RRVPNL, 132 KV GSS (GIS) OLD POWER HOUSE
JODHPUR (RAJ.)
submitted in partial fulfilment
for the award of the Degree of
BACHELOR OF TECHNOLOGY
(Rajasthan Technical University, Kota)
IN
Department of Electrical Engineering
Submitted To : Submitted By:
Mr. Vikas Bhalla Harish kumar
Assistant Professor EnrolmentNo.:
12ECTEE019
GAS INSULATED SUBSTATION
BY:
HARISH KUMAR
ELECTRICAL
ENGINEERING
1510-15
2
3
4
5
CONTENTS:
Substation
Conventional substations (AIS)
Limitations of AIS
The need for GIS
Introduction to GIS
Properties of SF6
GIS assembly
Advantages of GIS
Design features
Drawbacks
SF6 – Environmental concerns
SF6 /N2 mixtures
Future trends in GIS
Conclusion.
6
SUBSTATION:
• An assembly of apparatus installed to control
transmission and distribution of electric power.
A : P R I M A R Y P O W E R L I N E S ' S I D E B : S E C O N D A R Y P O W E R L I N E S ' S I D E
1 . P R I M A R Y P O W E R L I N E S 2 . G R O U N D W I R E 3 . O V E R H E A D L I N E S 4 . T R A N S F O R M E R
F O R M E A S U R E M E N T O F E L E C T R I C V O L T A G E 5 . D I S C O N N E C T S W I T C H 6 . C I R C U I T
B R E A K E R 7 . C U R R E N T T R A N S F O R M E R 8 . L I G H T N I N G A R R E S T E R 9 . M A I N
T R A N S F O R M E R 1 0 . C O N T R O L B U I L D I N G 1 1 . S E C U R I T Y F E N C E 1 2 . S E C O N D A R Y P O W E R
L I N E S
7
AIR INSULATED SUBSTATION(AIS):
Air used as a dielectric.
Normally used for outdoor substations.
In very few cases used for indoor substations.
Easy to expand (in case that space is not an
issue)
Excellent overview, simple handling and easy
access.
8
LIMITATIONS OF AIS:
Large dimensions due to statutory clearances and
poor dielectric strength of air.
Insulation deterioration with ambient conditions and
susceptibility to pollutants.
Wastage of space.
Life of steel structures degrades.
Seismic instability.
Large planning & execution time.
Regular maintenance of the substation required.
9
10
INTRODUCTION TO GAS INSULATED
SUBSTATION
What is GIS?
 A gas insulated substation is an electrical substation in which the major
structures are contained in a sealed environment with sulfur
hexafluoride gas (SF6) as the insulating medium.
Where and why Gas Insulated Substations
are used ?
 Gas Insulated Substations are used where there is space for providing
the substation is expensive in large cities and towns. In normal
substation the clearances between the phase to phase and phase to
ground is very large. Due to this, large space is required for the normal
or Air Insulated Substation (AIS).
 But the dielectric strength of SF6 gas is higher compared to the air, the
clearances required for phase to phase and phase to ground for all
equipments are quite lower. Hence, the overall size of each equipment
and the complete substation is reduced to about 10% of the
conventional air insulated substation
THE NEED FOR G.I.S:
Non availability of sufficient space.
Difficult climatic and seismic conditions at site.
Urban site (high rise building).
High altitudes.
Limitations of AIS.
11
GAS INSULATED SUBSTATION:
Introduction:
Compact, multi-component assembly.
Enclosed in a ground metallic housing.
Sulphur Hexaflouride (SF6) gas – the primary
insulating medium.
(SF6) gas- superior dielectric properties used at
moderate pressure for phase to phase and phase to
ground insulation
Preferred for voltage ratings of 72.5 kV, 145 kV, 300 kV
and 420 kV and above.
Various equipments like Circuit Breakers, Bus-Bars,
Isolators, Load Break Switches, Current
Transformers, Voltage Transformers, Earthing
Switches, etc. housed in metal enclosed modules
filled with SF6 gas.
12
PROPERTIES OF SF6:
• N O N - TO X I C , V E RY S TA B L E
C H E M I C A L LY.
• M A N - M A D E .
• L I F E T I M E – V E RY L O N G ( 8 0 0 TO
3 2 0 0 Y E A R S ! ) .
• I N S U L AT I N G P R O P E RT I E S 3 - T I M E S
T H AT O F A I R .
• C O L O R L E S S & H E AV I E R T H A N A I R .
• A L M O S T WAT E R I N S O L U B L E .
• N O N I N F L A M M A B L E .
13
14
Kalisindh Thermal Power
GIS ASSEMBLY:
ESSENTIAL PARTS OF GIS:
1. Bus bar
2. Circuit Breaker
3. Disconnector (line or bus)
4. Earthing switch (line or bus)
5. Current transformer (feeder / bus)
6. Voltage transformer (feeder/ bus)
7. Feeder Disconnector
8. Feeder Earthing switch
9. Lightning / Surge Arrester
10. Cable termination
11. Control Panel.
15
16
BUS BAR
 When a number of lines operating at the same voltage have to
directly connect electrically bus bar are used as the common
electrical component.
 There are following bus at the 132 gss:-
• 132 kv main bus bar
• 132 kv auxiliary bus bar
ISOLATOR
 Isolator is used to break the circuit under off-load
where as on-load circuit breaking is done by circuit
breaker
 Isolators are classified as:-
• Off load isolator
• On load isolator
17
18
CIRCUIT BREAKER
An automatic switch that stops the flow of
electric current in a suddenly overloaded
or otherwise abnormally stressed electric
circuit.
Types of circuit breaker:-
• Vaccum circuit breaker
• SF6 Circuit breaker
• Air blast circuit breaker
• Oil circuit breaker
19
CIRCUIT BREAKER OPERATION
MECHANISM
20
INSULATOR
Barrier insulator: The GIS is sectionalized into
individual gas compartments by means of gas-
tight barrier insulators. By this, the impact of
extension or internal faults on the overall
installation is reduced to a minimum, and control,
supervision and maintenance are greatly eased.
All flange connections are sealed by means of
age-resistant O-rings. Due to the gas tight design
of the insulators no leakage between
components can occur.
Support insulator: Support insulators are used
to mechanically support the conductors. They
mainly used for long SF6 bus duct connection.
21
22
CURRENT TRANSFORMER
Current transformer is used for measurement
of alternating electric current.
The objective of C.T. is :-
Reduce the scale of the metering scale.
Insulated the measuring instrument from
voltage.
• Used for protective system
23
24
POTENTIAL TRANSFORMER
Potential transformer is used for step down the
line voltage.
PT is connected in prallel with line.
Secondary voltage of the PT is generally 110v.
25
26
CAPACITOR
VOLTAGE
TRANSFORMER
 A capacitor voltage transformer
consists of a Capacitor Voltage
Divider (CVD) and an inductive
Intermediate Voltage Transformer
(IVT).
 The rated voltage of the complete
capacitor voltage transformer
determines the ratio at the capacitor
voltage divider.
 It is more convenient to make an
Inductive voltage transformer for
lower voltage levels and let the CVD
take care of the high voltage.
LIGHTENING ARRESTER
27
28
LIGTHNING ARRESTOR
Lightening arrester is used to protect the power station
sub station and transmission line against the voltage
wave reaching there.
It is also known as surge diverter which is connected
between line and earth to divert the incoming high
voltage to earth.
 It is the first equipment in a substation.
Generally arresters are connected in parallel with the
equipment to be protected, typically between phase and
earth for three phase installations.
29
GIS ASSEMBLY:
30
31
Supervisory Control And Data Acquisition
(SCADA)
 Supervisory Control and Data Acquisition (SCADA) offers the
ease of monitoring of sensors placed at distances, from one central
location.
 SCADA systems are used to monitor and control a plant or equipment
in industries such as telecommunications, water and waste control,
energy, oil and gas refining and transportation.
 A SCADA system gathers information, such as where a leak on a
pipeline has occurred, transfers the information back to a central site,
alerting the home station that the leak has occurred, carrying out
necessary analysis and control, such as determining if the leak is
critical, and displaying the information in a logical and organized
fashion.
 SCADA systems can be relatively simple, such as one that monitors
environmental conditions of a small office building, or incredibly
complex, such as a system that monitors all the activity in a nuclear
power plant or the activity of a municipal water system.
 SCADA systems were first used in the 1960s.
SCADA CONTROL ROOM
32
LARGE SCADA DISPLAY
33
ADVANTAGES :
Occupies very less space (1/10th) compared to
ordinary substations.
Hence, most preferred where area for substation
is small (eg: Cities)
Most reliable compared to Air Insulated
Substations.
Number of outages due to the fault is less
Maintenance Free.
Can be assembled at workshop and modules can
be commissioned in the plant easily.
Pollution free
Explosion proof & fire proof installation
Increased safety
Easy operation & long life 34
DESIGN CHALLENGES:
1 . S A F E T Y :
• O P T I M I Z I N G O P E R AT I N G E L E C T R I C A L
S T R E S S E S T O S A F E L E V E L S B Y B E T T E R
I N T E R E L E C T R O D E S PA C I N G .
• I N C R E A S I N G T H E G A S V O L U M E A N D T H E
T H E R M A L I N E R T I A O F T H E S Y S T E M T O
E N H A N C E C O O L I N G A N D R E T A I N
I N S U L AT I O N S T R E N G T H .
2 . H I G H R E L I A B I L I T Y :
• S U P E R I O R C O N T A C T S Y S T E M S F O R
C I R C U I T B R E A K E R S A N D
D I S C O N N E C T O R S .
• M U LT I - C O N T A C T A N D F R I C T I O N F R E E
S U R F A C E S I N C O R P O R AT E D F O R L O N G
O P E R AT I N G C Y C L E S .
• R U G G E D , T I M E P R O V E N O P E R AT I N G
D R I V E S U S E D .
35
GIS FAILURE STATISTICS:
57.30%
18.10%
12.40%
12.30%
INSULATION FAILURE
MECHANICAL
TROUBLE
GAS LEAK
OTHERS
36
MAIN DRAWBACKS:
• H I G H C O S T C O M PA R E D T O
C O N V E N T I O N A L S U B S TAT I O N ( A I S ) .
• E X C E S S I V E D A M A G E I N C A S E O F
I N T E R N A L FA U LT.
• D I A G N O S I S O F I N T E R N A L FA U LT A N D
R E C T I F Y I N G TA K E S V E R Y L O N G T I M E
( H I G H O U TA G E T I M E ) .
• S F 6 G A S P R E S S U R E M U S T B E
M O N I T O R E D I N E A C H C O M PA R T M E N T.
• R E D U C T I O N I N T H E P R E S S U R E O F
T H E S F 6 G A S I N A N Y
M O D U L E R E S U LT S I N F L A S H
O V E R A N D FA U LT S .
• S F 6 C A U S E S O Z O N E D E P L E T I O N A N D
G L O B A L WA R M I N G .
37
SF6 – ENVIRONMENTAL CONCERNS:
• C U R R E N T LY, 8 0 % U S E D B Y
E L E C T R I C A L P O W E R I N D U S T RY.
• O T H E R U S E S – M I C R O -
E L E C T R O N I C S ; A L & M G
P R O D U C T I O N .
• 7 0 0 0 M E T R I C TO N S / Y R I N 1 9 9 3 .
• R E A C H E D 1 0 , 0 0 0 M E T R I C TO N S / Y R
B Y 2 0 1 0 .
• T W O A R E A S O F H E A LT H A N D
E N V I R O N M E N TA L I M PA C T:
I . T H R O U G H I T S N O R M A L U S E I N A
W O R K P L A C E – A R C I N G
B Y P R O D U C T S .
I I . G L O B A L E N V I R O N M E N TA L I M PA C T 38
SF6/N2 MIXTURES FOR GIS?
• S F 6 G A S – S P E C I F I C A L LY M E N T I O N E D
I N K Y O T O P R O T O C O L .
• S M A L L Q U A N T I T I E S O F S F 6 I N N 2 C A N
I M P R O V E D I E L E C T R I C S T R E N G T H
D R A S T I C A L LY.
• A L L O F T H E D I E L E C T R I C S T R E N G T H
O F S F 6 , N E A R LY, C A N B E A C H I E V E D
B Y A D D I N G L E S S T H A N 2 0 % S F 6 I N T O
N 2 .
• S F 6 / N 2 M I X T U R E S L E S S
S U S C E P T I B L E T O E F F E C T S O F F I E L D
N O N U N I F O R M I T Y T H A N P U R E S F 6 .
• T H U S M I T I G AT I N G T H E E F F E C T S O F
PA R T I C L E S A N D S U R FA C E
P R O T R U S I O N S .
39
FUTURE TRENDS:
• C O M PA C T D E S I G N O F S W I T C H
G E A R B Y U S I N G T H R E E P H A S E
M O D U L E S .
• U S E O F VA C U U M C I R C U I T B R E A K E R
C E L L S I N T H E M E D I U M H I G H
V O LTA G E G I S .
• O P T I M I Z AT I O N O F G I S D E S I G N TO
A L L O W E A S I E R M A I N T E N A N C E .
• D E V E L O P M E N T O F D C G I S F O R
I N C O R P O R AT I N G I N TO E X PA N D I N G
N AT I O N A L / I N T E R N AT I O N A L H V D C
S Y S T E M S .
• S E A R C H F O R R E P L A C E M E N T
G A S E S F O R S F 6 . 40
CONCLUSION:
• G I S – N E C E S S A R Y F O R E X T R A H V &
U LT R A H V
• S O M E I M P O R TA N T A R E A S T O B E
S T U D I E D I N C L U D E :
• M O R E C O N S E R VAT I V E D E S I G N .
• I M P R O V E D G A S H A N D L I N G .
• D E C O M P O S I T I O N P R O D U C T
M A N A G E M E N T T E C H N I Q U E S .
• A C H I E V I N G & M A I N TA I N I N G H I G H
L E V E L S O F AVA I L A B I L I T Y R E Q U I R E –
M O R E I N T E G R AT E D A P P R O A C H T O
Q U A L I T Y C O N T R O L B Y B O T H U S E R S
A N D M A N U FA C T U R E S .
41
42

Más contenido relacionado

La actualidad más candente

ELECTRICAL DESIGN ENGINEER - RESUME
ELECTRICAL DESIGN ENGINEER -  RESUMEELECTRICAL DESIGN ENGINEER -  RESUME
ELECTRICAL DESIGN ENGINEER - RESUME
VEERABHARATHI MUNI
 
MM GUANZON, CV- MAINTENANCE ENGINEER
MM GUANZON, CV- MAINTENANCE ENGINEERMM GUANZON, CV- MAINTENANCE ENGINEER
MM GUANZON, CV- MAINTENANCE ENGINEER
jongguanzon
 
Equipments in switchyard and its protection
Equipments in switchyard and its protectionEquipments in switchyard and its protection
Equipments in switchyard and its protection
Jayashree Behera
 

La actualidad más candente (20)

ELECTRICAL ENGINEER CV, SITE ENGINEER CV, PROJECT ENGINEER CV
ELECTRICAL ENGINEER CV, SITE ENGINEER CV, PROJECT ENGINEER CVELECTRICAL ENGINEER CV, SITE ENGINEER CV, PROJECT ENGINEER CV
ELECTRICAL ENGINEER CV, SITE ENGINEER CV, PROJECT ENGINEER CV
 
Basics of plc programming
Basics of plc programmingBasics of plc programming
Basics of plc programming
 
Seminar on Gas Insulated Substation
Seminar on Gas Insulated SubstationSeminar on Gas Insulated Substation
Seminar on Gas Insulated Substation
 
VFD Basics.pptx
VFD Basics.pptxVFD Basics.pptx
VFD Basics.pptx
 
Sld for pmcc
Sld for pmccSld for pmcc
Sld for pmcc
 
Sr. Electrical & Instrument QA/QC Engineer CV
Sr. Electrical & Instrument QA/QC Engineer CVSr. Electrical & Instrument QA/QC Engineer CV
Sr. Electrical & Instrument QA/QC Engineer CV
 
TES-P-119-19-R1.pdf
TES-P-119-19-R1.pdfTES-P-119-19-R1.pdf
TES-P-119-19-R1.pdf
 
Vfd
VfdVfd
Vfd
 
Gas insulated substation
Gas insulated substationGas insulated substation
Gas insulated substation
 
ELECTRICAL DESIGN ENGINEER - RESUME
ELECTRICAL DESIGN ENGINEER -  RESUMEELECTRICAL DESIGN ENGINEER -  RESUME
ELECTRICAL DESIGN ENGINEER - RESUME
 
Gas insulated substation
Gas insulated substationGas insulated substation
Gas insulated substation
 
High Voltage Gas Insulted Switchgear (GIS) Field Testing According to IEEE C3...
High Voltage Gas Insulted Switchgear (GIS) Field Testing According to IEEE C3...High Voltage Gas Insulted Switchgear (GIS) Field Testing According to IEEE C3...
High Voltage Gas Insulted Switchgear (GIS) Field Testing According to IEEE C3...
 
Gas Insulated Switchgear? Gas-Insulated High-Voltage Switchgear (GIS)
Gas Insulated Switchgear?  Gas-Insulated High-Voltage Switchgear (GIS)Gas Insulated Switchgear?  Gas-Insulated High-Voltage Switchgear (GIS)
Gas Insulated Switchgear? Gas-Insulated High-Voltage Switchgear (GIS)
 
Characteristic of idmt curves for overcurrent relays
Characteristic of idmt curves for overcurrent relaysCharacteristic of idmt curves for overcurrent relays
Characteristic of idmt curves for overcurrent relays
 
MM GUANZON, CV- MAINTENANCE ENGINEER
MM GUANZON, CV- MAINTENANCE ENGINEERMM GUANZON, CV- MAINTENANCE ENGINEER
MM GUANZON, CV- MAINTENANCE ENGINEER
 
Design Checklist_Electrical
Design Checklist_Electrical Design Checklist_Electrical
Design Checklist_Electrical
 
Electrical Engineer
Electrical EngineerElectrical Engineer
Electrical Engineer
 
Simple 100 w inverter circuit
Simple 100 w inverter circuitSimple 100 w inverter circuit
Simple 100 w inverter circuit
 
ABB Price List -2019..pdf
ABB Price List -2019..pdfABB Price List -2019..pdf
ABB Price List -2019..pdf
 
Equipments in switchyard and its protection
Equipments in switchyard and its protectionEquipments in switchyard and its protection
Equipments in switchyard and its protection
 

Destacado

Gas insulated substation
Gas insulated substationGas insulated substation
Gas insulated substation
sharique_64
 

Destacado (12)

Gas insulated substation
Gas insulated substationGas insulated substation
Gas insulated substation
 
132 gss ppt
132 gss ppt132 gss ppt
132 gss ppt
 
27072013140225 gas-insulated-substations
27072013140225 gas-insulated-substations27072013140225 gas-insulated-substations
27072013140225 gas-insulated-substations
 
Gas insulated substation 1
Gas insulated substation 1Gas insulated substation 1
Gas insulated substation 1
 
132 kv gss
132 kv gss132 kv gss
132 kv gss
 
Mit ppt 132/33kv ppt
Mit ppt 132/33kv pptMit ppt 132/33kv ppt
Mit ppt 132/33kv ppt
 
GIS-NESCL-6
GIS-NESCL-6GIS-NESCL-6
GIS-NESCL-6
 
Sub stations-air insulated substations
Sub stations-air insulated substationsSub stations-air insulated substations
Sub stations-air insulated substations
 
Gas insulated substation.
Gas insulated substation.Gas insulated substation.
Gas insulated substation.
 
Summer Training presentation on 132/33 KV sub-station Minto park, Allahabad
Summer Training presentation on 132/33 KV sub-station Minto park, AllahabadSummer Training presentation on 132/33 KV sub-station Minto park, Allahabad
Summer Training presentation on 132/33 KV sub-station Minto park, Allahabad
 
Substation Training presentation
Substation Training presentationSubstation Training presentation
Substation Training presentation
 
Substation overview
Substation overviewSubstation overview
Substation overview
 

Similar a GSS (GIS) OLD POWER HOUSE JODHPUR

substation 101
substation 101substation 101
substation 101
danica11
 
Design of Grounding System for Substation
Design of Grounding System for SubstationDesign of Grounding System for Substation
Design of Grounding System for Substation
ijtsrd
 

Similar a GSS (GIS) OLD POWER HOUSE JODHPUR (20)

Gas insulated substation
Gas insulated substationGas insulated substation
Gas insulated substation
 
Chapter 11 Introduction to Gas Insulation Substation (GIS).pptx
Chapter 11 Introduction to Gas Insulation Substation (GIS).pptxChapter 11 Introduction to Gas Insulation Substation (GIS).pptx
Chapter 11 Introduction to Gas Insulation Substation (GIS).pptx
 
Gases insulation powerstation
Gases  insulation powerstationGases  insulation powerstation
Gases insulation powerstation
 
Gis ppt (gas insulated sub station) deepak kumar kannaujiya,
Gis ppt (gas insulated sub station)  deepak kumar kannaujiya,Gis ppt (gas insulated sub station)  deepak kumar kannaujiya,
Gis ppt (gas insulated sub station) deepak kumar kannaujiya,
 
Ppt
PptPpt
Ppt
 
Substation
Substation Substation
Substation
 
Internship ppt(santhosh).pptx
Internship ppt(santhosh).pptxInternship ppt(santhosh).pptx
Internship ppt(santhosh).pptx
 
GIS (Gas-Insulated Substation) by Bharat & Shanni
GIS (Gas-Insulated Substation) by Bharat & ShanniGIS (Gas-Insulated Substation) by Bharat & Shanni
GIS (Gas-Insulated Substation) by Bharat & Shanni
 
GIS PRESENTATION.pdf
GIS PRESENTATION.pdfGIS PRESENTATION.pdf
GIS PRESENTATION.pdf
 
Substation_fundamental.pptx
Substation_fundamental.pptxSubstation_fundamental.pptx
Substation_fundamental.pptx
 
GIS(GAS INSULATED SUBSTATION)
GIS(GAS  INSULATED  SUBSTATION) GIS(GAS  INSULATED  SUBSTATION)
GIS(GAS INSULATED SUBSTATION)
 
Gagan
GaganGagan
Gagan
 
Deepak kumar
Deepak kumarDeepak kumar
Deepak kumar
 
Gas insulated substation 2
Gas insulated substation 2Gas insulated substation 2
Gas insulated substation 2
 
FACULTY OF ENGINEERING & TECHNOLOGY , GURUKULA KANGARI UNIVERSITY ,HARIDWAR
FACULTY OF ENGINEERING & TECHNOLOGY , GURUKULA KANGARI UNIVERSITY ,HARIDWARFACULTY OF ENGINEERING & TECHNOLOGY , GURUKULA KANGARI UNIVERSITY ,HARIDWAR
FACULTY OF ENGINEERING & TECHNOLOGY , GURUKULA KANGARI UNIVERSITY ,HARIDWAR
 
substation 101
substation 101substation 101
substation 101
 
Executive summary
Executive summaryExecutive summary
Executive summary
 
Gis91
Gis91Gis91
Gis91
 
Gi e
Gi eGi e
Gi e
 
Design of Grounding System for Substation
Design of Grounding System for SubstationDesign of Grounding System for Substation
Design of Grounding System for Substation
 

GSS (GIS) OLD POWER HOUSE JODHPUR

  • 1. 1 A presentation ON RRVPNL, 132 KV GSS (GIS) OLD POWER HOUSE JODHPUR (RAJ.) submitted in partial fulfilment for the award of the Degree of BACHELOR OF TECHNOLOGY (Rajasthan Technical University, Kota) IN Department of Electrical Engineering Submitted To : Submitted By: Mr. Vikas Bhalla Harish kumar Assistant Professor EnrolmentNo.: 12ECTEE019
  • 2. GAS INSULATED SUBSTATION BY: HARISH KUMAR ELECTRICAL ENGINEERING 1510-15 2
  • 3. 3
  • 4. 4
  • 5. 5
  • 6. CONTENTS: Substation Conventional substations (AIS) Limitations of AIS The need for GIS Introduction to GIS Properties of SF6 GIS assembly Advantages of GIS Design features Drawbacks SF6 – Environmental concerns SF6 /N2 mixtures Future trends in GIS Conclusion. 6
  • 7. SUBSTATION: • An assembly of apparatus installed to control transmission and distribution of electric power. A : P R I M A R Y P O W E R L I N E S ' S I D E B : S E C O N D A R Y P O W E R L I N E S ' S I D E 1 . P R I M A R Y P O W E R L I N E S 2 . G R O U N D W I R E 3 . O V E R H E A D L I N E S 4 . T R A N S F O R M E R F O R M E A S U R E M E N T O F E L E C T R I C V O L T A G E 5 . D I S C O N N E C T S W I T C H 6 . C I R C U I T B R E A K E R 7 . C U R R E N T T R A N S F O R M E R 8 . L I G H T N I N G A R R E S T E R 9 . M A I N T R A N S F O R M E R 1 0 . C O N T R O L B U I L D I N G 1 1 . S E C U R I T Y F E N C E 1 2 . S E C O N D A R Y P O W E R L I N E S 7
  • 8. AIR INSULATED SUBSTATION(AIS): Air used as a dielectric. Normally used for outdoor substations. In very few cases used for indoor substations. Easy to expand (in case that space is not an issue) Excellent overview, simple handling and easy access. 8
  • 9. LIMITATIONS OF AIS: Large dimensions due to statutory clearances and poor dielectric strength of air. Insulation deterioration with ambient conditions and susceptibility to pollutants. Wastage of space. Life of steel structures degrades. Seismic instability. Large planning & execution time. Regular maintenance of the substation required. 9
  • 10. 10 INTRODUCTION TO GAS INSULATED SUBSTATION What is GIS?  A gas insulated substation is an electrical substation in which the major structures are contained in a sealed environment with sulfur hexafluoride gas (SF6) as the insulating medium. Where and why Gas Insulated Substations are used ?  Gas Insulated Substations are used where there is space for providing the substation is expensive in large cities and towns. In normal substation the clearances between the phase to phase and phase to ground is very large. Due to this, large space is required for the normal or Air Insulated Substation (AIS).  But the dielectric strength of SF6 gas is higher compared to the air, the clearances required for phase to phase and phase to ground for all equipments are quite lower. Hence, the overall size of each equipment and the complete substation is reduced to about 10% of the conventional air insulated substation
  • 11. THE NEED FOR G.I.S: Non availability of sufficient space. Difficult climatic and seismic conditions at site. Urban site (high rise building). High altitudes. Limitations of AIS. 11
  • 12. GAS INSULATED SUBSTATION: Introduction: Compact, multi-component assembly. Enclosed in a ground metallic housing. Sulphur Hexaflouride (SF6) gas – the primary insulating medium. (SF6) gas- superior dielectric properties used at moderate pressure for phase to phase and phase to ground insulation Preferred for voltage ratings of 72.5 kV, 145 kV, 300 kV and 420 kV and above. Various equipments like Circuit Breakers, Bus-Bars, Isolators, Load Break Switches, Current Transformers, Voltage Transformers, Earthing Switches, etc. housed in metal enclosed modules filled with SF6 gas. 12
  • 13. PROPERTIES OF SF6: • N O N - TO X I C , V E RY S TA B L E C H E M I C A L LY. • M A N - M A D E . • L I F E T I M E – V E RY L O N G ( 8 0 0 TO 3 2 0 0 Y E A R S ! ) . • I N S U L AT I N G P R O P E RT I E S 3 - T I M E S T H AT O F A I R . • C O L O R L E S S & H E AV I E R T H A N A I R . • A L M O S T WAT E R I N S O L U B L E . • N O N I N F L A M M A B L E . 13
  • 15. GIS ASSEMBLY: ESSENTIAL PARTS OF GIS: 1. Bus bar 2. Circuit Breaker 3. Disconnector (line or bus) 4. Earthing switch (line or bus) 5. Current transformer (feeder / bus) 6. Voltage transformer (feeder/ bus) 7. Feeder Disconnector 8. Feeder Earthing switch 9. Lightning / Surge Arrester 10. Cable termination 11. Control Panel. 15
  • 16. 16 BUS BAR  When a number of lines operating at the same voltage have to directly connect electrically bus bar are used as the common electrical component.  There are following bus at the 132 gss:- • 132 kv main bus bar • 132 kv auxiliary bus bar ISOLATOR  Isolator is used to break the circuit under off-load where as on-load circuit breaking is done by circuit breaker  Isolators are classified as:- • Off load isolator • On load isolator
  • 17. 17
  • 18. 18 CIRCUIT BREAKER An automatic switch that stops the flow of electric current in a suddenly overloaded or otherwise abnormally stressed electric circuit. Types of circuit breaker:- • Vaccum circuit breaker • SF6 Circuit breaker • Air blast circuit breaker • Oil circuit breaker
  • 20. 20 INSULATOR Barrier insulator: The GIS is sectionalized into individual gas compartments by means of gas- tight barrier insulators. By this, the impact of extension or internal faults on the overall installation is reduced to a minimum, and control, supervision and maintenance are greatly eased. All flange connections are sealed by means of age-resistant O-rings. Due to the gas tight design of the insulators no leakage between components can occur. Support insulator: Support insulators are used to mechanically support the conductors. They mainly used for long SF6 bus duct connection.
  • 21. 21
  • 22. 22
  • 23. CURRENT TRANSFORMER Current transformer is used for measurement of alternating electric current. The objective of C.T. is :- Reduce the scale of the metering scale. Insulated the measuring instrument from voltage. • Used for protective system 23
  • 24. 24
  • 25. POTENTIAL TRANSFORMER Potential transformer is used for step down the line voltage. PT is connected in prallel with line. Secondary voltage of the PT is generally 110v. 25
  • 26. 26 CAPACITOR VOLTAGE TRANSFORMER  A capacitor voltage transformer consists of a Capacitor Voltage Divider (CVD) and an inductive Intermediate Voltage Transformer (IVT).  The rated voltage of the complete capacitor voltage transformer determines the ratio at the capacitor voltage divider.  It is more convenient to make an Inductive voltage transformer for lower voltage levels and let the CVD take care of the high voltage.
  • 28. 28 LIGTHNING ARRESTOR Lightening arrester is used to protect the power station sub station and transmission line against the voltage wave reaching there. It is also known as surge diverter which is connected between line and earth to divert the incoming high voltage to earth.  It is the first equipment in a substation. Generally arresters are connected in parallel with the equipment to be protected, typically between phase and earth for three phase installations.
  • 29. 29
  • 31. 31 Supervisory Control And Data Acquisition (SCADA)  Supervisory Control and Data Acquisition (SCADA) offers the ease of monitoring of sensors placed at distances, from one central location.  SCADA systems are used to monitor and control a plant or equipment in industries such as telecommunications, water and waste control, energy, oil and gas refining and transportation.  A SCADA system gathers information, such as where a leak on a pipeline has occurred, transfers the information back to a central site, alerting the home station that the leak has occurred, carrying out necessary analysis and control, such as determining if the leak is critical, and displaying the information in a logical and organized fashion.  SCADA systems can be relatively simple, such as one that monitors environmental conditions of a small office building, or incredibly complex, such as a system that monitors all the activity in a nuclear power plant or the activity of a municipal water system.  SCADA systems were first used in the 1960s.
  • 34. ADVANTAGES : Occupies very less space (1/10th) compared to ordinary substations. Hence, most preferred where area for substation is small (eg: Cities) Most reliable compared to Air Insulated Substations. Number of outages due to the fault is less Maintenance Free. Can be assembled at workshop and modules can be commissioned in the plant easily. Pollution free Explosion proof & fire proof installation Increased safety Easy operation & long life 34
  • 35. DESIGN CHALLENGES: 1 . S A F E T Y : • O P T I M I Z I N G O P E R AT I N G E L E C T R I C A L S T R E S S E S T O S A F E L E V E L S B Y B E T T E R I N T E R E L E C T R O D E S PA C I N G . • I N C R E A S I N G T H E G A S V O L U M E A N D T H E T H E R M A L I N E R T I A O F T H E S Y S T E M T O E N H A N C E C O O L I N G A N D R E T A I N I N S U L AT I O N S T R E N G T H . 2 . H I G H R E L I A B I L I T Y : • S U P E R I O R C O N T A C T S Y S T E M S F O R C I R C U I T B R E A K E R S A N D D I S C O N N E C T O R S . • M U LT I - C O N T A C T A N D F R I C T I O N F R E E S U R F A C E S I N C O R P O R AT E D F O R L O N G O P E R AT I N G C Y C L E S . • R U G G E D , T I M E P R O V E N O P E R AT I N G D R I V E S U S E D . 35
  • 36. GIS FAILURE STATISTICS: 57.30% 18.10% 12.40% 12.30% INSULATION FAILURE MECHANICAL TROUBLE GAS LEAK OTHERS 36
  • 37. MAIN DRAWBACKS: • H I G H C O S T C O M PA R E D T O C O N V E N T I O N A L S U B S TAT I O N ( A I S ) . • E X C E S S I V E D A M A G E I N C A S E O F I N T E R N A L FA U LT. • D I A G N O S I S O F I N T E R N A L FA U LT A N D R E C T I F Y I N G TA K E S V E R Y L O N G T I M E ( H I G H O U TA G E T I M E ) . • S F 6 G A S P R E S S U R E M U S T B E M O N I T O R E D I N E A C H C O M PA R T M E N T. • R E D U C T I O N I N T H E P R E S S U R E O F T H E S F 6 G A S I N A N Y M O D U L E R E S U LT S I N F L A S H O V E R A N D FA U LT S . • S F 6 C A U S E S O Z O N E D E P L E T I O N A N D G L O B A L WA R M I N G . 37
  • 38. SF6 – ENVIRONMENTAL CONCERNS: • C U R R E N T LY, 8 0 % U S E D B Y E L E C T R I C A L P O W E R I N D U S T RY. • O T H E R U S E S – M I C R O - E L E C T R O N I C S ; A L & M G P R O D U C T I O N . • 7 0 0 0 M E T R I C TO N S / Y R I N 1 9 9 3 . • R E A C H E D 1 0 , 0 0 0 M E T R I C TO N S / Y R B Y 2 0 1 0 . • T W O A R E A S O F H E A LT H A N D E N V I R O N M E N TA L I M PA C T: I . T H R O U G H I T S N O R M A L U S E I N A W O R K P L A C E – A R C I N G B Y P R O D U C T S . I I . G L O B A L E N V I R O N M E N TA L I M PA C T 38
  • 39. SF6/N2 MIXTURES FOR GIS? • S F 6 G A S – S P E C I F I C A L LY M E N T I O N E D I N K Y O T O P R O T O C O L . • S M A L L Q U A N T I T I E S O F S F 6 I N N 2 C A N I M P R O V E D I E L E C T R I C S T R E N G T H D R A S T I C A L LY. • A L L O F T H E D I E L E C T R I C S T R E N G T H O F S F 6 , N E A R LY, C A N B E A C H I E V E D B Y A D D I N G L E S S T H A N 2 0 % S F 6 I N T O N 2 . • S F 6 / N 2 M I X T U R E S L E S S S U S C E P T I B L E T O E F F E C T S O F F I E L D N O N U N I F O R M I T Y T H A N P U R E S F 6 . • T H U S M I T I G AT I N G T H E E F F E C T S O F PA R T I C L E S A N D S U R FA C E P R O T R U S I O N S . 39
  • 40. FUTURE TRENDS: • C O M PA C T D E S I G N O F S W I T C H G E A R B Y U S I N G T H R E E P H A S E M O D U L E S . • U S E O F VA C U U M C I R C U I T B R E A K E R C E L L S I N T H E M E D I U M H I G H V O LTA G E G I S . • O P T I M I Z AT I O N O F G I S D E S I G N TO A L L O W E A S I E R M A I N T E N A N C E . • D E V E L O P M E N T O F D C G I S F O R I N C O R P O R AT I N G I N TO E X PA N D I N G N AT I O N A L / I N T E R N AT I O N A L H V D C S Y S T E M S . • S E A R C H F O R R E P L A C E M E N T G A S E S F O R S F 6 . 40
  • 41. CONCLUSION: • G I S – N E C E S S A R Y F O R E X T R A H V & U LT R A H V • S O M E I M P O R TA N T A R E A S T O B E S T U D I E D I N C L U D E : • M O R E C O N S E R VAT I V E D E S I G N . • I M P R O V E D G A S H A N D L I N G . • D E C O M P O S I T I O N P R O D U C T M A N A G E M E N T T E C H N I Q U E S . • A C H I E V I N G & M A I N TA I N I N G H I G H L E V E L S O F AVA I L A B I L I T Y R E Q U I R E – M O R E I N T E G R AT E D A P P R O A C H T O Q U A L I T Y C O N T R O L B Y B O T H U S E R S A N D M A N U FA C T U R E S . 41
  • 42. 42