Control Network
Distributed Control System and Programmable Logic Control



        Course Aim


               The aim of this training course is to build up the procedural and
        declarative knowledge required to be recognized by projects engineer that
        don not have past background of DCS or PLC. This will help them to
        supervise projects dealing with control systems with a strong background.
        In this course, the training cycle is divided in five steps that necessitate
        the cooperation between the instructor and the trainees. These steps are
        shown in figure below, they are summarized as follows:
            1. Define the knowledge and skills required to be developed.
            2. Define the elements of each knowledge or skill.
            3. Formulate a verbal phrase for the learning objective of each
               element.
            4. Choose an adequate instructional activity to present each element.
            5. Set up an indicator to measure the outcomes of the course and
               modify the training skills to adapt the vocational needs.



                                  Define
                                Knowledge                Determine
                                 & Skills                Elements




                            Measure                           Learning
                          & Correction                        Objectives

                                           Instruction
                                             Activity

                                            Training Cycle.




                                                                                    1
Distributed Control System and Programmable Logic Control



        Knowledge and Elements


             Illustrate DCS & PLC Benefits, Usage and History.
                    Overview of control system history.
                    Control system benefits and usage.
                    Types of control


             Develop Knowledge of DCS Components (Hardware & Software).
                    Infrastructure [Communication Bus, Interfaces, Controllers,
                      Gateways, RTU, Others].
                    Hardware and technologies.
                    Software [Configuration, Graphics, Alarming, Trending, System
                      Management, Others].


             Extend Knowledge of DCS installation and Maintenance.
                    Site Installation, Commissioning and Startup.
                    Diagnostics, Spares, Tools and Power Distribution.
                    Maintenance [Backup, Replacements and System Installation].


             Develop Knowledge of PLC Components.
                    PLC fundamentals.
                    PLC Logic.




                                                                                   2
Distributed Control System and Programmable Logic Control



        Table of Contents


                                           Section I
        Chapter 1      Introduction
        Chapter 2      Regulatory Control
                                           Section II
        Chapter 3      DCS Infrastructure
        Chapter 4      DCS Hardware
        Chapter 5      DCS Software
                                          Section III
        Chapter 6      Installation
        Chapter 7      Maintenance
        Chapter 8      Power Distribution
                                          Section IV
        Chapter 9      PLC Fundamentals.
        Chapter 10     Ladder Logic And SFC


                                         Appendices
              A        Electrical Relay Diagram And P&ID Symbols
              B        Serial Communication
              C        Networking
              D        Software Engineering




                                                                   3
Distributed Control System and Programmable Logic Control




                                                            4
Distributed Control System and Programmable Logic Control




                                                 Chapter 1
                                           Control Systems

        1.1 Automation System Structure


                 Although applications differ widely, there is little difference in the
        overall architecture of their control systems. Why the control system of a
        power plant is not sold also for automating a brewery depends largely on
        small differences (e.g. explosion-proof), on regulations (e.g. Food and
        Drug Administration) and also tradition, customer relationship.
        The ANSI/ISA standard 95 defines terminology and good practices
         Level
         4          Business Planning & Logistics             Enterprise Resource
                      Plant Production Scheduling             Planning
                     Operational Management, etc.


         Level              Manufacturing
         3                Operations & Control
                   Dispatching Production, Detailed Product   Manufacturing Execution
                     Scheduling, Reliability Assurance,...    System


         Level
         2,1,0
                  Batch         Continuous        Discrete    Control & Command
                  Control        Control          Control     System




        1.1.1 Large Control System Hierarchy


             Administration: Production goals, planning
             Enterprise: Manages resources, workflow, coordinates activities of
                 different sites, quality supervision, maintenance, distribution and
                 planning.




                                                                                        5
Distributed Control System and Programmable Logic Control



             Supervision: Supervision of the site, optimization, on-line
                operations. Control room, Process Data Base, logging (open loop)
             Group (Area): Control of a well-defined part of the plant. closed
                loop, except for intervention of an operator)
                   o Coordinates individual subgroups
                   o Adjusting set-points and parameters
                   o Commands several units as a whole
             Unit (Cell): Control (regulation, monitoring and protection) of a
                small part of a group (closed loop except for maintenance).
                   o Measure: Sampling, scaling, processing, calibration.
                   o Control: regulation, set-points and parameters
                   o Command: sequencing, protection and interlocking
             Field: Sensors & Actors, data acquisition, digitalization, data
                transmission, no processing except measurement correction and
                built-in protection.


            4     Planning, Statistics, Finances                               administration

            3     Workflow, Resources, Interactions                                enterprise


                                               SCADA                           supervision
                  Supervisory                 Supervisory
                                               =
            2
                                              And Data
                                              Control
                                              Acquisition



                  Group Control


                  Unit Control
            1
                  Field

                  Sensors                                                                           T
                  & Actors                                              A      V

            0     Primary
                  technology


                                   Figure 1.1 Large control system hierarchy


                                                                                                6
Distributed Control System and Programmable Logic Control



        1.1.2 Response Time and Hierarchical Level


             Planning                                                               ERP
             Level                                                         (Enterprise Resource
                                                                                 Planning)


                                                            MES
            Execution                                  (Manufacturing
            Level                                     Execution System)

                                                   SCADA
                                          (Supervisory Control
            Supervisory                   and Data Acquisition)
            Level
                                         DCS
                                     (Distributed
                                   Control System)
            Control
            Level
                                    PLC
                               (Programmable
                               Logic Controller)

                          ms      seconds     hours     days       weeks         month    years
                               Figure 1.2 Response Time And Hierarchical Level



        1.2 What is DCS?


             A DCS is an integrated set of modules with distributed functions.
                   – Multi-loop controllers (10’s-100’s) that connect to field
                        devices
                   – Supervisory coordinating controllers
                   – Multi-loop operator stations and engineering stations
                   – Servers for system data management
                   – Control network for intercommunication
                   – External connections




                                                                                                  7
Distributed Control System and Programmable Logic Control




                                                 Supervisory     Operator
                                        System                   Stations
           Remote Users                           Controller
                                  www   Server
                                                                            Engineering
                                                                              Station

                              Remote
                              Server

                    Control Network


                      Multi-loop
                      Controller

              Direct I/O Module




                                                                                   Other Industrial Devices




                                           Figure 1.3 DCS Hierarchy



             A DCS, throughout the whole system, must provide:
                       – Performance: control must be faster than the process.
                       – Determinism: control must always take the same time.
                       – Fault tolerance: redundancy; must fail to a known state.
                       – Security: must have access restrictions/controls.


                 Even though performance, ease of use, and interoperability are key
        evaluation criteria for any control system software package, the following
        is intended to provide the manufacturing engineer with a concise list of
        control system software evaluation criteria.
                 1. INTEROPERABILITY.
                 This refers to the interaction of all control system hardware and
                 software components at all levels.
                 2. INTERCONNECTIVITY.
                 This criterion is concerned with the transmission medium, which is
                 constrained by the network topology and how efficiently the
                 system’s components communicate with each other.

                                                                                                              8
Distributed Control System and Programmable Logic Control



               3. DISASTER PROCESSING.
               This component is defined by the efficiency with which the
               software provides the operator with system failure information and
               the ease at which the operator is permitted to bring the system back
               to maximum operation after system failure.
               4. DATABASE.
               This refers to the software’s ability to maintain the system’s
               database.
               5. PROCESSES/DATA.
               This criterion is concerned with the variety of processes and data
               that can be controlled by the SCADA package.
               6. DIAGNOSTICS.
               The SCADA package’s ability to assist in the resolution of system
               failures is evaluated by this diagnostic utility.
               7. SECURITY.
               This component is concerned with the levels of security provided
               by the software.
               8. MONITORING/CONTROL
               Monitoring of a given process in real-time and control of that
               process, within preset parameters, is evaluated by this criteria.
               9. ALARM MANAGEMENT/LOGGING.
               This is the category for detecting, annunciating, managing, and
               storing alarm conditions.
               10. STATISTICAL PROCESS CONTROL.
               This is the portion of the SCADA package that evaluates the
               process data. Production and quality is greatly effected by this data.
               12. OPERATOR INTERFACE.
               The graphical user interface (GUI) is evaluated using this criterion.



                                                                                   9
Distributed Control System and Programmable Logic Control



               13. TRENDING.
               The software’s ability to display trending plots using historical and
               current data is considered in this category.
               14. REPORT GENERATION.
               The production of logs and reports using current real-time data and
               data retrieved from historical files is evaluated under this category.


               Due to the advancements in computer technology and low cost, a
        personal computer-based distributed control system can be installed for a
        fraction of the cost required just a few years ago. However, prior to
        selecting any piece of DCS equipment, first examine the existing
        equipment, in particular the smart controllers, for network compatibility.
        Then, examine and select the software to be employed.


        1.3 What is PLC?


               A programmable logic controller, also called a PLC or
        programmable controller, is a computer-type device used to control
        equipment in an industrial facility. The kinds of equipment that PLCs can
        control are as varied as industrial facilities themselves. Conveyor
        systems, food processing machinery, auto assembly lines…you name it
        and there’s probably a PLC out there controlling it.
               In a traditional industrial control system, all control devices are
        wired directly to each other according to how the system is supposed to
        operate. In a PLC system, however, the PLC replaces the wiring between
        the devices. Thus, instead of being wired directly to each other, all
        equipment is wired to the PLC. Then, the control program inside the PLC
        provides the “wiring” connection between the devices.



                                                                                   10
Distributed Control System and Programmable Logic Control



               The control program is the computer program stored in the PLC’s
        memory that tells the PLC what’s supposed to be going on in the system.
        The use of a PLC to provide the wiring connections between system
        devices is called soft-wiring.
               Let's say that a push button is supposed to control the operation of
        a motor. In a traditional control system, the push button would be wired
        directly to the motor. In a PLC system, however, both the push button and
        the motor would be wired to the PLC instead. Then, the PLC's control
        program would complete the electrical circuit between the two, allowing
        the button to control the motor.




                                     Figure 1.4 PLC development



        A PLC basically consists of two elements:
             The central processing unit
             The input/output system


        1.3.1 The Central Processing Unit


               The central processing unit (CPU) is the part of a programmable
        controller that retrieves, decodes, stores, and processes information. It
        also executes the control program stored in the PLC’s memory. In

                                                                                 11
Distributed Control System and Programmable Logic Control



        essence, the CPU is the “brains” of a programmable controller. It
        functions much the same way the CPU of a regular computer does, except
        that it uses special instructions and coding to perform its functions. The
        CPU has three parts:
             The processor
             The memory system
             The power supply
        The processor is the section of the CPU that codes, decodes, and
        computes data. The memory system is the section of the CPU that stores
        both the control program and data from the equipment connected to the
        PLC. The power supply is the section that provides the PLC with the
        voltage and current it needs to operate.




                                  Figure 1.5 Microprocessor Hardware



        1.3.2 The input/output (I/O) system


               It is the section of a PLC to which all of the field devices are
        connected. If the CPU can be thought of as the brains of a PLC, then the
        I/O system can be thought of as the arms and legs. The I/O system is what
        actually physically carries out the control commands from the program
        stored in the PLC’s memory.

                                                                               12
Distributed Control System and Programmable Logic Control



        The I/O system consists of two main parts:
             The rack
               The rack is an enclosure with slots in it that is connected to the CPU.
             I/O modules
               I/O modules are devices with connection terminals to which the field
               devices are wired.


        Together, the rack and the I/O modules form the interface between the
        field devices and the PLC. When set up properly, each I/O module is both
        securely wired to its corresponding field devices and securely installed in
        a slot in the rack. This creates the physical connection between the field
        equipment and the PLC. In some small PLCs, the rack and the I/O
        modules come prepackaged as one unit.




                                        Figure 1.6 I/O Racks




                                                                                         13
Distributed Control System and Programmable Logic Control



        1.4 How is a DCS different from a PLC system?


                         DCS                                           PLC
        Mfr sells a complete system of integrated   Mfr sells some components; an SI
        components.                                 acquires others and engineers the system.
        Mfr supports the system.                    Mfr supports the components.
        On-line repair/ maintenance are the norm. Off-line repair/ maintenance are the norm.
        System management built-in.                 System management designed per project.
        Users expect to evolve/upgrade/expand a     System is a one-off project (like a house).
        system over 10/20/30 years.                 Upgrades / expansions are new projects.



        1.5 Redundancy and Fault Tolerance


        1.5.1 Redundancy
             Hardware redundancy
               – add extra hardware for detection or tolerating faults
             Software redundancy
               – add extra software for detection and possibly tolerating faults


        1.5.2 Fault Tolerance
             Error Detection
             Damage Confinement
             Error Recovery
             Fault Treatment


        1.5.2.1 Error Detection
             Ideal check
               – Check should be independent from system
               – Check fails if system crashes

                                                                                             14
Distributed Control System and Programmable Logic Control



             Acceptable check
               – Cost
               – Reasonable check, e.g. monitor rate of change
             diagnostics
               – Performed “by system on system components”
               – E.g. power-up diagnostics


        1.5.2.2 Damage Confinement
             Error might propagate and spread
             Identify boundaries to state beyond which no information exchange
               has occurred


        1.5.2.3 Error Recovery
             Backward recovery
               – State is restored to an earlier state
               – Requires checkpoints
               – Most frequently used
               – Recovery overhead
             Forward recovery
               – Try to make state error-free
               – Need accurate assessment of damage
               – Highly application-dependent


        1.5.2.4 Fault Treatment
             If transient fault: restart system, goto error-free state
             System repair
               – On-line, no manual intervention, (automatic)
               – Dynamic system reconfiguration
               – Spare (hot or cold)

                                                                             15
Distributed Control System and Programmable Logic Control



        1.5.2.5 Fault Coverage
             Measure of system’s ability to perform:
               – Fault detection
               – Fault location
               – Fault containment
               – (and/or fault recovery)
             Note:
               – Recovery implies that the system as a whole is operational
               – This does not imply that a “repair” occurred
               – E.g. duplex system with benign fault can recover to continue
               operation on one non-faulty processor


        1.5.2.6 Hardware Redundancy
             Passive (static)
               – Uses fault masking to hide occurrence of fault
               – No action from the system is required
               – E.g. voting
             Active (dynamic)
               – Uses comparison for detection and/or diagnoses
               – Remove faulty hardware from system => reconfiguration
             Hybrid
               – Combine both approaches
               – Masking until diagnostic complete
               – Expensive, but better to achieve higher reliability


        1.5.2.7 Passive Hardware Redundancy
             N-Modular Redundancy (NMR)
               – N independent modules replicate the same function


                                                                              16
Distributed Control System and Programmable Logic Control



             Parallelism
               – Results are voted on requirements: N >= 3
             TMR (Triple Modular Redundancy)


        1.5.2.8 Fault tolerant structures
               Fault tolerance allows continuing operation in spite of a limited
        number of independent failures. Fault tolerance relies on work
        redundancy.


        1.5.2.9 Static redundancy: 2 out of 3
             Workby of 3 synchronised and identical units.
               – All 3 units OK:                              Correct output.
               – 2 units OK:                                  Majority output correct.
               – 2 or 3 units failure:               Incorrect output.
               – Otherwise:                                   Error detection output.


                                                          Process input


                                      sync                 sync




                                                 Voter

                                                           Process output

                                   Figure 1.7 (2 out of 3) Redundancy

        1.5.2.10 Dynamic Redundancy
             Redundancy only activated after an error is detected.
            – Primary components (non-redundant)
            – Reserve components (redundancy), standby (cold/hot standby)


                                                                                         17
Distributed Control System and Programmable Logic Control




                                                       Input



                                   Primary unit                                     Standby unit



                                                  Switch
                                                                     Output

                                              Figure 1.8 Dynamic Redundancy

        1.5.2.11 Workby and Standby
                           Workby                      Hot standby                      Cold standby




                            sync                                 sync
                 on-line             workby            on-line           standby


                             =?



              Both computers are doing   Standby is not computing                    Standby is no operational
                  the same calculations   Error detection needed.                     Error detection needed.
                  at the same time       Easy switchover in case                      Long switchover period
                Comparison for easy              of failure.                           with loss of state info.
                   error detection.     Easy repair of reserve unit.                 No aging of reserve unit.
                Comparator needed.
             Non-redundant continuation
                    in case of failure?

                                              Figure 1.9 Workby and Standby

        1.5.2.12 Workby Fault-Tolerance for Integrity and Persistency
                                    input                                               input

                            synchronization                                        synchronization

                   Worker                         Co                    E Worker                      Co      E
                                               Worker
                                                -                       D                            Worker
                                                                                                      -       D
                              Matching                                               Matching

                                   Output                                               Output


                                             comparator                             commutator

             disjunctor


                                    output                                              output

                                  INTEGER                                            PERSISTENT

                           Figure 1.10 Workby Fault-Tolerance for Integrity and Persistency


                                                                                                                  18
Distributed Control System and Programmable Logic Control



        1.5.2.13 Hybrid Redundancy
        Mixture of workby (static redundancy) and standby (dynamic redundancy).


              work-    work-    work-    stand-   stand-
               by       by       by        by       by


                       voter


                               Reconfiguration     work-                work-   work-   stand-
                                                    by       failed      by      by       by
                               (self-purging
                               redundancy)

                                                             voter



                                        Figure 1.11 Hybrid Redundancy



        1.6 Microprocessor Control


               For simple programming the relay model of the PLC is sufficient.
        As more complex functions are used the more complex VonNeuman
        model of the PLC must be used. A computer processes one instruction at
        a time. Most computers operate this way, although they appear to be
        doing many things at once. Consider the computer components shown in
        Figure 1.12.




                           Figure 1.12 Simplified Personal Computer Architecture


                                                                                                 19
Distributed Control System and Programmable Logic Control



        Input is obtained from the keyboard and mouse, output is sent to the
        screen, and the disk and memory are used for both input and output for
        storage. (Note: the directions of these arrows are very important to
        engineers, always pay attention to indicate where information is flowing.)
        This figure can be redrawn as in Figure 1.13 to clarify the role of inputs
        and outputs.




                            Figure 1.13 An Input-Output Oriented Architecture



               In this figure the data enters the left side through the inputs. (Note:
        most engineering diagrams have inputs on the left and outputs on the
        right.) It travels through buffering circuits before it enters the CPU. The
        CPU outputs data through other circuits. Memory and disks are used for
        storage of data that is not destined for output. If we look at a personal
        computer as a controller, it is controlling the user by outputting stimuli on
        the screen, and inputting responses from the mouse and the keyboard.
               A PLC is also a computer controlling a process. When fully
        integrated into an application the analogies become;
             Inputs - the keyboard is analogous to a proximity switch input
               circuits - the serial input chip is like a 24Vdc input card

                                                                                   20
Distributed Control System and Programmable Logic Control



             Computer - the 686 CPU is like a PLC CPU unit
             Output circuits - a graphics card is like a triac output card
             Outputs - a monitor is like a light
             Storage - memory in PLCs is similar to memories in personal
               computers


        It is also possible to implement a PLC using a normal Personal Computer,
        although this is not advisable. In the case of a PLC the inputs and outputs
        are designed to be more reliable and rugged for harsh production
        environments.


        1.7 Role Play


        Each trainee should act a role play on the following:
            1. Automation system structure.
            2. What DCS and PLC and their differences?
            3. Redundancy and fault tolerance.




                                                                                21
Distributed Control System and Programmable Logic Control




                                         Chapter 2
                                  Regulatory Control

        2.1 Learning Objectives


         Introduce Regulatory Control.
         Understanding PID control.
         Differentiate between various control loops.


        2.2 Introduction


               Most of the applications of industrial control process used simple
        loops which regulated flows, temperatures, pressures and levels.
        Occasionally ratio and cascade control loops could be found. There are
        many benefits for using regulatory control. One of the most important is
        simply closer control of the process. Process control is one part of an
        overall control hierarchy that extends downwards to safety controls and
        other directly connected process devices, and upward to encompass
        process optimization and even higher business levels of control such as
        scheduling, inventory management.


               Most control engineers would recognize the form of response
        shown in figure 2.1. Actually the response could be determined by
        solving a differential equation. It is more important to have a good
        understanding of the physical response than to be able to predict the
        solution by solving the differential equation.




                                                                              22
Distributed Control System and Programmable Logic Control




                      Figure 2.1 Response of simple dynamic process to step input change

               Instrumentation, control and process engineers abstract the pictorial
        form of the process into an iconographic diagram called "Piping and
        Instrumentation Diagram", i.e. P&ID. Figure 2.2 is an example of the
        P&ID.




                             Figure 2.2 Control loop representation used on P&IDs.

               For description and analysis of a control loop, without referring to
        whether it is implemented with analog or digital hardware, a block
        diagram as shown in figure 2.3 is beneficial.




                   Figure 2.3 Simplified block diagram representation of process control loop.




                                                                                                 23
Distributed Control System and Programmable Logic Control



        2.3 PID Control


        2.3.1 Feedback Control


               The principle of feedback is one of the most intuitive concepts
        known. An action is taken to correct a less satisfactory situation then the
        results of the action are evaluated. If the situation is not corrected then
        further action takes place. Feedback control can be classified by the form
        of the controller output. One of the simplest forms of output is discrete
        form, also called on-off or two position control. An example of this is the
        household thermostat, which activates heating unit if the temperature is
        below the setting, or deactivates the unit if the temperature is above the
        setting.




                                      Figure 2.4 On-Off Control.

               The idea of two position control can be extended to multi-position
        control; an example is commercial air-conditioning refrigeration
        equipment which is operated by loading and unloading compressor
        cylinders. The ultimate extension is infinite number of positions which is
        called modulating control; an example is the process controller output
        that can drive a valve to any position between 0 and 100 percent, as
        shown in figure 2.5.

                                                                                24
Distributed Control System and Programmable Logic Control




                          Figure 2.5 Flow versus position, infinite position Control.



        2.3.2 Modes of Control


               Feedback controllers use one, two, or three methods to determine
        the controller output. These methods, called the modes of control,
        including the following:
         Proportional (P)
         Integral (I)
         Derivative (D)
        In general these modes can be used singly or in combination.


        2.3.2.1 Proportional Mode


               With a controller containing only the proportional mode, the
        controller output is proportional to the measurement value only. Neither
        history of the measurement value nor consideration to the rate of change
        is utilized. Adjustment, i.e. tuning, of the controller is simple because
        there is only one adjustment as shown in figure 2.6.




                                                                                        25
Distributed Control System and Programmable Logic Control




                   Figure 2.6 Relationship between input and output for proportional control.

               Figure 2.7 illustrates a proportional control system. The rate of
        fluid flow into the tank represents the load. To be in equilibrium, the
        outflow must be the same as the inflow. The outflow is achieved by a
        particular valve position where the fixed mechanism between the float,
        pivot and link attain.




                                        Figure 2.7 Proportional control.



        2.3.2.2 Integral Mode
               An integrator is the ideal device for automating the procedure for
        adjusting the controller output bias. It is called the automatic reset.


        2.3.2.3 Derivative Mode
               The derivative is used to anticipate the effect of load changes by
        adding a component to the controller output that is proportional to the rate
        of change of the measurement. See figure 2.8.

                                                                                                26
Distributed Control System and Programmable Logic Control




                                       Figure 2.8 PID control.



        2.3.3 Control Loop Structure


               For microprocessor control system, control strategy is configured
        by a series of software function blocks. Just like a set of hardware
        modules require interconnections to form a complete control system, a set
        of software function blocks also acquire interconnections, i.e. soft-wiring.


        Figure 2.9 shows a simple feedback loop with the software portion
        consists of three function blocks:
         An analog input block that causes the analog to digital converter to
            convert the incoming 4-20mA signal to an analogous value. The value
            is deposited in a memory register.
         A PID control block which obtains the measurement value from the
            analog input block and compares it with the setpoint then it executes a
            PID algorithm to calculate the output.
         An analog output block that obtains from the PID block the required
            valve position value. The value is converted by a digital to analog
            converter to 4-20mA signal.



                                                                                 27
Distributed Control System and Programmable Logic Control




                            Figure 2.9 Control loop hardware/software structure.



        2.3.4 Control Loop Tuning


               The power of PID control is that by good choice of control
        parameters the controller can be adjusted to provide the desired behavior
        on a wide variety of process applications. Determining acceptable values
        of these parameters is called tuning the controller. A good criterion for
        acceptable performance is the "quarter cycle decay" shown in figure 2.10.




                                 Figure 2.10 quarter cycle decay criterion



        Most loops are tuned by experimental techniques, i.e. trial and error.
        Figures 2.11 and 2.12 give a tuning map for adjusting control parameters.



                                                                                   28
Distributed Control System and Programmable Logic Control




                                   Figure 2.11 Gain and Reset effects.




                                     Figure 2.12 Derivative effects.

        2.4 Control Loop Types
        2.4.1 Ratio Control


               Figure 2.13 shows the P&ID of a process heater in which the fuel
        flow is measured and multiplied by the required air-to-fuel ratio; this
        results in the required air flow rate, which is introduced as a setpoint of
        the feedback controller. The required air-to-fuel ratio is automatically
        adjusted as the output of the stack O2 controller.



                                                                                29
Distributed Control System and Programmable Logic Control




                                      Figure 2.13 ratio Control..

        2.4.2 Cascade Control


               In figure 2.14 the temperature controller cascades a steam flow
        controller. The temperature controller would react to outlet temperature
        drop by increasing the setpoint of the steam flow controller, which in turn
        would increase the signal to the valve. The flow will quickly respond to
        increased demand from the temperature controller and thus reaching the
        desired setpoint of the outlet temperature stream.




                                     Figure 2.13 Cascade Control.

        2.4.3 Feedforward Control


               With feedforward control, the objective is to drive the controlling
        device from a measurement of the disturbance that is affecting the
        process, rather than from the process variable itself. In figure 2.14, the


                                                                                30
Distributed Control System and Programmable Logic Control



        application was analyzed the variation in process inlet temperature was
        the principle of disturbance. Hence, a feedforward controller is used to
        drive the fuel flow controller by sensing the inlet temperature.




                                   Figure 2.14 Feedforward Control.

        2.4.4 Selector (Override) Control


                There are several ways of using selector switches in control
        strategies. One way is to select the higher (or lower) of several
        measurement signals to pass the process variable to a feedback controller.
        For example, the highest of several process temperatures may be selected
        automatically to become the controlling temperature as shown in figure
        2.15.




                                     Figure 2.15 Override Control.



                                                                               31
Distributed Control System and Programmable Logic Control



        2.4.5 Split Range Control


               Split range control when one process variable such as plant inlet
        pressure is used to manage two different output devices such as plant
        bypass control valve and flow control loop for fractionation area. The 4-
        12 mA signal is used to control the flow control loop. If the plant cannot
        handle all incoming feed, the 12-20 mA signal control the plant bypass
        valve to direct extra feed to the outside of the plant.


        2.5 Role Play


        The trainees are required to play roles about:
            1. Introducing regulatory control.
            2. Introducing modes of control.
            3. Intruding control loop types.




                                                                                32
Distributed Control System and Programmable Logic Control




                                                            33
Distributed Control System and Programmable Logic Control




                                         Chapter 3
                                  DCS Infrastructure

        3.1 Learning Objectives


         Introduce system infrastructure interoperability and interconnectivity.
         Illustrate system components of level 2 control.


        3.2 Communication Bus




                                    Figure 3.1: Communication Bus

               The communication bus, i.e. the Nodebus, interconnects stations
        (Control Processors, Application Processors, Application Workstations,
        and so forth) in the system to form a process management and control
        node. Depending on application requirements, the node can serve as a
        single, stand-alone entity, or it can be configured to be part of a more
        extensive communications network.
               Operating in conjunction with the Nodebus interface electronics in
        each station, the Nodebus provides high-speed, redundant, peer-to-peer
        communications between the stations.
               The high speed, coupled with the redundancy and peer-to-peer
        characteristics, provide performance and security superior to that


                                                                               34
Distributed Control System and Programmable Logic Control



        provided by communication media used in conventional computer-based
        systems. Station interfaces to the Nodebus are also redundant, further
        ensuring secure communications between the stations. The Nodebus can
        be implemented in a basic, non-extended configuration or it can be
        extended through the use of Nodebus Extenders and Dual Nodebus
        Interface Extenders.


        3.2.1 Nodebus Interface


               The Nodebus Interface is a module which allows direct connection
        of a personal workstation (PW), with appropriate Nodebus connector card
        and software, to the Nodebus figure 3.2. In this configuration, the PW
        functions as a station on the node. The Nodebus Interface allows
        connection of a station application workstation hosting an Ethernet
        configuration to Nodebus. See figure 3.2.




                           Figure 3.2 Nodebus Interface Implementation (Typical)




                                                                                   35
Distributed Control System and Programmable Logic Control



               An Attachment Unit Interface (AUI) cable, connects the PW or an
        Ethernet hub configuration to the Nodebus via a Nodebus Interface. A
        coaxial cable (ThinNet) connects an Ethernet daisy chain configuration to
        the Nodebus via a Nodebus Extender. The Nodebus Interface is non-
        redundant, and can be used in any of the Nodebus configurations
        described.


        3.2.2 Dual Nodebus Interface


               The Dual Nodebus Interface (DNBI) is a module which allows
        direct connection of stations to the appropriate Nodebus. Connection
        between the DNBI and station is made via an AUI cable.


               For data transmission security, a separate (RS-423) control cable
        connects between the station and the DNBI to allow switching between
        the two redundant Nodebus cables. Switching of the Nodebus cables is
        controlled by the station, which transmits commands to the DNBI via the
        control cable. Figure 3.3 shows connection of a station to the Nodebus
        using a DNBI.




                                 Figure 3.3 Local Connection of Station



        3.2.3 Dual Nodebus Interface Extender


               The Dual Nodebus Interface Extender (DNBX) is functionally
        similar to the DNBI, but provides a greater cabling distance. The

                                                                               36
Distributed Control System and Programmable Logic Control



        principal transmission medium used is a coaxial Ethernet cable directly
        connected to the station end by a standard Ethernet transceiver. Figure 3.4
        remote connection of a station to the Nodebus using a DNBX.




                                Figure 3.4 Remote Connection of Station



        3.3 Control Processor


            The Control Processor performs regulatory, logic, timing, and
        sequential control together with connected:
               Fieldbus Modules (FBMs)
               Fieldbus Cluster I/O Cards (FBCs)
        It also performs data acquisition (via the Fieldbus Modules), alarm
        detection and notification, and may optionally serve as an interface for
        one or more Panel Display Stations.
        The non-fault-tolerant version of the Control Processor is a single-width
        processor module. The fault-tolerant version consists of two single-width
        processor modules.


        3.3.1 Enhanced Reliability


                The Control Processor offers optional fault- tolerance for enhanced
        reliability. The fault-tolerant control processor configuration consists of
        two parallel-operating modules with two separate connections to the
        Nodebus and to the Fieldbus.

                                                                                37
Distributed Control System and Programmable Logic Control



                  The two control processor modules, married together as a fault-
        tolerant pair, are designed to provide continued operation of the unit in
        the event of virtually any hardware failure occurring within one module
        of       the   pair.   Both   modules   receive     and   process   information
        simultaneously, and the modules themselves detect faults. One of the
        significant methods of fault detection is comparison of communication
        messages at the module external interfaces. Upon detection of a fault,
        self-diagnostics are run by both modules to determine which module is
        defective. The non-defective module then assumes control without
        affecting normal system operations.


                  To further ensure reliable communications, the fault-tolerant
        control processor performs error detection and address verification tests
        in its Nodebus and Fieldbus interfaces. For enhanced reliability during
        maintenance operations, the Control Processor is equipped with a
        recessed reset button. This feature provides for manually forcing a
        module power off and on (reboot) without removing the module from the
        enclosure.


        3.3.2 Diagnostics


                  The Control Processor uses three types of diagnostic tests to detect
        and/or isolate faults:
                 Power-up self-checks
                 Run-time and watchdog timer checks
                 Off-line diagnostics
                  Power-up self-checks are self-initiated when power is applied to
        the control processor. These checks perform sequential tests on the
        various control processor functional elements. Red and green indicators at

                                                                                     38
Distributed Control System and Programmable Logic Control



        the front of the control processor module reflect the successful (or non-
        successful) completion of the various phases of the control processor
        startup sequence.
                The run-time and watchdog timer checks provide continuous
        monitoring of control processor functions during normal system
        operations. The operator is informed of a malfunction by means of
        printed or displayed system messages.
                Off-line diagnostics are temporarily loaded into the system for the
        purpose of performing comprehensive tests and checks on various system
        stations and devices. Using the off-line diagnostics, a suspected fault in
        the control processor can be isolated and/or confirmed.


        3.4 Engineering Interface


                The   engineering     interface,   i.e.     Application   Processor,   is
        microprocessor-based application processor/file server stations. They
        perform two basic functions:
               As application processor (computer) stations, they perform
                computation intensive functions.
               As file server stations, they process file requests from tasks within
                themselves or from other stations. Bulk storage devices used with
                the Application Processors include floppy disk drives, hard disk
                drives, streaming tape drives, and CD-ROMs.


                The Application Processors operate in concert with other system
        stations (such as communication processors, workstation processors, and
        control processors), which provide the necessary means for data
        input/output and operator interfacing. A smaller system can utilize a
        single Application Processor, while a larger system can incorporate

                                                                                       39
Distributed Control System and Programmable Logic Control



        several Application Processors, each configured to perform specific
        functions. Some functions can be performed by individual Application
        Processors, while others can be shared by two or more Application
        Processors in the same network.
               For all models of the Application Processor, applications range
        from minimal functions, such as the storage of memory images, alarm
        events, and historical data, to larger-scale applications such as database
        management and program development.


        3.4.1 Application Processor Functions


               The following sections describe the major functions performed by
        the Application Processors.


        3.4.1.1 System and Network Management Functions

               The    Application     Processors     perform    system   management
        functions, which include collecting system performance statistics, data
        reconciliation,    performing      station   reloads,   providing   message
        broadcasting, handling all station alarms and messages, and maintaining
        consistent time and date in all system stations. The Application Processor
        also performs network management functions, which comprise that
        portion of system management functions which deal with the network.


        3.4.1.2 Database Management

               Database management involves the storage, manipulation, and
        retrieval of files containing data received and/or produced by the system.
        The Application Processors utilize the industry-standard Relational Data
        Base Management System.

                                                                                 40
Distributed Control System and Programmable Logic Control



        3.4.1.3 File Requests


               Each Application Processor contains a file manager, which
        manages all file requests associated with bulk memory attached to the
        Application Processor. Each Application Processor also supports a
        remote file system that allows tasks in one station to share files in
        another.


        3.4.1.4 Historical Data


               The Application Processors can be configured to contain the
        Historian function, which maintains a history of application messages and
        continuous and discrete I/O values. These values may represent any
        parameters such as measurements, setpoints, outputs, and status switches
        from stations that have been configured to collect data and send it to a
        Historian. In addition, the Historian computes and stores a history of
        averages, maximums, minimums, and other derived values. This
        information is maintained for display, reporting, and access by
        application programs. An archiving facility saves the data on removable
        media, where applicable.


               The Application Processors can be configured to maintain a history
        of errors, alarm conditions, and selected operator actions. The occurrence
        of errors, alarms, and events in other stations can be stored (for later
        review and analysis) by sending a message defining the event to the
        Historian in one or more Application Processors.




                                                                               41
Distributed Control System and Programmable Logic Control



        3.4.1.5 Graphic Display Support


                The Application Processor supports graphic displays by storing and
        retrieving display formats, by providing access to objects stored on the
        Application Processor, and by storing tasks which execute in a
        workstation processor. Application Processors not only provide storage of
        information and file management for displays, but also execute programs
        that perform display and trend service.


        3.4.1.6 Production Control Software


                Production control software represents a large range of packages
        that require varied Application Processor resources. The following is a
        list of packages provided:
               DBMS
               Historian
               Spreadsheet
               Physical Properties Library
               Mathematics Library
               BATCH
        The operation and performance of the production control software are
        determined by the particular Application Processor configuration.


        3.4.1.7 Configuration


                Configuration refers to the process of entering or selecting
        parameters to define what a software package does, or to define the
        environment for a software package. The Application Processors support
        configuration functions by providing bulk storage for configuration
        parameters and by executing some of the configuration processes.

                                                                                42
Distributed Control System and Programmable Logic Control



        3.4.1.8 Application Development Facilities


                Application development tools are provided to build programs for
        all system stations. These include tools to document, enter, translate, link,
        test, and maintain programs written in several programming languages.
        The Application Processor supports program development for all stations
        (workstation processors, control processors, and so forth).
                Assembly language, FORTRAN, and C programs can be written on
        the Application Processor using standard operating system tools. An
        optional package is available including text editors, debuggers, linkers,
        revision control, and compilers, plus execution statistics functions.


        3.4.1.9 User Application Program Execution


                The Application Processors also execute user application programs.
        These may be application packages such as special optimizations, test
        data collections, special data reductions, or other packages that you may
        have already developed. The allocation of resources reserved for user
        application varies with each Application Processor.


        3.4.2 Diagnostics


                The Application Processors utilize three types of diagnostic tests to
        detect and/or isolate faults:
               Power-up self-checks
               Run-time and watchdog timer checks
               Off-line diagnostics
                Power-up self-checks are initiated when power is applied to the
        Application Processor. These checks perform sequential tests on the

                                                                                  43
Distributed Control System and Programmable Logic Control



        various Application Processor functional elements. Any malfunction
        detected during the power-up self-checks is reported by means of
        messages printed or displayed on a directly connected printer or terminal.
                The run-time and watchdog timer checks provide continuous
        monitoring of Application Processor functions during normal system
        operations. For any processor model, you are informed of a malfunction
        by means of printed or displayed system messages. Off-line diagnostics
        are temporarily loaded into the system for the purpose of performing
        comprehensive tests and checks on various system stations and devices.
                Using the off-line diagnostics, a suspected fault in the Application
        Processor can be isolated and/or confirmed.


        3.4.3 Workstation Components


                The workstation components provide user interface to all System
        CRT display functions. A selection of workstation components is
        available for command and data entry, along with CRT pointer
        manipulation and control. These components interact with software
        resident in versions of the system Workstation Processors (WPs) and
        Application Workstation Processors (AWs). Many of these components
        (displays and keyboards) are "common" and allow interchangeability and
        simplicity in mixed technology configurations.
        Workstation components include:
               Alphanumeric Keyboard
               Annunciator and Annunciator/Numeric Keyboards
               Workstation Display (with/without Touchscreen)
               Mouse
               Trackball
               Industrial Pointing Device

                                                                                 44
Distributed Control System and Programmable Logic Control



               Workstation Processor or Application Workstation Processor
               Personal Workstation
               Modular Industrial Console
                Selection of the touch screen, mouse, trackball or industrial
        pointing device is required for picking display objects on the CRT. The
        touch screen has sufficient resolution for all functions normally
        associated with a process operator. Only the mouse or trackball provides
        the picking resolution necessary for engineer-related functions (for
        example, building graphic displays). The touch screen associated with
        Workstation Display and the annunciator type keyboards connects to a
        Graphics Controller Input Output (GCIO) interface unit located beneath
        the workstation display. The GCIO interfaces to the Workstation
        Processor and/or Application Workstation that provide secure, high-
        speed, bidirectional data flow. The alphanumeric keyboard and trackball
        connect together in a functional grouping via a serial communications
        link to the processors. Personal Workstations (PW) utilize separate serial
        communication links for alphanumeric keyboard and mouse/trackball.
        These buses allow a variety of component connections.




                               Figure 3.5 Table- Workstation Components.



                                                                                45
Distributed Control System and Programmable Logic Control



        3.4.3.1 Alphanumeric Keyboard


               The alphanumeric keyboard is used any time text is entered into the
        system. It consists of the full set of alphanumeric keys plus punctuation
        and special symbol keys laid out in the standard format, and a numeric
        data entry pad (with cursor control).




                                  Figure 3.6 Alphanumeric Keyboard

        3.4.3.2 Annunciator Keyboard


               The Annunciator Keyboard Figure 3.7 is an array of LED/switch
        pairs. It also contains a horn silence switch and a lamp-test switch. Each
        LED, under control of the processor software, may be ON, OFF, or
        FLASHING as determined by the process conditions. The LEDs, when
        used in conjunction with the unit's audible annunciator, form an effective
        means of calling a user's attention to specific areas of the system. The
        switch associated with each LED can be used to invoke any pre-
        configured displays or operator responses..




                                   Figure 3.7 Annunciator Keyboard

        3.4.3.3 Workstation Display with/without Touchscreen


               The workstation display is an analog cathode ray tube (CRT) color
        monitor supporting ultra-high resolution applications. The monitor is
        suitable for mounting onto a Modular Industrial Workstation or on a


                                                                                46
Distributed Control System and Programmable Logic Control



        desktop. The monitor can include a touchscreen optional feature. Figure
        3.8 shows the monitor with a tilt and swivel base mounted on the GCIO
        interface unit. The GCIO interface supports the touchscreen, annunciator
        and annunciator/ numeric keyboard, and audible horn options.




                                Figure 3.8 Table-Top Workstation Display

               The optional touch screen is bonded to the front surface of the CRT
        monitor. The user selects display objects by touching them on the screen.
        The touch screen senses the action and sends a data signal to the
        workstation processor's software indicating the position of the selection.
        3.4.3.4 Trackball


               The trackball is a stationary component that contains a rotatable
        sphere. The trackball can be located on a table top. Rotation of the sphere
        causes CRT pointer movement analogous to the mouse action. Buttons
        are also provided for user selections/manipulations. See Figure 3.9




                                          Figure 3.9 Trackball

        3.4.3.5 Modular Industrial Console

               Modular      Industrial     Consoles         provide        flexible   mounting
        arrangements of components. They allow users to configure centralized
        or distributed control centers tailored to the functional requirements of
        each interaction point in the plant. The modular console furniture

                                                                                            47
Distributed Control System and Programmable Logic Control



        described herein may incorporate a mix of equipment - console displays,
        input devices, processors, Fieldbus Modules, data storage devices, and so
        on. Alternately, only display-specific equipment can be incorporated.
        Modular Industrial Consoles (MICs) are ideal for supporting powerful
        multiple-screen, real-time display software interactions. This combination
        allows console resources to be optimally allocated to meet changing day-
        to-day needs.


        3.5 Operator Interface


               Operating in conjunction with human interface input/output
        components, the workstation processors serve as a link between the
        operator and other distributed processor modules. They receive graphic
        and textual information both stored internally or from application
        processors and generate signals to display the information on a
        workstation display. Display formats and data files are available from
        bulk storage. Live display information (distributed data objects) is
        available from any control -processor, or from shared system global data.
        The video information displayed can include free form combinations of
        text, graphic illustrations, charts, and control displays.
               The workstation processors display textual information as 80 text
        characters per line, with four fonts. The processors provide resizable and
        restackable windows. Displays for all of the workstation processors may
        also be developed using the system software running in a compatible
        personal computer.
        A workstation processor, together with its workstation monitor and input
        components, can be configured with combinations of peripherals to suit
        functions and user preferences.



                                                                               48
Distributed Control System and Programmable Logic Control



        3.6 Gateways


               The architecture of the DCS permits it to be connected to other
        foreign systems using a gateway module for adapting different
        communication protocols. See figure 3.10.




                                Figure 3.10 Field Automation Subsystem




        3.7 Role Play


        Each trainee should introduce one of the main components:
            1. Communication Bus
            2. Control Processor.
            3. Application Processor
            4. Operator Interfaces and Gateways




                                                                            49
Distributed Control System and Programmable Logic Control




                                         Chapter 4
                                     DCS Hardware

        4.1 Learning Objectives


         Define fieldbus communication.
         Illustrate system components of level 1 control.
         Demonstrate interconnection between different components.
         Develop knowledge base of foundation fieldbus technology.


        4.2 Fieldbus Modules


                Fieldbus Modules provide connection of digital I/O, analog I/O,
        and Intelligent Transmitters to control processors. There are two types of
        Fieldbus Modules: Main and Expansion. Some main modules can be
        expanded using an expansion module.


                A wide range of Fieldbus Modules is available to perform the
        signal conversion necessary to interface the control processor with field
        sensors and actuators.


        4.3 Fieldbus Interconnection


            The Control Processor is used in three different configurations, which
        provide broad flexibility in Fieldbus implementation:
               Local Fieldbus (Figure 4.1) - Used only within the enclosure.
                Fieldbus Modules attach directly to the redundant local bus.



                                                                                50
Distributed Control System and Programmable Logic Control




                                            Figure 4.1 Local Fieldbus

               Twinaxial (Dual-Conductor Coaxial) Fieldbus Extension (Figure
                4.2) - Using twinaxial cable, the Fieldbus can optionally extend
                outside of the enclosure. Fieldbus Modules attach to the extended
                bus through Fieldbus isolators. The twinaxial Fieldbus extension
                may be redundant.




                                Figure 4.2 Twinaxial Fieldbus Extension

               Fiber Optic Fieldbus Extension (Figure 4.3) - The fiber optic
                Fieldbus can optionally extend the distance as well as add
                application versatility and security.




                                Figure 4.3 Fiber Optic Fieldbus Extension




                                                                               51
Distributed Control System and Programmable Logic Control



        All three Fieldbus configurations use serial data communication
        complying with Electronic Industrial Association (EIA) Standard RS-485.


        4.4 Cluster I/O Subsystem Interfacing


               The Control Processor interfaces with the Fieldbus Cluster
        Input/Output Subsystem that consists of the Fieldbus, a multi-slot chassis
        configuration of a Fieldbus Processor, analog/digital Fieldbus Cards
        (FBCs), and power supply and power monitor card. These Cluster I/O
        subsystems meet the needs of applications where a high number of
        channels per card are required. Figure 4.4 shows a typical twinaxial
        Fieldbus configuration.




                  Figure 4.4 Twinaxial Fieldbus Cluster I/O Subsystem Interface Configuration


        4.5 Fieldbus Cluster I/O Subsystem


               The Fieldbus Cluster Input/Output Subsystem provides full support
        for analog measurement, digital sensing, and analog or discrete control
        capabilities. The Subsystem integrates with the Control Processor or
        Personal Workstation via the Fieldbus, and includes a multi-slot chassis
        configuration made up of a Fieldbus Processor, Analog/Digital Fieldbus
        Cards (FBC), subsystem main power supply, and power monitor card.



                                                                                                52
Distributed Control System and Programmable Logic Control



                The Fieldbus Cluster I/O Subsystem is configurable, gathering
        analog measurements, while simultaneously handling analog and digital
        input and output channels. The Fieldbus Cluster I/O Subsystem is offered
        in both non-redundant and redundant configurations. Each in a redundant
        pair is individually addressable on the Fieldbus with a unique logical
        address. In a redundant configuration, the FBPs provide switchover from
        the primary FBP to the redundant FBP and back again automatically. The
        FBCs are suitable in applications where a high number of channels per
        card are required. They are ideal for non-isolated and isolated input signal
        gathering and data acquisition systems where high quantities of "points
        per cluster" areas are desired. The FBCs may be optionally connected as
        redundant pairs. Various input cards are available with one of the
        following three levels of isolation:
               Non-isolated - Each channel is referenced to ground and the card
                itself is referenced to ground.
               Group-isolated - Electrically separate card-to-card but not channel-
                to-channel on the same card.
               Isolated - Each channel is electrically separated from any other
                channel, card, group, building, site, etc.


        4.6 Fieldbus Processor


                The Fieldbus Processor (FBP) module provides communication
        between the Fieldbus Cards (FBCs) and the Control Processor. Optionally
        available is redundancy for the FBP module. Each FBP module is
        individually addressable via the Fieldbus. If the primary FBP fails or is
        taken off-line, the secondary FBP automatically assumes control. It
        remains in control until the primary FBP returns on-line (figure 4.5).



                                                                                 53
Distributed Control System and Programmable Logic Control




                                      Figure 4.5 FBP Overview

        4.7 Fieldbus Cards


               The Fieldbus Cards support a variety of analog and digital I/O
        signals. The FBCs convert electrical I/O signals used by field devices to
        permit communication with these devices via the Fieldbus.
               The FBCs can be connected in a redundant configuration via the
        hardware. The redundant FBCs must be in adjacent slots and they are
        connected via a hardware adapter at the interface to the field devices. In
        an FBC redundant configuration, the FBP determines which FBC of the
        redundant pair is to supply the data to the Control Processor. This is done
        in the software by a predetermined set of conditions.


        4.7.1 Analog FBCS


               The analog FBCs support analog signal types and control functions
        equipped with accurate signal conditioning circuitry, the analog cards
        interface between process sensors and actuators.
               To input an analog voltage (into DCS) the continuous voltage value
        must be sampled and then converted to a numerical value by an A/D

                                                                                54
Distributed Control System and Programmable Logic Control



        converter. Figure 4.6 shows a continuous voltage changing over time.
        There are three samples shown on the figure. The process of sampling the
        data is not instantaneous, so each sample has a start and stop time. The
        time required to acquire the sample is called the sampling time. A/D
        converters can only acquire a limited number of samples per second. The
        time between samples is called the sampling period T, and the inverse of
        the sampling period is the sampling frequency (also called sampling rate).
        The sampling time is often much smaller than the sampling period.




                                 Figure 4.6 Sampling an analog voltage

               Analog outputs are much simpler than analog inputs. To set an
        analog output an integer is converted to a voltage. This process is very
        fast, and does not experience the timing problems with analog inputs.
        But, analog outputs are subject to quantization errors. Figure 4.7 gives a
        summary of the important relationships. These relationships are almost
        identical to those of the A/D converter. Assume we are using an 8 bit D/A
        converter that outputs values between 0V and 10V. We have a resolution
        of 256, where 0 results in an output of 0V and 255 results in 10V. The
        quantization error will be 20mV. If we want to output a voltage of
        6.234V, we would specify an output integer of 159, this would result in
        an output voltage of 6.235V. The quantization error would be 6.235V-
        6.234V=0.001V. The current output from a D/A converter is normally
        limited to a small value, typically less than 20mA.

                                                                                55
Distributed Control System and Programmable Logic Control




                                       Figure 4.7 D/A converter



        4.7.2 Digital FBCS


               The digital FBCs consist of 32- and 64-channel types. Inputs can
        be either voltage monitoring or contact sensing.
               Contact inputs must convert a variety of logic levels to the 5Vdc
        logic levels used on the data bus. This can be done with circuits similar to
        figure 4.8. Basically the circuits condition the input to drive an
        optocoupler. This electrically isolates the external electrical circuitry from
        the internal circuitry. Other circuit components are used to guard against
        excess or reversed voltage polarity.




                                   Figure 4.8 Contact input circuitry.

               Contact outputs must convert the 5Vdc logic levels on the DCS
        data bus to external voltage levels. This can be done with circuits similar
        to figure 4.9. Basically the circuits use an optocoupler to switch external
        circuitry. This electrically isolates the external electrical circuitry from




                                                                                   56
Distributed Control System and Programmable Logic Control



        the internal circuitry. Other circuit components are used to guard against
        excess or reversed voltage polarity.




                                   Figure 4.9 Contact output circuitry.




        4.8 Other Modules


             0 to 20 mA Input/Output Interface
             Pulse Input, 0 to 20 mA Output Interface
             Thermocouple/ Millivolt Input Interface
             RTD Input Interface
             High Power Contact/dc Input/Output Interface


        4.9 Foundation Fieldbus Technology


               FOUNDATION fieldbus is an all-digital, serial, two-way
        communications system that serves as the base-level network in a plant or
        factory automation environment.




                                Figure 4.10 Foundation Fieldbus Network


                                                                                57
Distributed Control System and Programmable Logic Control




                        Figure 4.11 Historical development of field devices technology.



                It's ideal for applications using basic and advanced regulatory
        control, and for much of the discrete control associated with those
        functions. Two related implementations of FOUNDATION fieldbus have
        been introduced to meet different needs within the process automation
        environment. These two implementations use different physical media
        and communication speeds.
               H1 works at 31.25 Kbit/sec and generally connects to field devices.
                It provides communication and power over standard twisted-pair
                wiring. H1 is currently the most common implementation and is
                therefore the focus of these courses.
               HSE (High-speed Ethernet) works at 100 Mbit/sec and generally
                connects input/output subsystems, host systems, linking devices,
                gateways, and field devices using standard Ethernet cabling. It
                doesn't currently provide power over the cable, although work is
                under way to address this.




                                      Figure 4.12 Field Device Capacity.


                                                                                          58
Distributed Control System and Programmable Logic Control



               Conventional analog and discrete field instruments use point-to-
        point wiring: one wire pair per device. They're also limited to carrying
        only one piece of information -- usually a process variable or control
        output -- over those wires. As a digital bus, FOUNDATION fieldbus
        doesn't have those limitations.


             Multidrop wiring. FOUNDATION fieldbus will support up to 32
               devices on a single pair of wires (called a segment) -- more if
               repeaters are used. In actual practice, considerations such as power,
               process modularity, and loop execution speed make 4 to 16 devices
               per H1 segment more typical.


        That means if you have 1000 devices -- which would require 1000 wire
        pairs with traditional technology -- you only need 60 to 250 wire pairs
        with FOUNDATION fieldbus. That's a lot of savings in wiring (and
        wiring installation).




                                  Figure 4.12 Fieldbus wiring diagram.




                                                                                 59
Distributed Control System and Programmable Logic Control



             Multivariable instruments. That same wire pair can handle
               multiple variables from one field device. For example, one
               temperature transmitter might communicate inputs from as many as
               eight sensors -- reducing both wiring and instrument costs.


        Other benefits of reducing several devices to one can include fewer pipe
        penetrations and lower engineering costs.


             Two-way communication. In addition, the information flow can
               now be two-way. A valve controller can accept a control output
               from a host system or other source and send back the actual valve
               position for more precise control. In an analog world, that would
               take another pair of wires.
             New types of information. Traditional analog and discrete devices
               have no way to tell you if they're operating correctly, or if the
               process information they're sending is valid.


        But FOUNDATION fieldbus devices can tell you if they're operating
        correctly, and if the information they're sending is good, bad, or
        uncertain. This eliminates the need for most routine checks -- and helps
        you detect failure conditions before they cause a major process problem.


             Control in the field. FOUNDATION fieldbus also offers the
               option of executing some or all control algorithms in field devices
               rather than a central host system. Depending on the application,
               control in the field may provide lower costs and better performance
               -- while enabling automatic control to continue even if there's a
               host-related failure.


                                                                               60
Distributed Control System and Programmable Logic Control



        FOUNDATION fieldbus is covered by standards from three major
        organizations:
               ANSI/ISA 50.02
               IEC 61158
               CENELEC EN50170:1996/A1


                The technology is managed by the independent, not-for-profit
        Fieldbus Foundation, whose 150+ member companies include users as
        well as all major process automation suppliers around the globe.
        Some suppliers have even donated fieldbus-related patents to the Fieldbus
        Foundation to encourage wider use of the technology by all Foundation
        members.


                Interoperability simply means that FOUNDATION fieldbus
        devices and host systems can work together while giving you the full
        functionality of each component.


        4.10 Role Play


        Each trainee should introduce one of the main components:
            5. Fieldbus Module and Interconnection
            6. Fieldbus Processor and Clusters.
            7. Foundation Fieldbus technology




                                                                              61
Distributed Control System and Programmable Logic Control




                                         Chapter 5
                                      DCS Software

        5.1 Learning objectives


         To be familiar with main software components of DCS.
         Understand main tasks for each application.


        5.2 Standard Application Packages
        5.2.1 System Management
        Features include:
               Display of equipment information for the station and its associated
                input/output devices, buses, and printers.
               Capability for change actions directed to the associated equipment.
               Processing of station alarm conditions and messages.
        5.2.2 Database Management
        Features include:
               Storage, retrieval, and manipulation of system data files.
               A run-time license for the embedded use of the Relational Database
                Management System.
               A spreadsheet package.


        5.2.3 Historian
        Features include:
               Maintenance     of   a   history   of   values   for   process-related
                measurements that have been configured for retention by the
                Historian.



                                                                                   62
Distributed Control System and Programmable Logic Control



               Maintenance of a history of application messages that have been
                sent to the Historian.
               Maintenance of a history of alarms and error conditions which
                generate messages for the Historian.
               Access to all Historian data by display and report application
                programs.


        5.2.4 View Display Manager
        Features include:
               Presentation of the operating environment.
               Setting of the overall operating environment according to the type
                of user. Process engineers, process operators, and software
                engineers have access to specialized functions and databases suited
                to their specific requirements and authorizations.
               Dynamic and interactive process graphics.
               Display and processing of current process alarms.
               Group and default displays for control blocks.
               Execution of embedded trending within displays.


        5.2.5 Draw Display Builder
        Features include:
               Graphical display configuration for viewing and control of process
                operation.
               Access to graphical object palettes allowing easy inclusion of
                pumps, tanks, valves, ISA symbols, and similar complex objects.
               Ready modification of existing displays using a mouse pointer,
                menu items, and quick-access toolbars.
               Association of process variables with objects in the displays.



                                                                                  63
Distributed Control System and Programmable Logic Control



               Dynamic variation of object attributes such as fill level, color,
                position, size and visibility with changes in the associated process
                variable.
               Inclusion of operator control elements such as pushbuttons and
                sliders into displays.
               A library of faceplates which may be configured by simply
                specifying the compound and block name of the block to which the
                faceplate is to be connected.


        5.3 Alarm System




                                         Figure 5.1 Alarm manger

                Alarm Manager provides an easy-to-use graphical interface of
        preconfigured alarm displays for viewing and quickly responding to
        process alarm conditions. The alarm display windows present alarm
        messages initiated by the control blocks and related to digital input, state
        change, absolute analog, deviation, rate of change, device status
        mismatch, and other alarm conditions.
        Accessible from any environment, the Alarm Manager Display windows
        provide:




                                                                                 64
Distributed Control System and Programmable Logic Control



               Quick, easy access to the most recent alarm messages via the Most
                Recent Alarm display or Current Alarm display
               Alarm status and value information dynamically updated from the
                control station
               Color-coded priority and status indicators that allow you to quickly
                focus in on critical alarms
               Summary displays for different views of the alarm database based
                on alarm status
               An historical list of alarms
               The capability to view subsets of alarms based on specific user-
                defined criteria
               The capability to silence or temporarily mute workstation and
                annunciator horns.
               Secured access to alarming functions dependent on user or system
                responsibility
        This set of resizable alarm displays providing a variety of current and
        historic views of the process alarm database includes:
               A multi-page list of all the current alarms
               A single page of the most recent, active, unacknowledged alarms
                with dynamically updating value and status fields
               Three summary displays specific to alarm status also with updating
                values and statuses:
                   o   all active, unacknowledged alarms
                   o   all unacknowledged alarms that have returned to normal
                   o   all active, acknowledged alarms
               A list of historized alarms related to the selected historian database
               An operations display for silencing horns, temporarily muting
                horns, changing environments



                                                                                    65
Distributed Control System and Programmable Logic Control



        These displays allow you to respond to alarm conditions, filter and
        analyze specific alarm data, and maintain alarm message files for
        reporting purposes.
            The Process or Alarm button in the Display Manager (DM) window
        indicates    the     presence   of    alarms    (both   acknowledged   and
        unacknowledged) and provides access to Alarm Manager Displays.
        Initially, the Current Alarm Display (CAD) appears and the other
        displays are easily accessible from the CAD via its default Displays
        menu:
               Most Recent Alarm display (MRA)
               New Alarm display (NEWALM)
               Unacknowledged Alarms display (UNACK)
               Acknowledged Alarms display (ACKALM)
               Alarm History display (AHD)
               Operations display (OPR)
        These easy-to-use displays support the following features:
               A pre-configured number of alarms per screen or page
               Pre-configured alarm message information and formatting per
                alarm type
               A status area for indication of current Alarm Manager and display
                status, such as horns muted, match active, display paused, initial
                call-up time
               Buttons for responding to alarm conditions, such as acknowledging
                or clearing alarms, and for accessing additional alarm information
                and process displays
               Pull-down menus for editing, viewing, and filing functions
               A pull-down menu for accessing other displays
               Pop-up menus for quick access to commonly used functions



                                                                                66
Distributed Control System and Programmable Logic Control



               A scroll bar and Go To Page option for moving easily through the
                alarm list
        Although a preconfigured set of alarm displays is provided, many aspects
        of the displays and alarm message content are user configurable to
        accommodate different process control applications and operational
        needs. See the section on Alarm/Display Manager Configurator.


        5.4 Historian


                The Historian collects, stores, processes, and archives process data
        from the control system to provide data for trends, Statistical Process
        Control (SPC) charts, logs, reports, spreadsheets, and application
        programs. The Historian software is an easy-to-use data collection tool
        that allows the user to organize and enforce a plant data collection
        philosophy. The Historian provides extensive data collection and
        management functions, and data display functions for use by process
        engineers or operators.
                Typical historical data are process analog and/or digital variables
        (points). The Historian can also collect and display application generated
        messages. You can use the Historian to collect data in support of the
        following production control functions:
               Cost accounting
               Equipment performance analysis
               Historical trending
               Information retrieval
               Inventory management
               Legal record maintenance
               Lost time analysis


                                                                                 67
Distributed Control System and Programmable Logic Control



               Maintenance reporting
               Material accounting
               Process analysis
               Production reporting
               Quality control
        The Historian can:
               Retrieve variables from process databases or accept data from
                production control databases maintained by user application
                programs.
               Perform built-in calculations on the collected data.
               Store calculated (reduced) data in a real time, relational database.
        Application software in a plant-wide control system can access the
        Historian database to obtain historical data for process control, production
        control, and management information reporting.
        You can use SPC chart displays of Historian data to monitor process
        variables on-line via the Statistical Process Control Package (SPCP).
        You can build displays for trending historical data via the Display Builder
        and Display Configurator with Trending software.
        Using the Report Writer, you can generate detailed reports of historical
        data for management information.
        Examples of Industrial Software that interface with the Historian are:
               Batch Plant Management
               Data Validator
               Display Manager
               Display Configurator with Trending
               Object Manager (for process data histories)
               Operator Action Journal
               Operator Message Interface
               Real-Time Data Base Manager

                                                                                   68
Distributed Control System and Programmable Logic Control



               Spreadsheet
               Statistical Process Control Package
               System Monitor
               Report Writer


        5.5 Draw




                                          Figure 5.2 Draw

                Draw is a display builder and configurator that allow you to create
        and maintain dynamically updating process displays. Displays can
        represent the plant, a process area or a detailed portion of the process.
        You can draw basic objects using Draw's toolbars, menu items and
        shortcut keys. You assign graphic attributes such as color and line style to
        the objects, and then configure them to reflect process variable changes or
        operator actions. Draw includes numerous palettes of objects such as
        operator buttons, pumps, tanks, pipes, motors, valves and ISA symbols.
        You can also create your own palettes for storing complex objects and
        company-standard symbols. Displays can include faceplates, trends and
        bitmapped images. You can easily edit your displays to reflect changes in
        the process control scheme or to maximize operating efficiency and
        security.


                                                                                    69
Dcs course
Dcs course
Dcs course
Dcs course
Dcs course
Dcs course
Dcs course
Dcs course
Dcs course
Dcs course
Dcs course
Dcs course
Dcs course
Dcs course
Dcs course
Dcs course
Dcs course
Dcs course
Dcs course
Dcs course
Dcs course
Dcs course
Dcs course
Dcs course
Dcs course
Dcs course
Dcs course
Dcs course
Dcs course
Dcs course
Dcs course
Dcs course
Dcs course
Dcs course
Dcs course
Dcs course
Dcs course
Dcs course
Dcs course
Dcs course
Dcs course
Dcs course
Dcs course
Dcs course
Dcs course
Dcs course
Dcs course
Dcs course
Dcs course
Dcs course
Dcs course
Dcs course
Dcs course
Dcs course
Dcs course
Dcs course
Dcs course
Dcs course
Dcs course
Dcs course
Dcs course
Dcs course
Dcs course
Dcs course
Dcs course
Dcs course
Dcs course
Dcs course
Dcs course
Dcs course
Dcs course

Más contenido relacionado

La actualidad más candente

Distributed Control System (DCS) Notes
Distributed Control System (DCS) NotesDistributed Control System (DCS) Notes
Distributed Control System (DCS) Notes
Raj Nayak
 
Plc example presentation
Plc example presentationPlc example presentation
Plc example presentation
Roshit Kadiru
 
Foundation fieldbus technology
Foundation fieldbus technologyFoundation fieldbus technology
Foundation fieldbus technology
Mohamed A Hakim
 

La actualidad más candente (20)

Distributed Control System Basics
Distributed Control System BasicsDistributed Control System Basics
Distributed Control System Basics
 
Classic control in industry
Classic control in industry Classic control in industry
Classic control in industry
 
PLC - Programmable Logic Controller
PLC - Programmable Logic ControllerPLC - Programmable Logic Controller
PLC - Programmable Logic Controller
 
Distributed Control System (DCS) Notes
Distributed Control System (DCS) NotesDistributed Control System (DCS) Notes
Distributed Control System (DCS) Notes
 
Dcs operator training
Dcs operator trainingDcs operator training
Dcs operator training
 
ppt on PLC automation
ppt on PLC automationppt on PLC automation
ppt on PLC automation
 
Plc example presentation
Plc example presentationPlc example presentation
Plc example presentation
 
Distributed control system presentation
Distributed control system presentationDistributed control system presentation
Distributed control system presentation
 
programmable logic controller presentation
programmable logic controller presentationprogrammable logic controller presentation
programmable logic controller presentation
 
DCS Introduction
DCS IntroductionDCS Introduction
DCS Introduction
 
Troubleshooting in plc
Troubleshooting in plcTroubleshooting in plc
Troubleshooting in plc
 
Plc presentation
Plc presentation Plc presentation
Plc presentation
 
Fieldbus wiring guide
Fieldbus wiring guideFieldbus wiring guide
Fieldbus wiring guide
 
Allenbradley Control Logix PLC Network Architecture
Allenbradley Control Logix PLC Network  ArchitectureAllenbradley Control Logix PLC Network  Architecture
Allenbradley Control Logix PLC Network Architecture
 
Plc basics
Plc   basicsPlc   basics
Plc basics
 
YOKOGAWA CENTUM CS 3000 R3
YOKOGAWA CENTUM CS 3000 R3YOKOGAWA CENTUM CS 3000 R3
YOKOGAWA CENTUM CS 3000 R3
 
DCS - Distributed Control System
DCS - Distributed Control System DCS - Distributed Control System
DCS - Distributed Control System
 
Foundation fieldbus technology
Foundation fieldbus technologyFoundation fieldbus technology
Foundation fieldbus technology
 
Dcs functional block diagrams
Dcs functional block diagramsDcs functional block diagrams
Dcs functional block diagrams
 
PLC Basic
PLC BasicPLC Basic
PLC Basic
 

Destacado

A CASE STUDY OF THE BOILER ACCIDENT, Process Safety Management System
A CASE STUDY OF THE BOILER ACCIDENT, Process Safety Management SystemA CASE STUDY OF THE BOILER ACCIDENT, Process Safety Management System
A CASE STUDY OF THE BOILER ACCIDENT, Process Safety Management System
Hashim Badat
 
Matematica slides tx2
Matematica slides tx2Matematica slides tx2
Matematica slides tx2
educacao f
 

Destacado (13)

DCS PRESENTATION
DCS PRESENTATIONDCS PRESENTATION
DCS PRESENTATION
 
When is a SIL Rating of a Valve Required?
When is a SIL Rating of a Valve Required?When is a SIL Rating of a Valve Required?
When is a SIL Rating of a Valve Required?
 
A CASE STUDY OF THE BOILER ACCIDENT, Process Safety Management System
A CASE STUDY OF THE BOILER ACCIDENT, Process Safety Management SystemA CASE STUDY OF THE BOILER ACCIDENT, Process Safety Management System
A CASE STUDY OF THE BOILER ACCIDENT, Process Safety Management System
 
107 basic instrumentation
107 basic instrumentation 107 basic instrumentation
107 basic instrumentation
 
Safe Operation and Explosions in Boilers
Safe Operation and Explosions in BoilersSafe Operation and Explosions in Boilers
Safe Operation and Explosions in Boilers
 
Valves used in industry
Valves used in industryValves used in industry
Valves used in industry
 
Matematica slides tx2
Matematica slides tx2Matematica slides tx2
Matematica slides tx2
 
Boiler explosion at exxon mobil singapore
Boiler explosion at exxon mobil singaporeBoiler explosion at exxon mobil singapore
Boiler explosion at exxon mobil singapore
 
Caldeiras
CaldeirasCaldeiras
Caldeiras
 
Boiler Maintenance & Safety
Boiler Maintenance & SafetyBoiler Maintenance & Safety
Boiler Maintenance & Safety
 
Basic instrumentation
Basic instrumentationBasic instrumentation
Basic instrumentation
 
Basics Of Instrumentation
Basics Of InstrumentationBasics Of Instrumentation
Basics Of Instrumentation
 
DCS Or PLC
DCS Or PLCDCS Or PLC
DCS Or PLC
 

Similar a Dcs course

Asset Insight Manager Introduction 2014 (2)
Asset Insight Manager Introduction 2014 (2)Asset Insight Manager Introduction 2014 (2)
Asset Insight Manager Introduction 2014 (2)
Dean Bishop
 
Introdunction to Network Management Protocols - SNMP & TR-069
Introdunction to Network Management Protocols - SNMP & TR-069Introdunction to Network Management Protocols - SNMP & TR-069
Introdunction to Network Management Protocols - SNMP & TR-069
William Lee
 
Intel_Intelligent Solutions for Military and Aerospace
Intel_Intelligent Solutions for Military and AerospaceIntel_Intelligent Solutions for Military and Aerospace
Intel_Intelligent Solutions for Military and Aerospace
Işınsu Akçetin
 
Systems Lifecycle workbook
Systems Lifecycle workbookSystems Lifecycle workbook
Systems Lifecycle workbook
MISY
 
Time to Rethink Process Automation Systems
Time to Rethink Process Automation SystemsTime to Rethink Process Automation Systems
Time to Rethink Process Automation Systems
ARC Advisory Group
 

Similar a Dcs course (20)

Dcscourse doc
Dcscourse docDcscourse doc
Dcscourse doc
 
PID Advances in Industrial Control
PID Advances in Industrial ControlPID Advances in Industrial Control
PID Advances in Industrial Control
 
Analysis and Control of Computing Systems
Analysis and Control of Computing SystemsAnalysis and Control of Computing Systems
Analysis and Control of Computing Systems
 
Lecture 6 & 7.pdf
Lecture 6 & 7.pdfLecture 6 & 7.pdf
Lecture 6 & 7.pdf
 
Avanceon Plant PAx Process
Avanceon Plant PAx Process Avanceon Plant PAx Process
Avanceon Plant PAx Process
 
PlantPAx Process
PlantPAx ProcessPlantPAx Process
PlantPAx Process
 
Idc Ei Smart Buildings Maturity Model Webcast 4 3 12 Slides
Idc Ei Smart Buildings Maturity Model Webcast 4 3 12 SlidesIdc Ei Smart Buildings Maturity Model Webcast 4 3 12 Slides
Idc Ei Smart Buildings Maturity Model Webcast 4 3 12 Slides
 
Text-DISA_Review_Questions.docx
Text-DISA_Review_Questions.docxText-DISA_Review_Questions.docx
Text-DISA_Review_Questions.docx
 
Text-DISA_Review_Questions.docx
Text-DISA_Review_Questions.docxText-DISA_Review_Questions.docx
Text-DISA_Review_Questions.docx
 
Network Management in WSN
Network Management in WSNNetwork Management in WSN
Network Management in WSN
 
MEASURE Evaluation Data Quality Assessment Methodology and Tools
MEASURE Evaluation Data Quality Assessment Methodology and ToolsMEASURE Evaluation Data Quality Assessment Methodology and Tools
MEASURE Evaluation Data Quality Assessment Methodology and Tools
 
Asset Insight Manager Introduction 2014 (2)
Asset Insight Manager Introduction 2014 (2)Asset Insight Manager Introduction 2014 (2)
Asset Insight Manager Introduction 2014 (2)
 
TechEd 2012 NA - MGT332 - fighting fire to the cloud!
TechEd 2012 NA - MGT332 - fighting fire to the cloud!TechEd 2012 NA - MGT332 - fighting fire to the cloud!
TechEd 2012 NA - MGT332 - fighting fire to the cloud!
 
Introdunction to Network Management Protocols - SNMP & TR-069
Introdunction to Network Management Protocols - SNMP & TR-069Introdunction to Network Management Protocols - SNMP & TR-069
Introdunction to Network Management Protocols - SNMP & TR-069
 
Audit of it infrastructure
Audit of it infrastructureAudit of it infrastructure
Audit of it infrastructure
 
Intel_Intelligent Solutions for Military and Aerospace
Intel_Intelligent Solutions for Military and AerospaceIntel_Intelligent Solutions for Military and Aerospace
Intel_Intelligent Solutions for Military and Aerospace
 
Systems Lifecycle workbook
Systems Lifecycle workbookSystems Lifecycle workbook
Systems Lifecycle workbook
 
SCADA
SCADASCADA
SCADA
 
Network management aa
Network management  aaNetwork management  aa
Network management aa
 
Time to Rethink Process Automation Systems
Time to Rethink Process Automation SystemsTime to Rethink Process Automation Systems
Time to Rethink Process Automation Systems
 

Más de Mohamed A Hakim (10)

Maintenance KPI
Maintenance KPIMaintenance KPI
Maintenance KPI
 
Supply Chain in Maintenance
Supply Chain in MaintenanceSupply Chain in Maintenance
Supply Chain in Maintenance
 
Flowmeter course
Flowmeter courseFlowmeter course
Flowmeter course
 
Industrial process control
Industrial process controlIndustrial process control
Industrial process control
 
Instrumentation course
Instrumentation courseInstrumentation course
Instrumentation course
 
Introduction to foundation fieldbus
Introduction to foundation fieldbusIntroduction to foundation fieldbus
Introduction to foundation fieldbus
 
Plc (programming)
Plc (programming)Plc (programming)
Plc (programming)
 
Plc (analog and special io)
Plc (analog and special io)Plc (analog and special io)
Plc (analog and special io)
 
Plc (processors and dio)
Plc (processors and dio)Plc (processors and dio)
Plc (processors and dio)
 
Plc (introduction and logic)
Plc (introduction and logic)Plc (introduction and logic)
Plc (introduction and logic)
 

Último

Último (20)

Axa Assurance Maroc - Insurer Innovation Award 2024
Axa Assurance Maroc - Insurer Innovation Award 2024Axa Assurance Maroc - Insurer Innovation Award 2024
Axa Assurance Maroc - Insurer Innovation Award 2024
 
AWS Community Day CPH - Three problems of Terraform
AWS Community Day CPH - Three problems of TerraformAWS Community Day CPH - Three problems of Terraform
AWS Community Day CPH - Three problems of Terraform
 
Connector Corner: Accelerate revenue generation using UiPath API-centric busi...
Connector Corner: Accelerate revenue generation using UiPath API-centric busi...Connector Corner: Accelerate revenue generation using UiPath API-centric busi...
Connector Corner: Accelerate revenue generation using UiPath API-centric busi...
 
Apidays Singapore 2024 - Building Digital Trust in a Digital Economy by Veron...
Apidays Singapore 2024 - Building Digital Trust in a Digital Economy by Veron...Apidays Singapore 2024 - Building Digital Trust in a Digital Economy by Veron...
Apidays Singapore 2024 - Building Digital Trust in a Digital Economy by Veron...
 
🐬 The future of MySQL is Postgres 🐘
🐬  The future of MySQL is Postgres   🐘🐬  The future of MySQL is Postgres   🐘
🐬 The future of MySQL is Postgres 🐘
 
Data Cloud, More than a CDP by Matt Robison
Data Cloud, More than a CDP by Matt RobisonData Cloud, More than a CDP by Matt Robison
Data Cloud, More than a CDP by Matt Robison
 
Boost Fertility New Invention Ups Success Rates.pdf
Boost Fertility New Invention Ups Success Rates.pdfBoost Fertility New Invention Ups Success Rates.pdf
Boost Fertility New Invention Ups Success Rates.pdf
 
From Event to Action: Accelerate Your Decision Making with Real-Time Automation
From Event to Action: Accelerate Your Decision Making with Real-Time AutomationFrom Event to Action: Accelerate Your Decision Making with Real-Time Automation
From Event to Action: Accelerate Your Decision Making with Real-Time Automation
 
Tata AIG General Insurance Company - Insurer Innovation Award 2024
Tata AIG General Insurance Company - Insurer Innovation Award 2024Tata AIG General Insurance Company - Insurer Innovation Award 2024
Tata AIG General Insurance Company - Insurer Innovation Award 2024
 
Real Time Object Detection Using Open CV
Real Time Object Detection Using Open CVReal Time Object Detection Using Open CV
Real Time Object Detection Using Open CV
 
GenAI Risks & Security Meetup 01052024.pdf
GenAI Risks & Security Meetup 01052024.pdfGenAI Risks & Security Meetup 01052024.pdf
GenAI Risks & Security Meetup 01052024.pdf
 
2024: Domino Containers - The Next Step. News from the Domino Container commu...
2024: Domino Containers - The Next Step. News from the Domino Container commu...2024: Domino Containers - The Next Step. News from the Domino Container commu...
2024: Domino Containers - The Next Step. News from the Domino Container commu...
 
Top 5 Benefits OF Using Muvi Live Paywall For Live Streams
Top 5 Benefits OF Using Muvi Live Paywall For Live StreamsTop 5 Benefits OF Using Muvi Live Paywall For Live Streams
Top 5 Benefits OF Using Muvi Live Paywall For Live Streams
 
Artificial Intelligence Chap.5 : Uncertainty
Artificial Intelligence Chap.5 : UncertaintyArtificial Intelligence Chap.5 : Uncertainty
Artificial Intelligence Chap.5 : Uncertainty
 
Scaling API-first – The story of a global engineering organization
Scaling API-first – The story of a global engineering organizationScaling API-first – The story of a global engineering organization
Scaling API-first – The story of a global engineering organization
 
Top 10 Most Downloaded Games on Play Store in 2024
Top 10 Most Downloaded Games on Play Store in 2024Top 10 Most Downloaded Games on Play Store in 2024
Top 10 Most Downloaded Games on Play Store in 2024
 
Strategize a Smooth Tenant-to-tenant Migration and Copilot Takeoff
Strategize a Smooth Tenant-to-tenant Migration and Copilot TakeoffStrategize a Smooth Tenant-to-tenant Migration and Copilot Takeoff
Strategize a Smooth Tenant-to-tenant Migration and Copilot Takeoff
 
Powerful Google developer tools for immediate impact! (2023-24 C)
Powerful Google developer tools for immediate impact! (2023-24 C)Powerful Google developer tools for immediate impact! (2023-24 C)
Powerful Google developer tools for immediate impact! (2023-24 C)
 
Mastering MySQL Database Architecture: Deep Dive into MySQL Shell and MySQL R...
Mastering MySQL Database Architecture: Deep Dive into MySQL Shell and MySQL R...Mastering MySQL Database Architecture: Deep Dive into MySQL Shell and MySQL R...
Mastering MySQL Database Architecture: Deep Dive into MySQL Shell and MySQL R...
 
Bajaj Allianz Life Insurance Company - Insurer Innovation Award 2024
Bajaj Allianz Life Insurance Company - Insurer Innovation Award 2024Bajaj Allianz Life Insurance Company - Insurer Innovation Award 2024
Bajaj Allianz Life Insurance Company - Insurer Innovation Award 2024
 

Dcs course

  • 2. Distributed Control System and Programmable Logic Control Course Aim The aim of this training course is to build up the procedural and declarative knowledge required to be recognized by projects engineer that don not have past background of DCS or PLC. This will help them to supervise projects dealing with control systems with a strong background. In this course, the training cycle is divided in five steps that necessitate the cooperation between the instructor and the trainees. These steps are shown in figure below, they are summarized as follows: 1. Define the knowledge and skills required to be developed. 2. Define the elements of each knowledge or skill. 3. Formulate a verbal phrase for the learning objective of each element. 4. Choose an adequate instructional activity to present each element. 5. Set up an indicator to measure the outcomes of the course and modify the training skills to adapt the vocational needs. Define Knowledge Determine & Skills Elements Measure Learning & Correction Objectives Instruction Activity Training Cycle. 1
  • 3. Distributed Control System and Programmable Logic Control Knowledge and Elements  Illustrate DCS & PLC Benefits, Usage and History.  Overview of control system history.  Control system benefits and usage.  Types of control  Develop Knowledge of DCS Components (Hardware & Software).  Infrastructure [Communication Bus, Interfaces, Controllers, Gateways, RTU, Others].  Hardware and technologies.  Software [Configuration, Graphics, Alarming, Trending, System Management, Others].  Extend Knowledge of DCS installation and Maintenance.  Site Installation, Commissioning and Startup.  Diagnostics, Spares, Tools and Power Distribution.  Maintenance [Backup, Replacements and System Installation].  Develop Knowledge of PLC Components.  PLC fundamentals.  PLC Logic. 2
  • 4. Distributed Control System and Programmable Logic Control Table of Contents Section I Chapter 1 Introduction Chapter 2 Regulatory Control Section II Chapter 3 DCS Infrastructure Chapter 4 DCS Hardware Chapter 5 DCS Software Section III Chapter 6 Installation Chapter 7 Maintenance Chapter 8 Power Distribution Section IV Chapter 9 PLC Fundamentals. Chapter 10 Ladder Logic And SFC Appendices A Electrical Relay Diagram And P&ID Symbols B Serial Communication C Networking D Software Engineering 3
  • 5. Distributed Control System and Programmable Logic Control 4
  • 6. Distributed Control System and Programmable Logic Control Chapter 1 Control Systems 1.1 Automation System Structure Although applications differ widely, there is little difference in the overall architecture of their control systems. Why the control system of a power plant is not sold also for automating a brewery depends largely on small differences (e.g. explosion-proof), on regulations (e.g. Food and Drug Administration) and also tradition, customer relationship. The ANSI/ISA standard 95 defines terminology and good practices Level 4 Business Planning & Logistics Enterprise Resource Plant Production Scheduling Planning Operational Management, etc. Level Manufacturing 3 Operations & Control Dispatching Production, Detailed Product Manufacturing Execution Scheduling, Reliability Assurance,... System Level 2,1,0 Batch Continuous Discrete Control & Command Control Control Control System 1.1.1 Large Control System Hierarchy  Administration: Production goals, planning  Enterprise: Manages resources, workflow, coordinates activities of different sites, quality supervision, maintenance, distribution and planning. 5
  • 7. Distributed Control System and Programmable Logic Control  Supervision: Supervision of the site, optimization, on-line operations. Control room, Process Data Base, logging (open loop)  Group (Area): Control of a well-defined part of the plant. closed loop, except for intervention of an operator) o Coordinates individual subgroups o Adjusting set-points and parameters o Commands several units as a whole  Unit (Cell): Control (regulation, monitoring and protection) of a small part of a group (closed loop except for maintenance). o Measure: Sampling, scaling, processing, calibration. o Control: regulation, set-points and parameters o Command: sequencing, protection and interlocking  Field: Sensors & Actors, data acquisition, digitalization, data transmission, no processing except measurement correction and built-in protection. 4 Planning, Statistics, Finances administration 3 Workflow, Resources, Interactions enterprise SCADA supervision Supervisory Supervisory = 2 And Data Control Acquisition Group Control Unit Control 1 Field Sensors T & Actors A V 0 Primary technology Figure 1.1 Large control system hierarchy 6
  • 8. Distributed Control System and Programmable Logic Control 1.1.2 Response Time and Hierarchical Level Planning ERP Level (Enterprise Resource Planning) MES Execution (Manufacturing Level Execution System) SCADA (Supervisory Control Supervisory and Data Acquisition) Level DCS (Distributed Control System) Control Level PLC (Programmable Logic Controller) ms seconds hours days weeks month years Figure 1.2 Response Time And Hierarchical Level 1.2 What is DCS?  A DCS is an integrated set of modules with distributed functions. – Multi-loop controllers (10’s-100’s) that connect to field devices – Supervisory coordinating controllers – Multi-loop operator stations and engineering stations – Servers for system data management – Control network for intercommunication – External connections 7
  • 9. Distributed Control System and Programmable Logic Control Supervisory Operator System Stations Remote Users Controller www Server Engineering Station Remote Server Control Network Multi-loop Controller Direct I/O Module Other Industrial Devices Figure 1.3 DCS Hierarchy  A DCS, throughout the whole system, must provide: – Performance: control must be faster than the process. – Determinism: control must always take the same time. – Fault tolerance: redundancy; must fail to a known state. – Security: must have access restrictions/controls. Even though performance, ease of use, and interoperability are key evaluation criteria for any control system software package, the following is intended to provide the manufacturing engineer with a concise list of control system software evaluation criteria. 1. INTEROPERABILITY. This refers to the interaction of all control system hardware and software components at all levels. 2. INTERCONNECTIVITY. This criterion is concerned with the transmission medium, which is constrained by the network topology and how efficiently the system’s components communicate with each other. 8
  • 10. Distributed Control System and Programmable Logic Control 3. DISASTER PROCESSING. This component is defined by the efficiency with which the software provides the operator with system failure information and the ease at which the operator is permitted to bring the system back to maximum operation after system failure. 4. DATABASE. This refers to the software’s ability to maintain the system’s database. 5. PROCESSES/DATA. This criterion is concerned with the variety of processes and data that can be controlled by the SCADA package. 6. DIAGNOSTICS. The SCADA package’s ability to assist in the resolution of system failures is evaluated by this diagnostic utility. 7. SECURITY. This component is concerned with the levels of security provided by the software. 8. MONITORING/CONTROL Monitoring of a given process in real-time and control of that process, within preset parameters, is evaluated by this criteria. 9. ALARM MANAGEMENT/LOGGING. This is the category for detecting, annunciating, managing, and storing alarm conditions. 10. STATISTICAL PROCESS CONTROL. This is the portion of the SCADA package that evaluates the process data. Production and quality is greatly effected by this data. 12. OPERATOR INTERFACE. The graphical user interface (GUI) is evaluated using this criterion. 9
  • 11. Distributed Control System and Programmable Logic Control 13. TRENDING. The software’s ability to display trending plots using historical and current data is considered in this category. 14. REPORT GENERATION. The production of logs and reports using current real-time data and data retrieved from historical files is evaluated under this category. Due to the advancements in computer technology and low cost, a personal computer-based distributed control system can be installed for a fraction of the cost required just a few years ago. However, prior to selecting any piece of DCS equipment, first examine the existing equipment, in particular the smart controllers, for network compatibility. Then, examine and select the software to be employed. 1.3 What is PLC? A programmable logic controller, also called a PLC or programmable controller, is a computer-type device used to control equipment in an industrial facility. The kinds of equipment that PLCs can control are as varied as industrial facilities themselves. Conveyor systems, food processing machinery, auto assembly lines…you name it and there’s probably a PLC out there controlling it. In a traditional industrial control system, all control devices are wired directly to each other according to how the system is supposed to operate. In a PLC system, however, the PLC replaces the wiring between the devices. Thus, instead of being wired directly to each other, all equipment is wired to the PLC. Then, the control program inside the PLC provides the “wiring” connection between the devices. 10
  • 12. Distributed Control System and Programmable Logic Control The control program is the computer program stored in the PLC’s memory that tells the PLC what’s supposed to be going on in the system. The use of a PLC to provide the wiring connections between system devices is called soft-wiring. Let's say that a push button is supposed to control the operation of a motor. In a traditional control system, the push button would be wired directly to the motor. In a PLC system, however, both the push button and the motor would be wired to the PLC instead. Then, the PLC's control program would complete the electrical circuit between the two, allowing the button to control the motor. Figure 1.4 PLC development A PLC basically consists of two elements:  The central processing unit  The input/output system 1.3.1 The Central Processing Unit The central processing unit (CPU) is the part of a programmable controller that retrieves, decodes, stores, and processes information. It also executes the control program stored in the PLC’s memory. In 11
  • 13. Distributed Control System and Programmable Logic Control essence, the CPU is the “brains” of a programmable controller. It functions much the same way the CPU of a regular computer does, except that it uses special instructions and coding to perform its functions. The CPU has three parts:  The processor  The memory system  The power supply The processor is the section of the CPU that codes, decodes, and computes data. The memory system is the section of the CPU that stores both the control program and data from the equipment connected to the PLC. The power supply is the section that provides the PLC with the voltage and current it needs to operate. Figure 1.5 Microprocessor Hardware 1.3.2 The input/output (I/O) system It is the section of a PLC to which all of the field devices are connected. If the CPU can be thought of as the brains of a PLC, then the I/O system can be thought of as the arms and legs. The I/O system is what actually physically carries out the control commands from the program stored in the PLC’s memory. 12
  • 14. Distributed Control System and Programmable Logic Control The I/O system consists of two main parts:  The rack The rack is an enclosure with slots in it that is connected to the CPU.  I/O modules I/O modules are devices with connection terminals to which the field devices are wired. Together, the rack and the I/O modules form the interface between the field devices and the PLC. When set up properly, each I/O module is both securely wired to its corresponding field devices and securely installed in a slot in the rack. This creates the physical connection between the field equipment and the PLC. In some small PLCs, the rack and the I/O modules come prepackaged as one unit. Figure 1.6 I/O Racks 13
  • 15. Distributed Control System and Programmable Logic Control 1.4 How is a DCS different from a PLC system? DCS PLC Mfr sells a complete system of integrated Mfr sells some components; an SI components. acquires others and engineers the system. Mfr supports the system. Mfr supports the components. On-line repair/ maintenance are the norm. Off-line repair/ maintenance are the norm. System management built-in. System management designed per project. Users expect to evolve/upgrade/expand a System is a one-off project (like a house). system over 10/20/30 years. Upgrades / expansions are new projects. 1.5 Redundancy and Fault Tolerance 1.5.1 Redundancy  Hardware redundancy – add extra hardware for detection or tolerating faults  Software redundancy – add extra software for detection and possibly tolerating faults 1.5.2 Fault Tolerance  Error Detection  Damage Confinement  Error Recovery  Fault Treatment 1.5.2.1 Error Detection  Ideal check – Check should be independent from system – Check fails if system crashes 14
  • 16. Distributed Control System and Programmable Logic Control  Acceptable check – Cost – Reasonable check, e.g. monitor rate of change  diagnostics – Performed “by system on system components” – E.g. power-up diagnostics 1.5.2.2 Damage Confinement  Error might propagate and spread  Identify boundaries to state beyond which no information exchange has occurred 1.5.2.3 Error Recovery  Backward recovery – State is restored to an earlier state – Requires checkpoints – Most frequently used – Recovery overhead  Forward recovery – Try to make state error-free – Need accurate assessment of damage – Highly application-dependent 1.5.2.4 Fault Treatment  If transient fault: restart system, goto error-free state  System repair – On-line, no manual intervention, (automatic) – Dynamic system reconfiguration – Spare (hot or cold) 15
  • 17. Distributed Control System and Programmable Logic Control 1.5.2.5 Fault Coverage  Measure of system’s ability to perform: – Fault detection – Fault location – Fault containment – (and/or fault recovery)  Note: – Recovery implies that the system as a whole is operational – This does not imply that a “repair” occurred – E.g. duplex system with benign fault can recover to continue operation on one non-faulty processor 1.5.2.6 Hardware Redundancy  Passive (static) – Uses fault masking to hide occurrence of fault – No action from the system is required – E.g. voting  Active (dynamic) – Uses comparison for detection and/or diagnoses – Remove faulty hardware from system => reconfiguration  Hybrid – Combine both approaches – Masking until diagnostic complete – Expensive, but better to achieve higher reliability 1.5.2.7 Passive Hardware Redundancy  N-Modular Redundancy (NMR) – N independent modules replicate the same function 16
  • 18. Distributed Control System and Programmable Logic Control  Parallelism – Results are voted on requirements: N >= 3  TMR (Triple Modular Redundancy) 1.5.2.8 Fault tolerant structures Fault tolerance allows continuing operation in spite of a limited number of independent failures. Fault tolerance relies on work redundancy. 1.5.2.9 Static redundancy: 2 out of 3  Workby of 3 synchronised and identical units. – All 3 units OK: Correct output. – 2 units OK: Majority output correct. – 2 or 3 units failure: Incorrect output. – Otherwise: Error detection output. Process input sync sync Voter Process output Figure 1.7 (2 out of 3) Redundancy 1.5.2.10 Dynamic Redundancy  Redundancy only activated after an error is detected. – Primary components (non-redundant) – Reserve components (redundancy), standby (cold/hot standby) 17
  • 19. Distributed Control System and Programmable Logic Control Input Primary unit Standby unit Switch Output Figure 1.8 Dynamic Redundancy 1.5.2.11 Workby and Standby Workby Hot standby Cold standby sync sync on-line workby on-line standby =? Both computers are doing Standby is not computing Standby is no operational the same calculations Error detection needed. Error detection needed. at the same time Easy switchover in case Long switchover period Comparison for easy of failure. with loss of state info. error detection. Easy repair of reserve unit. No aging of reserve unit. Comparator needed. Non-redundant continuation in case of failure? Figure 1.9 Workby and Standby 1.5.2.12 Workby Fault-Tolerance for Integrity and Persistency input input synchronization synchronization Worker Co E Worker Co E Worker - D Worker - D Matching Matching Output Output comparator commutator disjunctor output output INTEGER PERSISTENT Figure 1.10 Workby Fault-Tolerance for Integrity and Persistency 18
  • 20. Distributed Control System and Programmable Logic Control 1.5.2.13 Hybrid Redundancy Mixture of workby (static redundancy) and standby (dynamic redundancy). work- work- work- stand- stand- by by by by by voter Reconfiguration work- work- work- stand- by failed by by by (self-purging redundancy) voter Figure 1.11 Hybrid Redundancy 1.6 Microprocessor Control For simple programming the relay model of the PLC is sufficient. As more complex functions are used the more complex VonNeuman model of the PLC must be used. A computer processes one instruction at a time. Most computers operate this way, although they appear to be doing many things at once. Consider the computer components shown in Figure 1.12. Figure 1.12 Simplified Personal Computer Architecture 19
  • 21. Distributed Control System and Programmable Logic Control Input is obtained from the keyboard and mouse, output is sent to the screen, and the disk and memory are used for both input and output for storage. (Note: the directions of these arrows are very important to engineers, always pay attention to indicate where information is flowing.) This figure can be redrawn as in Figure 1.13 to clarify the role of inputs and outputs. Figure 1.13 An Input-Output Oriented Architecture In this figure the data enters the left side through the inputs. (Note: most engineering diagrams have inputs on the left and outputs on the right.) It travels through buffering circuits before it enters the CPU. The CPU outputs data through other circuits. Memory and disks are used for storage of data that is not destined for output. If we look at a personal computer as a controller, it is controlling the user by outputting stimuli on the screen, and inputting responses from the mouse and the keyboard. A PLC is also a computer controlling a process. When fully integrated into an application the analogies become;  Inputs - the keyboard is analogous to a proximity switch input circuits - the serial input chip is like a 24Vdc input card 20
  • 22. Distributed Control System and Programmable Logic Control  Computer - the 686 CPU is like a PLC CPU unit  Output circuits - a graphics card is like a triac output card  Outputs - a monitor is like a light  Storage - memory in PLCs is similar to memories in personal computers It is also possible to implement a PLC using a normal Personal Computer, although this is not advisable. In the case of a PLC the inputs and outputs are designed to be more reliable and rugged for harsh production environments. 1.7 Role Play Each trainee should act a role play on the following: 1. Automation system structure. 2. What DCS and PLC and their differences? 3. Redundancy and fault tolerance. 21
  • 23. Distributed Control System and Programmable Logic Control Chapter 2 Regulatory Control 2.1 Learning Objectives  Introduce Regulatory Control.  Understanding PID control.  Differentiate between various control loops. 2.2 Introduction Most of the applications of industrial control process used simple loops which regulated flows, temperatures, pressures and levels. Occasionally ratio and cascade control loops could be found. There are many benefits for using regulatory control. One of the most important is simply closer control of the process. Process control is one part of an overall control hierarchy that extends downwards to safety controls and other directly connected process devices, and upward to encompass process optimization and even higher business levels of control such as scheduling, inventory management. Most control engineers would recognize the form of response shown in figure 2.1. Actually the response could be determined by solving a differential equation. It is more important to have a good understanding of the physical response than to be able to predict the solution by solving the differential equation. 22
  • 24. Distributed Control System and Programmable Logic Control Figure 2.1 Response of simple dynamic process to step input change Instrumentation, control and process engineers abstract the pictorial form of the process into an iconographic diagram called "Piping and Instrumentation Diagram", i.e. P&ID. Figure 2.2 is an example of the P&ID. Figure 2.2 Control loop representation used on P&IDs. For description and analysis of a control loop, without referring to whether it is implemented with analog or digital hardware, a block diagram as shown in figure 2.3 is beneficial. Figure 2.3 Simplified block diagram representation of process control loop. 23
  • 25. Distributed Control System and Programmable Logic Control 2.3 PID Control 2.3.1 Feedback Control The principle of feedback is one of the most intuitive concepts known. An action is taken to correct a less satisfactory situation then the results of the action are evaluated. If the situation is not corrected then further action takes place. Feedback control can be classified by the form of the controller output. One of the simplest forms of output is discrete form, also called on-off or two position control. An example of this is the household thermostat, which activates heating unit if the temperature is below the setting, or deactivates the unit if the temperature is above the setting. Figure 2.4 On-Off Control. The idea of two position control can be extended to multi-position control; an example is commercial air-conditioning refrigeration equipment which is operated by loading and unloading compressor cylinders. The ultimate extension is infinite number of positions which is called modulating control; an example is the process controller output that can drive a valve to any position between 0 and 100 percent, as shown in figure 2.5. 24
  • 26. Distributed Control System and Programmable Logic Control Figure 2.5 Flow versus position, infinite position Control. 2.3.2 Modes of Control Feedback controllers use one, two, or three methods to determine the controller output. These methods, called the modes of control, including the following:  Proportional (P)  Integral (I)  Derivative (D) In general these modes can be used singly or in combination. 2.3.2.1 Proportional Mode With a controller containing only the proportional mode, the controller output is proportional to the measurement value only. Neither history of the measurement value nor consideration to the rate of change is utilized. Adjustment, i.e. tuning, of the controller is simple because there is only one adjustment as shown in figure 2.6. 25
  • 27. Distributed Control System and Programmable Logic Control Figure 2.6 Relationship between input and output for proportional control. Figure 2.7 illustrates a proportional control system. The rate of fluid flow into the tank represents the load. To be in equilibrium, the outflow must be the same as the inflow. The outflow is achieved by a particular valve position where the fixed mechanism between the float, pivot and link attain. Figure 2.7 Proportional control. 2.3.2.2 Integral Mode An integrator is the ideal device for automating the procedure for adjusting the controller output bias. It is called the automatic reset. 2.3.2.3 Derivative Mode The derivative is used to anticipate the effect of load changes by adding a component to the controller output that is proportional to the rate of change of the measurement. See figure 2.8. 26
  • 28. Distributed Control System and Programmable Logic Control Figure 2.8 PID control. 2.3.3 Control Loop Structure For microprocessor control system, control strategy is configured by a series of software function blocks. Just like a set of hardware modules require interconnections to form a complete control system, a set of software function blocks also acquire interconnections, i.e. soft-wiring. Figure 2.9 shows a simple feedback loop with the software portion consists of three function blocks:  An analog input block that causes the analog to digital converter to convert the incoming 4-20mA signal to an analogous value. The value is deposited in a memory register.  A PID control block which obtains the measurement value from the analog input block and compares it with the setpoint then it executes a PID algorithm to calculate the output.  An analog output block that obtains from the PID block the required valve position value. The value is converted by a digital to analog converter to 4-20mA signal. 27
  • 29. Distributed Control System and Programmable Logic Control Figure 2.9 Control loop hardware/software structure. 2.3.4 Control Loop Tuning The power of PID control is that by good choice of control parameters the controller can be adjusted to provide the desired behavior on a wide variety of process applications. Determining acceptable values of these parameters is called tuning the controller. A good criterion for acceptable performance is the "quarter cycle decay" shown in figure 2.10. Figure 2.10 quarter cycle decay criterion Most loops are tuned by experimental techniques, i.e. trial and error. Figures 2.11 and 2.12 give a tuning map for adjusting control parameters. 28
  • 30. Distributed Control System and Programmable Logic Control Figure 2.11 Gain and Reset effects. Figure 2.12 Derivative effects. 2.4 Control Loop Types 2.4.1 Ratio Control Figure 2.13 shows the P&ID of a process heater in which the fuel flow is measured and multiplied by the required air-to-fuel ratio; this results in the required air flow rate, which is introduced as a setpoint of the feedback controller. The required air-to-fuel ratio is automatically adjusted as the output of the stack O2 controller. 29
  • 31. Distributed Control System and Programmable Logic Control Figure 2.13 ratio Control.. 2.4.2 Cascade Control In figure 2.14 the temperature controller cascades a steam flow controller. The temperature controller would react to outlet temperature drop by increasing the setpoint of the steam flow controller, which in turn would increase the signal to the valve. The flow will quickly respond to increased demand from the temperature controller and thus reaching the desired setpoint of the outlet temperature stream. Figure 2.13 Cascade Control. 2.4.3 Feedforward Control With feedforward control, the objective is to drive the controlling device from a measurement of the disturbance that is affecting the process, rather than from the process variable itself. In figure 2.14, the 30
  • 32. Distributed Control System and Programmable Logic Control application was analyzed the variation in process inlet temperature was the principle of disturbance. Hence, a feedforward controller is used to drive the fuel flow controller by sensing the inlet temperature. Figure 2.14 Feedforward Control. 2.4.4 Selector (Override) Control There are several ways of using selector switches in control strategies. One way is to select the higher (or lower) of several measurement signals to pass the process variable to a feedback controller. For example, the highest of several process temperatures may be selected automatically to become the controlling temperature as shown in figure 2.15. Figure 2.15 Override Control. 31
  • 33. Distributed Control System and Programmable Logic Control 2.4.5 Split Range Control Split range control when one process variable such as plant inlet pressure is used to manage two different output devices such as plant bypass control valve and flow control loop for fractionation area. The 4- 12 mA signal is used to control the flow control loop. If the plant cannot handle all incoming feed, the 12-20 mA signal control the plant bypass valve to direct extra feed to the outside of the plant. 2.5 Role Play The trainees are required to play roles about: 1. Introducing regulatory control. 2. Introducing modes of control. 3. Intruding control loop types. 32
  • 34. Distributed Control System and Programmable Logic Control 33
  • 35. Distributed Control System and Programmable Logic Control Chapter 3 DCS Infrastructure 3.1 Learning Objectives  Introduce system infrastructure interoperability and interconnectivity.  Illustrate system components of level 2 control. 3.2 Communication Bus Figure 3.1: Communication Bus The communication bus, i.e. the Nodebus, interconnects stations (Control Processors, Application Processors, Application Workstations, and so forth) in the system to form a process management and control node. Depending on application requirements, the node can serve as a single, stand-alone entity, or it can be configured to be part of a more extensive communications network. Operating in conjunction with the Nodebus interface electronics in each station, the Nodebus provides high-speed, redundant, peer-to-peer communications between the stations. The high speed, coupled with the redundancy and peer-to-peer characteristics, provide performance and security superior to that 34
  • 36. Distributed Control System and Programmable Logic Control provided by communication media used in conventional computer-based systems. Station interfaces to the Nodebus are also redundant, further ensuring secure communications between the stations. The Nodebus can be implemented in a basic, non-extended configuration or it can be extended through the use of Nodebus Extenders and Dual Nodebus Interface Extenders. 3.2.1 Nodebus Interface The Nodebus Interface is a module which allows direct connection of a personal workstation (PW), with appropriate Nodebus connector card and software, to the Nodebus figure 3.2. In this configuration, the PW functions as a station on the node. The Nodebus Interface allows connection of a station application workstation hosting an Ethernet configuration to Nodebus. See figure 3.2. Figure 3.2 Nodebus Interface Implementation (Typical) 35
  • 37. Distributed Control System and Programmable Logic Control An Attachment Unit Interface (AUI) cable, connects the PW or an Ethernet hub configuration to the Nodebus via a Nodebus Interface. A coaxial cable (ThinNet) connects an Ethernet daisy chain configuration to the Nodebus via a Nodebus Extender. The Nodebus Interface is non- redundant, and can be used in any of the Nodebus configurations described. 3.2.2 Dual Nodebus Interface The Dual Nodebus Interface (DNBI) is a module which allows direct connection of stations to the appropriate Nodebus. Connection between the DNBI and station is made via an AUI cable. For data transmission security, a separate (RS-423) control cable connects between the station and the DNBI to allow switching between the two redundant Nodebus cables. Switching of the Nodebus cables is controlled by the station, which transmits commands to the DNBI via the control cable. Figure 3.3 shows connection of a station to the Nodebus using a DNBI. Figure 3.3 Local Connection of Station 3.2.3 Dual Nodebus Interface Extender The Dual Nodebus Interface Extender (DNBX) is functionally similar to the DNBI, but provides a greater cabling distance. The 36
  • 38. Distributed Control System and Programmable Logic Control principal transmission medium used is a coaxial Ethernet cable directly connected to the station end by a standard Ethernet transceiver. Figure 3.4 remote connection of a station to the Nodebus using a DNBX. Figure 3.4 Remote Connection of Station 3.3 Control Processor The Control Processor performs regulatory, logic, timing, and sequential control together with connected:  Fieldbus Modules (FBMs)  Fieldbus Cluster I/O Cards (FBCs) It also performs data acquisition (via the Fieldbus Modules), alarm detection and notification, and may optionally serve as an interface for one or more Panel Display Stations. The non-fault-tolerant version of the Control Processor is a single-width processor module. The fault-tolerant version consists of two single-width processor modules. 3.3.1 Enhanced Reliability The Control Processor offers optional fault- tolerance for enhanced reliability. The fault-tolerant control processor configuration consists of two parallel-operating modules with two separate connections to the Nodebus and to the Fieldbus. 37
  • 39. Distributed Control System and Programmable Logic Control The two control processor modules, married together as a fault- tolerant pair, are designed to provide continued operation of the unit in the event of virtually any hardware failure occurring within one module of the pair. Both modules receive and process information simultaneously, and the modules themselves detect faults. One of the significant methods of fault detection is comparison of communication messages at the module external interfaces. Upon detection of a fault, self-diagnostics are run by both modules to determine which module is defective. The non-defective module then assumes control without affecting normal system operations. To further ensure reliable communications, the fault-tolerant control processor performs error detection and address verification tests in its Nodebus and Fieldbus interfaces. For enhanced reliability during maintenance operations, the Control Processor is equipped with a recessed reset button. This feature provides for manually forcing a module power off and on (reboot) without removing the module from the enclosure. 3.3.2 Diagnostics The Control Processor uses three types of diagnostic tests to detect and/or isolate faults:  Power-up self-checks  Run-time and watchdog timer checks  Off-line diagnostics Power-up self-checks are self-initiated when power is applied to the control processor. These checks perform sequential tests on the various control processor functional elements. Red and green indicators at 38
  • 40. Distributed Control System and Programmable Logic Control the front of the control processor module reflect the successful (or non- successful) completion of the various phases of the control processor startup sequence. The run-time and watchdog timer checks provide continuous monitoring of control processor functions during normal system operations. The operator is informed of a malfunction by means of printed or displayed system messages. Off-line diagnostics are temporarily loaded into the system for the purpose of performing comprehensive tests and checks on various system stations and devices. Using the off-line diagnostics, a suspected fault in the control processor can be isolated and/or confirmed. 3.4 Engineering Interface The engineering interface, i.e. Application Processor, is microprocessor-based application processor/file server stations. They perform two basic functions:  As application processor (computer) stations, they perform computation intensive functions.  As file server stations, they process file requests from tasks within themselves or from other stations. Bulk storage devices used with the Application Processors include floppy disk drives, hard disk drives, streaming tape drives, and CD-ROMs. The Application Processors operate in concert with other system stations (such as communication processors, workstation processors, and control processors), which provide the necessary means for data input/output and operator interfacing. A smaller system can utilize a single Application Processor, while a larger system can incorporate 39
  • 41. Distributed Control System and Programmable Logic Control several Application Processors, each configured to perform specific functions. Some functions can be performed by individual Application Processors, while others can be shared by two or more Application Processors in the same network. For all models of the Application Processor, applications range from minimal functions, such as the storage of memory images, alarm events, and historical data, to larger-scale applications such as database management and program development. 3.4.1 Application Processor Functions The following sections describe the major functions performed by the Application Processors. 3.4.1.1 System and Network Management Functions The Application Processors perform system management functions, which include collecting system performance statistics, data reconciliation, performing station reloads, providing message broadcasting, handling all station alarms and messages, and maintaining consistent time and date in all system stations. The Application Processor also performs network management functions, which comprise that portion of system management functions which deal with the network. 3.4.1.2 Database Management Database management involves the storage, manipulation, and retrieval of files containing data received and/or produced by the system. The Application Processors utilize the industry-standard Relational Data Base Management System. 40
  • 42. Distributed Control System and Programmable Logic Control 3.4.1.3 File Requests Each Application Processor contains a file manager, which manages all file requests associated with bulk memory attached to the Application Processor. Each Application Processor also supports a remote file system that allows tasks in one station to share files in another. 3.4.1.4 Historical Data The Application Processors can be configured to contain the Historian function, which maintains a history of application messages and continuous and discrete I/O values. These values may represent any parameters such as measurements, setpoints, outputs, and status switches from stations that have been configured to collect data and send it to a Historian. In addition, the Historian computes and stores a history of averages, maximums, minimums, and other derived values. This information is maintained for display, reporting, and access by application programs. An archiving facility saves the data on removable media, where applicable. The Application Processors can be configured to maintain a history of errors, alarm conditions, and selected operator actions. The occurrence of errors, alarms, and events in other stations can be stored (for later review and analysis) by sending a message defining the event to the Historian in one or more Application Processors. 41
  • 43. Distributed Control System and Programmable Logic Control 3.4.1.5 Graphic Display Support The Application Processor supports graphic displays by storing and retrieving display formats, by providing access to objects stored on the Application Processor, and by storing tasks which execute in a workstation processor. Application Processors not only provide storage of information and file management for displays, but also execute programs that perform display and trend service. 3.4.1.6 Production Control Software Production control software represents a large range of packages that require varied Application Processor resources. The following is a list of packages provided:  DBMS  Historian  Spreadsheet  Physical Properties Library  Mathematics Library  BATCH The operation and performance of the production control software are determined by the particular Application Processor configuration. 3.4.1.7 Configuration Configuration refers to the process of entering or selecting parameters to define what a software package does, or to define the environment for a software package. The Application Processors support configuration functions by providing bulk storage for configuration parameters and by executing some of the configuration processes. 42
  • 44. Distributed Control System and Programmable Logic Control 3.4.1.8 Application Development Facilities Application development tools are provided to build programs for all system stations. These include tools to document, enter, translate, link, test, and maintain programs written in several programming languages. The Application Processor supports program development for all stations (workstation processors, control processors, and so forth). Assembly language, FORTRAN, and C programs can be written on the Application Processor using standard operating system tools. An optional package is available including text editors, debuggers, linkers, revision control, and compilers, plus execution statistics functions. 3.4.1.9 User Application Program Execution The Application Processors also execute user application programs. These may be application packages such as special optimizations, test data collections, special data reductions, or other packages that you may have already developed. The allocation of resources reserved for user application varies with each Application Processor. 3.4.2 Diagnostics The Application Processors utilize three types of diagnostic tests to detect and/or isolate faults:  Power-up self-checks  Run-time and watchdog timer checks  Off-line diagnostics Power-up self-checks are initiated when power is applied to the Application Processor. These checks perform sequential tests on the 43
  • 45. Distributed Control System and Programmable Logic Control various Application Processor functional elements. Any malfunction detected during the power-up self-checks is reported by means of messages printed or displayed on a directly connected printer or terminal. The run-time and watchdog timer checks provide continuous monitoring of Application Processor functions during normal system operations. For any processor model, you are informed of a malfunction by means of printed or displayed system messages. Off-line diagnostics are temporarily loaded into the system for the purpose of performing comprehensive tests and checks on various system stations and devices. Using the off-line diagnostics, a suspected fault in the Application Processor can be isolated and/or confirmed. 3.4.3 Workstation Components The workstation components provide user interface to all System CRT display functions. A selection of workstation components is available for command and data entry, along with CRT pointer manipulation and control. These components interact with software resident in versions of the system Workstation Processors (WPs) and Application Workstation Processors (AWs). Many of these components (displays and keyboards) are "common" and allow interchangeability and simplicity in mixed technology configurations. Workstation components include:  Alphanumeric Keyboard  Annunciator and Annunciator/Numeric Keyboards  Workstation Display (with/without Touchscreen)  Mouse  Trackball  Industrial Pointing Device 44
  • 46. Distributed Control System and Programmable Logic Control  Workstation Processor or Application Workstation Processor  Personal Workstation  Modular Industrial Console Selection of the touch screen, mouse, trackball or industrial pointing device is required for picking display objects on the CRT. The touch screen has sufficient resolution for all functions normally associated with a process operator. Only the mouse or trackball provides the picking resolution necessary for engineer-related functions (for example, building graphic displays). The touch screen associated with Workstation Display and the annunciator type keyboards connects to a Graphics Controller Input Output (GCIO) interface unit located beneath the workstation display. The GCIO interfaces to the Workstation Processor and/or Application Workstation that provide secure, high- speed, bidirectional data flow. The alphanumeric keyboard and trackball connect together in a functional grouping via a serial communications link to the processors. Personal Workstations (PW) utilize separate serial communication links for alphanumeric keyboard and mouse/trackball. These buses allow a variety of component connections. Figure 3.5 Table- Workstation Components. 45
  • 47. Distributed Control System and Programmable Logic Control 3.4.3.1 Alphanumeric Keyboard The alphanumeric keyboard is used any time text is entered into the system. It consists of the full set of alphanumeric keys plus punctuation and special symbol keys laid out in the standard format, and a numeric data entry pad (with cursor control). Figure 3.6 Alphanumeric Keyboard 3.4.3.2 Annunciator Keyboard The Annunciator Keyboard Figure 3.7 is an array of LED/switch pairs. It also contains a horn silence switch and a lamp-test switch. Each LED, under control of the processor software, may be ON, OFF, or FLASHING as determined by the process conditions. The LEDs, when used in conjunction with the unit's audible annunciator, form an effective means of calling a user's attention to specific areas of the system. The switch associated with each LED can be used to invoke any pre- configured displays or operator responses.. Figure 3.7 Annunciator Keyboard 3.4.3.3 Workstation Display with/without Touchscreen The workstation display is an analog cathode ray tube (CRT) color monitor supporting ultra-high resolution applications. The monitor is suitable for mounting onto a Modular Industrial Workstation or on a 46
  • 48. Distributed Control System and Programmable Logic Control desktop. The monitor can include a touchscreen optional feature. Figure 3.8 shows the monitor with a tilt and swivel base mounted on the GCIO interface unit. The GCIO interface supports the touchscreen, annunciator and annunciator/ numeric keyboard, and audible horn options. Figure 3.8 Table-Top Workstation Display The optional touch screen is bonded to the front surface of the CRT monitor. The user selects display objects by touching them on the screen. The touch screen senses the action and sends a data signal to the workstation processor's software indicating the position of the selection. 3.4.3.4 Trackball The trackball is a stationary component that contains a rotatable sphere. The trackball can be located on a table top. Rotation of the sphere causes CRT pointer movement analogous to the mouse action. Buttons are also provided for user selections/manipulations. See Figure 3.9 Figure 3.9 Trackball 3.4.3.5 Modular Industrial Console Modular Industrial Consoles provide flexible mounting arrangements of components. They allow users to configure centralized or distributed control centers tailored to the functional requirements of each interaction point in the plant. The modular console furniture 47
  • 49. Distributed Control System and Programmable Logic Control described herein may incorporate a mix of equipment - console displays, input devices, processors, Fieldbus Modules, data storage devices, and so on. Alternately, only display-specific equipment can be incorporated. Modular Industrial Consoles (MICs) are ideal for supporting powerful multiple-screen, real-time display software interactions. This combination allows console resources to be optimally allocated to meet changing day- to-day needs. 3.5 Operator Interface Operating in conjunction with human interface input/output components, the workstation processors serve as a link between the operator and other distributed processor modules. They receive graphic and textual information both stored internally or from application processors and generate signals to display the information on a workstation display. Display formats and data files are available from bulk storage. Live display information (distributed data objects) is available from any control -processor, or from shared system global data. The video information displayed can include free form combinations of text, graphic illustrations, charts, and control displays. The workstation processors display textual information as 80 text characters per line, with four fonts. The processors provide resizable and restackable windows. Displays for all of the workstation processors may also be developed using the system software running in a compatible personal computer. A workstation processor, together with its workstation monitor and input components, can be configured with combinations of peripherals to suit functions and user preferences. 48
  • 50. Distributed Control System and Programmable Logic Control 3.6 Gateways The architecture of the DCS permits it to be connected to other foreign systems using a gateway module for adapting different communication protocols. See figure 3.10. Figure 3.10 Field Automation Subsystem 3.7 Role Play Each trainee should introduce one of the main components: 1. Communication Bus 2. Control Processor. 3. Application Processor 4. Operator Interfaces and Gateways 49
  • 51. Distributed Control System and Programmable Logic Control Chapter 4 DCS Hardware 4.1 Learning Objectives  Define fieldbus communication.  Illustrate system components of level 1 control.  Demonstrate interconnection between different components.  Develop knowledge base of foundation fieldbus technology. 4.2 Fieldbus Modules Fieldbus Modules provide connection of digital I/O, analog I/O, and Intelligent Transmitters to control processors. There are two types of Fieldbus Modules: Main and Expansion. Some main modules can be expanded using an expansion module. A wide range of Fieldbus Modules is available to perform the signal conversion necessary to interface the control processor with field sensors and actuators. 4.3 Fieldbus Interconnection The Control Processor is used in three different configurations, which provide broad flexibility in Fieldbus implementation:  Local Fieldbus (Figure 4.1) - Used only within the enclosure. Fieldbus Modules attach directly to the redundant local bus. 50
  • 52. Distributed Control System and Programmable Logic Control Figure 4.1 Local Fieldbus  Twinaxial (Dual-Conductor Coaxial) Fieldbus Extension (Figure 4.2) - Using twinaxial cable, the Fieldbus can optionally extend outside of the enclosure. Fieldbus Modules attach to the extended bus through Fieldbus isolators. The twinaxial Fieldbus extension may be redundant. Figure 4.2 Twinaxial Fieldbus Extension  Fiber Optic Fieldbus Extension (Figure 4.3) - The fiber optic Fieldbus can optionally extend the distance as well as add application versatility and security. Figure 4.3 Fiber Optic Fieldbus Extension 51
  • 53. Distributed Control System and Programmable Logic Control All three Fieldbus configurations use serial data communication complying with Electronic Industrial Association (EIA) Standard RS-485. 4.4 Cluster I/O Subsystem Interfacing The Control Processor interfaces with the Fieldbus Cluster Input/Output Subsystem that consists of the Fieldbus, a multi-slot chassis configuration of a Fieldbus Processor, analog/digital Fieldbus Cards (FBCs), and power supply and power monitor card. These Cluster I/O subsystems meet the needs of applications where a high number of channels per card are required. Figure 4.4 shows a typical twinaxial Fieldbus configuration. Figure 4.4 Twinaxial Fieldbus Cluster I/O Subsystem Interface Configuration 4.5 Fieldbus Cluster I/O Subsystem The Fieldbus Cluster Input/Output Subsystem provides full support for analog measurement, digital sensing, and analog or discrete control capabilities. The Subsystem integrates with the Control Processor or Personal Workstation via the Fieldbus, and includes a multi-slot chassis configuration made up of a Fieldbus Processor, Analog/Digital Fieldbus Cards (FBC), subsystem main power supply, and power monitor card. 52
  • 54. Distributed Control System and Programmable Logic Control The Fieldbus Cluster I/O Subsystem is configurable, gathering analog measurements, while simultaneously handling analog and digital input and output channels. The Fieldbus Cluster I/O Subsystem is offered in both non-redundant and redundant configurations. Each in a redundant pair is individually addressable on the Fieldbus with a unique logical address. In a redundant configuration, the FBPs provide switchover from the primary FBP to the redundant FBP and back again automatically. The FBCs are suitable in applications where a high number of channels per card are required. They are ideal for non-isolated and isolated input signal gathering and data acquisition systems where high quantities of "points per cluster" areas are desired. The FBCs may be optionally connected as redundant pairs. Various input cards are available with one of the following three levels of isolation:  Non-isolated - Each channel is referenced to ground and the card itself is referenced to ground.  Group-isolated - Electrically separate card-to-card but not channel- to-channel on the same card.  Isolated - Each channel is electrically separated from any other channel, card, group, building, site, etc. 4.6 Fieldbus Processor The Fieldbus Processor (FBP) module provides communication between the Fieldbus Cards (FBCs) and the Control Processor. Optionally available is redundancy for the FBP module. Each FBP module is individually addressable via the Fieldbus. If the primary FBP fails or is taken off-line, the secondary FBP automatically assumes control. It remains in control until the primary FBP returns on-line (figure 4.5). 53
  • 55. Distributed Control System and Programmable Logic Control Figure 4.5 FBP Overview 4.7 Fieldbus Cards The Fieldbus Cards support a variety of analog and digital I/O signals. The FBCs convert electrical I/O signals used by field devices to permit communication with these devices via the Fieldbus. The FBCs can be connected in a redundant configuration via the hardware. The redundant FBCs must be in adjacent slots and they are connected via a hardware adapter at the interface to the field devices. In an FBC redundant configuration, the FBP determines which FBC of the redundant pair is to supply the data to the Control Processor. This is done in the software by a predetermined set of conditions. 4.7.1 Analog FBCS The analog FBCs support analog signal types and control functions equipped with accurate signal conditioning circuitry, the analog cards interface between process sensors and actuators. To input an analog voltage (into DCS) the continuous voltage value must be sampled and then converted to a numerical value by an A/D 54
  • 56. Distributed Control System and Programmable Logic Control converter. Figure 4.6 shows a continuous voltage changing over time. There are three samples shown on the figure. The process of sampling the data is not instantaneous, so each sample has a start and stop time. The time required to acquire the sample is called the sampling time. A/D converters can only acquire a limited number of samples per second. The time between samples is called the sampling period T, and the inverse of the sampling period is the sampling frequency (also called sampling rate). The sampling time is often much smaller than the sampling period. Figure 4.6 Sampling an analog voltage Analog outputs are much simpler than analog inputs. To set an analog output an integer is converted to a voltage. This process is very fast, and does not experience the timing problems with analog inputs. But, analog outputs are subject to quantization errors. Figure 4.7 gives a summary of the important relationships. These relationships are almost identical to those of the A/D converter. Assume we are using an 8 bit D/A converter that outputs values between 0V and 10V. We have a resolution of 256, where 0 results in an output of 0V and 255 results in 10V. The quantization error will be 20mV. If we want to output a voltage of 6.234V, we would specify an output integer of 159, this would result in an output voltage of 6.235V. The quantization error would be 6.235V- 6.234V=0.001V. The current output from a D/A converter is normally limited to a small value, typically less than 20mA. 55
  • 57. Distributed Control System and Programmable Logic Control Figure 4.7 D/A converter 4.7.2 Digital FBCS The digital FBCs consist of 32- and 64-channel types. Inputs can be either voltage monitoring or contact sensing. Contact inputs must convert a variety of logic levels to the 5Vdc logic levels used on the data bus. This can be done with circuits similar to figure 4.8. Basically the circuits condition the input to drive an optocoupler. This electrically isolates the external electrical circuitry from the internal circuitry. Other circuit components are used to guard against excess or reversed voltage polarity. Figure 4.8 Contact input circuitry. Contact outputs must convert the 5Vdc logic levels on the DCS data bus to external voltage levels. This can be done with circuits similar to figure 4.9. Basically the circuits use an optocoupler to switch external circuitry. This electrically isolates the external electrical circuitry from 56
  • 58. Distributed Control System and Programmable Logic Control the internal circuitry. Other circuit components are used to guard against excess or reversed voltage polarity. Figure 4.9 Contact output circuitry. 4.8 Other Modules  0 to 20 mA Input/Output Interface  Pulse Input, 0 to 20 mA Output Interface  Thermocouple/ Millivolt Input Interface  RTD Input Interface  High Power Contact/dc Input/Output Interface 4.9 Foundation Fieldbus Technology FOUNDATION fieldbus is an all-digital, serial, two-way communications system that serves as the base-level network in a plant or factory automation environment. Figure 4.10 Foundation Fieldbus Network 57
  • 59. Distributed Control System and Programmable Logic Control Figure 4.11 Historical development of field devices technology. It's ideal for applications using basic and advanced regulatory control, and for much of the discrete control associated with those functions. Two related implementations of FOUNDATION fieldbus have been introduced to meet different needs within the process automation environment. These two implementations use different physical media and communication speeds.  H1 works at 31.25 Kbit/sec and generally connects to field devices. It provides communication and power over standard twisted-pair wiring. H1 is currently the most common implementation and is therefore the focus of these courses.  HSE (High-speed Ethernet) works at 100 Mbit/sec and generally connects input/output subsystems, host systems, linking devices, gateways, and field devices using standard Ethernet cabling. It doesn't currently provide power over the cable, although work is under way to address this. Figure 4.12 Field Device Capacity. 58
  • 60. Distributed Control System and Programmable Logic Control Conventional analog and discrete field instruments use point-to- point wiring: one wire pair per device. They're also limited to carrying only one piece of information -- usually a process variable or control output -- over those wires. As a digital bus, FOUNDATION fieldbus doesn't have those limitations.  Multidrop wiring. FOUNDATION fieldbus will support up to 32 devices on a single pair of wires (called a segment) -- more if repeaters are used. In actual practice, considerations such as power, process modularity, and loop execution speed make 4 to 16 devices per H1 segment more typical. That means if you have 1000 devices -- which would require 1000 wire pairs with traditional technology -- you only need 60 to 250 wire pairs with FOUNDATION fieldbus. That's a lot of savings in wiring (and wiring installation). Figure 4.12 Fieldbus wiring diagram. 59
  • 61. Distributed Control System and Programmable Logic Control  Multivariable instruments. That same wire pair can handle multiple variables from one field device. For example, one temperature transmitter might communicate inputs from as many as eight sensors -- reducing both wiring and instrument costs. Other benefits of reducing several devices to one can include fewer pipe penetrations and lower engineering costs.  Two-way communication. In addition, the information flow can now be two-way. A valve controller can accept a control output from a host system or other source and send back the actual valve position for more precise control. In an analog world, that would take another pair of wires.  New types of information. Traditional analog and discrete devices have no way to tell you if they're operating correctly, or if the process information they're sending is valid. But FOUNDATION fieldbus devices can tell you if they're operating correctly, and if the information they're sending is good, bad, or uncertain. This eliminates the need for most routine checks -- and helps you detect failure conditions before they cause a major process problem.  Control in the field. FOUNDATION fieldbus also offers the option of executing some or all control algorithms in field devices rather than a central host system. Depending on the application, control in the field may provide lower costs and better performance -- while enabling automatic control to continue even if there's a host-related failure. 60
  • 62. Distributed Control System and Programmable Logic Control FOUNDATION fieldbus is covered by standards from three major organizations:  ANSI/ISA 50.02  IEC 61158  CENELEC EN50170:1996/A1 The technology is managed by the independent, not-for-profit Fieldbus Foundation, whose 150+ member companies include users as well as all major process automation suppliers around the globe. Some suppliers have even donated fieldbus-related patents to the Fieldbus Foundation to encourage wider use of the technology by all Foundation members. Interoperability simply means that FOUNDATION fieldbus devices and host systems can work together while giving you the full functionality of each component. 4.10 Role Play Each trainee should introduce one of the main components: 5. Fieldbus Module and Interconnection 6. Fieldbus Processor and Clusters. 7. Foundation Fieldbus technology 61
  • 63. Distributed Control System and Programmable Logic Control Chapter 5 DCS Software 5.1 Learning objectives  To be familiar with main software components of DCS.  Understand main tasks for each application. 5.2 Standard Application Packages 5.2.1 System Management Features include:  Display of equipment information for the station and its associated input/output devices, buses, and printers.  Capability for change actions directed to the associated equipment.  Processing of station alarm conditions and messages. 5.2.2 Database Management Features include:  Storage, retrieval, and manipulation of system data files.  A run-time license for the embedded use of the Relational Database Management System.  A spreadsheet package. 5.2.3 Historian Features include:  Maintenance of a history of values for process-related measurements that have been configured for retention by the Historian. 62
  • 64. Distributed Control System and Programmable Logic Control  Maintenance of a history of application messages that have been sent to the Historian.  Maintenance of a history of alarms and error conditions which generate messages for the Historian.  Access to all Historian data by display and report application programs. 5.2.4 View Display Manager Features include:  Presentation of the operating environment.  Setting of the overall operating environment according to the type of user. Process engineers, process operators, and software engineers have access to specialized functions and databases suited to their specific requirements and authorizations.  Dynamic and interactive process graphics.  Display and processing of current process alarms.  Group and default displays for control blocks.  Execution of embedded trending within displays. 5.2.5 Draw Display Builder Features include:  Graphical display configuration for viewing and control of process operation.  Access to graphical object palettes allowing easy inclusion of pumps, tanks, valves, ISA symbols, and similar complex objects.  Ready modification of existing displays using a mouse pointer, menu items, and quick-access toolbars.  Association of process variables with objects in the displays. 63
  • 65. Distributed Control System and Programmable Logic Control  Dynamic variation of object attributes such as fill level, color, position, size and visibility with changes in the associated process variable.  Inclusion of operator control elements such as pushbuttons and sliders into displays.  A library of faceplates which may be configured by simply specifying the compound and block name of the block to which the faceplate is to be connected. 5.3 Alarm System Figure 5.1 Alarm manger Alarm Manager provides an easy-to-use graphical interface of preconfigured alarm displays for viewing and quickly responding to process alarm conditions. The alarm display windows present alarm messages initiated by the control blocks and related to digital input, state change, absolute analog, deviation, rate of change, device status mismatch, and other alarm conditions. Accessible from any environment, the Alarm Manager Display windows provide: 64
  • 66. Distributed Control System and Programmable Logic Control  Quick, easy access to the most recent alarm messages via the Most Recent Alarm display or Current Alarm display  Alarm status and value information dynamically updated from the control station  Color-coded priority and status indicators that allow you to quickly focus in on critical alarms  Summary displays for different views of the alarm database based on alarm status  An historical list of alarms  The capability to view subsets of alarms based on specific user- defined criteria  The capability to silence or temporarily mute workstation and annunciator horns.  Secured access to alarming functions dependent on user or system responsibility This set of resizable alarm displays providing a variety of current and historic views of the process alarm database includes:  A multi-page list of all the current alarms  A single page of the most recent, active, unacknowledged alarms with dynamically updating value and status fields  Three summary displays specific to alarm status also with updating values and statuses: o all active, unacknowledged alarms o all unacknowledged alarms that have returned to normal o all active, acknowledged alarms  A list of historized alarms related to the selected historian database  An operations display for silencing horns, temporarily muting horns, changing environments 65
  • 67. Distributed Control System and Programmable Logic Control These displays allow you to respond to alarm conditions, filter and analyze specific alarm data, and maintain alarm message files for reporting purposes. The Process or Alarm button in the Display Manager (DM) window indicates the presence of alarms (both acknowledged and unacknowledged) and provides access to Alarm Manager Displays. Initially, the Current Alarm Display (CAD) appears and the other displays are easily accessible from the CAD via its default Displays menu:  Most Recent Alarm display (MRA)  New Alarm display (NEWALM)  Unacknowledged Alarms display (UNACK)  Acknowledged Alarms display (ACKALM)  Alarm History display (AHD)  Operations display (OPR) These easy-to-use displays support the following features:  A pre-configured number of alarms per screen or page  Pre-configured alarm message information and formatting per alarm type  A status area for indication of current Alarm Manager and display status, such as horns muted, match active, display paused, initial call-up time  Buttons for responding to alarm conditions, such as acknowledging or clearing alarms, and for accessing additional alarm information and process displays  Pull-down menus for editing, viewing, and filing functions  A pull-down menu for accessing other displays  Pop-up menus for quick access to commonly used functions 66
  • 68. Distributed Control System and Programmable Logic Control  A scroll bar and Go To Page option for moving easily through the alarm list Although a preconfigured set of alarm displays is provided, many aspects of the displays and alarm message content are user configurable to accommodate different process control applications and operational needs. See the section on Alarm/Display Manager Configurator. 5.4 Historian The Historian collects, stores, processes, and archives process data from the control system to provide data for trends, Statistical Process Control (SPC) charts, logs, reports, spreadsheets, and application programs. The Historian software is an easy-to-use data collection tool that allows the user to organize and enforce a plant data collection philosophy. The Historian provides extensive data collection and management functions, and data display functions for use by process engineers or operators. Typical historical data are process analog and/or digital variables (points). The Historian can also collect and display application generated messages. You can use the Historian to collect data in support of the following production control functions:  Cost accounting  Equipment performance analysis  Historical trending  Information retrieval  Inventory management  Legal record maintenance  Lost time analysis 67
  • 69. Distributed Control System and Programmable Logic Control  Maintenance reporting  Material accounting  Process analysis  Production reporting  Quality control The Historian can:  Retrieve variables from process databases or accept data from production control databases maintained by user application programs.  Perform built-in calculations on the collected data.  Store calculated (reduced) data in a real time, relational database. Application software in a plant-wide control system can access the Historian database to obtain historical data for process control, production control, and management information reporting. You can use SPC chart displays of Historian data to monitor process variables on-line via the Statistical Process Control Package (SPCP). You can build displays for trending historical data via the Display Builder and Display Configurator with Trending software. Using the Report Writer, you can generate detailed reports of historical data for management information. Examples of Industrial Software that interface with the Historian are:  Batch Plant Management  Data Validator  Display Manager  Display Configurator with Trending  Object Manager (for process data histories)  Operator Action Journal  Operator Message Interface  Real-Time Data Base Manager 68
  • 70. Distributed Control System and Programmable Logic Control  Spreadsheet  Statistical Process Control Package  System Monitor  Report Writer 5.5 Draw Figure 5.2 Draw Draw is a display builder and configurator that allow you to create and maintain dynamically updating process displays. Displays can represent the plant, a process area or a detailed portion of the process. You can draw basic objects using Draw's toolbars, menu items and shortcut keys. You assign graphic attributes such as color and line style to the objects, and then configure them to reflect process variable changes or operator actions. Draw includes numerous palettes of objects such as operator buttons, pumps, tanks, pipes, motors, valves and ISA symbols. You can also create your own palettes for storing complex objects and company-standard symbols. Displays can include faceplates, trends and bitmapped images. You can easily edit your displays to reflect changes in the process control scheme or to maximize operating efficiency and security. 69