insight into power quality related power grid parameters within transformer
stations. For this reason we proposed equipping a majority of their MV/LV transformer stations with network analyzers MC 760, network
recordersMC750andsomepowerqualityanalyzersMC774.Characteristicsofourmeasuringdevicesaredescribedbelow.
Benefits MC 774 Benefits MC 760, MC 750
Key user benefits
ź
ź
ź
ź
ź
ź
ź
ź
ź
ź
ź
ź
ź
ź
ź
ź
EN50160voltagequalityevaluation
Measurementsofinstantaneousvaluesofmorethan140quantitiesincludingharmonics,flicker,powerlinesignallingvoltage,unbalance...
Monitoringdetectionofpowerqualitydeviations(MiSMART,MiQensoftwaresolution)
Widevarietyofrealtimesynchronizationoptions
Webbased3-tiercentraliseddistributedinstrumentdatamonitoringsoftwareMiSMART
Voltageandcurrentautorangemeasurementsupto1000VRMS,12.5A
4voltageand4currentchannelswith32mssamplingtime
Widefrequencymeasurementrange16-400Hz
Up to three independent communication ports (Serial, Ethernet and USB communication)
Support for GPS, IRIG-B and NTP real time synchronisation
Up to 20 I/0 modules (analogue in/out, pulse in/out, digital in/out, alarm/watchdog out, tariff in)
Wide range of input and output modules (competitive products in most cases “only” voltage quality analyzers)
MODBUS and DNP3 communication protocols
Multilingual support (Menus in 15 languages)
User-friendly setting and evaluation software MiQen
Highaccuracy-classA-measurements(certifiedbyPSL-PowerStandardsLab)
.
.
.
.
.
.
.
.
.
ź
ź
ź
ź
ź
ź
ź
ź
ź
ź
ź
ź
ź
Measurementsofinstantaneousvaluesofmorethan140quantities(U,I,P,Q,S,PF,PA,f,ϕ,THD,MD,energy,energycostbytariffs,etc.)
Accuracyclass0.5(optional0.2)
ActiveenergyClass1(optionalClass0.5S)
32adjustablealarms
Frequencyrangefrom16Hzto400Hz
RS232/RS485communicationupto115,200bit/sorEthernet/USBcommunication
MODBUSandDNP3communicationprotocol
Upto4inputsoroutputs(analogue,pulse,relayandwatchdogoutputs,digital,tariff,pulseandanalogueinputs)
Universal or AC power supply
Automatic range of nominal current and voltage (max. 12.5 A and 750 V)
Adjustable tariff clock, display of electric energy consumption in optional currency
Multilingual support User-friendly powerful setting and evaluation software MiQen (freeware)
EvaluationoftheelectricitysupplyqualityincompliancewithEN50160(onlyMC760)
.
.
.
.
.
.
We also had to properly address the problem of data collection from transformer stations. For this purpose we introduced the MiSmart server
for remote monitoring and collecting operational measurements from transformer stations. These recorder measurements were setup to
includeenergycounters,powers,powerfactors,voltages,currentsetc.Recorderevaluationperiodsweresetat1,5or10minutesmeaningthat
all data was sent to the server immediately after evaluation and successful storage into the device recorder. Along with recorded
measurements our system also provided real time alarm information to the electro-distribution company. This was setup by using alarms
about voltage absence, overvoltage undervoltage, overcurrent andfrequency deviations.. Alarms also enable detection of overheating of
interioroftransformerstationsorphysicalintrusion.
Description of MiSmart software
MC 774
Power Quality Analyser
MC 760
Network Analyser
MC 750
Network Recorder ź R
phaseangles,maximalperiodvalues,minimalperiodvalues)
ź Remoteandcentralizedalarmmonitoringinrealtime–alarmsaresentintothesystemuponappearance
ź owerqualityparametermonitoringaccordingtoEN50160on19locations
ź Realtimeinformationontheoperationofinstalledequipment
ź ExcelandPQDIFdataexportcapabilityforregulatorreporting
ź Betterandfastermaintenanceplanningaccordingtohistoricdataofferedbythesystem
ź Quickerresponsetofailuresaswellasfailureanalysis
ź Bettersupervisionoverenergylosseswithinthepowergridbycomparingconsumptiondatawiththeoneofthebillingsystem
.
ź SCADAsystemintegrationovertheIEC60870-5-104protocol
emote and centralized measurement monitoring of different electrical quantities (energy, active power, reactive power, currents, voltages,
P
At the beginning of 2014 our system for electrical quantities recording and power quality monitoring consisted of approximately 260
measuringcentres:MC750,MC760,MC774andsoftwareMiSmart.Thekeyadvantagesafterintroducingthesystemare:Meter
points 5
Web
Clients
Remote
Device
Setting & Monitoring
Local
Device
Setting & Monitoring
System
Server
Meter
points 6
Meter
points 7
Meter
points 1
Meter
points 2
Meter
points 3
Database
Data
Collector
Web
Server
Remote
System
Data
Monitoring
GPRS/UMTS
HSPA/WiMAX
Meter
points 4
5. MC 774
Power Quality Analyser
MC 760
Network Analyser
MC 750
Network Recorder
Our Solution
Our solution
ź
ź
ź
ź
ź
ź
Data aquisition & analysis
Three arch architecture
Real time alarm management
Data access administration
Power quality reports
Graphical monitoring
The management of Elektro Gorenjska wanted to have better insight into power quality related power grid parameters within transformer
stations. For this reason we proposed equipping a majority of their MV/LV transformer stations with network analyzers MC 760, network
recordersMC750andsomepowerqualityanalyzersMC774.Characteristicsofourmeasuringdevicesaredescribedbelow.
Benefits MC 774 Benefits MC 760, MC 750
Key user benefits
ź
ź
ź
ź
ź
ź
ź
ź
ź
ź
ź
ź
ź
ź
ź
ź
EN50160voltagequalityevaluation
Measurementsofinstantaneousvaluesofmorethan140quantitiesincludingharmonics,flicker,powerlinesignallingvoltage,unbalance...
Monitoringdetectionofpowerqualitydeviations(MiSMART,MiQensoftwaresolution)
Widevarietyofrealtimesynchronizationoptions
Webbased3-tiercentraliseddistributedinstrumentdatamonitoringsoftwareMiSMART
Voltageandcurrentautorangemeasurementsupto1000VRMS,12.5A
4voltageand4currentchannelswith32mssamplingtime
Widefrequencymeasurementrange16-400Hz
Up to three independent communication ports (Serial, Ethernet and USB communication)
Support for GPS, IRIG-B and NTP real time synchronisation
Up to 20 I/0 modules (analogue in/out, pulse in/out, digital in/out, alarm/watchdog out, tariff in)
Wide range of input and output modules (competitive products in most cases “only” voltage quality analyzers)
MODBUS and DNP3 communication protocols
Multilingual support (Menus in 15 languages)
User-friendly setting and evaluation software MiQen
Highaccuracy-classA-measurements(certifiedbyPSL-PowerStandardsLab)
.
.
.
.
.
.
.
.
.
ź
ź
ź
ź
ź
ź
ź
ź
ź
ź
ź
ź
ź
Measurementsofinstantaneousvaluesofmorethan140quantities(U,I,P,Q,S,PF,PA,f,ϕ,THD,MD,energy,energycostbytariffs,etc.)
Accuracyclass0.5(optional0.2)
ActiveenergyClass1(optionalClass0.5S)
32adjustablealarms
Frequencyrangefrom16Hzto400Hz
RS232/RS485communicationupto115,200bit/sorEthernet/USBcommunication
MODBUSandDNP3communicationprotocol
Upto4inputsoroutputs(analogue,pulse,relayandwatchdogoutputs,digital,tariff,pulseandanalogueinputs)
Universal or AC power supply
Automatic range of nominal current and voltage (max. 12.5 A and 750 V)
Adjustable tariff clock, display of electric energy consumption in optional currency
Multilingual support User-friendly powerful setting and evaluation software MiQen (freeware)
EvaluationoftheelectricitysupplyqualityincompliancewithEN50160(onlyMC760)
.
.
.
.
.
.
We also had to properly address the problem of data collection from transformer stations. For this purpose we introduced the MiSmart server
for remote monitoring and collecting operational measurements from transformer stations. These recorder measurements were setup to
includeenergycounters,powers,powerfactors,voltages,currentsetc.Recorderevaluationperiodsweresetat1,5or10minutesmeaningthat
all data was sent to the server immediately after evaluation and successful storage into the device recorder. Along with recorded
measurements our system also provided real time alarm information to the electro-distribution company. This was setup by using alarms
about voltage absence, overvoltage undervoltage, overcurrent andfrequency deviations.. Alarms also enable detection of overheating of
interioroftransformerstationsorphysicalintrusion.
Description of MiSmart software
MC 774
Power Quality Analyser
MC 760
Network Analyser
MC 750
Network Recorder ź R
phaseangles,maximalperiodvalues,minimalperiodvalues)
ź Remoteandcentralizedalarmmonitoringinrealtime–alarmsaresentintothesystemuponappearance
ź owerqualityparametermonitoringaccordingtoEN50160on19locations
ź Realtimeinformationontheoperationofinstalledequipment
ź ExcelandPQDIFdataexportcapabilityforregulatorreporting
ź Betterandfastermaintenanceplanningaccordingtohistoricdataofferedbythesystem
ź Quickerresponsetofailuresaswellasfailureanalysis
ź Bettersupervisionoverenergylosseswithinthepowergridbycomparingconsumptiondatawiththeoneofthebillingsystem
.
ź SCADAsystemintegrationovertheIEC60870-5-104protocol
emote and centralized measurement monitoring of different electrical quantities (energy, active power, reactive power, currents, voltages,
P
At the beginning of 2014 our system for electrical quantities recording and power quality monitoring consisted of approximately 260
measuringcentres:MC750,MC760,MC774andsoftwareMiSmart.Thekeyadvantagesafterintroducingthesystemare:Meter
points 5
Web
Clients
Remote
Device
Setting & Monitoring
Local
Device
Setting & Monitoring
System
Server
Meter
points 6
Meter
points 7
Meter
points 1
Meter
points 2
Meter
points 3
Database
Data
Collector
Web
Server
Remote
System
Data
Monitoring
GPRS/UMTS
HSPA/WiMAX
Meter
points 4
6. MC 774
Power Quality Analyser
MC 760
Network Analyser
MC 750
Network Recorder
Our Solution
Our solution
ź
ź
ź
ź
ź
ź
Data aquisition & analysis
Three arch architecture
Real time alarm management
Data access administration
Power quality reports
Graphical monitoring
The management of Elektro Gorenjska wanted to have better insight into power quality related power grid parameters within transformer
stations. For this reason we proposed equipping a majority of their MV/LV transformer stations with network analyzers MC 760, network
recordersMC750andsomepowerqualityanalyzersMC774.Characteristicsofourmeasuringdevicesaredescribedbelow.
Benefits MC 774 Benefits MC 760, MC 750
Key user benefits
ź
ź
ź
ź
ź
ź
ź
ź
ź
ź
ź
ź
ź
ź
ź
ź
EN50160voltagequalityevaluation
Measurementsofinstantaneousvaluesofmorethan140quantitiesincludingharmonics,flicker,powerlinesignallingvoltage,unbalance...
Monitoringdetectionofpowerqualitydeviations(MiSMART,MiQensoftwaresolution)
Widevarietyofrealtimesynchronizationoptions
Webbased3-tiercentraliseddistributedinstrumentdatamonitoringsoftwareMiSMART
Voltageandcurrentautorangemeasurementsupto1000VRMS,12.5A
4voltageand4currentchannelswith32mssamplingtime
Widefrequencymeasurementrange16-400Hz
Up to three independent communication ports (Serial, Ethernet and USB communication)
Support for GPS, IRIG-B and NTP real time synchronisation
Up to 20 I/0 modules (analogue in/out, pulse in/out, digital in/out, alarm/watchdog out, tariff in)
Wide range of input and output modules (competitive products in most cases “only” voltage quality analyzers)
MODBUS and DNP3 communication protocols
Multilingual support (Menus in 15 languages)
User-friendly setting and evaluation software MiQen
Highaccuracy-classA-measurements(certifiedbyPSL-PowerStandardsLab)
.
.
.
.
.
.
.
.
.
ź
ź
ź
ź
ź
ź
ź
ź
ź
ź
ź
ź
ź
Measurementsofinstantaneousvaluesofmorethan140quantities(U,I,P,Q,S,PF,PA,f,ϕ,THD,MD,energy,energycostbytariffs,etc.)
Accuracyclass0.5(optional0.2)
ActiveenergyClass1(optionalClass0.5S)
32adjustablealarms
Frequencyrangefrom16Hzto400Hz
RS232/RS485communicationupto115,200bit/sorEthernet/USBcommunication
MODBUSandDNP3communicationprotocol
Upto4inputsoroutputs(analogue,pulse,relayandwatchdogoutputs,digital,tariff,pulseandanalogueinputs)
Universal or AC power supply
Automatic range of nominal current and voltage (max. 12.5 A and 750 V)
Adjustable tariff clock, display of electric energy consumption in optional currency
Multilingual support User-friendly powerful setting and evaluation software MiQen (freeware)
EvaluationoftheelectricitysupplyqualityincompliancewithEN50160(onlyMC760)
.
.
.
.
.
.
We also had to properly address the problem of data collection from transformer stations. For this purpose we introduced the MiSmart server
for remote monitoring and collecting operational measurements from transformer stations. These recorder measurements were setup to
includeenergycounters,powers,powerfactors,voltages,currentsetc.Recorderevaluationperiodsweresetat1,5or10minutesmeaningthat
all data was sent to the server immediately after evaluation and successful storage into the device recorder. Along with recorded
measurements our system also provided real time alarm information to the electro-distribution company. This was setup by using alarms
about voltage absence, overvoltage undervoltage, overcurrent andfrequency deviations.. Alarms also enable detection of overheating of
interioroftransformerstationsorphysicalintrusion.
Description of MiSmart software
MC 774
Power Quality Analyser
MC 760
Network Analyser
MC 750
Network Recorder ź R
phaseangles,maximalperiodvalues,minimalperiodvalues)
ź Remoteandcentralizedalarmmonitoringinrealtime–alarmsaresentintothesystemuponappearance
ź owerqualityparametermonitoringaccordingtoEN50160on19locations
ź Realtimeinformationontheoperationofinstalledequipment
ź ExcelandPQDIFdataexportcapabilityforregulatorreporting
ź Betterandfastermaintenanceplanningaccordingtohistoricdataofferedbythesystem
ź Quickerresponsetofailuresaswellasfailureanalysis
ź Bettersupervisionoverenergylosseswithinthepowergridbycomparingconsumptiondatawiththeoneofthebillingsystem
.
ź SCADAsystemintegrationovertheIEC60870-5-104protocol
emote and centralized measurement monitoring of different electrical quantities (energy, active power, reactive power, currents, voltages,
P
At the beginning of 2014 our system for electrical quantities recording and power quality monitoring consisted of approximately 260
measuringcentres:MC750,MC760,MC774andsoftwareMiSmart.Thekeyadvantagesafterintroducingthesystemare:Meter
points 5
Web
Clients
Remote
Device
Setting & Monitoring
Local
Device
Setting & Monitoring
System
Server
Meter
points 6
Meter
points 7
Meter
points 1
Meter
points 2
Meter
points 3
Database
Data
Collector
Web
Server
Remote
System
Data
Monitoring
GPRS/UMTS
HSPA/WiMAX
Meter
points 4
7. Energysector
Instruments Remote Monitoring in
Slovenian Electrodistribution Company
Elektro Gorenjska
Input/Output Modules Use
• Published by Iskra, d.d. • Version 1.0 March 2015
Input signals of PLC
Measurement of water, heat, gas etc. consumption
Substation control accessOvervoltage protection
Measurement of solar radiation, transformer
station temperature, wind speed etc.
Control
Auxiliary inputs
Use of Input /Output Modules
Power quality analyser functions also as a secondary protection device
High accurate data about consumption
Up to 32 alarms
Fast notification of faults in a system
Four energy counters for four-quadrant metering
Can be viewed on device or downloaded
Alarm
Energy
About Electrodistribution Company
Facts About Elektro Gorenjska
Elektro Gorenjska is one of the largest Slovenian Electrodistribution
Companies, which operates middle voltage (MV) as well as low voltage
(LV) infrastructure. It owns 1.333 MV/LV transformer stations and 14 HV
(high voltage)/LV transformer stations, mainly in the region of Gorenjska.
Its'customerbaseconsistsofaround87.000customers.
Elektro Gorenjska transformer stations were equipped with approximately 200 Iskra's measuring centres MI 7150, which were installed at the
beginning of this millennium. They were equipped with serial communication RS 232. A few of them were also equipped with new types of Iskra
instruments,namelywith18MC760networkanalyzersand25MC750networkrecorders.Fordatatransferfromtransformerstationsintothe
controlcentre,ElektroGorenjskausedWiMax,GPRSandEthernetcommunication.
www.iskra.eu
Situation before the intrduction of our systemSituation before the introduction of our system
20 kV
0,4 kV
MC MI
MC750
no. 1
MI7150
no. 2
Communication
terminal
WiMAX/GPRS
Ethernet
Offline data
reading from
MMC
Feeders
Substation 400/110 kV
HV 110 kV
Substation 110/20 kV
MV 20 kV
LV 0.4 kV
TS 20/0.4 kV
Distrbution network
8. Energysector
Instruments Remote Monitoring in
Slovenian Electrodistribution Company
Elektro Gorenjska
Input/Output Modules Use
• Published by Iskra, d.d. • Version 1.0 March 2015
Input signals of PLC
Measurement of water, heat, gas etc. consumption
Substation control accessOvervoltage protection
Measurement of solar radiation, transformer
station temperature, wind speed etc.
Control
Auxiliary inputs
Use of Input /Output Modules
Power quality analyser functions also as a secondary protection device
High accurate data about consumption
Up to 32 alarms
Fast notification of faults in a system
Four energy counters for four-quadrant metering
Can be viewed on device or downloaded
Alarm
Energy
About Electrodistribution Company
Facts About Elektro Gorenjska
Elektro Gorenjska is one of the largest Slovenian Electrodistribution
Companies, which operates middle voltage (MV) as well as low voltage
(LV) infrastructure. It owns 1.333 MV/LV transformer stations and 14 HV
(high voltage)/LV transformer stations, mainly in the region of Gorenjska.
Its'customerbaseconsistsofaround87.000customers.
Elektro Gorenjska transformer stations were equipped with approximately 200 Iskra's measuring centres MI 7150, which were installed at the
beginning of this millennium. They were equipped with serial communication RS 232. A few of them were also equipped with new types of Iskra
instruments,namelywith18MC760networkanalyzersand25MC750networkrecorders.Fordatatransferfromtransformerstationsintothe
controlcentre,ElektroGorenjskausedWiMax,GPRSandEthernetcommunication.
www.iskra.eu
Situation before the intrduction of our systemSituation before the introduction of our system
20 kV
0,4 kV
MC MI
MC750
no. 1
MI7150
no. 2
Communication
terminal
WiMAX/GPRS
Ethernet
Offline data
reading from
MMC
Feeders
Substation 400/110 kV
HV 110 kV
Substation 110/20 kV
MV 20 kV
LV 0.4 kV
TS 20/0.4 kV
Distrbution network