SlideShare una empresa de Scribd logo
1 de 40
Achieving High Performance
   Operation With Energy Alarms

                 PRESENTERS:

     Mike Eardley, Director of Commissioning
                  Cannon Design

Christopher Longchamps, Senior Facilities Engineer
          Partners Healthcare System, Inc
Agenda


• Define a High Performance Building
• Demonstrate how Commissioning (Cx) is a critical element
• Define new building Cx, Retro-Cx, and Ongoing Cx
• Ongoing Cx program at Massachusetts General Hospital
• Partners Healthcare System – Strategic Energy Master Plan
High Performance Buildings


Characteristics
• Functionality
• Energy Efficiency
• Indoor Environmental Quality
• Comfort
• Sustainability
   (ability to perform its function
   in a long term)
Building Systems Commissioning




           • Buildings function as intended
           • Realize high performance
Commissioning Definition
 • Commissioning (Cx) is a comprehensive and systematic
   process to verify and document that new or renovated
   facility systems function completely as designed to meet the
   owner’s requirements
 • A type of quality assurance to the systems being
   commissioned
 • Applied to building systems (e.g. HVAC)
 • Core element of sustainable buildings, along with energy
   modeling and measurement & verification
Without Commissioning
• Placement and calibration of Sensors
• Simultaneous Heating and Cooling
• Incorrect function of air-side Economizer and
   other efficiency measures
• Operating Schedule is not what is necessary,
   or assumed by energy model
• Cycling daylighting and other systems
Reference Standards
• ASHE
  Health Facility Commissioning Guidelines
  ashe.org

• ASHRAE Guideline 0
  The Commissioning Process
  ashrae.org

• Building Commissioning Association
  Essential Attributes of Building Commissioning
  bcxa.org
Why Commissioning?




    green cooling tower         shutoff valve impeded




      blocked daylight sensor    moisture penetration
Purpose of Functional Testing

• Verification of an operational system
• Reduces adjustment and tuning during occupancy
• Impacts
     energy
     comfort
     maintenance
     functionality
Types of Functional Testing

•   Building Automation System
•   False load
•   Seasonal testing
•   Trend analysis
Energy Impacts

• Large effort in sustainable and energy efficient design
• Will not be realized if design or intended use is:
     misunderstood
     ignored
• Or if building systems are:
     operating incorrectly
     not thoroughly tested
Common Problems – Air-side Economizer

• Damper is stuck / broken / non-functional
• Control algorithms fighting
    heating during economizer
    mechanical cooling when free
      cooling available
• Outside sensor calibration or location
Building Envelope Commissioning

                    • Not often considered in basic scope

                    • Affects Air infiltration, IAQ, air/water
                      leaks, building systems performance

                    • Involves many building components,
                      suppliers & subcontractors

                    • Coordination meetings; sketches or
                      drawings; wall systems, roof, trade
                      penetrations

                    • Checklist & Inspections
Building Envelope

Thermal
Bridging




           Moisture
           Penetration




                         Window Water Testing
Functional Test – Alarms and Safeties
• Varying levels of rigor
    verify software interactions
    verify hardware interactions
    verify actual conditions
        e.g. cold, smoke
• Pull the plug
    simulate actual loss of
        power
    does transfer and restart act
        as intended?
New and Existing Buildings


• Commissioning: Process applied to new construction or
  major building renovation
• Re-commissioning: Facility has previously been
  commissioned and is in need of a “tune-up”
• Retro-commissioning: Performed on facilities that have been
  in service and never commissioned
• Ongoing commissioning: Ongoing program of structured
  commissioning throughout the lifetime of a building
Retro-Commissioning


• Review of original design
• Targeted functional testing
• Identification of energy measures
• Evaluation of measures
• Energy modeling
• Implementation
• Verification and Persistence
Trending

• Functional testing before occupancy is a snapshot
• Trending shows operation over time
• Methods of trending
     building automation system
     portable data loggers
• Analyze trends
     spreadsheet calculations
     software tools
Ongoing Commissioning

• Good
     Cx process with
       functional testing
• Better
     Re-Cx program
• Best
     Ongoing Cx
• Combination of software,
  engineering support, action
PHS Strategic Energy
           Master Plan Objective


In 2008, PHS Utilities and Engineering Department was charged
to develop a Strategic Energy Master Plan to Address the
Hospital ever-growing demand for energy and the volatile nature
of the Energy market and concerns regarding global warming
and long term sustainability of resource consumption and its
impact on the delivery of critical health care services
PHS Strategic Energy
 Master Plan Goals
MGH Actual Energy Consumption Vs Projection
From PHS Strategic Energy Master Plan Study
2,500,000




2,000,000




1,500,000



                                                                           Total Energy Consumption (Do nothing) MMBTU based on
1,000,000                                                                  SEMP 2008 study, including Lunder building
              Notes:
                                                                           Actual Total Energy Consumption MMBTU After SEMP up to
                                                                           2012 including Lunder building from invoices
              1.Lunder Building came on line on May 2011
              but not fully occupied until late fall
                                                                           Projected Actual Total Energy ConsumptionMMBTU with
 500,000                                                                   MGH SEMP Projected savings from 2012 to 2026
              2.Based on escalation of 1.5% load growth
                                                                           Total Projected Energy Consumption MMBTU with Projected
                                                                           savings from SEMP including Lunder building

       0
            2008

                   2009

                          2010

                                 2011

                                        2012

                                               2013

                                                      2014

                                                             2015

                                                                    2016

                                                                           2017

                                                                                  2018

                                                                                         2019

                                                                                                2020

                                                                                                       2021

                                                                                                              2022

                                                                                                                     2023

                                                                                                                            2024

                                                                                                                                   2025

                                                                                                                                          2026
MGH SEMP Actual Total Energy Reduction Compared
    To 2008 PHS SEMP Energy Reduction Goal
         500,000

         450,000

         400,000

         350,000
 MMBTU




         300,000

         250,000                             MGH SEMP Primary Goal, 25% energy reduction
                                             from 2008 based line 1,509,875MMbtu

         200,000                             MGH actual energy reduction compare to Primary
                                             goal
         150,000
                                             MGH Projected Energy Reduction Compare to
                                             Primary Goal
         100,000

          50,000

              0
                   200




                         200




                               201




                                     201




                                           201




                                                     201




                                                                    201




                                                                                  201
                    8




                          9




                                0




                                      1




                                            2




                                                      3




                                                                     4




                                                                                   5
SEMP Impact On Utilities Cost Per Sq.Ft.

                                                      MGH Cost per Sq. Ft.
            $14
                           FY 2008 ($/sq ft)
                           FY 2012 ($/sq ft)                           $12.36
            $12
                                                                                                       $11.04

            $10                                       $9.02

             $8
                                                                             $7.67
                                                                                       $6.90
$ / sq ft




                  $6.56                                      $6.83
                                    $6.08
             $6                                                                                              $5.38
                          $4.97
                                           $4.43
                                                                                               $3.90
             $4


             $2


             $0
                  MGH Combined       MGH Main            CNY           Simches           Yawkey            Cox
                    including         Campus          149, 114, 75
                  CNY, Simches
                  (6,371,307 ft²)   (5,071,825 ft²)    (945,947 ft²)   (353,535 ft²)   (446,960 ft²)   (119,808 ft²)
SEMP Impact On Utilities Consumption Per Sq.Ft.

                600
                                                           MGH kBtu per Sq. Ft.               FY 2008 (kBtu/sq ft)
                                                                                              FY 2012 (kBtu/sq ft)
                500                                                         487


                       LABS 21
                400                                         376                                             383
                       Benchmark          DOE 2.1
                                          Hospital
 kBtu/sq. ft.




                                          Benchmark               294
                300
                        262               251                                     252
                              217              201                                          217                   210
                200
                                                                                                  142

                100



                  0
                      MGH Combined       MGH Main             CNY            Simches         Yawkey            Cox
                        including         Campus           149, 114, 75
                      CNY, Simches

                       (6,371,307 ft²)   (5,071,825 ft²)    (945,947 ft²)   (353,535 ft²)   (446,960 ft²)   (119,808 ft²)
ECMS That Have Major Savings On Outpatient,
Research and Outpatient/Research/Office Facility

    •   Building Occupied / Unoccupied schedule setback
    •   Reduce minimum CFM set point
    •   Schedule Room Thermostat with Dead Band
    •   Fume Hoods modification
    •   Lighting retrofits
    •   Chillers Plant optimization
    •   Steam Traps
    •   Steam Condensate Heat recovery
    •   Low temperature Run-Around Heat Recovery
    •   Reset Pump DP set point
    •   Reset AHU Supply and Return Fans S.P. set point
Lesson Learned
• The Energy conservation measures such as Set point or Schedule
  setback can be unintentional altered by mechanic
• The Energy Alarms system need to be developed to monitor the
  MEP system for equipment failures and/or operating out of range
• Energy Alarms can be part of an MEP Maintenance Program
• A continuous measurement & verification program needs to be
  established to ensure the savings are continued
Massachusetts General Hospital
• Researched ongoing Cx
  products in the market
• Some required installation
  of new equipment
• All were costly
• Concern about level of
  detail in the delivered
  product
• Settled on
  customized, built up
  approach
Massachusetts General Hospital

• Reviewed Design
• Developed rules based
  logic to identify
  inefficient operation
• Worked with campus
  controls provider to
  implement
What Do Energy Alarms Look At?
  •   VAV Airflow
  •   VAV Heating Coil
  •   VAV Occupancy Hours
  •   HW HX Valve Leaking
  •   AHU Preheat Valve Leaking
  •   AHU CHW Valve Leaking
  •   AHU Simultaneous Heating & Cooling
  •   CHW Low Delta T
  •   CHW Economizer w/ Chiller(s) Running
  •   AHU Should be in Economizer; Excessive CHW Use
  • AHU Should Not be in Economizer; Excessive outside air
  • More than 79 different types of Energy Alarm are monitored
Energy Alarms Alarm Window
Example of an Air Flow Alarm
  • Checks box’s damper operation
  • Very effective in locating broken damper actuators
  • Trigger: Box air flow is not meeting setpoint

  Logic:
  • |CFM – CFMSpt| > 0.15 x MaxCFMSpt

   [Delay = 1 hr]
  • CFM = Actual CFM
  • CFMSpt = CFM Setpoint
  • MaxCFMSpt = Maximum CFM Setpoint of box
What is One Air Flow Alarm Worth?




Schedule:               Occupied:
5:00AM – 6:30PM Mon-Fri (Extra CFM) x (hrs of CFM per week /Total hrs in a week)x($6/cfm)
Occ hrs/wk = 67.5 hr    (711 cfm – 145 cfm) x (67.5 hr/168 hr) x $4/cfm yr = $ 909 /yr
Unocc hrs/wk = 100.5 hr
                         Unoccupied:
                        711 cfm x (100.5 hr/168 hr) x $4/cfm yr = $ 1,701 /yr
                          Total Estimated Annual Savings= $ 2,610
Example of a Heating Coil Alarm
   • Checks that the box’s heating valve is closing completely
   • Trigger: An unexpected temperature difference across the
     heating coil

   Logic:
   • HWV% < 1% & |SAT – DAT| > 10 & CFMSpt > 0

   [Delay = 2 hr]
   • HWV% = Hot Water Valve Position
     [0%=Closed, 100%=Open]
   • SAT = Supply Air Temp [Supply Air from AHU to the Box]
   • DAT = Discharge Air Temp
   • CFMSpt = CFM Setpoint
What is One Heating Coil Alarm Worth?




   Schedule:                Air Side
   5:00AM-6:30PM Mon-Fri    (325 cfm – 216 cfm) x (3,534 hr / 8,760 hr)
   Occ hrs / yr = 3534 hr               = 44 cfm/yr
                            44 cfm/yr x $4 /cfm = $264/yr

                            Total Estimated Annual Savings = $176
How Does An Occupancy Alarm Work?
     • Checks if box switches to unoccupied mode
     • Trigger: Box remaining in occupied mode for a
       long period of time

     Logic:
     • Occ > 20 hrs in a 24 hr Period

      [Delay = 15 min]
     • Occ = Number of hours since midnight that the
       box has been occupied
Example Of An Occupancy Override
 Yawkey Floor 9 Found Overridden ON
 Cancer Center Psychiatric Oncology Area

 Normal Occupancy Schedule:
 5:00AM-6:30PM Mon-Fri
 Unoccupied hrs/week: 100.5 hr/wk
 Total Minimum CFM: 8,063 CFM
 Assuming $ 4/CFM yr

 8,063 cfm x (100.5hr/168hr) x $4 /cfm year

 Annual Savings: $ 19,294
How Does The Process Work?
•   Alarms are reviewed on a daily basis
•   Once validated there is a work order issued for the repair
•   Work directly with maintenance staff on difficult problems
•   Work order completed and issue closed
How Many Energy Alarms Are There?




      More than 400 validated work orders
      have been addressed since summer
      of 2010 and $600,000 were realized.
Questions / Discussion
    Achieving High Performance
   Operation With Energy Alarms
                  PRESENTERS:

Christopher Longchamps, Partners Healthcare System
              clongchamps@partners.org

           Mike Eardley, Cannon Design
            meardley@cannondesign.com
                  @MikeEardley

Más contenido relacionado

Destacado (6)

Goal orientation educational psychology
Goal orientation educational psychologyGoal orientation educational psychology
Goal orientation educational psychology
 
Goal Orientation
Goal Orientation Goal Orientation
Goal Orientation
 
how to manage you time
how to manage you timehow to manage you time
how to manage you time
 
Teamwork presentation
Teamwork presentation Teamwork presentation
Teamwork presentation
 
time-management-ppt
time-management-ppttime-management-ppt
time-management-ppt
 
TIME MANAGEMENT POWERPOINT
TIME MANAGEMENT POWERPOINTTIME MANAGEMENT POWERPOINT
TIME MANAGEMENT POWERPOINT
 

Similar a Achieving High Performance Operation With Energy Alarms

Milwaukee - Resource Recovery - Sustainable Water Reclamation (SeWeR)
Milwaukee - Resource Recovery - Sustainable Water Reclamation (SeWeR)Milwaukee - Resource Recovery - Sustainable Water Reclamation (SeWeR)
Milwaukee - Resource Recovery - Sustainable Water Reclamation (SeWeR)
U.S. Water Alliance
 
Building Performance Analysis using BIM align ECBC Regulations
Building Performance Analysis using BIM align ECBC RegulationsBuilding Performance Analysis using BIM align ECBC Regulations
Building Performance Analysis using BIM align ECBC Regulations
Saurabh Gupta
 
CIB TG66 India Webinar 20120628 Priyanka Kochhar Energy efficiency in buildings
CIB TG66 India Webinar 20120628 Priyanka Kochhar Energy efficiency in buildingsCIB TG66 India Webinar 20120628 Priyanka Kochhar Energy efficiency in buildings
CIB TG66 India Webinar 20120628 Priyanka Kochhar Energy efficiency in buildings
INIVE EEIG
 

Similar a Achieving High Performance Operation With Energy Alarms (20)

Milwaukee - Resource Recovery - Sustainable Water Reclamation (SeWeR)
Milwaukee - Resource Recovery - Sustainable Water Reclamation (SeWeR)Milwaukee - Resource Recovery - Sustainable Water Reclamation (SeWeR)
Milwaukee - Resource Recovery - Sustainable Water Reclamation (SeWeR)
 
3D Modeling and Energy Analysis of a Residential Building using BIM Tools
3D Modeling and Energy Analysis of a Residential Building using BIM Tools3D Modeling and Energy Analysis of a Residential Building using BIM Tools
3D Modeling and Energy Analysis of a Residential Building using BIM Tools
 
Introduction CRIF_Senior Officer Event 12th October
Introduction CRIF_Senior Officer Event 12th OctoberIntroduction CRIF_Senior Officer Event 12th October
Introduction CRIF_Senior Officer Event 12th October
 
Ofgem Presentation at Economist Energy Summit
Ofgem Presentation at Economist Energy SummitOfgem Presentation at Economist Energy Summit
Ofgem Presentation at Economist Energy Summit
 
Bim adoption
Bim adoptionBim adoption
Bim adoption
 
Julie Godefroy - TM54 Analysis Webinar
Julie Godefroy - TM54 Analysis WebinarJulie Godefroy - TM54 Analysis Webinar
Julie Godefroy - TM54 Analysis Webinar
 
Perspectives On Our Clean Energy Journey
Perspectives On Our Clean Energy JourneyPerspectives On Our Clean Energy Journey
Perspectives On Our Clean Energy Journey
 
NCPC IE Conference 2017 P Mukoma
NCPC IE Conference 2017 P MukomaNCPC IE Conference 2017 P Mukoma
NCPC IE Conference 2017 P Mukoma
 
Building Performance Analysis using BIM align ECBC Regulations
Building Performance Analysis using BIM align ECBC RegulationsBuilding Performance Analysis using BIM align ECBC Regulations
Building Performance Analysis using BIM align ECBC Regulations
 
Net zero energy and beyond
Net zero energy and beyondNet zero energy and beyond
Net zero energy and beyond
 
BIM for Owners.pptx
BIM for Owners.pptxBIM for Owners.pptx
BIM for Owners.pptx
 
Edited BIM for Owners deck FINAL.pptx
Edited BIM for Owners deck FINAL.pptxEdited BIM for Owners deck FINAL.pptx
Edited BIM for Owners deck FINAL.pptx
 
Bim for owners deck final
Bim for owners deck final Bim for owners deck final
Bim for owners deck final
 
Introduction to Energy Technology Roadmaps
Introduction to Energy Technology RoadmapsIntroduction to Energy Technology Roadmaps
Introduction to Energy Technology Roadmaps
 
ZERO ENERGY BUILDING; DESIGN AND SIMULATION
ZERO ENERGY BUILDING; DESIGN AND SIMULATIONZERO ENERGY BUILDING; DESIGN AND SIMULATION
ZERO ENERGY BUILDING; DESIGN AND SIMULATION
 
Selection of Slides Green Building Summit, Istanbul
Selection of Slides Green Building Summit, IstanbulSelection of Slides Green Building Summit, Istanbul
Selection of Slides Green Building Summit, Istanbul
 
CIB TG66 India Webinar 20120628 Priyanka Kochhar Energy efficiency in buildings
CIB TG66 India Webinar 20120628 Priyanka Kochhar Energy efficiency in buildingsCIB TG66 India Webinar 20120628 Priyanka Kochhar Energy efficiency in buildings
CIB TG66 India Webinar 20120628 Priyanka Kochhar Energy efficiency in buildings
 
Giá trị của BIM cho chủ đầu tư
Giá trị của BIM cho chủ đầu tưGiá trị của BIM cho chủ đầu tư
Giá trị của BIM cho chủ đầu tư
 
Use of BIM in planning and construction and implementation in real project
Use of BIM in planning and construction and implementation in real projectUse of BIM in planning and construction and implementation in real project
Use of BIM in planning and construction and implementation in real project
 
CBI Property Breakfast Seminar: Green Building, making it happen
CBI Property Breakfast Seminar: Green Building, making it happenCBI Property Breakfast Seminar: Green Building, making it happen
CBI Property Breakfast Seminar: Green Building, making it happen
 

Más de CannonDesign

Mehrdad Yazdani - Sketches-Q&A FORM magagzine JANFEB2014
Mehrdad Yazdani - Sketches-Q&A FORM magagzine JANFEB2014Mehrdad Yazdani - Sketches-Q&A FORM magagzine JANFEB2014
Mehrdad Yazdani - Sketches-Q&A FORM magagzine JANFEB2014
CannonDesign
 
IUHealth Neuroscience in World Health Design
IUHealth Neuroscience in World Health DesignIUHealth Neuroscience in World Health Design
IUHealth Neuroscience in World Health Design
CannonDesign
 
Facility Optimization Solutions Brochure
Facility Optimization Solutions BrochureFacility Optimization Solutions Brochure
Facility Optimization Solutions Brochure
CannonDesign
 
HCD Amato Audience Evaluation
HCD Amato Audience EvaluationHCD Amato Audience Evaluation
HCD Amato Audience Evaluation
CannonDesign
 
SMPS Marketer - December 2013
SMPS Marketer - December 2013SMPS Marketer - December 2013
SMPS Marketer - December 2013
CannonDesign
 
EPI - Bringing It In-House Series #4
EPI - Bringing It In-House Series #4EPI - Bringing It In-House Series #4
EPI - Bringing It In-House Series #4
CannonDesign
 
UC SAN DIEGO JACOBS - NYTIMES NOV 17 2013
UC SAN DIEGO JACOBS - NYTIMES NOV 17 2013UC SAN DIEGO JACOBS - NYTIMES NOV 17 2013
UC SAN DIEGO JACOBS - NYTIMES NOV 17 2013
CannonDesign
 

Más de CannonDesign (20)

SXSW: Embracing Transformative Design to Redefine Cancer Care
SXSW: Embracing Transformative Design to Redefine Cancer CareSXSW: Embracing Transformative Design to Redefine Cancer Care
SXSW: Embracing Transformative Design to Redefine Cancer Care
 
How Design Thinking Can Connect Cities of Today to Jobs of Tomorrow
How Design Thinking Can Connect Cities of Today to Jobs of TomorrowHow Design Thinking Can Connect Cities of Today to Jobs of Tomorrow
How Design Thinking Can Connect Cities of Today to Jobs of Tomorrow
 
How Intense Collaboration Fuels Brighter Civic Futures
How Intense Collaboration Fuels Brighter Civic FuturesHow Intense Collaboration Fuels Brighter Civic Futures
How Intense Collaboration Fuels Brighter Civic Futures
 
SXSW 2018 - Rethinking Urban Design to Elevate Social Justice
SXSW 2018 - Rethinking Urban Design to Elevate Social JusticeSXSW 2018 - Rethinking Urban Design to Elevate Social Justice
SXSW 2018 - Rethinking Urban Design to Elevate Social Justice
 
SXSW 2018 - Can You Prove Your Workplace is the Best?
SXSW 2018 - Can You Prove Your Workplace is the Best?SXSW 2018 - Can You Prove Your Workplace is the Best?
SXSW 2018 - Can You Prove Your Workplace is the Best?
 
Cost trends - Construction Strategies
Cost trends - Construction StrategiesCost trends - Construction Strategies
Cost trends - Construction Strategies
 
Actionable Education Prototyping New Learning Models
Actionable Education Prototyping New Learning ModelsActionable Education Prototyping New Learning Models
Actionable Education Prototyping New Learning Models
 
Learning Spaces 2.0: Catalysts for Socioeconomic Growth
Learning Spaces 2.0: Catalysts for Socioeconomic GrowthLearning Spaces 2.0: Catalysts for Socioeconomic Growth
Learning Spaces 2.0: Catalysts for Socioeconomic Growth
 
Mentoring Inspiration
Mentoring InspirationMentoring Inspiration
Mentoring Inspiration
 
Mehrdad Yazdani - Sketches-Q&A FORM magagzine JANFEB2014
Mehrdad Yazdani - Sketches-Q&A FORM magagzine JANFEB2014Mehrdad Yazdani - Sketches-Q&A FORM magagzine JANFEB2014
Mehrdad Yazdani - Sketches-Q&A FORM magagzine JANFEB2014
 
140311 koc school project
140311 koc school project140311 koc school project
140311 koc school project
 
IUHealth Neuroscience in World Health Design
IUHealth Neuroscience in World Health DesignIUHealth Neuroscience in World Health Design
IUHealth Neuroscience in World Health Design
 
Performance By Design
Performance By DesignPerformance By Design
Performance By Design
 
Facility Optimization Solutions Brochure
Facility Optimization Solutions BrochureFacility Optimization Solutions Brochure
Facility Optimization Solutions Brochure
 
Facility Optimization Solutions Brochure
Facility Optimization Solutions BrochureFacility Optimization Solutions Brochure
Facility Optimization Solutions Brochure
 
Shedding Light on the Incandescent Phase-Out
Shedding Light on the Incandescent Phase-OutShedding Light on the Incandescent Phase-Out
Shedding Light on the Incandescent Phase-Out
 
HCD Amato Audience Evaluation
HCD Amato Audience EvaluationHCD Amato Audience Evaluation
HCD Amato Audience Evaluation
 
SMPS Marketer - December 2013
SMPS Marketer - December 2013SMPS Marketer - December 2013
SMPS Marketer - December 2013
 
EPI - Bringing It In-House Series #4
EPI - Bringing It In-House Series #4EPI - Bringing It In-House Series #4
EPI - Bringing It In-House Series #4
 
UC SAN DIEGO JACOBS - NYTIMES NOV 17 2013
UC SAN DIEGO JACOBS - NYTIMES NOV 17 2013UC SAN DIEGO JACOBS - NYTIMES NOV 17 2013
UC SAN DIEGO JACOBS - NYTIMES NOV 17 2013
 

Achieving High Performance Operation With Energy Alarms

  • 1. Achieving High Performance Operation With Energy Alarms PRESENTERS: Mike Eardley, Director of Commissioning Cannon Design Christopher Longchamps, Senior Facilities Engineer Partners Healthcare System, Inc
  • 2. Agenda • Define a High Performance Building • Demonstrate how Commissioning (Cx) is a critical element • Define new building Cx, Retro-Cx, and Ongoing Cx • Ongoing Cx program at Massachusetts General Hospital • Partners Healthcare System – Strategic Energy Master Plan
  • 3. High Performance Buildings Characteristics • Functionality • Energy Efficiency • Indoor Environmental Quality • Comfort • Sustainability (ability to perform its function in a long term)
  • 4. Building Systems Commissioning • Buildings function as intended • Realize high performance
  • 5. Commissioning Definition • Commissioning (Cx) is a comprehensive and systematic process to verify and document that new or renovated facility systems function completely as designed to meet the owner’s requirements • A type of quality assurance to the systems being commissioned • Applied to building systems (e.g. HVAC) • Core element of sustainable buildings, along with energy modeling and measurement & verification
  • 6. Without Commissioning • Placement and calibration of Sensors • Simultaneous Heating and Cooling • Incorrect function of air-side Economizer and other efficiency measures • Operating Schedule is not what is necessary, or assumed by energy model • Cycling daylighting and other systems
  • 7. Reference Standards • ASHE Health Facility Commissioning Guidelines ashe.org • ASHRAE Guideline 0 The Commissioning Process ashrae.org • Building Commissioning Association Essential Attributes of Building Commissioning bcxa.org
  • 8. Why Commissioning? green cooling tower shutoff valve impeded blocked daylight sensor moisture penetration
  • 9. Purpose of Functional Testing • Verification of an operational system • Reduces adjustment and tuning during occupancy • Impacts  energy  comfort  maintenance  functionality
  • 10. Types of Functional Testing • Building Automation System • False load • Seasonal testing • Trend analysis
  • 11. Energy Impacts • Large effort in sustainable and energy efficient design • Will not be realized if design or intended use is:  misunderstood  ignored • Or if building systems are:  operating incorrectly  not thoroughly tested
  • 12. Common Problems – Air-side Economizer • Damper is stuck / broken / non-functional • Control algorithms fighting  heating during economizer  mechanical cooling when free cooling available • Outside sensor calibration or location
  • 13. Building Envelope Commissioning • Not often considered in basic scope • Affects Air infiltration, IAQ, air/water leaks, building systems performance • Involves many building components, suppliers & subcontractors • Coordination meetings; sketches or drawings; wall systems, roof, trade penetrations • Checklist & Inspections
  • 14. Building Envelope Thermal Bridging Moisture Penetration Window Water Testing
  • 15. Functional Test – Alarms and Safeties • Varying levels of rigor  verify software interactions  verify hardware interactions  verify actual conditions e.g. cold, smoke • Pull the plug  simulate actual loss of power  does transfer and restart act as intended?
  • 16. New and Existing Buildings • Commissioning: Process applied to new construction or major building renovation • Re-commissioning: Facility has previously been commissioned and is in need of a “tune-up” • Retro-commissioning: Performed on facilities that have been in service and never commissioned • Ongoing commissioning: Ongoing program of structured commissioning throughout the lifetime of a building
  • 17. Retro-Commissioning • Review of original design • Targeted functional testing • Identification of energy measures • Evaluation of measures • Energy modeling • Implementation • Verification and Persistence
  • 18. Trending • Functional testing before occupancy is a snapshot • Trending shows operation over time • Methods of trending  building automation system  portable data loggers • Analyze trends  spreadsheet calculations  software tools
  • 19. Ongoing Commissioning • Good  Cx process with functional testing • Better  Re-Cx program • Best  Ongoing Cx • Combination of software, engineering support, action
  • 20. PHS Strategic Energy Master Plan Objective In 2008, PHS Utilities and Engineering Department was charged to develop a Strategic Energy Master Plan to Address the Hospital ever-growing demand for energy and the volatile nature of the Energy market and concerns regarding global warming and long term sustainability of resource consumption and its impact on the delivery of critical health care services
  • 21. PHS Strategic Energy Master Plan Goals
  • 22. MGH Actual Energy Consumption Vs Projection From PHS Strategic Energy Master Plan Study 2,500,000 2,000,000 1,500,000 Total Energy Consumption (Do nothing) MMBTU based on 1,000,000 SEMP 2008 study, including Lunder building Notes: Actual Total Energy Consumption MMBTU After SEMP up to 2012 including Lunder building from invoices 1.Lunder Building came on line on May 2011 but not fully occupied until late fall Projected Actual Total Energy ConsumptionMMBTU with 500,000 MGH SEMP Projected savings from 2012 to 2026 2.Based on escalation of 1.5% load growth Total Projected Energy Consumption MMBTU with Projected savings from SEMP including Lunder building 0 2008 2009 2010 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020 2021 2022 2023 2024 2025 2026
  • 23. MGH SEMP Actual Total Energy Reduction Compared To 2008 PHS SEMP Energy Reduction Goal 500,000 450,000 400,000 350,000 MMBTU 300,000 250,000 MGH SEMP Primary Goal, 25% energy reduction from 2008 based line 1,509,875MMbtu 200,000 MGH actual energy reduction compare to Primary goal 150,000 MGH Projected Energy Reduction Compare to Primary Goal 100,000 50,000 0 200 200 201 201 201 201 201 201 8 9 0 1 2 3 4 5
  • 24. SEMP Impact On Utilities Cost Per Sq.Ft. MGH Cost per Sq. Ft. $14 FY 2008 ($/sq ft) FY 2012 ($/sq ft) $12.36 $12 $11.04 $10 $9.02 $8 $7.67 $6.90 $ / sq ft $6.56 $6.83 $6.08 $6 $5.38 $4.97 $4.43 $3.90 $4 $2 $0 MGH Combined MGH Main CNY Simches Yawkey Cox including Campus 149, 114, 75 CNY, Simches (6,371,307 ft²) (5,071,825 ft²) (945,947 ft²) (353,535 ft²) (446,960 ft²) (119,808 ft²)
  • 25. SEMP Impact On Utilities Consumption Per Sq.Ft. 600 MGH kBtu per Sq. Ft. FY 2008 (kBtu/sq ft) FY 2012 (kBtu/sq ft) 500 487 LABS 21 400 376 383 Benchmark DOE 2.1 Hospital kBtu/sq. ft. Benchmark 294 300 262 251 252 217 201 217 210 200 142 100 0 MGH Combined MGH Main CNY Simches Yawkey Cox including Campus 149, 114, 75 CNY, Simches (6,371,307 ft²) (5,071,825 ft²) (945,947 ft²) (353,535 ft²) (446,960 ft²) (119,808 ft²)
  • 26. ECMS That Have Major Savings On Outpatient, Research and Outpatient/Research/Office Facility • Building Occupied / Unoccupied schedule setback • Reduce minimum CFM set point • Schedule Room Thermostat with Dead Band • Fume Hoods modification • Lighting retrofits • Chillers Plant optimization • Steam Traps • Steam Condensate Heat recovery • Low temperature Run-Around Heat Recovery • Reset Pump DP set point • Reset AHU Supply and Return Fans S.P. set point
  • 27. Lesson Learned • The Energy conservation measures such as Set point or Schedule setback can be unintentional altered by mechanic • The Energy Alarms system need to be developed to monitor the MEP system for equipment failures and/or operating out of range • Energy Alarms can be part of an MEP Maintenance Program • A continuous measurement & verification program needs to be established to ensure the savings are continued
  • 28. Massachusetts General Hospital • Researched ongoing Cx products in the market • Some required installation of new equipment • All were costly • Concern about level of detail in the delivered product • Settled on customized, built up approach
  • 29. Massachusetts General Hospital • Reviewed Design • Developed rules based logic to identify inefficient operation • Worked with campus controls provider to implement
  • 30. What Do Energy Alarms Look At? • VAV Airflow • VAV Heating Coil • VAV Occupancy Hours • HW HX Valve Leaking • AHU Preheat Valve Leaking • AHU CHW Valve Leaking • AHU Simultaneous Heating & Cooling • CHW Low Delta T • CHW Economizer w/ Chiller(s) Running • AHU Should be in Economizer; Excessive CHW Use • AHU Should Not be in Economizer; Excessive outside air • More than 79 different types of Energy Alarm are monitored
  • 32. Example of an Air Flow Alarm • Checks box’s damper operation • Very effective in locating broken damper actuators • Trigger: Box air flow is not meeting setpoint Logic: • |CFM – CFMSpt| > 0.15 x MaxCFMSpt [Delay = 1 hr] • CFM = Actual CFM • CFMSpt = CFM Setpoint • MaxCFMSpt = Maximum CFM Setpoint of box
  • 33. What is One Air Flow Alarm Worth? Schedule: Occupied: 5:00AM – 6:30PM Mon-Fri (Extra CFM) x (hrs of CFM per week /Total hrs in a week)x($6/cfm) Occ hrs/wk = 67.5 hr (711 cfm – 145 cfm) x (67.5 hr/168 hr) x $4/cfm yr = $ 909 /yr Unocc hrs/wk = 100.5 hr Unoccupied: 711 cfm x (100.5 hr/168 hr) x $4/cfm yr = $ 1,701 /yr Total Estimated Annual Savings= $ 2,610
  • 34. Example of a Heating Coil Alarm • Checks that the box’s heating valve is closing completely • Trigger: An unexpected temperature difference across the heating coil Logic: • HWV% < 1% & |SAT – DAT| > 10 & CFMSpt > 0 [Delay = 2 hr] • HWV% = Hot Water Valve Position [0%=Closed, 100%=Open] • SAT = Supply Air Temp [Supply Air from AHU to the Box] • DAT = Discharge Air Temp • CFMSpt = CFM Setpoint
  • 35. What is One Heating Coil Alarm Worth? Schedule: Air Side 5:00AM-6:30PM Mon-Fri (325 cfm – 216 cfm) x (3,534 hr / 8,760 hr) Occ hrs / yr = 3534 hr = 44 cfm/yr 44 cfm/yr x $4 /cfm = $264/yr Total Estimated Annual Savings = $176
  • 36. How Does An Occupancy Alarm Work? • Checks if box switches to unoccupied mode • Trigger: Box remaining in occupied mode for a long period of time Logic: • Occ > 20 hrs in a 24 hr Period [Delay = 15 min] • Occ = Number of hours since midnight that the box has been occupied
  • 37. Example Of An Occupancy Override Yawkey Floor 9 Found Overridden ON Cancer Center Psychiatric Oncology Area Normal Occupancy Schedule: 5:00AM-6:30PM Mon-Fri Unoccupied hrs/week: 100.5 hr/wk Total Minimum CFM: 8,063 CFM Assuming $ 4/CFM yr 8,063 cfm x (100.5hr/168hr) x $4 /cfm year Annual Savings: $ 19,294
  • 38. How Does The Process Work? • Alarms are reviewed on a daily basis • Once validated there is a work order issued for the repair • Work directly with maintenance staff on difficult problems • Work order completed and issue closed
  • 39. How Many Energy Alarms Are There? More than 400 validated work orders have been addressed since summer of 2010 and $600,000 were realized.
  • 40. Questions / Discussion Achieving High Performance Operation With Energy Alarms PRESENTERS: Christopher Longchamps, Partners Healthcare System clongchamps@partners.org Mike Eardley, Cannon Design meardley@cannondesign.com @MikeEardley

Notas del editor

  1. HVACLighting / Daylight Control Building Automation SystemRealize High-Performance Design in OperationDocument and Ensure Owner/Facility RequirementsBuilding Functions as Intended and RequiredPromotes Energy Efficiency
  2. HVACLighting / Daylight Control Building Automation SystemRealize High-Performance Design in OperationDocument and Ensure Owner/Facility RequirementsBuilding Functions as Intended and RequiredPromotes Energy Efficiency
  3. HVACLighting / Daylight Control Building Automation SystemRealize High-Performance Design in OperationDocument and Ensure Owner/Facility RequirementsBuilding Functions as Intended and RequiredPromotes Energy Efficiency
  4. HVACLighting / Daylight Control Building Automation SystemRealize High-Performance Design in OperationDocument and Ensure Owner/Facility RequirementsBuilding Functions as Intended and RequiredPromotes Energy Efficiency
  5. HVACLighting / Daylight Control Building Automation SystemRealize High-Performance Design in OperationDocument and Ensure Owner/Facility RequirementsBuilding Functions as Intended and RequiredPromotes Energy Efficiency