A REPORT
ON

SUBSTATION LAYOUT AND ACCESSORIES
&
BUSBAR ARRANGEMENT

BY:SUB. TO:-

Mr. S P JAISWAL

AMIT KUMAR SINGH
NEJAMUL HOQUE
HEMENDRA KUMAR RAJPUT
CONTENTS
 Part A : “SUBSTATION LAYOUT”
• Single line diagram

•
•
•
•
•
•
•
•
•
•
•

Substation Switchyard Accessories
Lightning Arrestor
CVT
Earthing switch
Wave trap
Isolator
Current transformer
Circuit Breaker
Power Transformer
Current transformer
Reactors and capacitors
Other Switchyard Equipments
• PLCC
• SCADA

 PART B: “BUSBAR ARRANGEMENT”









Single bus system
Single bus system with bus sectionalizer
Double bus system
Double breaker bus system
One and a half breaker bus system
Main and transfer bus system
Double bus system with bypass isolator
Ring main bus system
PART- A
SWITCHYARD LAYOUTING
CLASSIFICATION OF SUBSTATIONS
• Based on working
I.
II.
III.
IV.

Generating substation (step up s/s)
Grid substation
Switching substation
Secondary substation
-- a) sub transmission voltage
b) primary distribution
c) distribution substation

• Based on structure
I.
II.
III.
IV.

Outdoor conventional air insulated substation (AIS)
Indoor substation
Compressed air insulated
GIS
SINGLE LINE DIAGRAM
LIGHTNING ARRESTOR
 A lightning arrester is a device used on electrical power systems to protect
the insulation on the system from the damaging effect of lightning.

 Metal oxide varistors (MOVs) have been used for power system protection since the
mid 1970s.
 The typical lightning arrester also known as surge arrester has a high voltage
terminal and a ground terminal.
 Current from the surge is diverted around the protected insulation in most cases
to earth.
PICTURES OF SURGE DIVERTER (LIGHTNING ARRESTOR)
CVT
Capacitor Voltage Transformer (CVT), Capacitance
Coupled Voltage Transformer(CCVT)

o To step down extra high voltage signals and provide
a low voltage .
o For measurement or to operate a protective relay.
EARTHING SWITCH
•Earth Switch is used to discharge the
voltage on the circuit to the earth for
safety.
•Earth switch is mounted on the frame
of the isolators.
•It is located for each incomer
transmission line and each side of the
busbar section.
LINE TRAP (WAVE TRAP)
Connected in series with the power (transmission) line.
 It blocks the high frequency carrier waves (24 KHz to 500 KHz) and let
power waves (50 Hz - 60 Hz) to pass through.
 It is basically an inductor of rating in Milli henry (approx 1 milli Henry
for 220 KV 1250 Amp.).
It has three main components:1. Main coil.
2. Tuning Device.
3. Lightning Arrestor.
ISOLATOR
• Disconnector or Isolator switch is

used to make sure that an electrical
circuit can be completely de-energised
for service or maintenance.

• Isolator is an off-load device.

• Types of Isolators are
1. Central rotating, horizontal swing
2. Centre-Break
3. Vertical swing
4. Pantograph type
CURRENT TRANSFORMER
Current transformers are used for
Stepping down current for
measurement, protection and control.

Current transformers are of two types
1. Protective CT
2. Measuring CT
CIRCUIT BREAKERS
 A Circuit breaker is an automatically operated electrical switch designed to

protect an electrical circuit from damage caused by overload or short
circuit. Its basic function is to detect a fault condition and, by interrupting
continuity, to immediately discontinue electrical flow.
 All circuit breakers have common features in their operation, although
details vary substantially depending on the voltage class, current rating and
type of the circuit breaker.
Once a fault is detected, contacts within the circuit breaker must open to
interrupt the circuit.
 Small circuit breakers may be manually operated; larger units
have solenoids to trip the mechanism, and electric motors to restore energy
to the springs.


Different techniques are used to extinguish the arc
: Lengthening / deflection of the arc
: Intensive cooling (in jet chambers)
: Division into partial arcs
: Zero point quenching
: Connecting capacitors in parallel with contacts in DC circuits



High-voltage breakers are broadly classified by
the medium used to extinguish the arc
•Bulk oil
•Minimum oil
•Air blast
•Vacuum
•SF6
BUSBAR

 Busbars receive power
from incoming circuits and
deliver power to outgoing
circuits.
POWER TRANSFORMERS

Power Transformers are used to step up or step down a.c.
voltages and to transfer electrical power from one voltage
level to another.
SHUNT REACTORS
• Shunt Reactors are used for long EHV transmission lines to control voltage
during low – load period.
• Shunt reactors is also used to compensate shunt capacitance of
transmission line during low load periods.
• Usually Shunt reactors are unswitched.
SEREIS REACTORS
Series reactors are used to
limit short – circuit current
and to limit current surges
associated with fluctuating
loads.
• Series reactors are located
at the strategic locations such
that the fault levels are
reduced.
SHUNT CAPACITORS
• Shunt capacitors are used for compensating reactive power of LPF.
• They are used for improving the power factor. It is also used for voltage
control during heavy lagging power factor loads.
• They are located at the receiving stations and distribution substations.
• They are switched on during heavy loads and switched off during low loads.
SERIES CAPACITOR
• Series Capacitors are used for some long EHV a.c. lines to improve power
transferability.
• They located at the sending end / receiving end of the lines.
• They are provided with by pass circuit breaker and protective spark –gaps.
NEUTRAL GROUNDING EQUIPMENT
•Neutral Grounding Equipment are
Resistors and reactors.
• They are used to limit the short
circuit current during ground fault.
•They are connected between
neutral point and ground.
OTHER SWITCHYARD EQUIPMENTS
. MARSHALLING KIOSKS
. STATION EARTHING SYSTEM
. POWER CABLES
. CONTROL CABLES
. INSULATORS
. METERING, RELAY AND CONTROL PANEL
. SUPPLY SYSTEM
POWER LINE CARRIER COMMUNICATION
 PLCC is mainly used for telecommunication, tele-protection and tele-monitoring
between electrical substations through power lines at high voltages, such as 110
kv, 220 kv, 400 kv.
 The voice signal is converted/compressed into the 300 Hz to 4000 Hz range.


It is known as :-

Power line Digital Subscriber Line (PDSL)
mains communication
power line telecom (PLT)
power line networking (PLN)
Broadband over Power Lines (BPL)
WHAT IS SCADA ?
•
SCADA stands for Supervisory Control And Data
Acquisition.
•
It is not a full control system, but rather focuses on the
supervisory level.
•
It is a purely software package that is positioned on top
of hardware to which it is interfaced. ( via Programmable
Logic Controllers(PLCs)) .
The SCADA systems are arranged to perform the following tasks.
•
•
•
•
•
•
•
•

Data Collection (Data Acquisition)
Data transmission (telemetry)
Scanning, Indication, Monitoring, Logging.
Control and indication.
Ensure sequential events.
Data presentation, display, reporting
Execution of operating, commands: on/off,raise/lower.
Network supervision, alarms and report any uncommon
change of state.
PART B

BUS BAR ARRANGEMENT
CONDUCTOR USED FOR BUSES
• All Aluminum conductor (AAC)
• All Aluminum alloy conductor (AAAC)
• Aluminum conductor with aluminum alloy reinforced
(ACAR)
• Aluminum conductor with steel reinforced (ACSR)
SINGLE BUS SYATEM
Advantages:
1.Simple in Design
2.Less Expenditure

Disadvantages:
1.In case of bus fault or bus bar isolator fault or maintenance total
Substation is out of service.
2.In case of maintenance of transformer circuit breaker the associated
transformer has also to be shut-down. Similarly for Line also.
SINGLE BUS WITH BUS SECTIONALISER
Advantages:
1. One complete section can be taken out for
Maintenance without disturbing the
continuity of other section.
2. If a fault occurs on one section of the Bus,
that faulty section alone will be isolated.

Disadvantages:
It will be a little more costly with the addition of one isolator and some cases with
Circuit breaker, C.Ts and C&R panel.
DOUBLE BUS SYSTEM
Advantages:
: Double Bus Bar Arrangement increases the
flexibility of system.

Disadvantages:
:The arrangement does not permit breaker
maintenance with out interruption.
DOUBLE BREAKER BUS SYSTEM
Advantages:
There is no need of bus coupler as because
the operation is done by breakers instead of
isolator

Disadvantages:
Most expensive as it involves additional breaker,
CT Isolators etc for each circuit.
ONE AND A HALF BREAKER BUS SYSTEM
Advantages:
During any fault on any one of the buses, that faulty bus will be cleared
instantly without interrupting any feeders in the system since all feeders will
continue to feed from other healthy bus.

Disadvantages:
This scheme is much expensive due to investment for
third breaker.
MAIN AND TRANSFER BUS SYSTEM
Switching operation:
1.First close the isolators at both side of the bus
coupler breaker.
2. Then close the bypass isolator of the feeder
which is to be transferred to transfer bus.
3. Now energized the transfer bus by closing the
bus coupler circuit breaker from remote.

4.After bus coupler breaker is closed, now the power from main bus flows to the
feeder line through its main breaker as well as bus coupler breaker viatransfer bus.
5. Now if main breaker of the feeder is switched off, total power flow will
instantaneously shift to the bus coupler breaker and hence this breaker will serve
the purpose of protection for the feeder.
6. At last the operating personnel open the isolators at both sides of the main circuit
breaker to make it isolated from rest of the live system.
DOUBLE BUS SYSTEM WITH BYPASS ISOLATOR
Advantages:
It permits breaker maintenance without interruption
of power which is not possible in double bus system
but it provides all the advantages of double bus
system.

Disadvantages:
It however requires one additional isolator (bypass isolator) for each feeder
circuit and introduces slight complication in system layout.
RING BUS SYSTEM
Advantages:
It provides a double feed to each feeder circuit,
opening one breaker under maintenance or
otherwise does not affect supply to any feeder.
But this system has two major disadvantages.
1.
2.
3.
4.
5.

Flexibility for breaker maintenance
Each breaker removable without disconnecting load
Only one breaker needed per branch,
Each branch connected to network by two breakers
All change-over switching done with circuit-breakers
& hence flexible.
presentation on substation layout and BUS bar arrangement.

Más contenido relacionado

La actualidad más candente

Relay and switchgear protection
Relay and switchgear protectionRelay and switchgear protection
Relay and switchgear protection
Binit Das
 
SWITCHYARD EQUIPMENTS & PROTECTION SYSTEMS
SWITCHYARD EQUIPMENTS & PROTECTION SYSTEMSSWITCHYARD EQUIPMENTS & PROTECTION SYSTEMS
SWITCHYARD EQUIPMENTS & PROTECTION SYSTEMS
Partha Parida
 
POWER SYSTEM PROTECTION
POWER SYSTEM PROTECTION POWER SYSTEM PROTECTION
POWER SYSTEM PROTECTION
moiz89
 
POWER DISTRIBUTION 2.docx
POWER DISTRIBUTION 2.docxPOWER DISTRIBUTION 2.docx
POWER DISTRIBUTION 2.docx
Jeffrey Dorsey
 

La actualidad más candente (20)

Electric substation
Electric substation Electric substation
Electric substation
 
Presentation on substations
Presentation on substationsPresentation on substations
Presentation on substations
 
Substation
SubstationSubstation
Substation
 
Design of substation
Design of substationDesign of substation
Design of substation
 
Presentation on 132/33 KVSubstation Training
Presentation on 132/33 KVSubstation Training Presentation on 132/33 KVSubstation Training
Presentation on 132/33 KVSubstation Training
 
industrial training on 132 kv substation
industrial training on 132 kv substationindustrial training on 132 kv substation
industrial training on 132 kv substation
 
220 KV Substation Operation & Maintenance
220 KV Substation Operation & Maintenance220 KV Substation Operation & Maintenance
220 KV Substation Operation & Maintenance
 
Protection of transmission lines (distance)
Protection of transmission lines (distance)Protection of transmission lines (distance)
Protection of transmission lines (distance)
 
Neutral grounding
Neutral groundingNeutral grounding
Neutral grounding
 
Substations
SubstationsSubstations
Substations
 
Presentation on Power transformer
Presentation on Power transformerPresentation on Power transformer
Presentation on Power transformer
 
Switchgear presentation
Switchgear presentationSwitchgear presentation
Switchgear presentation
 
33kv substation
33kv substation33kv substation
33kv substation
 
Switchgear presentation
Switchgear presentationSwitchgear presentation
Switchgear presentation
 
Switchyard
SwitchyardSwitchyard
Switchyard
 
Load Distribution
Load DistributionLoad Distribution
Load Distribution
 
Relay and switchgear protection
Relay and switchgear protectionRelay and switchgear protection
Relay and switchgear protection
 
SWITCHYARD EQUIPMENTS & PROTECTION SYSTEMS
SWITCHYARD EQUIPMENTS & PROTECTION SYSTEMSSWITCHYARD EQUIPMENTS & PROTECTION SYSTEMS
SWITCHYARD EQUIPMENTS & PROTECTION SYSTEMS
 
POWER SYSTEM PROTECTION
POWER SYSTEM PROTECTION POWER SYSTEM PROTECTION
POWER SYSTEM PROTECTION
 
POWER DISTRIBUTION 2.docx
POWER DISTRIBUTION 2.docxPOWER DISTRIBUTION 2.docx
POWER DISTRIBUTION 2.docx
 

Similar a presentation on substation layout and BUS bar arrangement.

Uttar pradesh power corporation limited
Uttar pradesh power corporation limitedUttar pradesh power corporation limited
Uttar pradesh power corporation limited
VSRAGHU
 

Similar a presentation on substation layout and BUS bar arrangement. (20)

DISTRIBUTION SYSTEM OPERATION AND CONTROL
DISTRIBUTION SYSTEM OPERATION AND CONTROLDISTRIBUTION SYSTEM OPERATION AND CONTROL
DISTRIBUTION SYSTEM OPERATION AND CONTROL
 
Ashwani kumar
Ashwani kumarAshwani kumar
Ashwani kumar
 
SUB-STATION DESIGN AND PROTECTION (AN OVERVIEW)
SUB-STATION DESIGN AND PROTECTION  (AN OVERVIEW)SUB-STATION DESIGN AND PROTECTION  (AN OVERVIEW)
SUB-STATION DESIGN AND PROTECTION (AN OVERVIEW)
 
33/11 KV TRANSMISSION LINE
33/11 KV TRANSMISSION LINE 33/11 KV TRANSMISSION LINE
33/11 KV TRANSMISSION LINE
 
Ppt on 400 kv gss raiser Bikaner- Yatendra Parashar
Ppt on 400 kv gss raiser Bikaner- Yatendra ParasharPpt on 400 kv gss raiser Bikaner- Yatendra Parashar
Ppt on 400 kv gss raiser Bikaner- Yatendra Parashar
 
400 kv Heerapura gss ppt by ishan pdf
400 kv Heerapura gss ppt by ishan pdf 400 kv Heerapura gss ppt by ishan pdf
400 kv Heerapura gss ppt by ishan pdf
 
Visit to 400 kV substation, Hadala
Visit to 400 kV substation, HadalaVisit to 400 kV substation, Hadala
Visit to 400 kV substation, Hadala
 
fdocuments.in_presentation-on-substation-220-kv.pptx
fdocuments.in_presentation-on-substation-220-kv.pptxfdocuments.in_presentation-on-substation-220-kv.pptx
fdocuments.in_presentation-on-substation-220-kv.pptx
 
Rajasthan Rajya Vidyut Prasaran Nigam.pptx
Rajasthan Rajya Vidyut Prasaran Nigam.pptxRajasthan Rajya Vidyut Prasaran Nigam.pptx
Rajasthan Rajya Vidyut Prasaran Nigam.pptx
 
Electrical power distribution and utilization
Electrical power distribution and utilizationElectrical power distribution and utilization
Electrical power distribution and utilization
 
Distribution System
Distribution SystemDistribution System
Distribution System
 
Report on 220kv substation at Jassure
Report on 220kv substation at JassureReport on 220kv substation at Jassure
Report on 220kv substation at Jassure
 
industrial-training-at-howrah-220-kv-substation.pptx
industrial-training-at-howrah-220-kv-substation.pptxindustrial-training-at-howrah-220-kv-substation.pptx
industrial-training-at-howrah-220-kv-substation.pptx
 
ntpc ppt
ntpc pptntpc ppt
ntpc ppt
 
132 KV GSS CHAMBAL JAIPUR
132 KV GSS CHAMBAL JAIPUR132 KV GSS CHAMBAL JAIPUR
132 KV GSS CHAMBAL JAIPUR
 
REGULATED_POWER_SUPPLY-1[1].pptx
REGULATED_POWER_SUPPLY-1[1].pptxREGULATED_POWER_SUPPLY-1[1].pptx
REGULATED_POWER_SUPPLY-1[1].pptx
 
Gss ppt by kanhaiya
Gss ppt  by kanhaiyaGss ppt  by kanhaiya
Gss ppt by kanhaiya
 
A PPT ON 220 KV GSS HINDAUN CITY
A PPT ON 220 KV GSS HINDAUN CITYA PPT ON 220 KV GSS HINDAUN CITY
A PPT ON 220 KV GSS HINDAUN CITY
 
WBSETCL Subhash Gram 220KV Substation Training Report
WBSETCL Subhash Gram 220KV Substation Training ReportWBSETCL Subhash Gram 220KV Substation Training Report
WBSETCL Subhash Gram 220KV Substation Training Report
 
Uttar pradesh power corporation limited
Uttar pradesh power corporation limitedUttar pradesh power corporation limited
Uttar pradesh power corporation limited
 

Último

1029-Danh muc Sach Giao Khoa khoi 6.pdf
1029-Danh muc Sach Giao Khoa khoi  6.pdf1029-Danh muc Sach Giao Khoa khoi  6.pdf
1029-Danh muc Sach Giao Khoa khoi 6.pdf
QucHHunhnh
 
Activity 01 - Artificial Culture (1).pdf
Activity 01 - Artificial Culture (1).pdfActivity 01 - Artificial Culture (1).pdf
Activity 01 - Artificial Culture (1).pdf
ciinovamais
 
Russian Escort Service in Delhi 11k Hotel Foreigner Russian Call Girls in Delhi
Russian Escort Service in Delhi 11k Hotel Foreigner Russian Call Girls in DelhiRussian Escort Service in Delhi 11k Hotel Foreigner Russian Call Girls in Delhi
Russian Escort Service in Delhi 11k Hotel Foreigner Russian Call Girls in Delhi
kauryashika82
 
1029 - Danh muc Sach Giao Khoa 10 . pdf
1029 -  Danh muc Sach Giao Khoa 10 . pdf1029 -  Danh muc Sach Giao Khoa 10 . pdf
1029 - Danh muc Sach Giao Khoa 10 . pdf
QucHHunhnh
 

Último (20)

Explore beautiful and ugly buildings. Mathematics helps us create beautiful d...
Explore beautiful and ugly buildings. Mathematics helps us create beautiful d...Explore beautiful and ugly buildings. Mathematics helps us create beautiful d...
Explore beautiful and ugly buildings. Mathematics helps us create beautiful d...
 
Python Notes for mca i year students osmania university.docx
Python Notes for mca i year students osmania university.docxPython Notes for mca i year students osmania university.docx
Python Notes for mca i year students osmania university.docx
 
Unit-V; Pricing (Pharma Marketing Management).pptx
Unit-V; Pricing (Pharma Marketing Management).pptxUnit-V; Pricing (Pharma Marketing Management).pptx
Unit-V; Pricing (Pharma Marketing Management).pptx
 
Magic bus Group work1and 2 (Team 3).pptx
Magic bus Group work1and 2 (Team 3).pptxMagic bus Group work1and 2 (Team 3).pptx
Magic bus Group work1and 2 (Team 3).pptx
 
ICT Role in 21st Century Education & its Challenges.pptx
ICT Role in 21st Century Education & its Challenges.pptxICT Role in 21st Century Education & its Challenges.pptx
ICT Role in 21st Century Education & its Challenges.pptx
 
Holdier Curriculum Vitae (April 2024).pdf
Holdier Curriculum Vitae (April 2024).pdfHoldier Curriculum Vitae (April 2024).pdf
Holdier Curriculum Vitae (April 2024).pdf
 
1029-Danh muc Sach Giao Khoa khoi 6.pdf
1029-Danh muc Sach Giao Khoa khoi  6.pdf1029-Danh muc Sach Giao Khoa khoi  6.pdf
1029-Danh muc Sach Giao Khoa khoi 6.pdf
 
Activity 01 - Artificial Culture (1).pdf
Activity 01 - Artificial Culture (1).pdfActivity 01 - Artificial Culture (1).pdf
Activity 01 - Artificial Culture (1).pdf
 
SKILL OF INTRODUCING THE LESSON MICRO SKILLS.pptx
SKILL OF INTRODUCING THE LESSON MICRO SKILLS.pptxSKILL OF INTRODUCING THE LESSON MICRO SKILLS.pptx
SKILL OF INTRODUCING THE LESSON MICRO SKILLS.pptx
 
ComPTIA Overview | Comptia Security+ Book SY0-701
ComPTIA Overview | Comptia Security+ Book SY0-701ComPTIA Overview | Comptia Security+ Book SY0-701
ComPTIA Overview | Comptia Security+ Book SY0-701
 
Grant Readiness 101 TechSoup and Remy Consulting
Grant Readiness 101 TechSoup and Remy ConsultingGrant Readiness 101 TechSoup and Remy Consulting
Grant Readiness 101 TechSoup and Remy Consulting
 
Unit-IV; Professional Sales Representative (PSR).pptx
Unit-IV; Professional Sales Representative (PSR).pptxUnit-IV; Professional Sales Representative (PSR).pptx
Unit-IV; Professional Sales Representative (PSR).pptx
 
Russian Escort Service in Delhi 11k Hotel Foreigner Russian Call Girls in Delhi
Russian Escort Service in Delhi 11k Hotel Foreigner Russian Call Girls in DelhiRussian Escort Service in Delhi 11k Hotel Foreigner Russian Call Girls in Delhi
Russian Escort Service in Delhi 11k Hotel Foreigner Russian Call Girls in Delhi
 
Sociology 101 Demonstration of Learning Exhibit
Sociology 101 Demonstration of Learning ExhibitSociology 101 Demonstration of Learning Exhibit
Sociology 101 Demonstration of Learning Exhibit
 
1029 - Danh muc Sach Giao Khoa 10 . pdf
1029 -  Danh muc Sach Giao Khoa 10 . pdf1029 -  Danh muc Sach Giao Khoa 10 . pdf
1029 - Danh muc Sach Giao Khoa 10 . pdf
 
This PowerPoint helps students to consider the concept of infinity.
This PowerPoint helps students to consider the concept of infinity.This PowerPoint helps students to consider the concept of infinity.
This PowerPoint helps students to consider the concept of infinity.
 
How to Create and Manage Wizard in Odoo 17
How to Create and Manage Wizard in Odoo 17How to Create and Manage Wizard in Odoo 17
How to Create and Manage Wizard in Odoo 17
 
Third Battle of Panipat detailed notes.pptx
Third Battle of Panipat detailed notes.pptxThird Battle of Panipat detailed notes.pptx
Third Battle of Panipat detailed notes.pptx
 
PROCESS RECORDING FORMAT.docx
PROCESS      RECORDING        FORMAT.docxPROCESS      RECORDING        FORMAT.docx
PROCESS RECORDING FORMAT.docx
 
Unit-IV- Pharma. Marketing Channels.pptx
Unit-IV- Pharma. Marketing Channels.pptxUnit-IV- Pharma. Marketing Channels.pptx
Unit-IV- Pharma. Marketing Channels.pptx
 

presentation on substation layout and BUS bar arrangement.

  • 1. A REPORT ON SUBSTATION LAYOUT AND ACCESSORIES & BUSBAR ARRANGEMENT BY:SUB. TO:- Mr. S P JAISWAL AMIT KUMAR SINGH NEJAMUL HOQUE HEMENDRA KUMAR RAJPUT
  • 2. CONTENTS  Part A : “SUBSTATION LAYOUT” • Single line diagram  • • • • • • • • • • • Substation Switchyard Accessories Lightning Arrestor CVT Earthing switch Wave trap Isolator Current transformer Circuit Breaker Power Transformer Current transformer Reactors and capacitors Other Switchyard Equipments
  • 3. • PLCC • SCADA  PART B: “BUSBAR ARRANGEMENT”         Single bus system Single bus system with bus sectionalizer Double bus system Double breaker bus system One and a half breaker bus system Main and transfer bus system Double bus system with bypass isolator Ring main bus system
  • 5. CLASSIFICATION OF SUBSTATIONS • Based on working I. II. III. IV. Generating substation (step up s/s) Grid substation Switching substation Secondary substation -- a) sub transmission voltage b) primary distribution c) distribution substation • Based on structure I. II. III. IV. Outdoor conventional air insulated substation (AIS) Indoor substation Compressed air insulated GIS
  • 7. LIGHTNING ARRESTOR  A lightning arrester is a device used on electrical power systems to protect the insulation on the system from the damaging effect of lightning.  Metal oxide varistors (MOVs) have been used for power system protection since the mid 1970s.  The typical lightning arrester also known as surge arrester has a high voltage terminal and a ground terminal.  Current from the surge is diverted around the protected insulation in most cases to earth.
  • 8. PICTURES OF SURGE DIVERTER (LIGHTNING ARRESTOR)
  • 9. CVT Capacitor Voltage Transformer (CVT), Capacitance Coupled Voltage Transformer(CCVT) o To step down extra high voltage signals and provide a low voltage . o For measurement or to operate a protective relay.
  • 10. EARTHING SWITCH •Earth Switch is used to discharge the voltage on the circuit to the earth for safety. •Earth switch is mounted on the frame of the isolators. •It is located for each incomer transmission line and each side of the busbar section.
  • 11. LINE TRAP (WAVE TRAP) Connected in series with the power (transmission) line.  It blocks the high frequency carrier waves (24 KHz to 500 KHz) and let power waves (50 Hz - 60 Hz) to pass through.  It is basically an inductor of rating in Milli henry (approx 1 milli Henry for 220 KV 1250 Amp.). It has three main components:1. Main coil. 2. Tuning Device. 3. Lightning Arrestor.
  • 12. ISOLATOR • Disconnector or Isolator switch is used to make sure that an electrical circuit can be completely de-energised for service or maintenance. • Isolator is an off-load device. • Types of Isolators are 1. Central rotating, horizontal swing 2. Centre-Break 3. Vertical swing 4. Pantograph type
  • 13. CURRENT TRANSFORMER Current transformers are used for Stepping down current for measurement, protection and control. Current transformers are of two types 1. Protective CT 2. Measuring CT
  • 14. CIRCUIT BREAKERS  A Circuit breaker is an automatically operated electrical switch designed to protect an electrical circuit from damage caused by overload or short circuit. Its basic function is to detect a fault condition and, by interrupting continuity, to immediately discontinue electrical flow.  All circuit breakers have common features in their operation, although details vary substantially depending on the voltage class, current rating and type of the circuit breaker. Once a fault is detected, contacts within the circuit breaker must open to interrupt the circuit.  Small circuit breakers may be manually operated; larger units have solenoids to trip the mechanism, and electric motors to restore energy to the springs.
  • 15.
  • 16.  Different techniques are used to extinguish the arc : Lengthening / deflection of the arc : Intensive cooling (in jet chambers) : Division into partial arcs : Zero point quenching : Connecting capacitors in parallel with contacts in DC circuits  High-voltage breakers are broadly classified by the medium used to extinguish the arc •Bulk oil •Minimum oil •Air blast •Vacuum •SF6
  • 17. BUSBAR  Busbars receive power from incoming circuits and deliver power to outgoing circuits.
  • 18. POWER TRANSFORMERS Power Transformers are used to step up or step down a.c. voltages and to transfer electrical power from one voltage level to another.
  • 19. SHUNT REACTORS • Shunt Reactors are used for long EHV transmission lines to control voltage during low – load period. • Shunt reactors is also used to compensate shunt capacitance of transmission line during low load periods. • Usually Shunt reactors are unswitched.
  • 20. SEREIS REACTORS Series reactors are used to limit short – circuit current and to limit current surges associated with fluctuating loads. • Series reactors are located at the strategic locations such that the fault levels are reduced.
  • 21. SHUNT CAPACITORS • Shunt capacitors are used for compensating reactive power of LPF. • They are used for improving the power factor. It is also used for voltage control during heavy lagging power factor loads. • They are located at the receiving stations and distribution substations. • They are switched on during heavy loads and switched off during low loads.
  • 22. SERIES CAPACITOR • Series Capacitors are used for some long EHV a.c. lines to improve power transferability. • They located at the sending end / receiving end of the lines. • They are provided with by pass circuit breaker and protective spark –gaps.
  • 23. NEUTRAL GROUNDING EQUIPMENT •Neutral Grounding Equipment are Resistors and reactors. • They are used to limit the short circuit current during ground fault. •They are connected between neutral point and ground.
  • 24. OTHER SWITCHYARD EQUIPMENTS . MARSHALLING KIOSKS . STATION EARTHING SYSTEM . POWER CABLES . CONTROL CABLES . INSULATORS . METERING, RELAY AND CONTROL PANEL . SUPPLY SYSTEM
  • 25. POWER LINE CARRIER COMMUNICATION  PLCC is mainly used for telecommunication, tele-protection and tele-monitoring between electrical substations through power lines at high voltages, such as 110 kv, 220 kv, 400 kv.  The voice signal is converted/compressed into the 300 Hz to 4000 Hz range.  It is known as :- Power line Digital Subscriber Line (PDSL) mains communication power line telecom (PLT) power line networking (PLN) Broadband over Power Lines (BPL)
  • 26. WHAT IS SCADA ? • SCADA stands for Supervisory Control And Data Acquisition. • It is not a full control system, but rather focuses on the supervisory level. • It is a purely software package that is positioned on top of hardware to which it is interfaced. ( via Programmable Logic Controllers(PLCs)) .
  • 27. The SCADA systems are arranged to perform the following tasks. • • • • • • • • Data Collection (Data Acquisition) Data transmission (telemetry) Scanning, Indication, Monitoring, Logging. Control and indication. Ensure sequential events. Data presentation, display, reporting Execution of operating, commands: on/off,raise/lower. Network supervision, alarms and report any uncommon change of state.
  • 28. PART B BUS BAR ARRANGEMENT
  • 29. CONDUCTOR USED FOR BUSES • All Aluminum conductor (AAC) • All Aluminum alloy conductor (AAAC) • Aluminum conductor with aluminum alloy reinforced (ACAR) • Aluminum conductor with steel reinforced (ACSR)
  • 30. SINGLE BUS SYATEM Advantages: 1.Simple in Design 2.Less Expenditure Disadvantages: 1.In case of bus fault or bus bar isolator fault or maintenance total Substation is out of service. 2.In case of maintenance of transformer circuit breaker the associated transformer has also to be shut-down. Similarly for Line also.
  • 31. SINGLE BUS WITH BUS SECTIONALISER Advantages: 1. One complete section can be taken out for Maintenance without disturbing the continuity of other section. 2. If a fault occurs on one section of the Bus, that faulty section alone will be isolated. Disadvantages: It will be a little more costly with the addition of one isolator and some cases with Circuit breaker, C.Ts and C&R panel.
  • 32. DOUBLE BUS SYSTEM Advantages: : Double Bus Bar Arrangement increases the flexibility of system. Disadvantages: :The arrangement does not permit breaker maintenance with out interruption.
  • 33. DOUBLE BREAKER BUS SYSTEM Advantages: There is no need of bus coupler as because the operation is done by breakers instead of isolator Disadvantages: Most expensive as it involves additional breaker, CT Isolators etc for each circuit.
  • 34. ONE AND A HALF BREAKER BUS SYSTEM Advantages: During any fault on any one of the buses, that faulty bus will be cleared instantly without interrupting any feeders in the system since all feeders will continue to feed from other healthy bus. Disadvantages: This scheme is much expensive due to investment for third breaker.
  • 35. MAIN AND TRANSFER BUS SYSTEM Switching operation: 1.First close the isolators at both side of the bus coupler breaker. 2. Then close the bypass isolator of the feeder which is to be transferred to transfer bus. 3. Now energized the transfer bus by closing the bus coupler circuit breaker from remote. 4.After bus coupler breaker is closed, now the power from main bus flows to the feeder line through its main breaker as well as bus coupler breaker viatransfer bus. 5. Now if main breaker of the feeder is switched off, total power flow will instantaneously shift to the bus coupler breaker and hence this breaker will serve the purpose of protection for the feeder. 6. At last the operating personnel open the isolators at both sides of the main circuit breaker to make it isolated from rest of the live system.
  • 36. DOUBLE BUS SYSTEM WITH BYPASS ISOLATOR Advantages: It permits breaker maintenance without interruption of power which is not possible in double bus system but it provides all the advantages of double bus system. Disadvantages: It however requires one additional isolator (bypass isolator) for each feeder circuit and introduces slight complication in system layout.
  • 37. RING BUS SYSTEM Advantages: It provides a double feed to each feeder circuit, opening one breaker under maintenance or otherwise does not affect supply to any feeder. But this system has two major disadvantages. 1. 2. 3. 4. 5. Flexibility for breaker maintenance Each breaker removable without disconnecting load Only one breaker needed per branch, Each branch connected to network by two breakers All change-over switching done with circuit-breakers & hence flexible.