2. SEWAGE TREATMENT
Sewage treatment is the process of removing
contaminants(bahan cemar) from wastewater and
household sewage, both runoff (effluents) aliran keluar
kumbahan and domestic. It includes physical,
chemical, and biological processes to remove
physical, chemical and biological contaminants.
4. 1) Pre-treatment (olahan permulaan)
Pre-treatment removes materials that can be
easily collected from the raw sewage before they
damage or clog the pumps and sewage lines of
primary treatment clarifiers (trash, tree limbs,
leaves, branches etc.
• Screening
• Grit removal
• Flow equalization
• Fat and grease removal
5. 2) Primary Treatment (pengendapan)
• sewage flows through large tanks, commonly called
"pre-settling basins", "primary sedimentation tanks"
or "primary clarifiers".
• The tanks are used to settle sludge while grease and
oils rise to the surface and are skimmed off.
• Primary settling tanks are usually equipped with
mechanically driven scrapers that continually drive
the collected sludge towards a hopper in the base of
the tank where it is pumped to sludge treatment
facilities.
• Grease and oil from the floating material can
sometimes be recovered for saponification.
6.
7. 2) Secondary treatment (olahan
biologi)
• is designed to substantially degrade the biological
content of the sewage which are derived from
human waste, food waste, soaps and detergent.
• The majority of municipal plants treat the settled
sewage liquor using aerobic biological processes.
• Secondary treatment systems are classified as fixed-
film or suspended-growth systems.
8.
9. 3) Tertiary treatment
• to provide a final treatment stage to raise the
effluent quality before it is discharged to the
receiving environment (sea, river, lake,
ground, etc.).
• More than one tertiary treatment process
may be used at any treatment plant. If
disinfection is practiced, it is always the final
process. It is also called "effluent polishing."
10.
11. SEPTIC TANK
• A septic tank is a key component of the septic
system, a small-scale sewage treatment system
common in areas with no connection to main
sewage pipes provided by local governments or
private corporations
The same tank
A septic tank before Septic tank and septic
partially installed in
installation drain field
the ground
13. Di dalam tangki septik, terdapat
satu bahagian simpanan
berbentuk segiempat bujur yang
dibina di bawah paras bumi untuk
menyimpan air buangan selama
sekurang-kurangnya 24 jam.
• Tangki septik dibahagikan kepada 2 kebuk (compartments).
• Kebuk pertama dimana berlakunya pengendapan dan pencernaan
enapcemar. Kebuk kedua pula digunakan bagi menyimpan
enapcemar yang telah dicernakan di kebuk pertama. Pepejal
terampai yang tidak mendak di dalam kebuk pertama akan
disalurkan ke dalam kebuk kedua bagi pemendakan seterusnya.
• Isipadu kebuk pertama lazimnya 2 kali ganda isipadu kebuk
kedua. Kedalaman tangki septik ialah diantara 1 hingga 2 meter
dan nisbah panjang : lebar lebih kurang 2:1 hingga 3:1.
• Mendakan enapcemar ini perlu dibuang setiap 3 hingga 5 tahun
untuk menjamin keberkesanan olahan.
14. In the Shit – A Septic Tank Guide
Two common misconceptions about
septic tanks.
1. Septic tanks are an acceptable sewage
treatment solution
2. Septic tanks are not supposed to
overflow
The first misconception is the biggy; A
septic tank on its own is not good
enough to treat sewage waste to an
acceptable standard. Further treatment
is required. The second misconception
shows a basic misunderstanding of the
processes at work in a septic tank.
This article illustrates what happens
inside a septic tank, what should happen
after the septic tank and appropriate
effluent standards to be aiming for.
15.
16. KAEDAH PENGAGIHAN EFLUEN TANGKI NAJIS
MELALUI PENAPIS BIOLOGI
Parit Penyerapan
Lubang Penyerapan
Lapisan Penapis
17. PENENTUAN SAIZ TANGKI SEPTIK DAN
PENAPIS BIOLOGI
Kaedah menentukan atau rekabentuk saiz-saiz tangki septik
dan penapis biologi melibatkan penggunaan beberapa
persamaan yang mudah. Apabila sesuatu rekabentuk itu hanya
melibatkan kumbahan dari sebuah rumah dengan bilangan
ahli yang tertentu, maka persamaan di bawah amat sesuai
untuk digunakan
C = 40p + 440 (persamaan 1)
Dimana C = Muatan tangki septik (gelen)
p = Bilangan orang
18. persamaan kedua yang lebih sesuai digunakan untuk
rekabentuk yang melibatkan air kumbahan dari suatu
kelompok kediaman seperti sebuah Flat.
C = 20p + 440 (persamaan 2)
Dimana C = Muatan tangki septik (gelen)
p = Bilangan orang
20. 2) Lubang Penyerapan
Isipadu lubang penyerapan = 2.5 x muatan tangki septik
(persamaan 4)
3) Lapisan Penapis
Muatan lapisan penapis = 0.3 x bilangan penduduk
(persamaan 5)
21. Contoh 1
Kirakan dimensi tangki septik dan parit
penyerapan untuk isi rumah yang mempunyai 8
orang penghuni.
22. Gunakan persamaan 1 untuk mengira muatan tangki
C = 40p + 440
C = (40 x 8) + 440
= 760 gelen
(Diketahui 1 gelen = 4.546 liter)
C = (760 x 4.546) / 1000
= 3.45 m3
Berdasarkan penentuan isipadu kebuk pertama 2 kali
ganda isipadu kebuk kedua, kedalaman tangki septik ialah
diantara 1 hingga 2 meter dan nisbah antara ukuran
panjang dengan lebar 2:1 hingga 3:1.
23. Kebuk pertama (1st compartment)
Muatan = (2/3) x 3.45
= 2.30 m3
Mendapatkan pilihan dimensi secara kaedah cuba jaya (try &
error)
Panjang = 1.7 m
Dalam = 1.8 m
Lebar = 0.8 m
Muatan sebenar = 2.45 m3 iaitu > 2.30 m3, maka memadai.
24. Kebuk Kedua (2nd compartment)
Muatan = (1/3) x 3.45
= 1.15 m3
Mendapatkan pilihan dimensi secara kaedah cuba jaya (try
& error)
Panjang = 1.0 m
Dalam = 1.5 m
Lebar = 0.8 m
Muatan sebenar = 1.20 m3 iaitu > 1.15 m3, maka memadai.
25.
26. Parit Penyerapan
Kemudian merekabentuk parit penyerapan menggunakan
persamaan 3
Q = 5/√T
= 5/√2
= 3.53 gelen/kaki2
(Diketahui 1 kaki = 0.3048 m)
Q = (3.53 x 4.546 / 1000 ) / 0.30482
= 0.17 m
27. Keluasan parit penyerapan ialah
A = 3.45 / 0.17
= 20.3 m2
Alirkan ke dalam dua paip berliang dan keluasan setiap
parit penyerapan adalah seperti berikut:
12.7 x 0.8 m = 10.2 m2
12.7 x 0.8 m = 10.2 m2
Jumlah = 20.4 m2 , Iaitu > 20.3 m2,
maka memadai.
28.
29. Contoh 2
Bagi tangki septik di dalam contoh 1, kira dimensi lubang
penyerapan yang diperlukan sebagi menggantikan parit
penyerapan.
Menggunakan persamaan 4 bagi mendapatkan lubang
penyerapan
Isipadu lubang penyerapan = 2.5 x muatan tangki septik
= 2.5 x 3.45
= 8.63 m3
30. Lebar dan dalam lubang penyerapan biasanya 1.2 m, oleh itu
panjangnya ialah
Panjang = Isipadu lubang penyerapan / (lebar x dalam)
Panjang = 8.63 / (1.2 x 1.2)
= 6.0 m
31. latihan
• Kirakan dimensi sebuah tangki septik dan
lapisan penapis untuk menampung satu skim
perumahan yang mengandungi 62 orang
penghuni.
• Menggunakan persamaan 2 untuk mengira
muatan tangki septik dan anggaran 0.3 m3
setiap orang untuk merekabentuk lapisan
penapis
33. Photograph of a typical
individual septic tank built
according to Malaysian
Standards (MS 1228)
• Sistem pembetungan yang banyak terdapat di Malaysia ialah tangki septik
individu.
• Dianggarkan lebih kurang 1.2 juta premis mempunyai tangki septik inidividu.
• Tangki septik individu yang sempurna iaitu mengikut Piawaian Malaysia – MS
1228 mempunyai 3 sehingga 4 penutup logam bersegi empat tepat dan pada
lazimnya berada di luar kawasan premis sama ada di bahagian hadapan,
belakang atau tepi premis.
• Adakalanya, tangki septik tersebut berada di dalam premis yang telah
diubahsuai.
• Kumbahan (najis) yang mengalir ke dalam tangki septik tidak menjalani
rawatan sepenuhnya dan oleh itu tangki septik tersebut perlu dikosongkan
secara berjadual, lebih kurang setiap dua tahun sekali; untuk memastikan
ianya berfungsi dengan efisien. IWK menyediakan perkhidmatan mandatori
dan amat penting ini untuk premis-premis kerajaan.
35. Connected Services
• Connected sewerage service Pelanggan perkhidmatan
customers have sewage outlets that pembetungan bersambung
are directly linked to a sewage mempunyai saluran paip
treatment plant via an underground pembetungan yang disambung terus
network of sewer pipes. IWK is ke loji rawatan kumbahan awam
responsible for the operations and
melalui rangkaian paip pembetungan
maintenance of all public sewage
treatment plants. Public sewage di bawah tanah. Bagi pelanggan yang
treatment plants are plants which menerima perkhidmatan ini, selalunya
have been handed over to the terdapat satu ruang kecil di luar
Government (National Water Services rumah mereka, sama ada di tepi,
Commission, Ministry of Energy, hadapan atau belakang. Ruang
Green Technology & Water) by the pemeriksaan ini mempunyai penutup
Developer. logam bersegi empat tepat dan
digunakan untuk memeriksa paip
pembetung persendirian sekiranya
terdapat masalah paip pembetungan
tersumbat.
36. (Picture of premises and connected sewerage service)
• Premise with connected sewerage service/system has one
rectangular metal cover, which is called an inspection chamber
and usually located outside the premises compound either at
the side, rear or front.
• In the inspection chamber are sewage outlets from the
premises' toilets, bathrooms and kitchen that are connected to
the public sewerage pipelines to the public sewage treatment
plant.
• If there is any blockage, the checking and clearing of the
blockage will be done via the inspection chamber.