Sizing Roof vent for your home.


ridge vent size per sq. ft.
Let's do some math.

house is 40 feet long by 30 feet deep, or 1,200 sq ft. This is the 'attic area' which
includes a 2 foot overhang, not the 'house area'.

Required ventilation is 1:300 if 50% or more is near the ridge, 1:150 if soffit vents
only.

1,200 sq ft / 300 = 4 sq ft / 2 = 2 sq ft. If *at least* 2 sq ft of net free vent area is at
the ridge, then we can use the 1:300, otherwise we need to use the 1:150 rule.

Okie dokie, the ridge is 40 feet long, or 480 inches long less 21 x 1.5 = 31.5 inches
for a total open area of 448.5 inches.

The ridge vent slot in the sheathing is 3/4 inch to each side of the ridge board, or 1-
1/2 inches wide total. 1.5 X 448.5 = 672.75 sq inches.

672.75 sq inches / 144 = 4.67 sq ft That makes it doable, now, though, what is the
net free vent area of the ridge vent itself?

This will be given in sq inches per linear foot.

The net free vent area of the ridge openings are 672.75 sq inches / 40 = 16.8 sq
inches per linear foot. Thus, as long as the given sq inches of ridge vent are less
than 16.8 inches per linear foot, that 3/4 inch cut out to each side of the ridge is
going to be adequate.

Anyone want to check my math and make I did it right? Thanks.

Re: ridge vent size
The minimum and maximum width of the slot are not usually specified by code but
by the manufacturer's installation instructions. The code will let you figure out the
minimum square inches of net free vent area NFVA) that you need.
Sizing Roof vent for your home.


The manufacturer makes a vent that has a certain amount (in square inches) of net
free vent area per lineal foot of ridge. This sets a limit on how narrow the slot can
be, so that the vent and not the slot is the limiting factor on air flow through the
vent. The vent itself will be made to a certain width and only extends to cover the
roof a few inches on either side of the ridge. The manufacturer will specify a
maximum slot width which, if not exceeded, should ensure a watertight joint
between the vent and the roof covering.

Let's go back to that minimum slot width again and see how narrow it could be.
I've seen typical ridge vents with NFVA as low as 9 sq in per ft of ridge and as
high as about 18-20. Take that low flow vent at 9 sq in/ft. If you use that one, you
need at least 9/12 or 3/4" total width of a slot (clear of the ridge board) or 3/8" on
either side of the ridge. This is to ensure that the vent, and not the slot, is limiting
air flow. Take a higher flow vent at 18 sq ft/in. On that one you need 18/12 or 1.5
inches minimum total width (clear of the ridge board) or 3/4" on each side if the
ridge. Cutting slots wider than the minimum based on the NFVA of the vent you
are using does nothing to increase ventilation; it increases the chances that the vent
will leak.

Check on Jerry's math:

2006 IRC 806.2 has the requirements.
Quote:
§RR806.2 Minimum area. The total net free ventilating area shall not be less than
1/150 of the area of the space ventilated except that reduction of the total area
1/300 is permitted, provided at least 50 percent and not more than 80 percent of the
required ventilating area is provided by ventilators located in the upper portion of
the space to be ventilated at least 3 feet above eave or cornice vents with the
balance of the required ventilation provided by eave or cornice vents. As an
alternative, the net free cross-ventilation area may be reduced to 1/300 when a
vapor barrier having a transmission rate not exceeding 1 perm is installed on the
warm-in-winter side of the ceiling.
Let's assume a gable roof and our ventilated space (inside the attic) is 40 feet long
(at the ridge) by 30 feet wide (eave to eave) or 1200 sq ft.
Sizing Roof vent for your home.

Using 1/150, the required total NFVA is at least 8 sq ft. Using 1/300, it is at least 4
sq ft.

Let's assume worst case of NO soffit vents and either no vapor barrier or one with
an effective perm greater than 1. If we cut a slot along the entire length of the ridge
inside the gable end walls (assumed to be 40 feet), we would need a minimum
clear slot width (8 sq ft / 40 ft) x (12 in/ft) = 2.4 inches (total on both sides of the
ridge board). For this to work, we'd need to find a vent that provided at least 29 sq
inch NFVA per foot of ridge. (Note - some manuf say you couldn't do this
configuration with their vents, because their install instructions specify use of their
vent in conjunction with soffit vents.)

Let's assume a more typical case where we have soffit vents and they provide at
least 50 percent of the required NFVA. Now we can use 1/300 which requires 4 sq
ft total. We are going to meet that by providing 1 sq ft at each soffit and 2 sq ft at
the ridge. Our slot running the full length of the ridge (inside the gable end walls)
can be reduced to (2 sq ft / 40 ft) x (12 in/ft) = 0.6 inches (total on both sides of the
ridge board). For this to work, we'd need to find a vent that provided at least 7.2 sq
inch NFVA per foot of ridge and run it the full 40 feet.

Let's say we want to use one of those low profile ridge vents with the filter inside,
that provides NFVA of 9 sq in/foot. For this vent we would need a slot 3/4 inches
wide and (2 sq ft x 144 sq in/sq ft) divided by (9 sq in/foot) = 32 feet long. Use one
of those higher flow ridge vents (NFVA of 18 in/foot) and you need a slot 1.5
inches wide (3/4" on each side of ridge board) and only (2 sq ft x 144 sq in/sq ft)
divided by (18 sq in/ft) = 16 feet long. In theory, you could use that higher flow
vent on a 3/4 inch slot if you ran it for 32 feet. BUT code says you must follow the
manufacturer’s instructions and they will tell you how wide of a slot to cut for their
vent.

Más contenido relacionado

Destacado

RMPG Learning Series CRM Workshop Day 2 session 3
RMPG Learning Series CRM Workshop Day 2 session 3RMPG Learning Series CRM Workshop Day 2 session 3
RMPG Learning Series CRM Workshop Day 2 session 3iNFiNiTi HR Company Limited
 
עמדת הקואליציה בנוגע להחלטות מועצת מרקרעי ישראל
עמדת הקואליציה בנוגע להחלטות מועצת מרקרעי ישראלעמדת הקואליציה בנוגע להחלטות מועצת מרקרעי ישראל
עמדת הקואליציה בנוגע להחלטות מועצת מרקרעי ישראלacri009
 
ערר על החלטת הועדה המחוזית ת"א בעניין תוכנית צפון מערב תא/3700
ערר על החלטת הועדה המחוזית ת"א בעניין תוכנית צפון מערב תא/3700ערר על החלטת הועדה המחוזית ת"א בעניין תוכנית צפון מערב תא/3700
ערר על החלטת הועדה המחוזית ת"א בעניין תוכנית צפון מערב תא/3700acri009
 
דו"ח המלצות לחברי הוד"לים
דו"ח המלצות לחברי הוד"ליםדו"ח המלצות לחברי הוד"לים
דו"ח המלצות לחברי הוד"ליםacri009
 
Swing down chariot.
Swing down chariot.Swing down chariot.
Swing down chariot.Linnea Good
 
Prayer to friends
Prayer to friendsPrayer to friends
Prayer to friendsLinnea Good
 
Social Media Best Practices 2014
Social Media Best Practices 2014Social Media Best Practices 2014
Social Media Best Practices 2014Flightpath Inc
 
13 old tyme gospel medley west can2010
13 old tyme gospel medley west can201013 old tyme gospel medley west can2010
13 old tyme gospel medley west can2010Linnea Good
 

Destacado (20)

Sizing roof vent for your home.
Sizing roof vent for your home.Sizing roof vent for your home.
Sizing roof vent for your home.
 
Ahit transcript
Ahit transcriptAhit transcript
Ahit transcript
 
RMPG Learning Series CRM Workshop Day 2 session 3
RMPG Learning Series CRM Workshop Day 2 session 3RMPG Learning Series CRM Workshop Day 2 session 3
RMPG Learning Series CRM Workshop Day 2 session 3
 
For the beauty
For the beautyFor the beauty
For the beauty
 
עמדת הקואליציה בנוגע להחלטות מועצת מרקרעי ישראל
עמדת הקואליציה בנוגע להחלטות מועצת מרקרעי ישראלעמדת הקואליציה בנוגע להחלטות מועצת מרקרעי ישראל
עמדת הקואליציה בנוגע להחלטות מועצת מרקרעי ישראל
 
ערר על החלטת הועדה המחוזית ת"א בעניין תוכנית צפון מערב תא/3700
ערר על החלטת הועדה המחוזית ת"א בעניין תוכנית צפון מערב תא/3700ערר על החלטת הועדה המחוזית ת"א בעניין תוכנית צפון מערב תא/3700
ערר על החלטת הועדה המחוזית ת"א בעניין תוכנית צפון מערב תא/3700
 
Jubilee!
Jubilee!Jubilee!
Jubilee!
 
ACSFS_O_BIOYVESSIMONEAU.pdf
ACSFS_O_BIOYVESSIMONEAU.pdfACSFS_O_BIOYVESSIMONEAU.pdf
ACSFS_O_BIOYVESSIMONEAU.pdf
 
sec9_technical-specifications.pdf
sec9_technical-specifications.pdfsec9_technical-specifications.pdf
sec9_technical-specifications.pdf
 
Lucky me
Lucky meLucky me
Lucky me
 
דו"ח המלצות לחברי הוד"לים
דו"ח המלצות לחברי הוד"ליםדו"ח המלצות לחברי הוד"לים
דו"ח המלצות לחברי הוד"לים
 
When a poor one
When a poor oneWhen a poor one
When a poor one
 
See amid
See amidSee amid
See amid
 
Guide my feet
Guide my feetGuide my feet
Guide my feet
 
Take my life
Take my lifeTake my life
Take my life
 
Bad hair day
Bad hair dayBad hair day
Bad hair day
 
Swing down chariot.
Swing down chariot.Swing down chariot.
Swing down chariot.
 
Prayer to friends
Prayer to friendsPrayer to friends
Prayer to friends
 
Social Media Best Practices 2014
Social Media Best Practices 2014Social Media Best Practices 2014
Social Media Best Practices 2014
 
13 old tyme gospel medley west can2010
13 old tyme gospel medley west can201013 old tyme gospel medley west can2010
13 old tyme gospel medley west can2010
 

Similar a Calculating roof vent size for your home under 40 characters

Management of Poultry House Ventilation by Dr.Muhammad Ashiq Toor
Management of Poultry House Ventilation  by Dr.Muhammad Ashiq ToorManagement of Poultry House Ventilation  by Dr.Muhammad Ashiq Toor
Management of Poultry House Ventilation by Dr.Muhammad Ashiq ToorAshiq Toor
 
Vent-Top X 1 and X 2 2005
Vent-Top X 1 and X 2 2005Vent-Top X 1 and X 2 2005
Vent-Top X 1 and X 2 2005Mike Coughlin
 
Design of active summer cooling system
Design of active summer cooling systemDesign of active summer cooling system
Design of active summer cooling systemAjay Singh Lodhi
 
59446885 hvac
59446885 hvac59446885 hvac
59446885 hvacbhattbhai
 
How To Install Cedar Shingles
How To Install Cedar ShinglesHow To Install Cedar Shingles
How To Install Cedar Shingleswildeagle
 
Deck structural design
Deck structural designDeck structural design
Deck structural designZulaiha Amaria
 
Design of active winter cooling system
Design of active winter cooling systemDesign of active winter cooling system
Design of active winter cooling systemAjay Singh Lodhi
 
Brioler management in cold weather part1
Brioler management in cold weather part1Brioler management in cold weather part1
Brioler management in cold weather part1Dr.Muhammad Awais
 
Unico Small Duct Air Handler Replacement Guide Carried by Unique Indoor Comfo...
Unico Small Duct Air Handler Replacement Guide Carried by Unique Indoor Comfo...Unico Small Duct Air Handler Replacement Guide Carried by Unique Indoor Comfo...
Unico Small Duct Air Handler Replacement Guide Carried by Unique Indoor Comfo...UniqueIndoorComfortLibertyville
 
Acoustical Design Considerations
Acoustical Design ConsiderationsAcoustical Design Considerations
Acoustical Design ConsiderationsIllinois ASHRAE
 
Air-5 final - Copy.pptx
Air-5 final - Copy.pptxAir-5 final - Copy.pptx
Air-5 final - Copy.pptxdejene1234567
 
Installing deck stairs
Installing deck stairsInstalling deck stairs
Installing deck stairsZulaiha Amaria
 
Visual dictionary FINAL COMPLETE REAL
Visual dictionary FINAL COMPLETE REALVisual dictionary FINAL COMPLETE REAL
Visual dictionary FINAL COMPLETE REALSp10Downspout
 
Visual dictionary COMPLETE
Visual dictionary COMPLETEVisual dictionary COMPLETE
Visual dictionary COMPLETESp10Downspout
 

Similar a Calculating roof vent size for your home under 40 characters (20)

Management of Poultry House Ventilation by Dr.Muhammad Ashiq Toor
Management of Poultry House Ventilation  by Dr.Muhammad Ashiq ToorManagement of Poultry House Ventilation  by Dr.Muhammad Ashiq Toor
Management of Poultry House Ventilation by Dr.Muhammad Ashiq Toor
 
Vent-Top X 1 and X 2 2005
Vent-Top X 1 and X 2 2005Vent-Top X 1 and X 2 2005
Vent-Top X 1 and X 2 2005
 
Design of active summer cooling system
Design of active summer cooling systemDesign of active summer cooling system
Design of active summer cooling system
 
Duct design
Duct designDuct design
Duct design
 
59446885 hvac
59446885 hvac59446885 hvac
59446885 hvac
 
How To Install Cedar Shingles
How To Install Cedar ShinglesHow To Install Cedar Shingles
How To Install Cedar Shingles
 
Deck structural design
Deck structural designDeck structural design
Deck structural design
 
Design of active winter cooling system
Design of active winter cooling systemDesign of active winter cooling system
Design of active winter cooling system
 
Brioler management in cold weather part1
Brioler management in cold weather part1Brioler management in cold weather part1
Brioler management in cold weather part1
 
Duct design
Duct designDuct design
Duct design
 
Hot Weather Ventilation
Hot Weather VentilationHot Weather Ventilation
Hot Weather Ventilation
 
Unico Small Duct Air Handler Replacement Guide Carried by Unique Indoor Comfo...
Unico Small Duct Air Handler Replacement Guide Carried by Unique Indoor Comfo...Unico Small Duct Air Handler Replacement Guide Carried by Unique Indoor Comfo...
Unico Small Duct Air Handler Replacement Guide Carried by Unique Indoor Comfo...
 
Designing an HVAC System
Designing an HVAC SystemDesigning an HVAC System
Designing an HVAC System
 
Acoustical Design Considerations
Acoustical Design ConsiderationsAcoustical Design Considerations
Acoustical Design Considerations
 
analysis-of-uniformity-and-energy-consumption.pdf
analysis-of-uniformity-and-energy-consumption.pdfanalysis-of-uniformity-and-energy-consumption.pdf
analysis-of-uniformity-and-energy-consumption.pdf
 
Air-5 final - Copy.pptx
Air-5 final - Copy.pptxAir-5 final - Copy.pptx
Air-5 final - Copy.pptx
 
Installing deck stairs
Installing deck stairsInstalling deck stairs
Installing deck stairs
 
Air distribution Product
Air distribution ProductAir distribution Product
Air distribution Product
 
Visual dictionary FINAL COMPLETE REAL
Visual dictionary FINAL COMPLETE REALVisual dictionary FINAL COMPLETE REAL
Visual dictionary FINAL COMPLETE REAL
 
Visual dictionary COMPLETE
Visual dictionary COMPLETEVisual dictionary COMPLETE
Visual dictionary COMPLETE
 

Último

RE Capital's Visionary Leadership under Newman Leech
RE Capital's Visionary Leadership under Newman LeechRE Capital's Visionary Leadership under Newman Leech
RE Capital's Visionary Leadership under Newman LeechNewman George Leech
 
Sales & Marketing Alignment: How to Synergize for Success
Sales & Marketing Alignment: How to Synergize for SuccessSales & Marketing Alignment: How to Synergize for Success
Sales & Marketing Alignment: How to Synergize for SuccessAggregage
 
The Coffee Bean & Tea Leaf(CBTL), Business strategy case study
The Coffee Bean & Tea Leaf(CBTL), Business strategy case studyThe Coffee Bean & Tea Leaf(CBTL), Business strategy case study
The Coffee Bean & Tea Leaf(CBTL), Business strategy case studyEthan lee
 
Regression analysis: Simple Linear Regression Multiple Linear Regression
Regression analysis:  Simple Linear Regression Multiple Linear RegressionRegression analysis:  Simple Linear Regression Multiple Linear Regression
Regression analysis: Simple Linear Regression Multiple Linear RegressionRavindra Nath Shukla
 
DEPED Work From Home WORKWEEK-PLAN.docx
DEPED Work From Home  WORKWEEK-PLAN.docxDEPED Work From Home  WORKWEEK-PLAN.docx
DEPED Work From Home WORKWEEK-PLAN.docxRodelinaLaud
 
Call Girls Navi Mumbai Just Call 9907093804 Top Class Call Girl Service Avail...
Call Girls Navi Mumbai Just Call 9907093804 Top Class Call Girl Service Avail...Call Girls Navi Mumbai Just Call 9907093804 Top Class Call Girl Service Avail...
Call Girls Navi Mumbai Just Call 9907093804 Top Class Call Girl Service Avail...Dipal Arora
 
Call Girls In DLf Gurgaon ➥99902@11544 ( Best price)100% Genuine Escort In 24...
Call Girls In DLf Gurgaon ➥99902@11544 ( Best price)100% Genuine Escort In 24...Call Girls In DLf Gurgaon ➥99902@11544 ( Best price)100% Genuine Escort In 24...
Call Girls In DLf Gurgaon ➥99902@11544 ( Best price)100% Genuine Escort In 24...lizamodels9
 
Mysore Call Girls 8617370543 WhatsApp Number 24x7 Best Services
Mysore Call Girls 8617370543 WhatsApp Number 24x7 Best ServicesMysore Call Girls 8617370543 WhatsApp Number 24x7 Best Services
Mysore Call Girls 8617370543 WhatsApp Number 24x7 Best ServicesDipal Arora
 
Catalogue ONG NƯỚC uPVC - HDPE DE NHAT.pdf
Catalogue ONG NƯỚC uPVC - HDPE DE NHAT.pdfCatalogue ONG NƯỚC uPVC - HDPE DE NHAT.pdf
Catalogue ONG NƯỚC uPVC - HDPE DE NHAT.pdfOrient Homes
 
A DAY IN THE LIFE OF A SALESMAN / WOMAN
A DAY IN THE LIFE OF A  SALESMAN / WOMANA DAY IN THE LIFE OF A  SALESMAN / WOMAN
A DAY IN THE LIFE OF A SALESMAN / WOMANIlamathiKannappan
 
Grateful 7 speech thanking everyone that has helped.pdf
Grateful 7 speech thanking everyone that has helped.pdfGrateful 7 speech thanking everyone that has helped.pdf
Grateful 7 speech thanking everyone that has helped.pdfPaul Menig
 
VIP Kolkata Call Girl Howrah 👉 8250192130 Available With Room
VIP Kolkata Call Girl Howrah 👉 8250192130  Available With RoomVIP Kolkata Call Girl Howrah 👉 8250192130  Available With Room
VIP Kolkata Call Girl Howrah 👉 8250192130 Available With Roomdivyansh0kumar0
 
Eni 2024 1Q Results - 24.04.24 business.
Eni 2024 1Q Results - 24.04.24 business.Eni 2024 1Q Results - 24.04.24 business.
Eni 2024 1Q Results - 24.04.24 business.Eni
 
Enhancing and Restoring Safety & Quality Cultures - Dave Litwiller - May 2024...
Enhancing and Restoring Safety & Quality Cultures - Dave Litwiller - May 2024...Enhancing and Restoring Safety & Quality Cultures - Dave Litwiller - May 2024...
Enhancing and Restoring Safety & Quality Cultures - Dave Litwiller - May 2024...Dave Litwiller
 
Monthly Social Media Update April 2024 pptx.pptx
Monthly Social Media Update April 2024 pptx.pptxMonthly Social Media Update April 2024 pptx.pptx
Monthly Social Media Update April 2024 pptx.pptxAndy Lambert
 
Call Girls In Panjim North Goa 9971646499 Genuine Service
Call Girls In Panjim North Goa 9971646499 Genuine ServiceCall Girls In Panjim North Goa 9971646499 Genuine Service
Call Girls In Panjim North Goa 9971646499 Genuine Serviceritikaroy0888
 
Progress Report - Oracle Database Analyst Summit
Progress  Report - Oracle Database Analyst SummitProgress  Report - Oracle Database Analyst Summit
Progress Report - Oracle Database Analyst SummitHolger Mueller
 
Socio-economic-Impact-of-business-consumers-suppliers-and.pptx
Socio-economic-Impact-of-business-consumers-suppliers-and.pptxSocio-economic-Impact-of-business-consumers-suppliers-and.pptx
Socio-economic-Impact-of-business-consumers-suppliers-and.pptxtrishalcan8
 
Russian Faridabad Call Girls(Badarpur) : ☎ 8168257667, @4999
Russian Faridabad Call Girls(Badarpur) : ☎ 8168257667, @4999Russian Faridabad Call Girls(Badarpur) : ☎ 8168257667, @4999
Russian Faridabad Call Girls(Badarpur) : ☎ 8168257667, @4999Tina Ji
 

Último (20)

RE Capital's Visionary Leadership under Newman Leech
RE Capital's Visionary Leadership under Newman LeechRE Capital's Visionary Leadership under Newman Leech
RE Capital's Visionary Leadership under Newman Leech
 
Best Practices for Implementing an External Recruiting Partnership
Best Practices for Implementing an External Recruiting PartnershipBest Practices for Implementing an External Recruiting Partnership
Best Practices for Implementing an External Recruiting Partnership
 
Sales & Marketing Alignment: How to Synergize for Success
Sales & Marketing Alignment: How to Synergize for SuccessSales & Marketing Alignment: How to Synergize for Success
Sales & Marketing Alignment: How to Synergize for Success
 
The Coffee Bean & Tea Leaf(CBTL), Business strategy case study
The Coffee Bean & Tea Leaf(CBTL), Business strategy case studyThe Coffee Bean & Tea Leaf(CBTL), Business strategy case study
The Coffee Bean & Tea Leaf(CBTL), Business strategy case study
 
Regression analysis: Simple Linear Regression Multiple Linear Regression
Regression analysis:  Simple Linear Regression Multiple Linear RegressionRegression analysis:  Simple Linear Regression Multiple Linear Regression
Regression analysis: Simple Linear Regression Multiple Linear Regression
 
DEPED Work From Home WORKWEEK-PLAN.docx
DEPED Work From Home  WORKWEEK-PLAN.docxDEPED Work From Home  WORKWEEK-PLAN.docx
DEPED Work From Home WORKWEEK-PLAN.docx
 
Call Girls Navi Mumbai Just Call 9907093804 Top Class Call Girl Service Avail...
Call Girls Navi Mumbai Just Call 9907093804 Top Class Call Girl Service Avail...Call Girls Navi Mumbai Just Call 9907093804 Top Class Call Girl Service Avail...
Call Girls Navi Mumbai Just Call 9907093804 Top Class Call Girl Service Avail...
 
Call Girls In DLf Gurgaon ➥99902@11544 ( Best price)100% Genuine Escort In 24...
Call Girls In DLf Gurgaon ➥99902@11544 ( Best price)100% Genuine Escort In 24...Call Girls In DLf Gurgaon ➥99902@11544 ( Best price)100% Genuine Escort In 24...
Call Girls In DLf Gurgaon ➥99902@11544 ( Best price)100% Genuine Escort In 24...
 
Mysore Call Girls 8617370543 WhatsApp Number 24x7 Best Services
Mysore Call Girls 8617370543 WhatsApp Number 24x7 Best ServicesMysore Call Girls 8617370543 WhatsApp Number 24x7 Best Services
Mysore Call Girls 8617370543 WhatsApp Number 24x7 Best Services
 
Catalogue ONG NƯỚC uPVC - HDPE DE NHAT.pdf
Catalogue ONG NƯỚC uPVC - HDPE DE NHAT.pdfCatalogue ONG NƯỚC uPVC - HDPE DE NHAT.pdf
Catalogue ONG NƯỚC uPVC - HDPE DE NHAT.pdf
 
A DAY IN THE LIFE OF A SALESMAN / WOMAN
A DAY IN THE LIFE OF A  SALESMAN / WOMANA DAY IN THE LIFE OF A  SALESMAN / WOMAN
A DAY IN THE LIFE OF A SALESMAN / WOMAN
 
Grateful 7 speech thanking everyone that has helped.pdf
Grateful 7 speech thanking everyone that has helped.pdfGrateful 7 speech thanking everyone that has helped.pdf
Grateful 7 speech thanking everyone that has helped.pdf
 
VIP Kolkata Call Girl Howrah 👉 8250192130 Available With Room
VIP Kolkata Call Girl Howrah 👉 8250192130  Available With RoomVIP Kolkata Call Girl Howrah 👉 8250192130  Available With Room
VIP Kolkata Call Girl Howrah 👉 8250192130 Available With Room
 
Eni 2024 1Q Results - 24.04.24 business.
Eni 2024 1Q Results - 24.04.24 business.Eni 2024 1Q Results - 24.04.24 business.
Eni 2024 1Q Results - 24.04.24 business.
 
Enhancing and Restoring Safety & Quality Cultures - Dave Litwiller - May 2024...
Enhancing and Restoring Safety & Quality Cultures - Dave Litwiller - May 2024...Enhancing and Restoring Safety & Quality Cultures - Dave Litwiller - May 2024...
Enhancing and Restoring Safety & Quality Cultures - Dave Litwiller - May 2024...
 
Monthly Social Media Update April 2024 pptx.pptx
Monthly Social Media Update April 2024 pptx.pptxMonthly Social Media Update April 2024 pptx.pptx
Monthly Social Media Update April 2024 pptx.pptx
 
Call Girls In Panjim North Goa 9971646499 Genuine Service
Call Girls In Panjim North Goa 9971646499 Genuine ServiceCall Girls In Panjim North Goa 9971646499 Genuine Service
Call Girls In Panjim North Goa 9971646499 Genuine Service
 
Progress Report - Oracle Database Analyst Summit
Progress  Report - Oracle Database Analyst SummitProgress  Report - Oracle Database Analyst Summit
Progress Report - Oracle Database Analyst Summit
 
Socio-economic-Impact-of-business-consumers-suppliers-and.pptx
Socio-economic-Impact-of-business-consumers-suppliers-and.pptxSocio-economic-Impact-of-business-consumers-suppliers-and.pptx
Socio-economic-Impact-of-business-consumers-suppliers-and.pptx
 
Russian Faridabad Call Girls(Badarpur) : ☎ 8168257667, @4999
Russian Faridabad Call Girls(Badarpur) : ☎ 8168257667, @4999Russian Faridabad Call Girls(Badarpur) : ☎ 8168257667, @4999
Russian Faridabad Call Girls(Badarpur) : ☎ 8168257667, @4999
 

Calculating roof vent size for your home under 40 characters

  • 1. Sizing Roof vent for your home. ridge vent size per sq. ft. Let's do some math. house is 40 feet long by 30 feet deep, or 1,200 sq ft. This is the 'attic area' which includes a 2 foot overhang, not the 'house area'. Required ventilation is 1:300 if 50% or more is near the ridge, 1:150 if soffit vents only. 1,200 sq ft / 300 = 4 sq ft / 2 = 2 sq ft. If *at least* 2 sq ft of net free vent area is at the ridge, then we can use the 1:300, otherwise we need to use the 1:150 rule. Okie dokie, the ridge is 40 feet long, or 480 inches long less 21 x 1.5 = 31.5 inches for a total open area of 448.5 inches. The ridge vent slot in the sheathing is 3/4 inch to each side of the ridge board, or 1- 1/2 inches wide total. 1.5 X 448.5 = 672.75 sq inches. 672.75 sq inches / 144 = 4.67 sq ft That makes it doable, now, though, what is the net free vent area of the ridge vent itself? This will be given in sq inches per linear foot. The net free vent area of the ridge openings are 672.75 sq inches / 40 = 16.8 sq inches per linear foot. Thus, as long as the given sq inches of ridge vent are less than 16.8 inches per linear foot, that 3/4 inch cut out to each side of the ridge is going to be adequate. Anyone want to check my math and make I did it right? Thanks. Re: ridge vent size The minimum and maximum width of the slot are not usually specified by code but by the manufacturer's installation instructions. The code will let you figure out the minimum square inches of net free vent area NFVA) that you need.
  • 2. Sizing Roof vent for your home. The manufacturer makes a vent that has a certain amount (in square inches) of net free vent area per lineal foot of ridge. This sets a limit on how narrow the slot can be, so that the vent and not the slot is the limiting factor on air flow through the vent. The vent itself will be made to a certain width and only extends to cover the roof a few inches on either side of the ridge. The manufacturer will specify a maximum slot width which, if not exceeded, should ensure a watertight joint between the vent and the roof covering. Let's go back to that minimum slot width again and see how narrow it could be. I've seen typical ridge vents with NFVA as low as 9 sq in per ft of ridge and as high as about 18-20. Take that low flow vent at 9 sq in/ft. If you use that one, you need at least 9/12 or 3/4" total width of a slot (clear of the ridge board) or 3/8" on either side of the ridge. This is to ensure that the vent, and not the slot, is limiting air flow. Take a higher flow vent at 18 sq ft/in. On that one you need 18/12 or 1.5 inches minimum total width (clear of the ridge board) or 3/4" on each side if the ridge. Cutting slots wider than the minimum based on the NFVA of the vent you are using does nothing to increase ventilation; it increases the chances that the vent will leak. Check on Jerry's math: 2006 IRC 806.2 has the requirements. Quote: §RR806.2 Minimum area. The total net free ventilating area shall not be less than 1/150 of the area of the space ventilated except that reduction of the total area 1/300 is permitted, provided at least 50 percent and not more than 80 percent of the required ventilating area is provided by ventilators located in the upper portion of the space to be ventilated at least 3 feet above eave or cornice vents with the balance of the required ventilation provided by eave or cornice vents. As an alternative, the net free cross-ventilation area may be reduced to 1/300 when a vapor barrier having a transmission rate not exceeding 1 perm is installed on the warm-in-winter side of the ceiling. Let's assume a gable roof and our ventilated space (inside the attic) is 40 feet long (at the ridge) by 30 feet wide (eave to eave) or 1200 sq ft.
  • 3. Sizing Roof vent for your home. Using 1/150, the required total NFVA is at least 8 sq ft. Using 1/300, it is at least 4 sq ft. Let's assume worst case of NO soffit vents and either no vapor barrier or one with an effective perm greater than 1. If we cut a slot along the entire length of the ridge inside the gable end walls (assumed to be 40 feet), we would need a minimum clear slot width (8 sq ft / 40 ft) x (12 in/ft) = 2.4 inches (total on both sides of the ridge board). For this to work, we'd need to find a vent that provided at least 29 sq inch NFVA per foot of ridge. (Note - some manuf say you couldn't do this configuration with their vents, because their install instructions specify use of their vent in conjunction with soffit vents.) Let's assume a more typical case where we have soffit vents and they provide at least 50 percent of the required NFVA. Now we can use 1/300 which requires 4 sq ft total. We are going to meet that by providing 1 sq ft at each soffit and 2 sq ft at the ridge. Our slot running the full length of the ridge (inside the gable end walls) can be reduced to (2 sq ft / 40 ft) x (12 in/ft) = 0.6 inches (total on both sides of the ridge board). For this to work, we'd need to find a vent that provided at least 7.2 sq inch NFVA per foot of ridge and run it the full 40 feet. Let's say we want to use one of those low profile ridge vents with the filter inside, that provides NFVA of 9 sq in/foot. For this vent we would need a slot 3/4 inches wide and (2 sq ft x 144 sq in/sq ft) divided by (9 sq in/foot) = 32 feet long. Use one of those higher flow ridge vents (NFVA of 18 in/foot) and you need a slot 1.5 inches wide (3/4" on each side of ridge board) and only (2 sq ft x 144 sq in/sq ft) divided by (18 sq in/ft) = 16 feet long. In theory, you could use that higher flow vent on a 3/4 inch slot if you ran it for 32 feet. BUT code says you must follow the manufacturer’s instructions and they will tell you how wide of a slot to cut for their vent.