CHAPTER 1

INTRODUCTION TO PROTECTION
          SYSTEM
Introduction:Need for Protective Systems



•   Power system consists of; generators, transformers, transmission and
    distribution lines, etc…..etc.
     –   Sistem kuasa mengandungi: penjana, pengubah, talian penghantaran dan pengagihan dsbnya


•   Short circuits and other abnormal conditions often occur on a power system
     –   Litar pintas dan keadaan tidak normal kerap berlaku pada sistem kuasa


•   Heavy current associated with short circuits is likely to cause damage to
    equipments
     –   Arus yg tinggi ketika litar pintas mungkin menyebabkan kerosakan pada peralatan jika geganti
         perlindungan dan pemutus litar tidak di bekalkan untuk perlindungan bagi setiap seksyen
         sistem kuasa
Need for Protective Systems

•   Short circuit is a faults (power engineer)

•   Failure of conducting path due to a break in a conductor is a type of fault

•   Fault occurs – automatic protective device is needed to isolate the faulty
    element as quickly as possible to keep the healthy section of the system in
    normal operation

•   Fault must be cleared within fraction of a second

•   Uncleared short circuits may cause total failure of the system
•   A protective scheme includes transducers, protective relays and circuit
    breakers to isolate the faulty section of the system from the healthy section

•   Protection is needed not only against short circuit but also against any
    abnormal condition
     – Overspeed of generators and motors
     – Overvoltage
     – Underfrequency
     – Loss of excitation
     – Overheating of stator or rotor of an alternator
     – Etc…etc…etc

•   Protection is a pre-requisite for an effective and reliable system

•   A protective relay does not anticipate or prevent the occurrence of fault,
    rather it takes action only after a fault has occurred – except Buchholz relay; a
    gas actuated relay
Nature and causes of Faults

•   Faults are caused either by;

     – Insulation failure –
     – Conducting path failure
         • results in short circuit

•   Faults on transmission and distribution lines are caused by
    overvoltage
     – Lightning and switching surges
     – External conducting objects falling on overhead line.

•   Birds also may cause faults on overhead line if their bodies touch one
    of the phase and earth wire
•   If conductors are broken – failure of conducting path and the conductor
    becomes open-circuited
     – If broken conductor fall to the ground, results in short circuit

•   Joint failure on cables and overhead lines also cause a failure of the
    conducting path

•   Opening of one or two of the three phases makes the system unbalanced
     – Set-up harmonics
•   Other causes of faults in o/h line
     –   Direct lightning strokes
     –   Aircraft
     –   Snakes
     –   Ice and snow loading
     –   Abnormal loading
     –   Storm
     –   Earthquakes
     –   Creepers
     –   Etc…..etc……etc……etc
•   Cables, transformer generators and other equipment:
     –   Failure of solid insulation due to aging
     –   Heat
     –   Moisture
     –   Overvoltage
     –   Mechanical damage
     –   Accidental with earth
     –   Flashover due to overvoltages
     –   Etc…etc…..etc
Types of faults


• Symmetrical faults
• Unsymmetrical faults

• Symmetrical faults
  – Kerosakan tiga fasa atau tiga fasa ke bumi


• Unsymmetrical faults
  – Single line to earth, line-to-line, double line to
    earth, open-circuited phases
•       Faults can interrupt power system in several ways:

    –      Heavy current to flow
          •   Effect : overheating of power system component

    –      Fault is a short circuit and exist as electrical arc and liquid e.g air
          •    Effect: equipment faulty and fire
•   Fault
     – can increase/decrease voltage system outside its acceptable range


     – Can cause unstable three phase system, improper operation of three phase
       equipments

     – Prevent power flow

     – Can cause system to be unstable and collapse
• Faults incur MONEY.

• If fault is isolated as quickly as possible and
  accurate –less money required

• Cost of protective equipment is 5% of the total
  cost of the system
• PROTECTION DOES NOT MEAN
  PREVENTION
 – A protective relay does not anticipate or prevent the occurrence of fault,
   rather it takes action only after a fault has occurred – except Buchholz relay; a
   gas actuated relay
Functions of Protective
                            System
•   Fast and automatically opens the faulty section in the power system

•   Increase system reliability and security – only affected area will be
    isolated and maintain the healthy line
     – Ensure consumers receive continuity of supply

•   Delay in isolating the fault
     – System unstable, loss of synchronism, total failure of the system
     – Fire
Requirements of Protective
                    System
• The basic requirements of a protective
  system are as follows:

  – Discrimination/selectivity
  – Sensitivity
  – Reliable
  – Stability
  – Speed
(Discrimination/Selectivity)

• Ability to select either to operate or not
  – Keupayaan untuk memilih sama ada bekerja atau tidak


• Select to isolate the faulty section only (the
  rest normal condition)
  – Memilih untuk mengasingkan bahagian rosak sahaja (yang lain berkeadaan
    normal)

• The nearest circuit breaker will trip
  – Pemutus litar yang hampir sahaja terbelantik (trip)
Radial protection system




      SD2                 SD3
SD1




SD1     SD2                SD3
Sensitivity

•   Relay should operate when the magnitude of the current exceeds the
    preset value

•   This value is called pick up current

•   Should not operate when current is below its pick-up value

•   Should be sufficiently sensitive to operate when the operatinfg current
    just exceeds the pick-up value – relate with minimum operating current
Reliability

• A protective system must operate reliably
  when a fault occurs in its zone of protection
• Failure may due to its protective element
  system; CT, PT, CB, relay etc….
• Reliability of protective system 95%
Stability
• A protective system should remain stable even
  when a large current is flowing through its
  protective zone due to an external fault

• Concerned circuit breaker is supposed to clear
  the fault
No                 Yes




     SD1             SD2    SD3

 Radial system protection
Speed-fast operation

•   Isolate fault as quickly as possible (at shortest time possible )

•   Isolate disturbances before loss of synchronism and plant stop operation – time
    should not exceed critical clearing time

•   Speed balanced with economy
     – Cost of protective equipment should be relevant to the cost of the protected
        zone

•   Avoid fire to equipments, interruption of supply to consumer, voltage drop
    operating time; 1 cycle, ½ cycle are also available; distribution system > 1 cycle
Operating time

• Total time to accomplish the isolation

• Calculated at the instance of fault until the
  given trip signal

• Must be low for the sake of plant and
  equipment safety

• Delay time – for discrimination
Protection economy
• Protection system can be designed as:
  – Simple and cheap
  – Complex and expensive


• Baesd on:
  – The cost of fault
  – Safety level requirement
Protection economics…
•   Cost of fault
     – Cost of damage toward the plant
     – Cost loss of revenue due to cut-out supply
     – Cost of customers confidence


•   Higher the cost of fault, more expensive the protection system

•   Higher the plant kVA, more complex protection system required
Protection system at customer level



• Simple fuse – protect equipment and certain
  circuits

• Fius ringkas melindungi alat-alat dan litar
  tertentu

• Miniature circuit breaker- MCB
Protection system at distribution
                               level


• Fuse and switch fuse

• Automatic reclosing circuit breaker
  – For rural area
  – Transient fault is corrected by self clearing
Protection system at transmission
                                          level

•   Technical consideration outweighs the economy

•   275kV dan 400kV System require a protection system which is:
     – very reliable
     – Full discrimation
     – High speed

•   Expensive and complex

•   Provide back-up protection
Zone of Protection
                                                           GENERATOR
                                                           PROTECTION



                                                            CIRCUIT BREAKER
•   Power system is divided into                             HV SWITCHGEAR
    several zones                                             PROTECTION


•   Each zone of protection is                           TRANSFORMER

    provided with 2 types of
                                                          PROTECTION


    protection:
                                                             EHV SWITCHGEAR
     – Primary protection                                      PROTECTION

     – Backup protection
                                                          TRANSMISSION LINE
                                                             PROTECTION



                                                             EHV SWITCHGEAR
                                                               PROTECTION




                                              ZONE OF
                                            PROTECTION
Protection zone

• Region or area encompass a protection system
Protection zone
                                    CB3
                       CB3
CB1
         CB2




      SD1               SD2   SD3




  Radial protection system
Main/primary protection


• In general primary protection is provided for
  each transmission line segment, major piece
  of equipment and switchgear
• If fault occurs, it is the duty of the primary
  protective scheme to clear the fault
• First line of defence - Responsible to isolate
  fault as quickly as possible
• Fails, back-up protection clears the fault
Backup Protection

• Act when primary protection fails – second
  line of defence

• Usually several back up protection scheme will
  act to control the power system

• Longer time delay
Radial protection system




SD1             SD2                 SD3


                                           Main protection


  Back-up protection
Zone of protection
• Zone of protection usually overlap
Fault detection

•   Current magnitude
•   Current in abnormal path (earth)
•   Current balance (current out#current in)
•   Voltage balance
•   Changes in impedance
•   Protective system damage(Buchholz), power flow direction, temeprature
    & pressure
Protective system components




1.       Circuit breaker
2.       Transducer – current transformer (CT), voltage transformer (VT),
         potential transformer (PT)
3.       Communication links
     –      Pilot wire
     –      Radio link
     –      Overlapping signal, power line carrier (PLC)
Protective system components

4.       Relay
     –      Electromagnetic

     –      Static – improve reliability,versatile, fast response (1/4 cycle)

     –      Microprocessor- VLSI teknologi – current interest to power engineers;
            adv:attractive flexibility due to programmable approach, can provide
            protection at low cost and compete with conventional relays

5.       Fuse
Transducer

     Serves as a sensor to detect
 abnormal system conditions and to
  transform the high values of short
circuit current and voltage to a lower
                 values




                                         43
Protective relays
• Process the signals provided by the
  transducers which may be in the form of
  current, voltage or a combination of current
  and voltage




                                                 44
Circuit breaker


• Mechanical device used to energize and
  interrupt an electric circuit




                                           45
Ex. Protective system: power
                      flow balance
        2. CT, PT
1. PL                                    1. P.L


                         4. Relay

                    R1              R2




                     3
Classifications of relay based on its
                                   function



•   Overcurrent relay
•   Undervoltage relay
•   Impedance relay
•   Under frequency relay
•   Directional relay etc….etc….etc
Classification of protective scheme




•   Overcurrent protection
•   Distance protection
•   Current carrier protection
•   Differential protection
Transformer in a protective system


                                   •   CT assume ideal
 Feeder                Ip          •   Normal rating:
 conductor                              – 1:1, 2:1. 2.5:1, 4:1, 5:1
                                        – 20:1, 40:1, 100:1, 200:1, 300:1,
                                          600:1
                  Is        CT          – 1000:1, 2000:1, 4500:1
                                   •   Secondary coil is connected to a
             Vp                        “sensitive device” eg voltmeter
Vs
                                   •   Low Stray impedance so that voltage
                                       drop small




     VT
Current transformer (CT)

•   Normal rating
     – 1A (Europe)
     – 5A (USA)

•   Example :
     – 50:5, 100:5, 150:5, 200:5, 250:5
     – 450:5, 500:5,……1000:5, ……, 6000:

•   Secondary coil is connected to a “current sensing device” of zero
    impedance

•   Shunt impedance high so that I0 low.
(current transformer CT)


•   Working principle similar to voltage transformer
•   Supply by current source
•   Primary winding connected in series with power circuit
     – Carries full load current
•   Transformer impedance (referred to secondary and can be neglected)
•   Secondary coil connected to load (burden)
(current transformer CT)

• Secondary winding feeds the protective system
• Current is reduced but must be almost the same with the power system
  current
• Secondary rated current 5 A or 1 A
• Fault current 10 – 20 X rated current. Transformer must be capable to
  operate reliably/accurately at this value
• Burden usually usually small – flux do not saturate
Current transformer construction

           Bar Type
    Core
                      Power system
                      current

                         Primary winding
                         (1 turn)- from power system

Secondary winding wound
on the core
Current transformer construction




Wound type
design
• CT – similar to a normal transformer emf
  equation

• Average induced voltage = product of No. of
  turn and rate of change of flux magnet; eaverage
  = N(dΦ/dt)

• Knee point voltage(rms) = 4.44 BAfN
Burden
• Defined as the load connected across its
  secondary CT
  – express in VA (VA taken as nominal secondary
    current of CT) or
  – Impedance (at the rated secondary current at a
    given power factor usually 07. lagging

• Increase in impedance – increase burden
• CT unloaded if secondary winding is short
  circuited
Example
• 5VA burden at 1A transformer, gives 5 Ohms
  impedance.
• 5VA/1A = 5V
• impedance = 5V/1A = 5Ω

• or

• At 5A CT
• 5VA/5A
• impedance = 1V/5A = 0.2 Ω
Example
• CT ratio 300/1, core area 40x30 mm
• Voltage at knee point?

• V = 4.44 x 0.0018 x 300 x 50 = 120 V
• 1.5 x 40 x 30 x10-6 = 0.0018 Wb ( B for sheet
  steel, 1.5 tesla at knee point)
CT open circuit

•   If burden high, Es high– exceed Vkp (knee point voltage)
•   Io high ; I2 less

•   Limited value when the secondary CT open circuit; I2 = 0;
•   Then N1I1 = N2 (I2+Io) = N2Io

•   This will drive the CT to saturation level
•   dΦ/dt = 100 x Vkp (induced = 100 Vkp )
•   Cause insulation failure and overheated
Current transformer equivalent circuit

            Ip’                   x         r        Is

                     I0’
                                Ic ’                       Load (burden)
  Es        Im’                                 Vs
                                                           R



                                                           Ip = primary current
(nominal ratio) Kn
                                                          I0 = primary excitation
                                                          current (no load)

 I 'p   =   I p / Kn        '
                           I0   =      I0 / Kn
Current transformer equivalent circuit
       Ip’                                  x    r            Is

                              I0’

                      Im’                 Ic ’                        Load (burden)
       Es                                            Vs
                                                                      R


Es
                                    Ip’
                                                                   I 'p   = Is   + I0
                                                                                    '

             Is
                  θ
                                                                   Is     =   I 'p − I 0
                                                                                       '
                            I0’
Ic ’                                                      φ
              Im’
relationship Es and φ (flux)



N=no of turn in secondary
                dφ
 es       =   N
                dt                                π
                             es = Nωφm sin(ωt +       )
                                                  2
φ     =       φ m sin ωt
                                        Nωφ m
es    =       Nωφm cos ωt      Es   =         ∠90°
                                          2
(Nominal Turn Ratio)
•   Determine from the given current ratio
     – Eg.1000/5 (bar type)




                                             Ip
                                           200
                K n = nominal ratio =    =
                                      Is    1
Actual Ratio
•   Actual ratio value Ip and Is



                                                          ′
                                                     Ip
         actual ratio = winding ratio ×
                                                     Is
                                                 ′
                                            Ip
                                   = Kt ×
                                            Is
•   Winding ratio= secondary coil turn if transformer is of bar type l
     – Kt = N2/1


•   Ideally                               ′
                                     Ip
                                              =1
                                     Is
•   Practically
                                                   ′
                                              Ip
                                                       〉1
                                              Is
      Actual turn≥ nominal ratio
CT error
• Current error or ratio error
• Phase error
• Composite error
Ratio error or current error


                  nominal ratio -actual ration
    ratio error =                              × 100%
                        actual ratio



Nominal ratio= Kn                                               ′
                                                           Ip
                                    actual ratio = K t ×
Turn ratio= Kt                                             Is
No compensation Kn=Kt
Cont’d
                                    '
                                   Ip
                    K n − Kt
                                   Is
  ratio error =                '
                              Ip               Kn=Kt
                       Kt
                              Is
                                               (no compensation)
                    K n I s − Kt I      '

                =
                                        p
                                 '
                            Kt I p
                                            difference in
                I s − I 'p                  magnitude between
ratio error =                   × 100%      Ip’ and Is
                     I 'p
Phase Error
Difference in angle between Ip’ and Is


    Phase error= θ
                           Es

                                               Ip’
                                Is
      α                              θ
                                         I0’

                                                         φ
                                Im’
Compensating winding

• Secondary coil winding is reduced (1 or 2 turn)
  to compensate current error due by I0’.

• Secondary coil current will be high, but the
  value will be minimised by the excitation
  current component

• This can minimised the current error
Example T1

•   A current transformer 50 Hz has a secondary current of 3A,Sebuah
•   Secondary impedance circuit (0.6+j0.45),
•   Maximum flux 0.253 weber
•   Magnetisation current and core loss current (primary circuit) at this load
    are 0.2 and 0.15 A respectively
•   Turn ratio1:10, assume no compensation
•   Determine no of turn, ratio error and phase error of transformer
CT equivalent circuit
                                                                r
           Ip’                                             Is=3 ∠ αº
                                      I0’

                          Im’                     Ic ’                       Load (burden)
           Es                                                     Vs
                                                                             = 0.6+j0.45


    Es
                                                                              '
                                            Ip’          I 'p =   I p / Kn   I0      =   I0 / Kn
                 Is
                      θ                                                       I 'p   = Is    + I0
                                                                                                '

                                I0’
    Ic ’                                                               φ
                                                                              Is     =   I 'p − I 0
                                                                                                  '
                      Im’
α
N1:N2 = 1:10    Kt = 10 = Kn
Is=3 ∠ αº         Im = 0.2 A
                                            Es = I s Z
    Ic = 0.15 A
                                                  = 3∠α ° × 0.75∠36.87°
             N s × φm × ω                         = 2.25∠(α + 36.87)°
        Es =              ∠90°
                    2
         Es
                                            (α + 36.87)° = 90°
                                    Ip’                     α = 90 − 36.87
α                 Is                                          = 53.13°
                       θ

                             I0’
         Ic’
                       Im’                    φ
N s × φm × ω
             = 2.25
       2
                2.25 × 2
        Ns =
             0.253 × 2π × 50
           = 40



  ∴ N1:N2 = 4:40
I 0 = 0.20 + j 0.15
     Is=3 ∠ αº
                                                 ′                        1
                                            I0       = (0.20 + j 0.15) ×
     Im = 0.2 A                                                          10
      Ic = 0.15 A                                    = 0.02 + j 0.015

                                              ′    ′
                                           I p = I0 + Is
       Es
                                                 = 0.020 + j 0.015 + 3∠53.13°
                                     Ip’
                                                 = 3.024∠52.9975°
                    Is
                         θ

                               I0’
Ic’                                                          φ
                         Im’
′
              Is + I p     3 − 3.024
ratio error =            =           × 100%
                    ′        3.024
                 Ip
           = −0.794 %


     phase error = 53.13 − 52.9975
                  = 0.1325
Ex 1


•   A current transformer has 15 turn on the primary and 75 turn on the
    secondary. The relay burden is (1.2+j2.6)Ω and secondary winding
    impedance of the transformer is (3.6+j0.4)Ω. If the magnitude of the
    secondary voltage is 26 volt and magnetization current referred to
    secondary is 0.24∠-45o amp. Determine the ratio error and phase error.
Ex 2


•   A new non compensated CT with a cross sectional area of 40 cm2 has a nominal
    ratio of 2000/5. When 5A is supplied to a relay, the combination of load relay and
    secondary winding impedance is (10+j5.77) Ω. If the magnetisation amp-turn is
    100 and core loss amp-turn is 50, determine the ratio error and phase error. Using
    the same data, calculate also the compensating turn to reduce the ratio error to a
    minimum.
Ex. 3


•   A CT, 50 Hz has a primary winding of 10 turn and its cross sectional area is 8 cm2.
    Secondary current is 5A. The total load and secondary impedance is 0.8+j0.5 Ω.
    The excitation current required at the primary winding to establish a working flux
    with the secondary open is 0.6∠45o amp. If the flux density is 0.1878
    wb/m2,determine the nominal ratio of the transformer. Determine also the ratio
    error and phase error of the transformer.
Composite error
• BS 3938:1973
  – (r.m.s.) value; difference between ideal secondary
    current (i.e CT is ideal ; no excitation component)
    with actual secondary current.
• Encompass (current error, phase error and
  harmonic effect)
Accuracy limit current of a
                       protection system CT

• Accuracy limit current (saturation current)
  – The maximum current a CT can sustain before
    exceed its accuracy
  – Specify either in term of primary current or
    secondary current
• Accuracy limit factor (saturation factor)
  – Ratio of accuracy limit primary current and
    rated primary current
  – Standard values are 5, 10, 15, 20 and 30
CT specification

•   Expressed in
     – VA at rated current /class accuracy/accuracy limit factor
     – Burden standard rated values
         • 2.5,5,7.5,10,15 and 30 VA
     – 2 accuracy class: 5P and 10P – gives composite error at rated accuracy limit 5%
       and 10% respectively
     – Standard accuracy limit factor:
         • 5, 10, 15, 20 and 30
Rating of CT

  •   Method to explain CT

       – 10VA/5P/25


                                   Accuracy limit current is 25 x rated
                                   current
                                   Transformer works in good
                                   condition/reliably until 25 x its
Rated burden      Class – error    rated curent
                  do not exceed
                  5%
Ex 1


• CT 10VA/5P/15
• Calculate the accuracy limit factor when the
  burden is half of its initial value.
• Secondary resistance of CT 0.15 ohm
Solution
Burden impedance 10VA at rated
current 5A

                                      r


                                 Es
   VA     V ×I
           =                                         Burden (R)

        = I × R× I                         V

        = I 2R

               10
   R   =
                   2
                       = 0.4   ohm
               5
Solution
Total impedance referred to                                     r
secondary winding
= 0.15 + 0.4 = 0.55 ohm
                                            Es

                                                                    V
                                                                        Burden (R)
Accuracy limit factor= ratio accuracy
limit current and rated current



Accuracy limit current= Accuracy limit factor × Rated current

         accuracy limit current                  =   15 × 5
                                                 = 75           A
secondary emf = 0.55 × 75      V
                             = 41.25 V

                                   r


                        Es
                                                   Burden
                                                   (R=0.4)
 When burden is half
 R = 0.2 ohm

Total secondary impedance= 0.15 + 0.2 = 0.35 ohm
new accuracy limit current          = 41.25 / 0.35
                                   = 117.8 A

new accuracy limit factor = 117.8 / 5
                          = 23.56
    Smaller the burden, the higher the accuracy
                    Therefore :
          burden has to be low possible
CT Class X


•   BS 3938 – CT for special application is known as Class “X’

•   Expressed in turn ratio, knee point voltage, excitation current at the specified voltage and
    secondary winding resistance

     – Application – scheme where the phase fault stability and/or accurate time grading required

•   Transformer rating specify in term of e.m.f maximum that can be use by the transformer

•   knee point
     – Point where an increase of 10% in secondary e.m.f require an addition of 50% excitation current
Definition of knee point

Excitation
voltage

             +10%


                            Knee
                            point
                    +50%



                               Excitation current
Voltage transformer/potential transformer(VT/PT)


•   Supply voltage lower than the sistem voltage

•   Nominal sekunder voltage110V

•   2 types
     – Wound ( electromagnetic) type(> 132 kV non economical)
     – Capacitor type- CVT

•   Element X and C consist of tuning circuit – to reduce the ratio and phase
    angle error secondary voltage
1/ωC2 = ωL pd 50 Hz; V2 = V’
          Talian


     C1

                         L
Vp

                                                   Rb
                             V’
                                              Vs
     C2            V2
                                                   Xb


                        V’ = 12 kV, C1 = 2000pF




                                  L
                        C2
     V2                                             110 V
                                             V’
Protection techniques



• Protection scheme:
     – Arrangements of CT, VT, pilot wire and relay so
       that the required operating characteristics can be
       obtained

•   Each section of the power system network is monitored by several
    protection scheme.
Main/primary scheme usually consists of:


                Unit Scheme

Backup scheme consists of:



                 Non Unit Scheme
Unit scheme




• ZONE OF PROTECTION IS WELL DEFINED
Unit protection scheme
      CT                                            CT



                           Protected zone

                                   P
                                                         Pilot wire
                                  R
                                        relay

                                  Q
Difference current scheme: circulating current

FAULT:
Non similar current flow in the relay
CB will trip
                                                R
CT


                                                 Healthy and fault
        e1          Protected zon           e2   external zone (through
                                                 fault):
                                                 No current in relay,
                                                 e1=e2




               R                        R
         FAULT:
         Current flow in circuit, result e1≠e2

     Differencec current scheme: voltage balance
Balance power direction
                  CT, PT
 PL                                                 P.L


                                Relay

                           R1           R2
                                             Trip
           Trip
Restrain


                                             Restrain
CB1                                                                           CB2

A
                                                                                          B
                                 R1                         R2
                                                                         Trip
               Trip
    Restrain


                                                                         Restrain

     Power flow entering the feeder (from point A) will cause relay (R1)
     close trip contact CB1
    Power flow exit fron the feeder (at point B) will cause relay R2 rotate
    and close restrain contact of the further circuit breaker (remote) (CB1)
    (relay R2 send restrain signal CB1)
CB1                                                                            CB2


A
                                                                                         B
                                 R1                         R2
                                                                        Trip
               Trip
    Restrain


                                                                        Restrain


        Power enter at A and exit at B, block trip will prevent the CB from
        opening.
CB1                                                                   CB2



A
                                                                                  B
                                R1                        R2
                                                                 Trip
               Trip
    Restrain


                                                                 Restrain


        Power enter at A and at B (fault occurs), both CB open
CB1                                                                        CB2



A                                                                                    B
                               R1                       R2
                                                                    Trip
            Trip
Restrain


                                                                    Restrain


    Power enter at A and no power at B, circuit breaker A, CB1 will open
NON UNIT SCHEME



 supervise/monitor one or several points in the power system


 signal will be detected at the points


 this signal is the input to the relay



 section monitored/supervised is not clearly defined
ZONE OF PROTECTION IS NOT WELL DEFINED
2 examples of non unit scheme
  (1.) Over Current Protection




  (2.) Distance Protection
‘click here to add title




•Q & A

Más contenido relacionado

La actualidad más candente

12.buku pedoman lightning arrester
12.buku pedoman lightning arrester12.buku pedoman lightning arrester
12.buku pedoman lightning arresteradiskurnia std
 
proteccionescapitulo1
proteccionescapitulo1proteccionescapitulo1
proteccionescapitulo1Sebastian J
 
139 09 seccion de los conductores
139 09 seccion de los conductores139 09 seccion de los conductores
139 09 seccion de los conductoresMarcelo Villalba
 
Safety Grounding, Lightning protection and building
Safety Grounding, Lightning protection and buildingSafety Grounding, Lightning protection and building
Safety Grounding, Lightning protection and buildingEdy Iskanto
 
PLC: Problemas resueltos con autómatas programables Paraninfo por J. Pedro Ro...
PLC: Problemas resueltos con autómatas programables Paraninfo por J. Pedro Ro...PLC: Problemas resueltos con autómatas programables Paraninfo por J. Pedro Ro...
PLC: Problemas resueltos con autómatas programables Paraninfo por J. Pedro Ro...SANTIAGO PABLO ALBERTO
 
Prot transf-potencia-rev
 Prot transf-potencia-rev Prot transf-potencia-rev
Prot transf-potencia-revDavid Moreno
 
Concept of insulation resistance & Polarization Index
Concept of insulation resistance & Polarization IndexConcept of insulation resistance & Polarization Index
Concept of insulation resistance & Polarization IndexHareshYadav4
 
CAPITULO 6 TRANSFORMADORES PARA INSTRUMENTOS (2).pdf
CAPITULO 6 TRANSFORMADORES PARA INSTRUMENTOS (2).pdfCAPITULO 6 TRANSFORMADORES PARA INSTRUMENTOS (2).pdf
CAPITULO 6 TRANSFORMADORES PARA INSTRUMENTOS (2).pdfRoloAmatLimachi
 
Transformer relays trips alarms.pptx
Transformer relays trips alarms.pptxTransformer relays trips alarms.pptx
Transformer relays trips alarms.pptxssuserb609311
 
2017 2 tutorial-ac_hv_circuit_breakers_dufournet
2017 2 tutorial-ac_hv_circuit_breakers_dufournet2017 2 tutorial-ac_hv_circuit_breakers_dufournet
2017 2 tutorial-ac_hv_circuit_breakers_dufournetZİYA MURAT KIRGIZ
 
Diagnóstico de Falhas em Cabos MT - Parecer Técnico
Diagnóstico de Falhas em Cabos MT - Parecer TécnicoDiagnóstico de Falhas em Cabos MT - Parecer Técnico
Diagnóstico de Falhas em Cabos MT - Parecer TécnicoAlexandre Grossi
 
Short circuit calculations
Short circuit calculationsShort circuit calculations
Short circuit calculationsMustafa Ismail
 
ETAP - Cortocircuito (short circuit)
ETAP - Cortocircuito (short circuit)ETAP - Cortocircuito (short circuit)
ETAP - Cortocircuito (short circuit)Himmelstern
 
Sistemas de protección para circuitos de control
Sistemas de protección para circuitos de controlSistemas de protección para circuitos de control
Sistemas de protección para circuitos de controlJhon Luque
 

La actualidad más candente (20)

12.buku pedoman lightning arrester
12.buku pedoman lightning arrester12.buku pedoman lightning arrester
12.buku pedoman lightning arrester
 
proteccionescapitulo1
proteccionescapitulo1proteccionescapitulo1
proteccionescapitulo1
 
139 09 seccion de los conductores
139 09 seccion de los conductores139 09 seccion de los conductores
139 09 seccion de los conductores
 
Safety Grounding, Lightning protection and building
Safety Grounding, Lightning protection and buildingSafety Grounding, Lightning protection and building
Safety Grounding, Lightning protection and building
 
Smk3 listrik
Smk3 listrikSmk3 listrik
Smk3 listrik
 
PLC: Problemas resueltos con autómatas programables Paraninfo por J. Pedro Ro...
PLC: Problemas resueltos con autómatas programables Paraninfo por J. Pedro Ro...PLC: Problemas resueltos con autómatas programables Paraninfo por J. Pedro Ro...
PLC: Problemas resueltos con autómatas programables Paraninfo por J. Pedro Ro...
 
Prot transf-potencia-rev
 Prot transf-potencia-rev Prot transf-potencia-rev
Prot transf-potencia-rev
 
Concept of insulation resistance & Polarization Index
Concept of insulation resistance & Polarization IndexConcept of insulation resistance & Polarization Index
Concept of insulation resistance & Polarization Index
 
CAPITULO 6 TRANSFORMADORES PARA INSTRUMENTOS (2).pdf
CAPITULO 6 TRANSFORMADORES PARA INSTRUMENTOS (2).pdfCAPITULO 6 TRANSFORMADORES PARA INSTRUMENTOS (2).pdf
CAPITULO 6 TRANSFORMADORES PARA INSTRUMENTOS (2).pdf
 
Curso etap
Curso etapCurso etap
Curso etap
 
Transformer relays trips alarms.pptx
Transformer relays trips alarms.pptxTransformer relays trips alarms.pptx
Transformer relays trips alarms.pptx
 
2017 2 tutorial-ac_hv_circuit_breakers_dufournet
2017 2 tutorial-ac_hv_circuit_breakers_dufournet2017 2 tutorial-ac_hv_circuit_breakers_dufournet
2017 2 tutorial-ac_hv_circuit_breakers_dufournet
 
PROTEKSI SISTEM TENAGA LISTRIK
PROTEKSI SISTEM TENAGA LISTRIK PROTEKSI SISTEM TENAGA LISTRIK
PROTEKSI SISTEM TENAGA LISTRIK
 
Diagnóstico de Falhas em Cabos MT - Parecer Técnico
Diagnóstico de Falhas em Cabos MT - Parecer TécnicoDiagnóstico de Falhas em Cabos MT - Parecer Técnico
Diagnóstico de Falhas em Cabos MT - Parecer Técnico
 
SISTEM PROTEKSI
SISTEM PROTEKSI SISTEM PROTEKSI
SISTEM PROTEKSI
 
Short circuit calculations
Short circuit calculationsShort circuit calculations
Short circuit calculations
 
Basic protection and relaying
Basic protection and relayingBasic protection and relaying
Basic protection and relaying
 
ETAP - Cortocircuito (short circuit)
ETAP - Cortocircuito (short circuit)ETAP - Cortocircuito (short circuit)
ETAP - Cortocircuito (short circuit)
 
Sistemas de protección para circuitos de control
Sistemas de protección para circuitos de controlSistemas de protección para circuitos de control
Sistemas de protección para circuitos de control
 
Hydrostatic Level Measurement-Deltapilot S DB50/50L/51/52/53
Hydrostatic Level Measurement-Deltapilot S DB50/50L/51/52/53Hydrostatic Level Measurement-Deltapilot S DB50/50L/51/52/53
Hydrostatic Level Measurement-Deltapilot S DB50/50L/51/52/53
 

Similar a See4423 chapter1 introduction[1]

Switchgear and Protection Engineering Lecture 01.pptx
Switchgear and Protection Engineering Lecture 01.pptxSwitchgear and Protection Engineering Lecture 01.pptx
Switchgear and Protection Engineering Lecture 01.pptxLoitaFredy
 
Ohiri-Principles-and-Philosophy-of-Protective-Relaying.pptx
Ohiri-Principles-and-Philosophy-of-Protective-Relaying.pptxOhiri-Principles-and-Philosophy-of-Protective-Relaying.pptx
Ohiri-Principles-and-Philosophy-of-Protective-Relaying.pptxGodwin308555
 
Power System Protection (Primary & Backup)
Power System Protection (Primary & Backup)Power System Protection (Primary & Backup)
Power System Protection (Primary & Backup)Kamran Gillani
 
14362648-Chapter 7 System Protection.ppt
14362648-Chapter 7 System Protection.ppt14362648-Chapter 7 System Protection.ppt
14362648-Chapter 7 System Protection.pptssuser157f0e1
 
Module 1 Power System Protection(18EE72).pptx
Module 1 Power System Protection(18EE72).pptxModule 1 Power System Protection(18EE72).pptx
Module 1 Power System Protection(18EE72).pptxssuser139a56
 
errahulsharmafeederprotection-141017104620-conversion-gate02.pdf
errahulsharmafeederprotection-141017104620-conversion-gate02.pdferrahulsharmafeederprotection-141017104620-conversion-gate02.pdf
errahulsharmafeederprotection-141017104620-conversion-gate02.pdfAbhishekYadav177511
 
2_Intro Protection + Protection CT.pdf
2_Intro Protection + Protection CT.pdf2_Intro Protection + Protection CT.pdf
2_Intro Protection + Protection CT.pdfLiewChiaPing
 
switchgear%20%20&%20protection%20introduction.pptx
switchgear%20%20&%20protection%20introduction.pptxswitchgear%20%20&%20protection%20introduction.pptx
switchgear%20%20&%20protection%20introduction.pptxSaishDalvi
 
Lec 1_Introduction to Power System Protection.pdf
Lec 1_Introduction to Power System 
Protection.pdfLec 1_Introduction to Power System 
Protection.pdf
Lec 1_Introduction to Power System Protection.pdfAhmedHElashry
 
Powerprotection 1421105031
Powerprotection 1421105031Powerprotection 1421105031
Powerprotection 1421105031Chandana Mallik
 
Unit IV.pptx
Unit IV.pptxUnit IV.pptx
Unit IV.pptxpmaheshh
 
Power System Protection course - Part I
Power System Protection course - Part IPower System Protection course - Part I
Power System Protection course - Part ISlides Hub
 
Switchgear and protection 1
Switchgear and protection 1Switchgear and protection 1
Switchgear and protection 1Md Irshad Ahmad
 
24620708 feeder-protection (1)
24620708 feeder-protection (1)24620708 feeder-protection (1)
24620708 feeder-protection (1)Adarsh Verma
 
Relaying and Protection Concepts.ppt
Relaying and Protection Concepts.pptRelaying and Protection Concepts.ppt
Relaying and Protection Concepts.pptSatish Pydimarla
 
Ieee generator protection
Ieee generator protectionIeee generator protection
Ieee generator protectionDr. Bindu Devan
 

Similar a See4423 chapter1 introduction[1] (20)

Protection and Switchgear
Protection and SwitchgearProtection and Switchgear
Protection and Switchgear
 
Switchgear and Protection Engineering Lecture 01.pptx
Switchgear and Protection Engineering Lecture 01.pptxSwitchgear and Protection Engineering Lecture 01.pptx
Switchgear and Protection Engineering Lecture 01.pptx
 
Ohiri-Principles-and-Philosophy-of-Protective-Relaying.pptx
Ohiri-Principles-and-Philosophy-of-Protective-Relaying.pptxOhiri-Principles-and-Philosophy-of-Protective-Relaying.pptx
Ohiri-Principles-and-Philosophy-of-Protective-Relaying.pptx
 
Power System Protection (Primary & Backup)
Power System Protection (Primary & Backup)Power System Protection (Primary & Backup)
Power System Protection (Primary & Backup)
 
14362648-Chapter 7 System Protection.ppt
14362648-Chapter 7 System Protection.ppt14362648-Chapter 7 System Protection.ppt
14362648-Chapter 7 System Protection.ppt
 
Module 1 Power System Protection(18EE72).pptx
Module 1 Power System Protection(18EE72).pptxModule 1 Power System Protection(18EE72).pptx
Module 1 Power System Protection(18EE72).pptx
 
errahulsharmafeederprotection-141017104620-conversion-gate02.pdf
errahulsharmafeederprotection-141017104620-conversion-gate02.pdferrahulsharmafeederprotection-141017104620-conversion-gate02.pdf
errahulsharmafeederprotection-141017104620-conversion-gate02.pdf
 
2_Intro Protection + Protection CT.pdf
2_Intro Protection + Protection CT.pdf2_Intro Protection + Protection CT.pdf
2_Intro Protection + Protection CT.pdf
 
Basics of Protection.pptx
Basics of Protection.pptxBasics of Protection.pptx
Basics of Protection.pptx
 
UNIT 1.pptx
UNIT 1.pptxUNIT 1.pptx
UNIT 1.pptx
 
Protective Relay by Shamim Reza
Protective Relay  by Shamim RezaProtective Relay  by Shamim Reza
Protective Relay by Shamim Reza
 
switchgear%20%20&%20protection%20introduction.pptx
switchgear%20%20&%20protection%20introduction.pptxswitchgear%20%20&%20protection%20introduction.pptx
switchgear%20%20&%20protection%20introduction.pptx
 
Lec 1_Introduction to Power System Protection.pdf
Lec 1_Introduction to Power System 
Protection.pdfLec 1_Introduction to Power System 
Protection.pdf
Lec 1_Introduction to Power System Protection.pdf
 
Powerprotection 1421105031
Powerprotection 1421105031Powerprotection 1421105031
Powerprotection 1421105031
 
Unit IV.pptx
Unit IV.pptxUnit IV.pptx
Unit IV.pptx
 
Power System Protection course - Part I
Power System Protection course - Part IPower System Protection course - Part I
Power System Protection course - Part I
 
Switchgear and protection 1
Switchgear and protection 1Switchgear and protection 1
Switchgear and protection 1
 
24620708 feeder-protection (1)
24620708 feeder-protection (1)24620708 feeder-protection (1)
24620708 feeder-protection (1)
 
Relaying and Protection Concepts.ppt
Relaying and Protection Concepts.pptRelaying and Protection Concepts.ppt
Relaying and Protection Concepts.ppt
 
Ieee generator protection
Ieee generator protectionIeee generator protection
Ieee generator protection
 

Último

1029-Danh muc Sach Giao Khoa khoi 6.pdf
1029-Danh muc Sach Giao Khoa khoi  6.pdf1029-Danh muc Sach Giao Khoa khoi  6.pdf
1029-Danh muc Sach Giao Khoa khoi 6.pdfQucHHunhnh
 
Key note speaker Neum_Admir Softic_ENG.pdf
Key note speaker Neum_Admir Softic_ENG.pdfKey note speaker Neum_Admir Softic_ENG.pdf
Key note speaker Neum_Admir Softic_ENG.pdfAdmir Softic
 
psychiatric nursing HISTORY COLLECTION .docx
psychiatric  nursing HISTORY  COLLECTION  .docxpsychiatric  nursing HISTORY  COLLECTION  .docx
psychiatric nursing HISTORY COLLECTION .docxPoojaSen20
 
Presentation by Andreas Schleicher Tackling the School Absenteeism Crisis 30 ...
Presentation by Andreas Schleicher Tackling the School Absenteeism Crisis 30 ...Presentation by Andreas Schleicher Tackling the School Absenteeism Crisis 30 ...
Presentation by Andreas Schleicher Tackling the School Absenteeism Crisis 30 ...EduSkills OECD
 
Application orientated numerical on hev.ppt
Application orientated numerical on hev.pptApplication orientated numerical on hev.ppt
Application orientated numerical on hev.pptRamjanShidvankar
 
Introduction to Nonprofit Accounting: The Basics
Introduction to Nonprofit Accounting: The BasicsIntroduction to Nonprofit Accounting: The Basics
Introduction to Nonprofit Accounting: The BasicsTechSoup
 
Beyond the EU: DORA and NIS 2 Directive's Global Impact
Beyond the EU: DORA and NIS 2 Directive's Global ImpactBeyond the EU: DORA and NIS 2 Directive's Global Impact
Beyond the EU: DORA and NIS 2 Directive's Global ImpactPECB
 
Energy Resources. ( B. Pharmacy, 1st Year, Sem-II) Natural Resources
Energy Resources. ( B. Pharmacy, 1st Year, Sem-II) Natural ResourcesEnergy Resources. ( B. Pharmacy, 1st Year, Sem-II) Natural Resources
Energy Resources. ( B. Pharmacy, 1st Year, Sem-II) Natural ResourcesShubhangi Sonawane
 
Basic Civil Engineering first year Notes- Chapter 4 Building.pptx
Basic Civil Engineering first year Notes- Chapter 4 Building.pptxBasic Civil Engineering first year Notes- Chapter 4 Building.pptx
Basic Civil Engineering first year Notes- Chapter 4 Building.pptxDenish Jangid
 
How to Give a Domain for a Field in Odoo 17
How to Give a Domain for a Field in Odoo 17How to Give a Domain for a Field in Odoo 17
How to Give a Domain for a Field in Odoo 17Celine George
 
Holdier Curriculum Vitae (April 2024).pdf
Holdier Curriculum Vitae (April 2024).pdfHoldier Curriculum Vitae (April 2024).pdf
Holdier Curriculum Vitae (April 2024).pdfagholdier
 
General Principles of Intellectual Property: Concepts of Intellectual Proper...
General Principles of Intellectual Property: Concepts of Intellectual  Proper...General Principles of Intellectual Property: Concepts of Intellectual  Proper...
General Principles of Intellectual Property: Concepts of Intellectual Proper...Poonam Aher Patil
 
Micro-Scholarship, What it is, How can it help me.pdf
Micro-Scholarship, What it is, How can it help me.pdfMicro-Scholarship, What it is, How can it help me.pdf
Micro-Scholarship, What it is, How can it help me.pdfPoh-Sun Goh
 
Sociology 101 Demonstration of Learning Exhibit
Sociology 101 Demonstration of Learning ExhibitSociology 101 Demonstration of Learning Exhibit
Sociology 101 Demonstration of Learning Exhibitjbellavia9
 
Class 11th Physics NEET formula sheet pdf
Class 11th Physics NEET formula sheet pdfClass 11th Physics NEET formula sheet pdf
Class 11th Physics NEET formula sheet pdfAyushMahapatra5
 
On National Teacher Day, meet the 2024-25 Kenan Fellows
On National Teacher Day, meet the 2024-25 Kenan FellowsOn National Teacher Day, meet the 2024-25 Kenan Fellows
On National Teacher Day, meet the 2024-25 Kenan FellowsMebane Rash
 
Advanced Views - Calendar View in Odoo 17
Advanced Views - Calendar View in Odoo 17Advanced Views - Calendar View in Odoo 17
Advanced Views - Calendar View in Odoo 17Celine George
 
Unit-IV- Pharma. Marketing Channels.pptx
Unit-IV- Pharma. Marketing Channels.pptxUnit-IV- Pharma. Marketing Channels.pptx
Unit-IV- Pharma. Marketing Channels.pptxVishalSingh1417
 
Role Of Transgenic Animal In Target Validation-1.pptx
Role Of Transgenic Animal In Target Validation-1.pptxRole Of Transgenic Animal In Target Validation-1.pptx
Role Of Transgenic Animal In Target Validation-1.pptxNikitaBankoti2
 
ComPTIA Overview | Comptia Security+ Book SY0-701
ComPTIA Overview | Comptia Security+ Book SY0-701ComPTIA Overview | Comptia Security+ Book SY0-701
ComPTIA Overview | Comptia Security+ Book SY0-701bronxfugly43
 

Último (20)

1029-Danh muc Sach Giao Khoa khoi 6.pdf
1029-Danh muc Sach Giao Khoa khoi  6.pdf1029-Danh muc Sach Giao Khoa khoi  6.pdf
1029-Danh muc Sach Giao Khoa khoi 6.pdf
 
Key note speaker Neum_Admir Softic_ENG.pdf
Key note speaker Neum_Admir Softic_ENG.pdfKey note speaker Neum_Admir Softic_ENG.pdf
Key note speaker Neum_Admir Softic_ENG.pdf
 
psychiatric nursing HISTORY COLLECTION .docx
psychiatric  nursing HISTORY  COLLECTION  .docxpsychiatric  nursing HISTORY  COLLECTION  .docx
psychiatric nursing HISTORY COLLECTION .docx
 
Presentation by Andreas Schleicher Tackling the School Absenteeism Crisis 30 ...
Presentation by Andreas Schleicher Tackling the School Absenteeism Crisis 30 ...Presentation by Andreas Schleicher Tackling the School Absenteeism Crisis 30 ...
Presentation by Andreas Schleicher Tackling the School Absenteeism Crisis 30 ...
 
Application orientated numerical on hev.ppt
Application orientated numerical on hev.pptApplication orientated numerical on hev.ppt
Application orientated numerical on hev.ppt
 
Introduction to Nonprofit Accounting: The Basics
Introduction to Nonprofit Accounting: The BasicsIntroduction to Nonprofit Accounting: The Basics
Introduction to Nonprofit Accounting: The Basics
 
Beyond the EU: DORA and NIS 2 Directive's Global Impact
Beyond the EU: DORA and NIS 2 Directive's Global ImpactBeyond the EU: DORA and NIS 2 Directive's Global Impact
Beyond the EU: DORA and NIS 2 Directive's Global Impact
 
Energy Resources. ( B. Pharmacy, 1st Year, Sem-II) Natural Resources
Energy Resources. ( B. Pharmacy, 1st Year, Sem-II) Natural ResourcesEnergy Resources. ( B. Pharmacy, 1st Year, Sem-II) Natural Resources
Energy Resources. ( B. Pharmacy, 1st Year, Sem-II) Natural Resources
 
Basic Civil Engineering first year Notes- Chapter 4 Building.pptx
Basic Civil Engineering first year Notes- Chapter 4 Building.pptxBasic Civil Engineering first year Notes- Chapter 4 Building.pptx
Basic Civil Engineering first year Notes- Chapter 4 Building.pptx
 
How to Give a Domain for a Field in Odoo 17
How to Give a Domain for a Field in Odoo 17How to Give a Domain for a Field in Odoo 17
How to Give a Domain for a Field in Odoo 17
 
Holdier Curriculum Vitae (April 2024).pdf
Holdier Curriculum Vitae (April 2024).pdfHoldier Curriculum Vitae (April 2024).pdf
Holdier Curriculum Vitae (April 2024).pdf
 
General Principles of Intellectual Property: Concepts of Intellectual Proper...
General Principles of Intellectual Property: Concepts of Intellectual  Proper...General Principles of Intellectual Property: Concepts of Intellectual  Proper...
General Principles of Intellectual Property: Concepts of Intellectual Proper...
 
Micro-Scholarship, What it is, How can it help me.pdf
Micro-Scholarship, What it is, How can it help me.pdfMicro-Scholarship, What it is, How can it help me.pdf
Micro-Scholarship, What it is, How can it help me.pdf
 
Sociology 101 Demonstration of Learning Exhibit
Sociology 101 Demonstration of Learning ExhibitSociology 101 Demonstration of Learning Exhibit
Sociology 101 Demonstration of Learning Exhibit
 
Class 11th Physics NEET formula sheet pdf
Class 11th Physics NEET formula sheet pdfClass 11th Physics NEET formula sheet pdf
Class 11th Physics NEET formula sheet pdf
 
On National Teacher Day, meet the 2024-25 Kenan Fellows
On National Teacher Day, meet the 2024-25 Kenan FellowsOn National Teacher Day, meet the 2024-25 Kenan Fellows
On National Teacher Day, meet the 2024-25 Kenan Fellows
 
Advanced Views - Calendar View in Odoo 17
Advanced Views - Calendar View in Odoo 17Advanced Views - Calendar View in Odoo 17
Advanced Views - Calendar View in Odoo 17
 
Unit-IV- Pharma. Marketing Channels.pptx
Unit-IV- Pharma. Marketing Channels.pptxUnit-IV- Pharma. Marketing Channels.pptx
Unit-IV- Pharma. Marketing Channels.pptx
 
Role Of Transgenic Animal In Target Validation-1.pptx
Role Of Transgenic Animal In Target Validation-1.pptxRole Of Transgenic Animal In Target Validation-1.pptx
Role Of Transgenic Animal In Target Validation-1.pptx
 
ComPTIA Overview | Comptia Security+ Book SY0-701
ComPTIA Overview | Comptia Security+ Book SY0-701ComPTIA Overview | Comptia Security+ Book SY0-701
ComPTIA Overview | Comptia Security+ Book SY0-701
 

See4423 chapter1 introduction[1]

  • 1. OFFICE: CENTER OF ELECTRICAL ENERGY SYSTEM (CEES) FACULTY ELECTRICAL ENGINEERING UNIVERSITI TEKNOLOGI MALAYSIA 81310 UTM JOHOR BAHRU JOHOR DARUL TAKZIM ROOM NO: P07-412 Tel: 07-5536262
  • 2. WELCOME • POWER SYSTEM ENGINEERING • SEE 4423 • LECTURER: ASSOC PROF MD SHAH MAJID • ROOM NO: P08-409/P07-417(CEES) • TEL: 07 -5535295/5536262 (CEES) • E-mail: mdshah@fke.utm.my, mdshah@ieee.org
  • 3. SEE 4423 POWER SYSTEM ENGINEERING SEMESTER II SESSION 2009/2010 Assoc Prof MD SHAH MAJID
  • 4. SEE 4423 POWER SYSTEM ENGINEERING SEMESTER 1 SESSION 2009/2010 4
  • 5. CHAPTER 1 INTRODUCTION TO PROTECTION SYSTEM
  • 6. Introduction:Need for Protective Systems • Power system consists of; generators, transformers, transmission and distribution lines, etc…..etc. – Sistem kuasa mengandungi: penjana, pengubah, talian penghantaran dan pengagihan dsbnya • Short circuits and other abnormal conditions often occur on a power system – Litar pintas dan keadaan tidak normal kerap berlaku pada sistem kuasa • Heavy current associated with short circuits is likely to cause damage to equipments – Arus yg tinggi ketika litar pintas mungkin menyebabkan kerosakan pada peralatan jika geganti perlindungan dan pemutus litar tidak di bekalkan untuk perlindungan bagi setiap seksyen sistem kuasa
  • 7. Need for Protective Systems • Short circuit is a faults (power engineer) • Failure of conducting path due to a break in a conductor is a type of fault • Fault occurs – automatic protective device is needed to isolate the faulty element as quickly as possible to keep the healthy section of the system in normal operation • Fault must be cleared within fraction of a second • Uncleared short circuits may cause total failure of the system
  • 8. A protective scheme includes transducers, protective relays and circuit breakers to isolate the faulty section of the system from the healthy section • Protection is needed not only against short circuit but also against any abnormal condition – Overspeed of generators and motors – Overvoltage – Underfrequency – Loss of excitation – Overheating of stator or rotor of an alternator – Etc…etc…etc • Protection is a pre-requisite for an effective and reliable system • A protective relay does not anticipate or prevent the occurrence of fault, rather it takes action only after a fault has occurred – except Buchholz relay; a gas actuated relay
  • 9. Nature and causes of Faults • Faults are caused either by; – Insulation failure – – Conducting path failure • results in short circuit • Faults on transmission and distribution lines are caused by overvoltage – Lightning and switching surges – External conducting objects falling on overhead line. • Birds also may cause faults on overhead line if their bodies touch one of the phase and earth wire
  • 10. If conductors are broken – failure of conducting path and the conductor becomes open-circuited – If broken conductor fall to the ground, results in short circuit • Joint failure on cables and overhead lines also cause a failure of the conducting path • Opening of one or two of the three phases makes the system unbalanced – Set-up harmonics
  • 11. Other causes of faults in o/h line – Direct lightning strokes – Aircraft – Snakes – Ice and snow loading – Abnormal loading – Storm – Earthquakes – Creepers – Etc…..etc……etc……etc
  • 12. Cables, transformer generators and other equipment: – Failure of solid insulation due to aging – Heat – Moisture – Overvoltage – Mechanical damage – Accidental with earth – Flashover due to overvoltages – Etc…etc…..etc
  • 13. Types of faults • Symmetrical faults • Unsymmetrical faults • Symmetrical faults – Kerosakan tiga fasa atau tiga fasa ke bumi • Unsymmetrical faults – Single line to earth, line-to-line, double line to earth, open-circuited phases
  • 14. Faults can interrupt power system in several ways: – Heavy current to flow • Effect : overheating of power system component – Fault is a short circuit and exist as electrical arc and liquid e.g air • Effect: equipment faulty and fire
  • 15. Fault – can increase/decrease voltage system outside its acceptable range – Can cause unstable three phase system, improper operation of three phase equipments – Prevent power flow – Can cause system to be unstable and collapse
  • 16. • Faults incur MONEY. • If fault is isolated as quickly as possible and accurate –less money required • Cost of protective equipment is 5% of the total cost of the system
  • 17. • PROTECTION DOES NOT MEAN PREVENTION – A protective relay does not anticipate or prevent the occurrence of fault, rather it takes action only after a fault has occurred – except Buchholz relay; a gas actuated relay
  • 18. Functions of Protective System • Fast and automatically opens the faulty section in the power system • Increase system reliability and security – only affected area will be isolated and maintain the healthy line – Ensure consumers receive continuity of supply • Delay in isolating the fault – System unstable, loss of synchronism, total failure of the system – Fire
  • 19. Requirements of Protective System • The basic requirements of a protective system are as follows: – Discrimination/selectivity – Sensitivity – Reliable – Stability – Speed
  • 20. (Discrimination/Selectivity) • Ability to select either to operate or not – Keupayaan untuk memilih sama ada bekerja atau tidak • Select to isolate the faulty section only (the rest normal condition) – Memilih untuk mengasingkan bahagian rosak sahaja (yang lain berkeadaan normal) • The nearest circuit breaker will trip – Pemutus litar yang hampir sahaja terbelantik (trip)
  • 21. Radial protection system SD2 SD3 SD1 SD1 SD2 SD3
  • 22. Sensitivity • Relay should operate when the magnitude of the current exceeds the preset value • This value is called pick up current • Should not operate when current is below its pick-up value • Should be sufficiently sensitive to operate when the operatinfg current just exceeds the pick-up value – relate with minimum operating current
  • 23. Reliability • A protective system must operate reliably when a fault occurs in its zone of protection • Failure may due to its protective element system; CT, PT, CB, relay etc…. • Reliability of protective system 95%
  • 24. Stability • A protective system should remain stable even when a large current is flowing through its protective zone due to an external fault • Concerned circuit breaker is supposed to clear the fault
  • 25. No Yes SD1 SD2 SD3 Radial system protection
  • 26. Speed-fast operation • Isolate fault as quickly as possible (at shortest time possible ) • Isolate disturbances before loss of synchronism and plant stop operation – time should not exceed critical clearing time • Speed balanced with economy – Cost of protective equipment should be relevant to the cost of the protected zone • Avoid fire to equipments, interruption of supply to consumer, voltage drop operating time; 1 cycle, ½ cycle are also available; distribution system > 1 cycle
  • 27. Operating time • Total time to accomplish the isolation • Calculated at the instance of fault until the given trip signal • Must be low for the sake of plant and equipment safety • Delay time – for discrimination
  • 28. Protection economy • Protection system can be designed as: – Simple and cheap – Complex and expensive • Baesd on: – The cost of fault – Safety level requirement
  • 29. Protection economics… • Cost of fault – Cost of damage toward the plant – Cost loss of revenue due to cut-out supply – Cost of customers confidence • Higher the cost of fault, more expensive the protection system • Higher the plant kVA, more complex protection system required
  • 30. Protection system at customer level • Simple fuse – protect equipment and certain circuits • Fius ringkas melindungi alat-alat dan litar tertentu • Miniature circuit breaker- MCB
  • 31. Protection system at distribution level • Fuse and switch fuse • Automatic reclosing circuit breaker – For rural area – Transient fault is corrected by self clearing
  • 32. Protection system at transmission level • Technical consideration outweighs the economy • 275kV dan 400kV System require a protection system which is: – very reliable – Full discrimation – High speed • Expensive and complex • Provide back-up protection
  • 33. Zone of Protection GENERATOR PROTECTION CIRCUIT BREAKER • Power system is divided into HV SWITCHGEAR several zones PROTECTION • Each zone of protection is TRANSFORMER provided with 2 types of PROTECTION protection: EHV SWITCHGEAR – Primary protection PROTECTION – Backup protection TRANSMISSION LINE PROTECTION EHV SWITCHGEAR PROTECTION ZONE OF PROTECTION
  • 34. Protection zone • Region or area encompass a protection system
  • 35. Protection zone CB3 CB3 CB1 CB2 SD1 SD2 SD3 Radial protection system
  • 36. Main/primary protection • In general primary protection is provided for each transmission line segment, major piece of equipment and switchgear • If fault occurs, it is the duty of the primary protective scheme to clear the fault • First line of defence - Responsible to isolate fault as quickly as possible • Fails, back-up protection clears the fault
  • 37. Backup Protection • Act when primary protection fails – second line of defence • Usually several back up protection scheme will act to control the power system • Longer time delay
  • 38. Radial protection system SD1 SD2 SD3 Main protection Back-up protection
  • 39. Zone of protection • Zone of protection usually overlap
  • 40. Fault detection • Current magnitude • Current in abnormal path (earth) • Current balance (current out#current in) • Voltage balance • Changes in impedance • Protective system damage(Buchholz), power flow direction, temeprature & pressure
  • 41. Protective system components 1. Circuit breaker 2. Transducer – current transformer (CT), voltage transformer (VT), potential transformer (PT) 3. Communication links – Pilot wire – Radio link – Overlapping signal, power line carrier (PLC)
  • 42. Protective system components 4. Relay – Electromagnetic – Static – improve reliability,versatile, fast response (1/4 cycle) – Microprocessor- VLSI teknologi – current interest to power engineers; adv:attractive flexibility due to programmable approach, can provide protection at low cost and compete with conventional relays 5. Fuse
  • 43. Transducer Serves as a sensor to detect abnormal system conditions and to transform the high values of short circuit current and voltage to a lower values 43
  • 44. Protective relays • Process the signals provided by the transducers which may be in the form of current, voltage or a combination of current and voltage 44
  • 45. Circuit breaker • Mechanical device used to energize and interrupt an electric circuit 45
  • 46. Ex. Protective system: power flow balance 2. CT, PT 1. PL 1. P.L 4. Relay R1 R2 3
  • 47. Classifications of relay based on its function • Overcurrent relay • Undervoltage relay • Impedance relay • Under frequency relay • Directional relay etc….etc….etc
  • 48. Classification of protective scheme • Overcurrent protection • Distance protection • Current carrier protection • Differential protection
  • 49. Transformer in a protective system • CT assume ideal Feeder Ip • Normal rating: conductor – 1:1, 2:1. 2.5:1, 4:1, 5:1 – 20:1, 40:1, 100:1, 200:1, 300:1, 600:1 Is CT – 1000:1, 2000:1, 4500:1 • Secondary coil is connected to a Vp “sensitive device” eg voltmeter Vs • Low Stray impedance so that voltage drop small VT
  • 50. Current transformer (CT) • Normal rating – 1A (Europe) – 5A (USA) • Example : – 50:5, 100:5, 150:5, 200:5, 250:5 – 450:5, 500:5,……1000:5, ……, 6000: • Secondary coil is connected to a “current sensing device” of zero impedance • Shunt impedance high so that I0 low.
  • 51. (current transformer CT) • Working principle similar to voltage transformer • Supply by current source • Primary winding connected in series with power circuit – Carries full load current • Transformer impedance (referred to secondary and can be neglected) • Secondary coil connected to load (burden)
  • 52. (current transformer CT) • Secondary winding feeds the protective system • Current is reduced but must be almost the same with the power system current • Secondary rated current 5 A or 1 A • Fault current 10 – 20 X rated current. Transformer must be capable to operate reliably/accurately at this value • Burden usually usually small – flux do not saturate
  • 53. Current transformer construction Bar Type Core Power system current Primary winding (1 turn)- from power system Secondary winding wound on the core
  • 55. design • CT – similar to a normal transformer emf equation • Average induced voltage = product of No. of turn and rate of change of flux magnet; eaverage = N(dΦ/dt) • Knee point voltage(rms) = 4.44 BAfN
  • 56. Burden • Defined as the load connected across its secondary CT – express in VA (VA taken as nominal secondary current of CT) or – Impedance (at the rated secondary current at a given power factor usually 07. lagging • Increase in impedance – increase burden • CT unloaded if secondary winding is short circuited
  • 57. Example • 5VA burden at 1A transformer, gives 5 Ohms impedance. • 5VA/1A = 5V • impedance = 5V/1A = 5Ω • or • At 5A CT • 5VA/5A • impedance = 1V/5A = 0.2 Ω
  • 58. Example • CT ratio 300/1, core area 40x30 mm • Voltage at knee point? • V = 4.44 x 0.0018 x 300 x 50 = 120 V • 1.5 x 40 x 30 x10-6 = 0.0018 Wb ( B for sheet steel, 1.5 tesla at knee point)
  • 59. CT open circuit • If burden high, Es high– exceed Vkp (knee point voltage) • Io high ; I2 less • Limited value when the secondary CT open circuit; I2 = 0; • Then N1I1 = N2 (I2+Io) = N2Io • This will drive the CT to saturation level • dΦ/dt = 100 x Vkp (induced = 100 Vkp ) • Cause insulation failure and overheated
  • 60. Current transformer equivalent circuit Ip’ x r Is I0’ Ic ’ Load (burden) Es Im’ Vs R Ip = primary current (nominal ratio) Kn I0 = primary excitation current (no load) I 'p = I p / Kn ' I0 = I0 / Kn
  • 61. Current transformer equivalent circuit Ip’ x r Is I0’ Im’ Ic ’ Load (burden) Es Vs R Es Ip’ I 'p = Is + I0 ' Is θ Is = I 'p − I 0 ' I0’ Ic ’ φ Im’
  • 62. relationship Es and φ (flux) N=no of turn in secondary dφ es = N dt π es = Nωφm sin(ωt + ) 2 φ = φ m sin ωt Nωφ m es = Nωφm cos ωt Es = ∠90° 2
  • 63. (Nominal Turn Ratio) • Determine from the given current ratio – Eg.1000/5 (bar type) Ip 200 K n = nominal ratio = = Is 1
  • 64. Actual Ratio • Actual ratio value Ip and Is ′ Ip actual ratio = winding ratio × Is ′ Ip = Kt × Is
  • 65. Winding ratio= secondary coil turn if transformer is of bar type l – Kt = N2/1 • Ideally ′ Ip =1 Is • Practically ′ Ip 〉1 Is Actual turn≥ nominal ratio
  • 66. CT error • Current error or ratio error • Phase error • Composite error
  • 67. Ratio error or current error nominal ratio -actual ration ratio error = × 100% actual ratio Nominal ratio= Kn ′ Ip actual ratio = K t × Turn ratio= Kt Is No compensation Kn=Kt
  • 68. Cont’d ' Ip K n − Kt Is ratio error = ' Ip Kn=Kt Kt Is (no compensation) K n I s − Kt I ' = p ' Kt I p difference in I s − I 'p magnitude between ratio error = × 100% Ip’ and Is I 'p
  • 69. Phase Error Difference in angle between Ip’ and Is Phase error= θ Es Ip’ Is α θ I0’ φ Im’
  • 70. Compensating winding • Secondary coil winding is reduced (1 or 2 turn) to compensate current error due by I0’. • Secondary coil current will be high, but the value will be minimised by the excitation current component • This can minimised the current error
  • 71. Example T1 • A current transformer 50 Hz has a secondary current of 3A,Sebuah • Secondary impedance circuit (0.6+j0.45), • Maximum flux 0.253 weber • Magnetisation current and core loss current (primary circuit) at this load are 0.2 and 0.15 A respectively • Turn ratio1:10, assume no compensation • Determine no of turn, ratio error and phase error of transformer
  • 72. CT equivalent circuit r Ip’ Is=3 ∠ αº I0’ Im’ Ic ’ Load (burden) Es Vs = 0.6+j0.45 Es ' Ip’ I 'p = I p / Kn I0 = I0 / Kn Is θ I 'p = Is + I0 ' I0’ Ic ’ φ Is = I 'p − I 0 ' Im’ α
  • 73. N1:N2 = 1:10 Kt = 10 = Kn Is=3 ∠ αº Im = 0.2 A Es = I s Z Ic = 0.15 A = 3∠α ° × 0.75∠36.87° N s × φm × ω = 2.25∠(α + 36.87)° Es = ∠90° 2 Es (α + 36.87)° = 90° Ip’ α = 90 − 36.87 α Is = 53.13° θ I0’ Ic’ Im’ φ
  • 74. N s × φm × ω = 2.25 2 2.25 × 2 Ns = 0.253 × 2π × 50 = 40 ∴ N1:N2 = 4:40
  • 75. I 0 = 0.20 + j 0.15 Is=3 ∠ αº ′ 1 I0 = (0.20 + j 0.15) × Im = 0.2 A 10 Ic = 0.15 A = 0.02 + j 0.015 ′ ′ I p = I0 + Is Es = 0.020 + j 0.015 + 3∠53.13° Ip’ = 3.024∠52.9975° Is θ I0’ Ic’ φ Im’
  • 76. Is + I p 3 − 3.024 ratio error = = × 100% ′ 3.024 Ip = −0.794 % phase error = 53.13 − 52.9975 = 0.1325
  • 77. Ex 1 • A current transformer has 15 turn on the primary and 75 turn on the secondary. The relay burden is (1.2+j2.6)Ω and secondary winding impedance of the transformer is (3.6+j0.4)Ω. If the magnitude of the secondary voltage is 26 volt and magnetization current referred to secondary is 0.24∠-45o amp. Determine the ratio error and phase error.
  • 78. Ex 2 • A new non compensated CT with a cross sectional area of 40 cm2 has a nominal ratio of 2000/5. When 5A is supplied to a relay, the combination of load relay and secondary winding impedance is (10+j5.77) Ω. If the magnetisation amp-turn is 100 and core loss amp-turn is 50, determine the ratio error and phase error. Using the same data, calculate also the compensating turn to reduce the ratio error to a minimum.
  • 79. Ex. 3 • A CT, 50 Hz has a primary winding of 10 turn and its cross sectional area is 8 cm2. Secondary current is 5A. The total load and secondary impedance is 0.8+j0.5 Ω. The excitation current required at the primary winding to establish a working flux with the secondary open is 0.6∠45o amp. If the flux density is 0.1878 wb/m2,determine the nominal ratio of the transformer. Determine also the ratio error and phase error of the transformer.
  • 80. Composite error • BS 3938:1973 – (r.m.s.) value; difference between ideal secondary current (i.e CT is ideal ; no excitation component) with actual secondary current. • Encompass (current error, phase error and harmonic effect)
  • 81. Accuracy limit current of a protection system CT • Accuracy limit current (saturation current) – The maximum current a CT can sustain before exceed its accuracy – Specify either in term of primary current or secondary current • Accuracy limit factor (saturation factor) – Ratio of accuracy limit primary current and rated primary current – Standard values are 5, 10, 15, 20 and 30
  • 82. CT specification • Expressed in – VA at rated current /class accuracy/accuracy limit factor – Burden standard rated values • 2.5,5,7.5,10,15 and 30 VA – 2 accuracy class: 5P and 10P – gives composite error at rated accuracy limit 5% and 10% respectively – Standard accuracy limit factor: • 5, 10, 15, 20 and 30
  • 83. Rating of CT • Method to explain CT – 10VA/5P/25 Accuracy limit current is 25 x rated current Transformer works in good condition/reliably until 25 x its Rated burden Class – error rated curent do not exceed 5%
  • 84. Ex 1 • CT 10VA/5P/15 • Calculate the accuracy limit factor when the burden is half of its initial value. • Secondary resistance of CT 0.15 ohm
  • 85. Solution Burden impedance 10VA at rated current 5A r Es VA V ×I = Burden (R) = I × R× I V = I 2R 10 R = 2 = 0.4 ohm 5
  • 86. Solution Total impedance referred to r secondary winding = 0.15 + 0.4 = 0.55 ohm Es V Burden (R) Accuracy limit factor= ratio accuracy limit current and rated current Accuracy limit current= Accuracy limit factor × Rated current accuracy limit current = 15 × 5 = 75 A
  • 87. secondary emf = 0.55 × 75 V = 41.25 V r Es Burden (R=0.4) When burden is half R = 0.2 ohm Total secondary impedance= 0.15 + 0.2 = 0.35 ohm
  • 88. new accuracy limit current = 41.25 / 0.35 = 117.8 A new accuracy limit factor = 117.8 / 5 = 23.56 Smaller the burden, the higher the accuracy Therefore : burden has to be low possible
  • 89. CT Class X • BS 3938 – CT for special application is known as Class “X’ • Expressed in turn ratio, knee point voltage, excitation current at the specified voltage and secondary winding resistance – Application – scheme where the phase fault stability and/or accurate time grading required • Transformer rating specify in term of e.m.f maximum that can be use by the transformer • knee point – Point where an increase of 10% in secondary e.m.f require an addition of 50% excitation current
  • 90. Definition of knee point Excitation voltage +10% Knee point +50% Excitation current
  • 91. Voltage transformer/potential transformer(VT/PT) • Supply voltage lower than the sistem voltage • Nominal sekunder voltage110V • 2 types – Wound ( electromagnetic) type(> 132 kV non economical) – Capacitor type- CVT • Element X and C consist of tuning circuit – to reduce the ratio and phase angle error secondary voltage
  • 92. 1/ωC2 = ωL pd 50 Hz; V2 = V’ Talian C1 L Vp Rb V’ Vs C2 V2 Xb V’ = 12 kV, C1 = 2000pF L C2 V2 110 V V’
  • 93. Protection techniques • Protection scheme: – Arrangements of CT, VT, pilot wire and relay so that the required operating characteristics can be obtained • Each section of the power system network is monitored by several protection scheme.
  • 94. Main/primary scheme usually consists of: Unit Scheme Backup scheme consists of: Non Unit Scheme
  • 95. Unit scheme • ZONE OF PROTECTION IS WELL DEFINED
  • 96. Unit protection scheme CT CT Protected zone P Pilot wire R relay Q Difference current scheme: circulating current FAULT: Non similar current flow in the relay CB will trip R
  • 97. CT Healthy and fault e1 Protected zon e2 external zone (through fault): No current in relay, e1=e2 R R FAULT: Current flow in circuit, result e1≠e2 Differencec current scheme: voltage balance
  • 98. Balance power direction CT, PT PL P.L Relay R1 R2 Trip Trip Restrain Restrain
  • 99. CB1 CB2 A B R1 R2 Trip Trip Restrain Restrain Power flow entering the feeder (from point A) will cause relay (R1) close trip contact CB1 Power flow exit fron the feeder (at point B) will cause relay R2 rotate and close restrain contact of the further circuit breaker (remote) (CB1) (relay R2 send restrain signal CB1)
  • 100. CB1 CB2 A B R1 R2 Trip Trip Restrain Restrain Power enter at A and exit at B, block trip will prevent the CB from opening.
  • 101. CB1 CB2 A B R1 R2 Trip Trip Restrain Restrain Power enter at A and at B (fault occurs), both CB open
  • 102. CB1 CB2 A B R1 R2 Trip Trip Restrain Restrain Power enter at A and no power at B, circuit breaker A, CB1 will open
  • 103. NON UNIT SCHEME  supervise/monitor one or several points in the power system  signal will be detected at the points  this signal is the input to the relay  section monitored/supervised is not clearly defined ZONE OF PROTECTION IS NOT WELL DEFINED
  • 104. 2 examples of non unit scheme (1.) Over Current Protection (2.) Distance Protection