Factory owners must ensure the boiler is:─
* Registered with the Boilers and Pressure Vessels Division, Labour Department
* Examined by an appointed examiner and has a valid certificate of fitness
* Supervised by a competent person whenever it is steaming
* In safe working order
* Properly maintained through regular periodic internal examinations every 14
months by an appointed examiner
A Guide for Fire-tube Boiler Operation
Boilers and Pressure Vessels Authority
Labour Department
May 1993
Printed by the Printing Department
(Printed with environmentally friendly ink on paper made
from woodpulp derived from renewable forests)
3
FOREWORD
This guide explains the main provisions of the Boilers and Pressure Vessels
Ordinance, Chapter 56, as applicable to fire tube steam boilers. Essentials of
operation are also briefly explained.
This equipment is extensively used in industry and insufficient knowledge
about its operation and proper maintenance has caused serious accidents. All
personnel engaged in the use of such equipment are strongly advised to
familiarise themselves with the contents of this guide.
This guide is not meant to replace the Ordinance or the maker's manuals
which remain the final authority for regulating operation of this equipment.
On request, the Labour Department will also offer further advice to owners
and operators of such equipment.
4
5
CONTENTS
Page
1. General 7
2. Features of Fire-Tube Boilers 7
3. Flashing Up Procedure 9
4. Testing of Gauge Glass 11
5. Low-water Level Cut-Off Switch 16
6. Steam Pressure Testing of Safety Valve 17
7. Testing of Steam Pressure Switch 18
8. Testing of Flame Detector 19
9. Fire-Tube Boiler Emergencies 19
10. Handling of Boiler Fires 20
11. Important Points for Compliance by workers and Factory Owners 20
12. Enquiries 20
6
7
1. GENERAL
The Boilers and Pressure Vessels Ordinance, Cap.56, controls the use and
operation of boilers. The responsibilities for personnel involved in its use are:─
OWNER * apply for registration at least 30 days prior
to its being put into use.
* engrave the registration number allocated
on the boiler in a conspicuous position.
APPOINTED EXAMINER * examine the boiler and its auxiliary
equipment.
* seal the safety valve at the approved
maximum permissible pressure.
* issue a Certificate of Fitness.
COMPETENT PERSON * possesses certificate of competency issued
by the Authority, Labour Department, for
his competence to operate the type of
boiler he is employed to operate.
* follows correct procedure for operation
and upkeep of boilers.
* supervises the boiler directly at all times
when it is in operation.
* ensures that the safety valve seal fixed by
the appointed examiner is not broken or
tampered with.
The owner of a boiler can be prosecuted and fined a maximum of $50,000
for operating the boiler:─
* without statutory examination or a valid certificate of fitness.
* without direct supervision of a competent person.
2. FEATURES OF FIRE-TUBE BOILERS
The fire-tube boilers are potentially dangerous as the steam pressures are high
and volume of hot water and steam content is large.
* water surrounds the tubes through which hot combustion gases pass
before venting to atmosphere through gas uptakes.
* water converted into high pressure steam by transfer of heat from very
high temperature combustion gases on water.
* hot combustion gases produced by burning diesel oil, town gas etc. in the
furnace.
* boilers are of fully automatic design.
* essential mountings include safety valve, steam pressure switch, pressure
gauge,gauge glass, valve fittings, low-water level cut-off and alarm devices
etc.
8
9
3. FLASHING UP PROCEDURE
(a) Check Certificate of Fitness and its validity date.
(b) Check maximum permissible working pressure which is indicated by a red
line on pressure gauge fitted.
(c) Check and close drain valves.
(d) Open water and steam cocks of water gauge glass and shut its drain cock.
(e) Clean and examine filter in feed water system.
(f) Open feed water tank outlet valve, and ensure water level in tank is at least
half the gauge glass.
(g) Check fuel oil daily service tank level and drain off any water present.
(h) Clean and examine filters in fuel oil system.
(i) Shut main steam stop valve and open air vent.
(j) Switch on power supply. Feed water pump will automatically supply water
to boiler till approximately half gauge glass.
(k) Fuel oil pump will automatically start. Fuel oil, if heavy diesel oil, will
circulate through fuel oil heater till the desired operating temperature
reached.
(l) The blower motor will start and purge furnace for at least 1-2 minutes to
clear any combustible gas accumulated in the furnace and avoid a blow
back.
(m) The burner will be ignited according to an automatic sequence, initially at
low fire rate.
(n) When steam comes out from air vent, shut off air vent and switch to high
fire rate. Steam pressure will gradually increase to normal working
pressure.
(o) Check gauge glass, safety valve, and all automatic safety devices to ensure
they are functioning normally.
(p) Open steam valve very slowly to permit warming through and draining of
the cold steam pipes to avoid damage due to water hammer.
10
11
4. TESTING OF GAUGE GLASS
When the boiler is in operation, the steam cocks A, D and water cocks B, E are
open and drain cock C is shut. FIG. 4
(a) First shut both steam and water cocks A, D, B and E. Open drain cock C
to prove that all the gauge cocks are in order. Then, with the drain cock C
still open, cocks B and E should be opened. If water blows out freely from
cock C, cocks B and E are clear. FIG. 4(A).
(b) Shut off cocks B and E and open cocks A and D with the drain cock C
still open. If steam blows out freely from cock C, cocks A and D are clear.
FIG. 4 (B).
(c) To cross test, close cocks D and B, leaving E, A and C open. If water blows
out from cock C, then E, A and the water-column are in order. FIG. 4(C).
(d) Close cocks E and A leaving D, B and C open. If steam blows out from
cock C, then D, B and the water-column are in order. FIG. 4(D).
12
13
14
15
16
Possible causes of gauge glass indicating incorrect level
(a) If cocks A and D or steam passage is shut or choked, boiler pressure will
press the water level in the glass higher than the real water level of the
boiler. The water level indication in glass will, therefore, be incorrect.
(b) If cocks B and E or water passage is shut or choked, steam will condense
on upper column of glass and accumulate. The apparent water level shown
can be higher than the actual water level, causing false reading.
Water gauge glass should be tested daily at least at every change of
attendant. The safety of boiler operation relies greatly on proper functioning of
the water gauge glass.
5. LOW-WATER LEVEL CUT-OFF SWITCH
This device should be checked daily to ensure it is in normal working order.
Switch off the feed water pump, drain the float control water chamber. If boiler
is tripped off automatically, the device is in good order.
LOWER WATER LEVEL CUT-OFF
17
6. STEAM PRESSURE TESTING OF SAFETY VALVE
The safe operation of steam boiler depends on the correct functioning of the
safety valve. The safety valve should be lifted daily with the easing gear to
prevent sticking of valve seat and it should be pressure tested weekly as
follows:-
(a) Shut off main steam stop valve.
(b) Adjust steam pressure switch to a setting slightly higher than maximum
permissible working pressure.
(c) With boiler on maximum firing rate, observe the pressure gauge. When
steam pressure reaches m.p.w.p., safety valve will automatically open to
release steam pressure. That means safety valve is set correctly and
working. Maximum permissible working pressure can be obtained from
the Certificate of Fitness.
(d) If the safety valve does not open when the steam pressure reaches the
m.p.w.p., boiler should be stopped immediately, and the easing gear
operated to release steam and lower the boiler pressure. Call the
Appointed Examiner for examination immediately.
SAFETY VALVE
18
7. TESTING OF STEAM PRESSURE SWITCH
This switch should be checked daily to ensure it is functioning properly. During
the initial start, make sure the boiler can be tripped off automatically when
boiler pressure attains the cut-off value of the pressure switch. Cut off pressure
and differential pressure can be adjusted with the adjusting screw on top of the
switch to suit the requirement of the factory.
STEAM PRESSURE SWITCH
19
8. TESTING OF FLAME DETECTOR
The detector should be tested weekly to ensure it is in normal working order.
An easy method of testing is by removing the detector head from the boiler and
shielding the sensing head with hand. If boiler trips off automatically, the flame
detector is in satisfactory condition.
FLAME DETECTOR (FLAME EYE)
9. FIRE-TUBE BOILER EMERGENCIES
(a) When the boiler is steaming with water level not visible in the gauge glass,
shut off the burner immediate1y. Test the gauge glass or test cocks. If low
water level established in the boiler NEVER add water into the boiler right
away. Locate and rectify the fault, wait until the boiler has cooled down,
seek advice of an Appointed Examiner for identifying defect or damage
before flashing the boiler again.
(b) If the steam pressure exceeds the maximum permissible working pressure
without lifting of safety valve, shut off the boiler immediately. Operate the
easing gear to release steam. If safety valve still does not open auto-
matically, release steam from air vent valve and contact an Appointed
Examiner for examination and advice on repair.
20
(c) Boiler water should be tested and chemically treated according to
manufacturer's schedule or on the advice of an Appointed Examiner. This
will avoid corrosion and scale formation on heating surfaces. Wastage of
furnace, fire tubes or boiler shell can develop and cause boiler explosion.
Consult an Appointed Examiner for advice.
10. HANDLING OF BOILER FIRES
(a) First raise fire alarm or shout to let all workers in the factory know of the
fire.
(b) Shut off the main power supply for boiler room. Shut off the fuel oil
isolating valve. Stop the boiler, and switch off the ventilation fan.
(c) Locate the site of fire, and check the cause and nature of fire. Use
appropriate fire extinguishers for different type of fires:─
Oil fire : foam, dry powder etc.
Electric fire : CO2, dry powder etc.
11. IMPORTANT POINTS FOR COMPLIANCE BY WORKERS
AND FACTORY OWNERS
* Don't break the seal of the safety valve, or try to adjust its setting to increase
the boiler pressure. This endangers the safety, will cause over-pressure of the
boiler and may cause boiler explosion with consequent injuries to personnel.
* All automatic safety devices such as safety valve, pressure switch and
low-water cut-off switches should be tested periodically to ensure they are in
good working condition at all times.
* If accident happens to a boiler or its auxiliary, owner must immediately stop
using the boiler and report the accident to the Authority of Boilers and
Pressure Vessels within 24 hours. The owner can be prosecuted and fined a
maximum of $10,000 for not complying this requirement.
12. ENQUIRIES
* For all enquiries please contact the BOILERS AND PRESSURE VESSELS
DIVISION of the Labour Department. The address is as follows:─
24/F., Western Harbour Centre
181 Connaught Road West
Hong Kong
Telephone: 2975 6428
A guide for firetube boiler   testes

Más contenido relacionado

La actualidad más candente

Pre commissioning steam turbines load trial
Pre commissioning steam turbines load trialPre commissioning steam turbines load trial
Pre commissioning steam turbines load trialNagesh H
 
Tecator soxtec-vetbepaling-manual
Tecator soxtec-vetbepaling-manualTecator soxtec-vetbepaling-manual
Tecator soxtec-vetbepaling-manualhovanchuong12
 
Handling of turbine side emergencies
Handling of turbine side emergenciesHandling of turbine side emergencies
Handling of turbine side emergenciesManohar Tatwawadi
 
Beebe steam turbines cm apr2016 r1
Beebe steam turbines cm apr2016 r1Beebe steam turbines cm apr2016 r1
Beebe steam turbines cm apr2016 r1Ray Beebe
 
7) hydro test 3
7) hydro test 37) hydro test 3
7) hydro test 3ALISAB123
 
Medical gas supply.pipelines and cylinders
Medical gas supply.pipelines and cylindersMedical gas supply.pipelines and cylinders
Medical gas supply.pipelines and cylindersdrsauravdas1977
 
The basic anaesthesia machine
The basic anaesthesia machineThe basic anaesthesia machine
The basic anaesthesia machinehrishi bharali
 
Cb gf web in aug 2016, controls r2 8.23.16 final
Cb gf web in aug 2016, controls r2 8.23.16 finalCb gf web in aug 2016, controls r2 8.23.16 final
Cb gf web in aug 2016, controls r2 8.23.16 finallorenzo Monasca
 
Coluna de Calibração _ Milton Roy
Coluna de Calibração _ Milton RoyColuna de Calibração _ Milton Roy
Coluna de Calibração _ Milton RoyVibropac
 
Steam blowing stages before turbine rolling
Steam blowing stages before turbine rollingSteam blowing stages before turbine rolling
Steam blowing stages before turbine rollingabhinav kumar
 
0.1-Overview-AZ-SA
0.1-Overview-AZ-SA0.1-Overview-AZ-SA
0.1-Overview-AZ-SANolan Chetty
 
Bhel STEAM safety valve_1700_series
Bhel STEAM safety valve_1700_seriesBhel STEAM safety valve_1700_series
Bhel STEAM safety valve_1700_seriesAshish Kumar Jain
 

La actualidad más candente (20)

Pre commissioning steam turbines load trial
Pre commissioning steam turbines load trialPre commissioning steam turbines load trial
Pre commissioning steam turbines load trial
 
SOP example
SOP exampleSOP example
SOP example
 
Ekit (B) Sdn Bhd
Ekit (B) Sdn BhdEkit (B) Sdn Bhd
Ekit (B) Sdn Bhd
 
Tecator soxtec-vetbepaling-manual
Tecator soxtec-vetbepaling-manualTecator soxtec-vetbepaling-manual
Tecator soxtec-vetbepaling-manual
 
Handling of turbine side emergencies
Handling of turbine side emergenciesHandling of turbine side emergencies
Handling of turbine side emergencies
 
Bfwp
BfwpBfwp
Bfwp
 
Beebe steam turbines cm apr2016 r1
Beebe steam turbines cm apr2016 r1Beebe steam turbines cm apr2016 r1
Beebe steam turbines cm apr2016 r1
 
7) hydro test 3
7) hydro test 37) hydro test 3
7) hydro test 3
 
Medical gas supply.pipelines and cylinders
Medical gas supply.pipelines and cylindersMedical gas supply.pipelines and cylinders
Medical gas supply.pipelines and cylinders
 
Fire pumps
Fire pumpsFire pumps
Fire pumps
 
The basic anaesthesia machine
The basic anaesthesia machineThe basic anaesthesia machine
The basic anaesthesia machine
 
NONG YAO PROJECT SUBSEA VALVE Rev 0
NONG YAO PROJECT SUBSEA VALVE Rev 0NONG YAO PROJECT SUBSEA VALVE Rev 0
NONG YAO PROJECT SUBSEA VALVE Rev 0
 
Production Operator
Production OperatorProduction Operator
Production Operator
 
Compressor Valves
Compressor ValvesCompressor Valves
Compressor Valves
 
Cb gf web in aug 2016, controls r2 8.23.16 final
Cb gf web in aug 2016, controls r2 8.23.16 finalCb gf web in aug 2016, controls r2 8.23.16 final
Cb gf web in aug 2016, controls r2 8.23.16 final
 
Coluna de Calibração _ Milton Roy
Coluna de Calibração _ Milton RoyColuna de Calibração _ Milton Roy
Coluna de Calibração _ Milton Roy
 
Steam blowing stages before turbine rolling
Steam blowing stages before turbine rollingSteam blowing stages before turbine rolling
Steam blowing stages before turbine rolling
 
0.1-Overview-AZ-SA
0.1-Overview-AZ-SA0.1-Overview-AZ-SA
0.1-Overview-AZ-SA
 
Bhel STEAM safety valve_1700_series
Bhel STEAM safety valve_1700_seriesBhel STEAM safety valve_1700_series
Bhel STEAM safety valve_1700_series
 
Cylinders
CylindersCylinders
Cylinders
 

Similar a A guide for firetube boiler testes

Training on OJT of Boiler Operation00.pdf
Training on OJT of Boiler Operation00.pdfTraining on OJT of Boiler Operation00.pdf
Training on OJT of Boiler Operation00.pdfMadan Karki
 
Final Turbine rolling ppt Akshay.pptx
Final Turbine rolling ppt Akshay.pptxFinal Turbine rolling ppt Akshay.pptx
Final Turbine rolling ppt Akshay.pptxBhimarajuKanireddy
 
171839416-commissioning-of-hydro-ppt.ppt
171839416-commissioning-of-hydro-ppt.ppt171839416-commissioning-of-hydro-ppt.ppt
171839416-commissioning-of-hydro-ppt.pptssuser9e9be71
 
API682 Mechanical Seal Plan and Requirements of Mechanical Seals
API682 Mechanical Seal Plan and Requirements of Mechanical SealsAPI682 Mechanical Seal Plan and Requirements of Mechanical Seals
API682 Mechanical Seal Plan and Requirements of Mechanical SealsElango Palaniappan
 
API 682 Seal piping plans.pdf
API 682 Seal piping plans.pdfAPI 682 Seal piping plans.pdf
API 682 Seal piping plans.pdfTeddy Setiady
 
Hazard operability study - in Industires and plant
Hazard operability study - in Industires and plantHazard operability study - in Industires and plant
Hazard operability study - in Industires and plantJayaKarthic1
 
Hyster b214 (h450 hds ec) forklift service repair manual
Hyster b214 (h450 hds ec) forklift service repair manualHyster b214 (h450 hds ec) forklift service repair manual
Hyster b214 (h450 hds ec) forklift service repair manualuufdjjjskkemm
 
Hyster b214 (h500 hd ec) forklift service repair manual
Hyster b214 (h500 hd ec) forklift service repair manualHyster b214 (h500 hd ec) forklift service repair manual
Hyster b214 (h500 hd ec) forklift service repair manualufjkskemfseol
 
Hyster b214 (h450 hds ec) forklift service repair manual
Hyster b214 (h450 hds ec) forklift service repair manualHyster b214 (h450 hds ec) forklift service repair manual
Hyster b214 (h450 hds ec) forklift service repair manualfujsjefkskem
 
Hyster b214 (h500 hd ec) forklift service repair manual
Hyster b214 (h500 hd ec) forklift service repair manualHyster b214 (h500 hd ec) forklift service repair manual
Hyster b214 (h500 hd ec) forklift service repair manualfhjsekfksemert
 
Hyster b214 (h450 hds ec) forklift service repair manual
Hyster b214 (h450 hds ec) forklift service repair manualHyster b214 (h450 hds ec) forklift service repair manual
Hyster b214 (h450 hds ec) forklift service repair manualfjkskmmdmme
 
Hyster b214 (h450 hds ec) forklift service repair manual
Hyster b214 (h450 hds ec) forklift service repair manualHyster b214 (h450 hds ec) forklift service repair manual
Hyster b214 (h450 hds ec) forklift service repair manualfjsjekdmmeme
 
Hyster b214 (h500 hd ec) forklift service repair manual
Hyster b214 (h500 hd ec) forklift service repair manualHyster b214 (h500 hd ec) forklift service repair manual
Hyster b214 (h500 hd ec) forklift service repair manualujdjfjkskmdm
 

Similar a A guide for firetube boiler testes (20)

Training on OJT of Boiler Operation00.pdf
Training on OJT of Boiler Operation00.pdfTraining on OJT of Boiler Operation00.pdf
Training on OJT of Boiler Operation00.pdf
 
Boiler safety
Boiler safetyBoiler safety
Boiler safety
 
Final Turbine rolling ppt Akshay.pptx
Final Turbine rolling ppt Akshay.pptxFinal Turbine rolling ppt Akshay.pptx
Final Turbine rolling ppt Akshay.pptx
 
171839416-commissioning-of-hydro-ppt.ppt
171839416-commissioning-of-hydro-ppt.ppt171839416-commissioning-of-hydro-ppt.ppt
171839416-commissioning-of-hydro-ppt.ppt
 
THERMAL ENGINEERING
THERMAL ENGINEERINGTHERMAL ENGINEERING
THERMAL ENGINEERING
 
API682 Mechanical Seal Plan and Requirements of Mechanical Seals
API682 Mechanical Seal Plan and Requirements of Mechanical SealsAPI682 Mechanical Seal Plan and Requirements of Mechanical Seals
API682 Mechanical Seal Plan and Requirements of Mechanical Seals
 
API 682 Seal piping plans.pdf
API 682 Seal piping plans.pdfAPI 682 Seal piping plans.pdf
API 682 Seal piping plans.pdf
 
Leak Tests.pptx
Leak Tests.pptxLeak Tests.pptx
Leak Tests.pptx
 
Boiler Mountings
Boiler MountingsBoiler Mountings
Boiler Mountings
 
FillingCylinders
FillingCylindersFillingCylinders
FillingCylinders
 
Hazard operability study - in Industires and plant
Hazard operability study - in Industires and plantHazard operability study - in Industires and plant
Hazard operability study - in Industires and plant
 
HAZOP.ppt
HAZOP.pptHAZOP.ppt
HAZOP.ppt
 
Boiler condition survey
Boiler condition surveyBoiler condition survey
Boiler condition survey
 
Hyster b214 (h450 hds ec) forklift service repair manual
Hyster b214 (h450 hds ec) forklift service repair manualHyster b214 (h450 hds ec) forklift service repair manual
Hyster b214 (h450 hds ec) forklift service repair manual
 
Hyster b214 (h500 hd ec) forklift service repair manual
Hyster b214 (h500 hd ec) forklift service repair manualHyster b214 (h500 hd ec) forklift service repair manual
Hyster b214 (h500 hd ec) forklift service repair manual
 
Hyster b214 (h450 hds ec) forklift service repair manual
Hyster b214 (h450 hds ec) forklift service repair manualHyster b214 (h450 hds ec) forklift service repair manual
Hyster b214 (h450 hds ec) forklift service repair manual
 
Hyster b214 (h500 hd ec) forklift service repair manual
Hyster b214 (h500 hd ec) forklift service repair manualHyster b214 (h500 hd ec) forklift service repair manual
Hyster b214 (h500 hd ec) forklift service repair manual
 
Hyster b214 (h450 hds ec) forklift service repair manual
Hyster b214 (h450 hds ec) forklift service repair manualHyster b214 (h450 hds ec) forklift service repair manual
Hyster b214 (h450 hds ec) forklift service repair manual
 
Hyster b214 (h450 hds ec) forklift service repair manual
Hyster b214 (h450 hds ec) forklift service repair manualHyster b214 (h450 hds ec) forklift service repair manual
Hyster b214 (h450 hds ec) forklift service repair manual
 
Hyster b214 (h500 hd ec) forklift service repair manual
Hyster b214 (h500 hd ec) forklift service repair manualHyster b214 (h500 hd ec) forklift service repair manual
Hyster b214 (h500 hd ec) forklift service repair manual
 

Último

Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Dr.Costas Sachpazis
 
Glass Ceramics: Processing and Properties
Glass Ceramics: Processing and PropertiesGlass Ceramics: Processing and Properties
Glass Ceramics: Processing and PropertiesPrabhanshu Chaturvedi
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCall Girls in Nagpur High Profile
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
Introduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxIntroduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxupamatechverse
 
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...ranjana rawat
 
KubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlyKubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlysanyuktamishra911
 
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Christo Ananth
 
UNIT-III FMM. DIMENSIONAL ANALYSIS
UNIT-III FMM.        DIMENSIONAL ANALYSISUNIT-III FMM.        DIMENSIONAL ANALYSIS
UNIT-III FMM. DIMENSIONAL ANALYSISrknatarajan
 
AKTU Computer Networks notes --- Unit 3.pdf
AKTU Computer Networks notes ---  Unit 3.pdfAKTU Computer Networks notes ---  Unit 3.pdf
AKTU Computer Networks notes --- Unit 3.pdfankushspencer015
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxAsutosh Ranjan
 
Extrusion Processes and Their Limitations
Extrusion Processes and Their LimitationsExtrusion Processes and Their Limitations
Extrusion Processes and Their Limitations120cr0395
 
MANUFACTURING PROCESS-II UNIT-1 THEORY OF METAL CUTTING
MANUFACTURING PROCESS-II UNIT-1 THEORY OF METAL CUTTINGMANUFACTURING PROCESS-II UNIT-1 THEORY OF METAL CUTTING
MANUFACTURING PROCESS-II UNIT-1 THEORY OF METAL CUTTINGSIVASHANKAR N
 
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...ranjana rawat
 
UNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular ConduitsUNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular Conduitsrknatarajan
 
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Bookingdharasingh5698
 
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSMANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSSIVASHANKAR N
 
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service NashikCall Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service NashikCall Girls in Nagpur High Profile
 

Último (20)

Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
 
Glass Ceramics: Processing and Properties
Glass Ceramics: Processing and PropertiesGlass Ceramics: Processing and Properties
Glass Ceramics: Processing and Properties
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024
 
Introduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxIntroduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptx
 
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
 
KubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlyKubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghly
 
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
 
UNIT-III FMM. DIMENSIONAL ANALYSIS
UNIT-III FMM.        DIMENSIONAL ANALYSISUNIT-III FMM.        DIMENSIONAL ANALYSIS
UNIT-III FMM. DIMENSIONAL ANALYSIS
 
AKTU Computer Networks notes --- Unit 3.pdf
AKTU Computer Networks notes ---  Unit 3.pdfAKTU Computer Networks notes ---  Unit 3.pdf
AKTU Computer Networks notes --- Unit 3.pdf
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptx
 
Extrusion Processes and Their Limitations
Extrusion Processes and Their LimitationsExtrusion Processes and Their Limitations
Extrusion Processes and Their Limitations
 
MANUFACTURING PROCESS-II UNIT-1 THEORY OF METAL CUTTING
MANUFACTURING PROCESS-II UNIT-1 THEORY OF METAL CUTTINGMANUFACTURING PROCESS-II UNIT-1 THEORY OF METAL CUTTING
MANUFACTURING PROCESS-II UNIT-1 THEORY OF METAL CUTTING
 
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
 
UNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular ConduitsUNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular Conduits
 
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
 
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSMANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
 
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service NashikCall Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
 

A guide for firetube boiler testes

  • 1.
  • 2. Factory owners must ensure the boiler is:─ * Registered with the Boilers and Pressure Vessels Division, Labour Department * Examined by an appointed examiner and has a valid certificate of fitness * Supervised by a competent person whenever it is steaming * In safe working order * Properly maintained through regular periodic internal examinations every 14 months by an appointed examiner
  • 3. A Guide for Fire-tube Boiler Operation Boilers and Pressure Vessels Authority Labour Department May 1993
  • 4. Printed by the Printing Department (Printed with environmentally friendly ink on paper made from woodpulp derived from renewable forests)
  • 5. 3 FOREWORD This guide explains the main provisions of the Boilers and Pressure Vessels Ordinance, Chapter 56, as applicable to fire tube steam boilers. Essentials of operation are also briefly explained. This equipment is extensively used in industry and insufficient knowledge about its operation and proper maintenance has caused serious accidents. All personnel engaged in the use of such equipment are strongly advised to familiarise themselves with the contents of this guide. This guide is not meant to replace the Ordinance or the maker's manuals which remain the final authority for regulating operation of this equipment. On request, the Labour Department will also offer further advice to owners and operators of such equipment.
  • 6. 4
  • 7. 5 CONTENTS Page 1. General 7 2. Features of Fire-Tube Boilers 7 3. Flashing Up Procedure 9 4. Testing of Gauge Glass 11 5. Low-water Level Cut-Off Switch 16 6. Steam Pressure Testing of Safety Valve 17 7. Testing of Steam Pressure Switch 18 8. Testing of Flame Detector 19 9. Fire-Tube Boiler Emergencies 19 10. Handling of Boiler Fires 20 11. Important Points for Compliance by workers and Factory Owners 20 12. Enquiries 20
  • 8. 6
  • 9. 7 1. GENERAL The Boilers and Pressure Vessels Ordinance, Cap.56, controls the use and operation of boilers. The responsibilities for personnel involved in its use are:─ OWNER * apply for registration at least 30 days prior to its being put into use. * engrave the registration number allocated on the boiler in a conspicuous position. APPOINTED EXAMINER * examine the boiler and its auxiliary equipment. * seal the safety valve at the approved maximum permissible pressure. * issue a Certificate of Fitness. COMPETENT PERSON * possesses certificate of competency issued by the Authority, Labour Department, for his competence to operate the type of boiler he is employed to operate. * follows correct procedure for operation and upkeep of boilers. * supervises the boiler directly at all times when it is in operation. * ensures that the safety valve seal fixed by the appointed examiner is not broken or tampered with. The owner of a boiler can be prosecuted and fined a maximum of $50,000 for operating the boiler:─ * without statutory examination or a valid certificate of fitness. * without direct supervision of a competent person. 2. FEATURES OF FIRE-TUBE BOILERS The fire-tube boilers are potentially dangerous as the steam pressures are high and volume of hot water and steam content is large. * water surrounds the tubes through which hot combustion gases pass before venting to atmosphere through gas uptakes. * water converted into high pressure steam by transfer of heat from very high temperature combustion gases on water. * hot combustion gases produced by burning diesel oil, town gas etc. in the furnace. * boilers are of fully automatic design. * essential mountings include safety valve, steam pressure switch, pressure gauge,gauge glass, valve fittings, low-water level cut-off and alarm devices etc.
  • 10. 8
  • 11. 9 3. FLASHING UP PROCEDURE (a) Check Certificate of Fitness and its validity date. (b) Check maximum permissible working pressure which is indicated by a red line on pressure gauge fitted. (c) Check and close drain valves. (d) Open water and steam cocks of water gauge glass and shut its drain cock. (e) Clean and examine filter in feed water system. (f) Open feed water tank outlet valve, and ensure water level in tank is at least half the gauge glass. (g) Check fuel oil daily service tank level and drain off any water present. (h) Clean and examine filters in fuel oil system. (i) Shut main steam stop valve and open air vent. (j) Switch on power supply. Feed water pump will automatically supply water to boiler till approximately half gauge glass. (k) Fuel oil pump will automatically start. Fuel oil, if heavy diesel oil, will circulate through fuel oil heater till the desired operating temperature reached. (l) The blower motor will start and purge furnace for at least 1-2 minutes to clear any combustible gas accumulated in the furnace and avoid a blow back. (m) The burner will be ignited according to an automatic sequence, initially at low fire rate. (n) When steam comes out from air vent, shut off air vent and switch to high fire rate. Steam pressure will gradually increase to normal working pressure. (o) Check gauge glass, safety valve, and all automatic safety devices to ensure they are functioning normally. (p) Open steam valve very slowly to permit warming through and draining of the cold steam pipes to avoid damage due to water hammer.
  • 12. 10
  • 13. 11 4. TESTING OF GAUGE GLASS When the boiler is in operation, the steam cocks A, D and water cocks B, E are open and drain cock C is shut. FIG. 4 (a) First shut both steam and water cocks A, D, B and E. Open drain cock C to prove that all the gauge cocks are in order. Then, with the drain cock C still open, cocks B and E should be opened. If water blows out freely from cock C, cocks B and E are clear. FIG. 4(A). (b) Shut off cocks B and E and open cocks A and D with the drain cock C still open. If steam blows out freely from cock C, cocks A and D are clear. FIG. 4 (B). (c) To cross test, close cocks D and B, leaving E, A and C open. If water blows out from cock C, then E, A and the water-column are in order. FIG. 4(C). (d) Close cocks E and A leaving D, B and C open. If steam blows out from cock C, then D, B and the water-column are in order. FIG. 4(D).
  • 14. 12
  • 15. 13
  • 16. 14
  • 17. 15
  • 18. 16 Possible causes of gauge glass indicating incorrect level (a) If cocks A and D or steam passage is shut or choked, boiler pressure will press the water level in the glass higher than the real water level of the boiler. The water level indication in glass will, therefore, be incorrect. (b) If cocks B and E or water passage is shut or choked, steam will condense on upper column of glass and accumulate. The apparent water level shown can be higher than the actual water level, causing false reading. Water gauge glass should be tested daily at least at every change of attendant. The safety of boiler operation relies greatly on proper functioning of the water gauge glass. 5. LOW-WATER LEVEL CUT-OFF SWITCH This device should be checked daily to ensure it is in normal working order. Switch off the feed water pump, drain the float control water chamber. If boiler is tripped off automatically, the device is in good order. LOWER WATER LEVEL CUT-OFF
  • 19. 17 6. STEAM PRESSURE TESTING OF SAFETY VALVE The safe operation of steam boiler depends on the correct functioning of the safety valve. The safety valve should be lifted daily with the easing gear to prevent sticking of valve seat and it should be pressure tested weekly as follows:- (a) Shut off main steam stop valve. (b) Adjust steam pressure switch to a setting slightly higher than maximum permissible working pressure. (c) With boiler on maximum firing rate, observe the pressure gauge. When steam pressure reaches m.p.w.p., safety valve will automatically open to release steam pressure. That means safety valve is set correctly and working. Maximum permissible working pressure can be obtained from the Certificate of Fitness. (d) If the safety valve does not open when the steam pressure reaches the m.p.w.p., boiler should be stopped immediately, and the easing gear operated to release steam and lower the boiler pressure. Call the Appointed Examiner for examination immediately. SAFETY VALVE
  • 20. 18 7. TESTING OF STEAM PRESSURE SWITCH This switch should be checked daily to ensure it is functioning properly. During the initial start, make sure the boiler can be tripped off automatically when boiler pressure attains the cut-off value of the pressure switch. Cut off pressure and differential pressure can be adjusted with the adjusting screw on top of the switch to suit the requirement of the factory. STEAM PRESSURE SWITCH
  • 21. 19 8. TESTING OF FLAME DETECTOR The detector should be tested weekly to ensure it is in normal working order. An easy method of testing is by removing the detector head from the boiler and shielding the sensing head with hand. If boiler trips off automatically, the flame detector is in satisfactory condition. FLAME DETECTOR (FLAME EYE) 9. FIRE-TUBE BOILER EMERGENCIES (a) When the boiler is steaming with water level not visible in the gauge glass, shut off the burner immediate1y. Test the gauge glass or test cocks. If low water level established in the boiler NEVER add water into the boiler right away. Locate and rectify the fault, wait until the boiler has cooled down, seek advice of an Appointed Examiner for identifying defect or damage before flashing the boiler again. (b) If the steam pressure exceeds the maximum permissible working pressure without lifting of safety valve, shut off the boiler immediately. Operate the easing gear to release steam. If safety valve still does not open auto- matically, release steam from air vent valve and contact an Appointed Examiner for examination and advice on repair.
  • 22. 20 (c) Boiler water should be tested and chemically treated according to manufacturer's schedule or on the advice of an Appointed Examiner. This will avoid corrosion and scale formation on heating surfaces. Wastage of furnace, fire tubes or boiler shell can develop and cause boiler explosion. Consult an Appointed Examiner for advice. 10. HANDLING OF BOILER FIRES (a) First raise fire alarm or shout to let all workers in the factory know of the fire. (b) Shut off the main power supply for boiler room. Shut off the fuel oil isolating valve. Stop the boiler, and switch off the ventilation fan. (c) Locate the site of fire, and check the cause and nature of fire. Use appropriate fire extinguishers for different type of fires:─ Oil fire : foam, dry powder etc. Electric fire : CO2, dry powder etc. 11. IMPORTANT POINTS FOR COMPLIANCE BY WORKERS AND FACTORY OWNERS * Don't break the seal of the safety valve, or try to adjust its setting to increase the boiler pressure. This endangers the safety, will cause over-pressure of the boiler and may cause boiler explosion with consequent injuries to personnel. * All automatic safety devices such as safety valve, pressure switch and low-water cut-off switches should be tested periodically to ensure they are in good working condition at all times. * If accident happens to a boiler or its auxiliary, owner must immediately stop using the boiler and report the accident to the Authority of Boilers and Pressure Vessels within 24 hours. The owner can be prosecuted and fined a maximum of $10,000 for not complying this requirement. 12. ENQUIRIES * For all enquiries please contact the BOILERS AND PRESSURE VESSELS DIVISION of the Labour Department. The address is as follows:─ 24/F., Western Harbour Centre 181 Connaught Road West Hong Kong Telephone: 2975 6428