rechter Rand right margin marge droite margine destra High challenge warehouse case study – Summary February 19, 2010 Richard Gallagher Michael Gollner Zurich Services Corporation
Objectives Review the results of the high challenge warehouse workshop Recognize participants Explain the project background Review case  Given information Question Summarize the eight presentations Recap the overall findings
Case study participants Schirmer Engineering 		Dan O’Connor, Garner Palenske Rolf Jensen and Associates 		Richard Bukowski	 FPI Consortium 			Warde Comeaux	 Telgian				Tracy Bellamy Summit Fire Protection 		Sean Merkel, Ryan Bierwerth	 Hughes Associates			Jerry Back, Joe Scheffey,  						Dan Gottuk UCSD 				Michael Gollner  	WPI 					Ali Rangawala 	Creative FPE Solutions		Jonathan Perricone XL GAPS				John Frank
Background NFPA 13 basis:  Automatic sprinklers control or suppression a fire Final fire extinguishment by the fire service Today’s warehouses High challenges to both sprinklers and fire service   Recent fire experience Not always reasonable to expect manual intervention Foundation Addressing research to support potential changes to NFPA standards.
Workshop approach Basis for workshop Theoretical Case Study Presentations Six leading FPE companies share innovative design concepts One presentation on novel approach to manual fire suppression One presentation addressing need to step back further and understand commodities and storage Format 20 minute presentations Panel Q&A
Case Study Warehouse 6 2/4/2010 High Challenge Warehouse Case Study
2/4/2010 7 High Challenge Warehouse Case Study General conditions Who -	XYZ Company What -	New warehouse Where -	Rural region of US
2/4/2010 8 High Challenge Warehouse Case Study Facility parameters Two attached buildings Low Bay 100’ x 150’ x 35’ tall High Bay   55’ x 150’ x 65’ tall
2/4/2010 9 High Challenge Warehouse Case Study Facility construction Roof –Noncombustible steel deck on steel bar joist High bay rack supported roof Exterior walls – Insulated metal panel Interior walls Between Low Bay and High Bay 150’ long Reinforced concrete block Up to Low Bay roof Floors – Reinforced concrete
2/4/2010 10 High Challenge Warehouse Case Study Public protection Public fire service Volunteer department XYZ Company is first storage facility in district Public water Extending main 3 miles to site Limited flow 60 psi static / 20 psi residual / 800 gpm flowing
2/4/2010 11 High Challenge Warehouse Case Study Private protection Water supply Two fire pumps – one electric, one diesel Ground water suction tank Detached fire pump house 300 feet from building
2/4/2010 12 High Challenge Warehouse Case Study Storage commodity Group A plastics Unexpanded In cartons Nonencapsulated Conventional wood pallets Pallet loads 4’ x 4’ x 4’
2/4/2010 13 High Challenge Warehouse Case Study Storage configuration Workshop focus The High Bay warehouse High bay Multiple row rack (4 pallets deep) flanked by double row racks Racks are separated aisles 5 ft wide Array 23 pallets long & 13 pallets high Nominal 6” flues around each pallet load Tiers 5’ tall Elevation View
2/4/2010 14 High Challenge Warehouse Case Study Stock handling Low Bay Industrial trucks High Bay Automatic storage and retrieval system (ASRS) Two ASRS systems Operate in 5 ft wide aisles Photo source: FEMA
2/4/2010 15 High Challenge Warehouse Case Study The challenge Local fire chief has made it clear that 	in the event of a fire - Will enter building to save people Will not enter building to save property Question:   	As the fire protection engineer of record, what fire protection design will be proposed to achieve final fire extinguishment without fire service intervention? Photo source: FEMA
Summary of case study presentations
Summary format Ignition -	Sources of ignition Agent -	Extinguishing media Detection/ 	Release -	Method of detection and release ASRS -	Uses for ASRS Failure -	Noted failure concerns for method Comments -	Additional comments Where no data provided – marked “NA” and grayed-out
Schirmer Engineering Ignition -	Arson, electrical, etc. Agent -	Water -	ESFR high zone at intersection of flues & over aisles 				ESFR low zone at intersection of flues 				One level in-racks in each zone 				1600 gpm either zone 				Horizontal barrier between high and low zones 			CO2 -	Low zone for redundancy (higher exposure area) 				Local application, can pipe long distances, can handle 				  flammable liquids and electrical fires, no pumps,  				Use a 30-60 second discharge 				Divide low zone into sections (CO2 volume calculations) Detection/ 	Release -	Sprinkler fusible element, In-rack linear/spot heat detection ASRS -		NA Failure -	NA Comments -	Test ESFR configuration, locate in flues, avoid water ricochet 		Test low zone detection concept 			Develop CO2 nozzle 			Technology proven and can implement today
Rolf Jensen and Associates Ignition -	NA Agent -	Water mist 			Zoned vertically (vertical risers) 			Spray either side of pallet and one side of adjacent pallet 			High velocity exhaust fans on outside walls  			- Produce airflow perpendicular to aisles to distribute water mist 			- Maintain visibility Detection/ 	Release -	In-rack linear heat detection to locate fire  ASRS -	Use self-contained foam skid IR camera guided nozzle 			Not for primary suppression due to response time  Failure -	NA Comments -	Low bay is typical for ESFR 			  Critical to maintain longitudinal and transverse flues 			High bay ceiling sprinklers to protect building
FPI Consortium Ignition -	ASRS (lights not usually in use) electrical rails top and  			  bottom, fires involve ASRS unit and spreads to storage Agent -	High expansion foam – submerge in 4 min 			13 foam generators 			30 minute duration 			100,000 gallons water for 30 minutes Detection/ -	Heat detection -  ceiling & in-rack spot heat detection Release	Ceiling 15’ x 15’, in-rack 10’ vertical & 8’ horizontal ASRS -	Not used, returned to home base and shutdown Failure -	Doors and openings must close 			False release of foam (cross-zone possible) Comments -	Sprinklers not considered due to environment impact
Telgian Ignition -	ASRS or lighting at elevated location Agent -	Water 			Design an in-rack sprinklers, quick response 			Need horizontal barriers above in-racks, perhaps each tier 			Use waterflow to locate fire vertically Detection/ 	Release -	Fusible sprinkler elements ASRS -	Locate fire using thermal imaging 			Relocate stock to safe area 			Handle wet and damaged loads (enclosed unit) Failure -	NA Comments -	Need in-rack sprinkler design guidance 			- In-rack response time 			- In-rack water distribution
Summit Fire Protection Ignition -	NA Agent -	Water 			Develop suppression mode in-racks 			Increased clearance for larger orifice in-rack sprinklers 			Fire barriers to provide fire confinement 			300,000 gallons – 2 hour duration Detection/ 	Release -	Fusible sprinklers elements ASRS -	Under fire conditions, ASRS not available Failure -	NA Comments -	Introduce ESRF into racks 			Evaluate all changes over time (personnel turnover,  			  commodities, maintenance, etc.
Hughes Associates Ignition -	NA Agent -	High expansion foam 			Zoned system, 4 quadrants, barriers wire mesh/noncombustible fabric 			  Curtains strips to allow ASRS passage   			Safety factors of 2+ compared to NFPA requirements 			20,000 gallons water – 30 minute duration Detection/ -	In-rack linear heat detection 	Release	Flame detection for open spaces ASRS -	Apply skid mounted fire suppression system 			Remove pallets of stock around fire 			Evaluate extinguishment – video monitoring 			Remove pallets of damaged stock Failure -	Fire at zone interface, Openings between zones, 			Collateral damage to stock remote from fire Comments -	Goals include low complexity, reasonable cost, rapid control,  			  extinguishment, minimum fire damage, and 			  minimum collateral damage
WPI, UCSD, Creative FPE Solutions Ignition -	NA Agent -	NA Detection	 	Release -	NA ASRS -		NA Failure -	NA Comments -	Must start at a more fundamental level 			Develop method to quantify warehouse fire control, 			  suppression, or extinguishment 			Limits to “modeling” and “small scale testing” 			Need new intermediate-scale test 			- Determine water application rate for suppression 			- Will discuss further in a few slides
XL GAPS Ignition -	NA Agent -	Water 			Mobilize remote special fire fighting team 			Need 12 hours (remote response, size-up, extinguish, overhaul) 			Sprinklers controlling fire during this time 			Need 900,000 gallons water Detection/ 	Release -	Fusible sprinkler elements ASRS -	Fire fighter access to upper tiers Failure -	NA Comments -	Interim solution until an engineered solution available 			Specialized fire team responding from central location 			Similar to private emergency services such as 			  urban search and rescue, oil wells, oil tanks  			Skills to verify building stability, locate fire, work  			  vertically, apply agent
Summary of work 	Ignition scenarios 	Proposed solutions 	Design challenges 	Gaps 	Manual intervention
Identified ignition scenarios ASRS equipment Power rails top and bottom Power on stacker crane Can introduce ignition source at any level Lighting Ignition exposure at roof Arson Anticipate low level exposure 2/4/2010 27 High Challenge Warehouse Case Study
Solutions Manual fire suppression – an immediate solution XL Gaps  Test & validate current sprinkler suppression practices WPI, UCSD, Edinburgh, and Creative FPE Solutions. Sprinklers – modify current designs – ESFR inracks Summit Fire Protection Telgian Sprinklers (2 levels ESFR) & CO2 Schirmer High expansion foam FPI Consortium Hughes Associates Water mist RJA 2/4/2010 28 High Challenge Warehouse Case Study
Design challenges  Water sources Reliability / redundancy Volume / duration Cost of system due to rural location Environmental concerns Release of contaminated water Recycling of used water Hazard of commodity Defining the hazard of a commodity Commodities changing or introducing unknown commodities In-rack sprinkler placement and type (ESFR)  highly specific to fuel type, configuration Avoiding complex designs  Can collateral damage be limited to limit business impact 2/4/2010 29 High Challenge Warehouse Case Study
GapsTest methodologies There are no methods, currently, to quantify warehouse fire control, suppression or extinguishment. A test methodology is needed to ensure adequacy of current and new design concepts   How much suppressant? Length of discharge? Limitations in full scale, small scale testing and modeling demand a new approach – small scale commodity classification verified by intermediate scale testing and large scale modeling/testing for validation
GapsDesign approach – WPI et al 2/4/2010 31 High Challenge Warehouse Case Study 2. SprinklerFlow Characterization Determine limits of current sprinkler protection systems Analyze the warehouse fire problem in pieces 1. Characterize sprinkler spray 2. Droplet losses from geometry, plume, radiation, etc. 3. Suppression/Extinction interaction between film/drops and fire Benefits: Design fixed system to provide suppression or extinction for any tested materials Utilize current sprinkler infrastructure and modify deficient systems if necessary Sprinkler Spray PLUME 1. Classification of Commodity FIRE
Gaps Design approach – WPI et al Engineering Approach to Warehouse Fire Protection Design 32
GapsTechnology In-rack sprinkler design No sprinkler designed to respond quickly in a rack No sprinkler designed to distribute water in a rack No suppression mode in-rack sprinkler Hardening of ASRS for use during fire event Carry self-contained extinguishing system skid Identify fire location within array Verify fire control/suppression progress Remove adjacent stock to isolate fire Remove wet or damaged stock
GapsManual intervention - the immediate solution Water supplies Are durations sufficient (2 hours vs. 12 hours) Thorough pre-emergency planning Safe work plan
Questions or comments? 2/4/2010 35 High Challenge Warehouse Case Study

Más contenido relacionado

La actualidad más candente

Passive fire measures vs active fire measues
Passive fire measures vs active fire measuesPassive fire measures vs active fire measues
Passive fire measures vs active fire measuesKamran Hassan
 
BS 9999 Fire Engineering
BS 9999 Fire EngineeringBS 9999 Fire Engineering
BS 9999 Fire Engineeringguesta5b4bba
 
Data center specific thermal and energy saving techniques
Data center specific thermal and energy saving techniquesData center specific thermal and energy saving techniques
Data center specific thermal and energy saving techniquesXiao Qin
 
Water Mist Systems - Akshay Jangam.
Water Mist Systems - Akshay Jangam. Water Mist Systems - Akshay Jangam.
Water Mist Systems - Akshay Jangam. Akshay Jangam
 
13. insulation and fire protection
13. insulation and fire protection13. insulation and fire protection
13. insulation and fire protectionNoshad Ahmed Wahocho
 
Cooling Optimization 101: A Beginner's Guide to Data Center Cooling
Cooling Optimization 101: A Beginner's Guide to Data Center CoolingCooling Optimization 101: A Beginner's Guide to Data Center Cooling
Cooling Optimization 101: A Beginner's Guide to Data Center CoolingUpsite Technologies
 
Roadwork from CPWD specification
Roadwork from CPWD specificationRoadwork from CPWD specification
Roadwork from CPWD specificationRajiva Gupta
 
Recycle material used in road construction
Recycle material used in road constructionRecycle material used in road construction
Recycle material used in road constructionpavan bathani
 
Types of fire sprinkler heads
Types of fire sprinkler headsTypes of fire sprinkler heads
Types of fire sprinkler headsRanjitMarketing
 
FIRE PROTECTION AND FIRE SAFETY REQUIREMENTS by Dr.Mahboob ali khan Phd
FIRE PROTECTION AND FIRE SAFETY REQUIREMENTS by Dr.Mahboob ali khan Phd FIRE PROTECTION AND FIRE SAFETY REQUIREMENTS by Dr.Mahboob ali khan Phd
FIRE PROTECTION AND FIRE SAFETY REQUIREMENTS by Dr.Mahboob ali khan Phd Healthcare consultant
 
Gabion structures ppt
Gabion  structures pptGabion  structures ppt
Gabion structures pptswetass8
 
Data Center Cooling System Design: Reducing Cooling Costs and Power Consumpti...
Data Center Cooling System Design: Reducing Cooling Costs and Power Consumpti...Data Center Cooling System Design: Reducing Cooling Costs and Power Consumpti...
Data Center Cooling System Design: Reducing Cooling Costs and Power Consumpti...SimScale
 

La actualidad más candente (20)

Warm Mix Asphalt research and performance
Warm Mix Asphalt research and performanceWarm Mix Asphalt research and performance
Warm Mix Asphalt research and performance
 
Passive fire measures vs active fire measues
Passive fire measures vs active fire measuesPassive fire measures vs active fire measues
Passive fire measures vs active fire measues
 
BS 9999 Fire Engineering
BS 9999 Fire EngineeringBS 9999 Fire Engineering
BS 9999 Fire Engineering
 
Nano concrete ppt
Nano concrete  pptNano concrete  ppt
Nano concrete ppt
 
Data center specific thermal and energy saving techniques
Data center specific thermal and energy saving techniquesData center specific thermal and energy saving techniques
Data center specific thermal and energy saving techniques
 
Water Mist Systems - Akshay Jangam.
Water Mist Systems - Akshay Jangam. Water Mist Systems - Akshay Jangam.
Water Mist Systems - Akshay Jangam.
 
Modular Data Center Design
Modular Data Center DesignModular Data Center Design
Modular Data Center Design
 
Chapter 05
Chapter 05Chapter 05
Chapter 05
 
13. insulation and fire protection
13. insulation and fire protection13. insulation and fire protection
13. insulation and fire protection
 
Cooling Optimization 101: A Beginner's Guide to Data Center Cooling
Cooling Optimization 101: A Beginner's Guide to Data Center CoolingCooling Optimization 101: A Beginner's Guide to Data Center Cooling
Cooling Optimization 101: A Beginner's Guide to Data Center Cooling
 
Roadwork from CPWD specification
Roadwork from CPWD specificationRoadwork from CPWD specification
Roadwork from CPWD specification
 
Recycle material used in road construction
Recycle material used in road constructionRecycle material used in road construction
Recycle material used in road construction
 
Types of fire sprinkler heads
Types of fire sprinkler headsTypes of fire sprinkler heads
Types of fire sprinkler heads
 
FIRE PROTECTION AND FIRE SAFETY REQUIREMENTS by Dr.Mahboob ali khan Phd
FIRE PROTECTION AND FIRE SAFETY REQUIREMENTS by Dr.Mahboob ali khan Phd FIRE PROTECTION AND FIRE SAFETY REQUIREMENTS by Dr.Mahboob ali khan Phd
FIRE PROTECTION AND FIRE SAFETY REQUIREMENTS by Dr.Mahboob ali khan Phd
 
Roof systems
Roof systemsRoof systems
Roof systems
 
Fire safety arrangement
Fire safety arrangementFire safety arrangement
Fire safety arrangement
 
Energy Modeling
Energy ModelingEnergy Modeling
Energy Modeling
 
Gabion structures ppt
Gabion  structures pptGabion  structures ppt
Gabion structures ppt
 
Data Center Cooling System Design: Reducing Cooling Costs and Power Consumpti...
Data Center Cooling System Design: Reducing Cooling Costs and Power Consumpti...Data Center Cooling System Design: Reducing Cooling Costs and Power Consumpti...
Data Center Cooling System Design: Reducing Cooling Costs and Power Consumpti...
 
9. DUCT DESIGN.pdf
9. DUCT DESIGN.pdf9. DUCT DESIGN.pdf
9. DUCT DESIGN.pdf
 

Destacado

Fire Protection Systems Unit-I
Fire Protection Systems Unit-IFire Protection Systems Unit-I
Fire Protection Systems Unit-IGAURAV. H .TANDON
 
Msc Structural Engineering and Mechanics Dissertation
Msc Structural Engineering and Mechanics DissertationMsc Structural Engineering and Mechanics Dissertation
Msc Structural Engineering and Mechanics DissertationAlexandros Alexandrou
 
Fire Dynamics Terminology
Fire Dynamics TerminologyFire Dynamics Terminology
Fire Dynamics TerminologyMias Coetzer
 
Fire and Forest Dynamics in Northern Boreal Forests
Fire and Forest Dynamics in Northern Boreal ForestsFire and Forest Dynamics in Northern Boreal Forests
Fire and Forest Dynamics in Northern Boreal Forestsakfireconsortium
 
Phil_Sutton-Portfolio
Phil_Sutton-PortfolioPhil_Sutton-Portfolio
Phil_Sutton-PortfolioPhil Sutton
 
PR-SOCO Personality Recognition in SOurce COde (PAN@FIRE 2016)
PR-SOCO Personality Recognition in SOurce COde (PAN@FIRE 2016)PR-SOCO Personality Recognition in SOurce COde (PAN@FIRE 2016)
PR-SOCO Personality Recognition in SOurce COde (PAN@FIRE 2016)Francisco Manuel Rangel Pardo
 
London Fire Brigade - Fire Resistance CPD Presentation
London Fire Brigade - Fire Resistance CPD PresentationLondon Fire Brigade - Fire Resistance CPD Presentation
London Fire Brigade - Fire Resistance CPD PresentationDanny Hopkin
 
Cutting Extinguishing Method Use Cases
Cutting Extinguishing Method Use CasesCutting Extinguishing Method Use Cases
Cutting Extinguishing Method Use CasesAnders Trewe
 
Modeling Stochasticity and Gap Junction Dynamics: Integrate and Fire Model
Modeling Stochasticity and Gap Junction Dynamics: Integrate and Fire ModelModeling Stochasticity and Gap Junction Dynamics: Integrate and Fire Model
Modeling Stochasticity and Gap Junction Dynamics: Integrate and Fire Modeldharmakarma
 
Introduction to bye laws
Introduction to bye lawsIntroduction to bye laws
Introduction to bye lawsNitin Thakral
 
National building codes 2005 history overview
National building codes 2005 history overviewNational building codes 2005 history overview
National building codes 2005 history overviewShourya Puri
 
Dr. B. Krishnamurthy medicall 2011 fms
Dr. B. Krishnamurthy medicall 2011 fmsDr. B. Krishnamurthy medicall 2011 fms
Dr. B. Krishnamurthy medicall 2011 fmsSatishkumar Durairajan
 

Destacado (19)

Fire Protection Systems Unit-I
Fire Protection Systems Unit-IFire Protection Systems Unit-I
Fire Protection Systems Unit-I
 
Msc Structural Engineering and Mechanics Dissertation
Msc Structural Engineering and Mechanics DissertationMsc Structural Engineering and Mechanics Dissertation
Msc Structural Engineering and Mechanics Dissertation
 
Fire Dynamics Terminology
Fire Dynamics TerminologyFire Dynamics Terminology
Fire Dynamics Terminology
 
Fire and Forest Dynamics in Northern Boreal Forests
Fire and Forest Dynamics in Northern Boreal ForestsFire and Forest Dynamics in Northern Boreal Forests
Fire and Forest Dynamics in Northern Boreal Forests
 
Phil_Sutton-Portfolio
Phil_Sutton-PortfolioPhil_Sutton-Portfolio
Phil_Sutton-Portfolio
 
Health & Safety
Health & SafetyHealth & Safety
Health & Safety
 
TpM2015, Gavin Bate, CEO Adventure Travel: Sharing Economy: The responsible t...
TpM2015, Gavin Bate, CEO Adventure Travel: Sharing Economy: The responsible t...TpM2015, Gavin Bate, CEO Adventure Travel: Sharing Economy: The responsible t...
TpM2015, Gavin Bate, CEO Adventure Travel: Sharing Economy: The responsible t...
 
Full dissertation
Full dissertationFull dissertation
Full dissertation
 
PR-SOCO Personality Recognition in SOurce COde (PAN@FIRE 2016)
PR-SOCO Personality Recognition in SOurce COde (PAN@FIRE 2016)PR-SOCO Personality Recognition in SOurce COde (PAN@FIRE 2016)
PR-SOCO Personality Recognition in SOurce COde (PAN@FIRE 2016)
 
TpM2015: Shadow hospitality: the view of the hoteliers
TpM2015: Shadow hospitality: the view of the hoteliersTpM2015: Shadow hospitality: the view of the hoteliers
TpM2015: Shadow hospitality: the view of the hoteliers
 
G
GG
G
 
London Fire Brigade - Fire Resistance CPD Presentation
London Fire Brigade - Fire Resistance CPD PresentationLondon Fire Brigade - Fire Resistance CPD Presentation
London Fire Brigade - Fire Resistance CPD Presentation
 
Chapter 05
Chapter 05Chapter 05
Chapter 05
 
Cutting Extinguishing Method Use Cases
Cutting Extinguishing Method Use CasesCutting Extinguishing Method Use Cases
Cutting Extinguishing Method Use Cases
 
Modeling Stochasticity and Gap Junction Dynamics: Integrate and Fire Model
Modeling Stochasticity and Gap Junction Dynamics: Integrate and Fire ModelModeling Stochasticity and Gap Junction Dynamics: Integrate and Fire Model
Modeling Stochasticity and Gap Junction Dynamics: Integrate and Fire Model
 
A Hands-On Guide for Inspection & Maintenance
A Hands-On Guide for Inspection & MaintenanceA Hands-On Guide for Inspection & Maintenance
A Hands-On Guide for Inspection & Maintenance
 
Introduction to bye laws
Introduction to bye lawsIntroduction to bye laws
Introduction to bye laws
 
National building codes 2005 history overview
National building codes 2005 history overviewNational building codes 2005 history overview
National building codes 2005 history overview
 
Dr. B. Krishnamurthy medicall 2011 fms
Dr. B. Krishnamurthy medicall 2011 fmsDr. B. Krishnamurthy medicall 2011 fms
Dr. B. Krishnamurthy medicall 2011 fms
 

Similar a High Challenge Warehouse case study

Sprinkler_Systems_Presentation.ppt
Sprinkler_Systems_Presentation.pptSprinkler_Systems_Presentation.ppt
Sprinkler_Systems_Presentation.pptRehan416661
 
Dafo FORREX - Conveyor Belt Proactive Fire Protection System
Dafo FORREX - Conveyor Belt Proactive Fire Protection SystemDafo FORREX - Conveyor Belt Proactive Fire Protection System
Dafo FORREX - Conveyor Belt Proactive Fire Protection SystemPedro Perim
 
ashraeqatar_16.04.09_s_p_introduction_to_car_park_jetfan_ventilation_1.pdf
ashraeqatar_16.04.09_s_p_introduction_to_car_park_jetfan_ventilation_1.pdfashraeqatar_16.04.09_s_p_introduction_to_car_park_jetfan_ventilation_1.pdf
ashraeqatar_16.04.09_s_p_introduction_to_car_park_jetfan_ventilation_1.pdfMarcGajudo
 
Psv fire training weldfit
Psv fire training weldfitPsv fire training weldfit
Psv fire training weldfitAdam Murray
 
Inspection of Fire Fighting Equipments | NFPA Regulations | Gaurav Singh Rajput
Inspection of Fire Fighting Equipments | NFPA Regulations | Gaurav Singh RajputInspection of Fire Fighting Equipments | NFPA Regulations | Gaurav Singh Rajput
Inspection of Fire Fighting Equipments | NFPA Regulations | Gaurav Singh RajputGaurav Singh Rajput
 
Engine company operations
Engine company operationsEngine company operations
Engine company operationsAndy Mihans
 
Part 3 - Fire Protection Systems in Buildings.pdf
Part 3 - Fire Protection Systems in Buildings.pdfPart 3 - Fire Protection Systems in Buildings.pdf
Part 3 - Fire Protection Systems in Buildings.pdfIgnacio J. Palma, Arch PhD.
 
2015 x472 class 02 - generation systems
2015 x472 class 02 - generation systems2015 x472 class 02 - generation systems
2015 x472 class 02 - generation systemsmichaeljmack
 
Introduction to Process Flares
Introduction to Process FlaresIntroduction to Process Flares
Introduction to Process FlaresKarl Kolmetz
 
Royex - generation 2 introduction
Royex - generation 2 introductionRoyex - generation 2 introduction
Royex - generation 2 introductionPyroDem Ltd
 
S lab 2014 eeco2 tel - presentation
S lab 2014 eeco2 tel - presentationS lab 2014 eeco2 tel - presentation
S lab 2014 eeco2 tel - presentationEECO2
 
Fire water netowrk presentation
Fire water netowrk presentationFire water netowrk presentation
Fire water netowrk presentationakbar_ali
 
2015 x472 class 02 - generation systems
2015 x472 class 02 - generation systems2015 x472 class 02 - generation systems
2015 x472 class 02 - generation systemsmichaeljmack
 
Storage Sprinkler Design.pptx
Storage Sprinkler Design.pptxStorage Sprinkler Design.pptx
Storage Sprinkler Design.pptxtanxtengineering
 
Water mist prepared by salah ramadan
Water mist prepared by salah ramadanWater mist prepared by salah ramadan
Water mist prepared by salah ramadanEng Salah Ramadan
 

Similar a High Challenge Warehouse case study (20)

Sprinkler_Systems_Presentation.ppt
Sprinkler_Systems_Presentation.pptSprinkler_Systems_Presentation.ppt
Sprinkler_Systems_Presentation.ppt
 
Dafo FORREX - Conveyor Belt Proactive Fire Protection System
Dafo FORREX - Conveyor Belt Proactive Fire Protection SystemDafo FORREX - Conveyor Belt Proactive Fire Protection System
Dafo FORREX - Conveyor Belt Proactive Fire Protection System
 
ashraeqatar_16.04.09_s_p_introduction_to_car_park_jetfan_ventilation_1.pdf
ashraeqatar_16.04.09_s_p_introduction_to_car_park_jetfan_ventilation_1.pdfashraeqatar_16.04.09_s_p_introduction_to_car_park_jetfan_ventilation_1.pdf
ashraeqatar_16.04.09_s_p_introduction_to_car_park_jetfan_ventilation_1.pdf
 
Psv fire training weldfit
Psv fire training weldfitPsv fire training weldfit
Psv fire training weldfit
 
Inspection of Fire Fighting Equipments | NFPA Regulations | Gaurav Singh Rajput
Inspection of Fire Fighting Equipments | NFPA Regulations | Gaurav Singh RajputInspection of Fire Fighting Equipments | NFPA Regulations | Gaurav Singh Rajput
Inspection of Fire Fighting Equipments | NFPA Regulations | Gaurav Singh Rajput
 
Engine company operations
Engine company operationsEngine company operations
Engine company operations
 
Part 3 - Fire Protection Systems in Buildings.pdf
Part 3 - Fire Protection Systems in Buildings.pdfPart 3 - Fire Protection Systems in Buildings.pdf
Part 3 - Fire Protection Systems in Buildings.pdf
 
4072721.ppt
4072721.ppt4072721.ppt
4072721.ppt
 
Safety and project solutions presentation
Safety and project solutions presentationSafety and project solutions presentation
Safety and project solutions presentation
 
Argonne Lab Project
Argonne Lab ProjectArgonne Lab Project
Argonne Lab Project
 
2015 x472 class 02 - generation systems
2015 x472 class 02 - generation systems2015 x472 class 02 - generation systems
2015 x472 class 02 - generation systems
 
Introduction to Process Flares
Introduction to Process FlaresIntroduction to Process Flares
Introduction to Process Flares
 
Royex - generation 2 introduction
Royex - generation 2 introductionRoyex - generation 2 introduction
Royex - generation 2 introduction
 
S lab 2014 eeco2 tel - presentation
S lab 2014 eeco2 tel - presentationS lab 2014 eeco2 tel - presentation
S lab 2014 eeco2 tel - presentation
 
Fire water netowrk presentation
Fire water netowrk presentationFire water netowrk presentation
Fire water netowrk presentation
 
2.5 suppression.sprinklers.wk12a
2.5 suppression.sprinklers.wk12a2.5 suppression.sprinklers.wk12a
2.5 suppression.sprinklers.wk12a
 
2015 x472 class 02 - generation systems
2015 x472 class 02 - generation systems2015 x472 class 02 - generation systems
2015 x472 class 02 - generation systems
 
Storage Sprinkler Design.pptx
Storage Sprinkler Design.pptxStorage Sprinkler Design.pptx
Storage Sprinkler Design.pptx
 
PPT-on-false-air.ppt
PPT-on-false-air.pptPPT-on-false-air.ppt
PPT-on-false-air.ppt
 
Water mist prepared by salah ramadan
Water mist prepared by salah ramadanWater mist prepared by salah ramadan
Water mist prepared by salah ramadan
 

Más de National Fire Protection Association (NFPA)

NFPA's Backyards & Beyond Conference - National Wildland Fire Safety Standard...
NFPA's Backyards & Beyond Conference - National Wildland Fire Safety Standard...NFPA's Backyards & Beyond Conference - National Wildland Fire Safety Standard...
NFPA's Backyards & Beyond Conference - National Wildland Fire Safety Standard...National Fire Protection Association (NFPA)
 
Smokers' Responses to the Introduction of Reduced-Ignition Propensity (RIP) C...
Smokers' Responses to the Introduction of Reduced-Ignition Propensity (RIP) C...Smokers' Responses to the Introduction of Reduced-Ignition Propensity (RIP) C...
Smokers' Responses to the Introduction of Reduced-Ignition Propensity (RIP) C...National Fire Protection Association (NFPA)
 

Más de National Fire Protection Association (NFPA) (20)

The Threats of Lightweight Construction and Modern Furnishings to Firefighters
The Threats of Lightweight Construction and Modern Furnishings to FirefightersThe Threats of Lightweight Construction and Modern Furnishings to Firefighters
The Threats of Lightweight Construction and Modern Furnishings to Firefighters
 
The smoking-material fire problem
The smoking-material fire problemThe smoking-material fire problem
The smoking-material fire problem
 
NFPA's Backyards & Beyond Conference - National Wildland Fire Safety Standard...
NFPA's Backyards & Beyond Conference - National Wildland Fire Safety Standard...NFPA's Backyards & Beyond Conference - National Wildland Fire Safety Standard...
NFPA's Backyards & Beyond Conference - National Wildland Fire Safety Standard...
 
Barriers and incentives related to the installation of home fire sprinklers
Barriers and incentives related to the installation of home fire sprinklersBarriers and incentives related to the installation of home fire sprinklers
Barriers and incentives related to the installation of home fire sprinklers
 
US-Canada_Firewise FireSmart Collaboration_South Africa Wildfire 2011
US-Canada_Firewise FireSmart Collaboration_South Africa Wildfire 2011US-Canada_Firewise FireSmart Collaboration_South Africa Wildfire 2011
US-Canada_Firewise FireSmart Collaboration_South Africa Wildfire 2011
 
Nfpa101 building rehab orlando2010
Nfpa101 building rehab orlando2010Nfpa101 building rehab orlando2010
Nfpa101 building rehab orlando2010
 
Nfpa72 emergingcommsystemsorlando2010
Nfpa72 emergingcommsystemsorlando2010Nfpa72 emergingcommsystemsorlando2010
Nfpa72 emergingcommsystemsorlando2010
 
New directions final120308
New directions final120308New directions final120308
New directions final120308
 
Smoking presentation
Smoking presentationSmoking presentation
Smoking presentation
 
Cultural change in the physical environment
Cultural change in the physical environmentCultural change in the physical environment
Cultural change in the physical environment
 
Policies and procedures
Policies and proceduresPolicies and procedures
Policies and procedures
 
Rsearch Foundation High Challenge Warehouse case study
Rsearch Foundation High Challenge Warehouse case studyRsearch Foundation High Challenge Warehouse case study
Rsearch Foundation High Challenge Warehouse case study
 
Smart Phone
Smart PhoneSmart Phone
Smart Phone
 
NFPA Technical Staff Training Module 14
NFPA Technical Staff Training Module 14NFPA Technical Staff Training Module 14
NFPA Technical Staff Training Module 14
 
Smokers' Responses to the Introduction of Reduced-Ignition Propensity (RIP) C...
Smokers' Responses to the Introduction of Reduced-Ignition Propensity (RIP) C...Smokers' Responses to the Introduction of Reduced-Ignition Propensity (RIP) C...
Smokers' Responses to the Introduction of Reduced-Ignition Propensity (RIP) C...
 
Implementing Fire-Safe Cigarette Laws in Massachusetts
Implementing Fire-Safe Cigarette Laws in MassachusettsImplementing Fire-Safe Cigarette Laws in Massachusetts
Implementing Fire-Safe Cigarette Laws in Massachusetts
 
Welcome to Fire-Safe Cigarette Conference
Welcome to Fire-Safe Cigarette ConferenceWelcome to Fire-Safe Cigarette Conference
Welcome to Fire-Safe Cigarette Conference
 
E-Cigarettes: Fire Safe?
E-Cigarettes: Fire Safe?E-Cigarettes: Fire Safe?
E-Cigarettes: Fire Safe?
 
Less Fire-Prone Cigarettes: How we got to the 1st plateau of success
Less Fire-Prone Cigarettes: How we got to the 1st plateau of successLess Fire-Prone Cigarettes: How we got to the 1st plateau of success
Less Fire-Prone Cigarettes: How we got to the 1st plateau of success
 
New York State's Cigarette Fire Safety Program
New York State's Cigarette Fire Safety ProgramNew York State's Cigarette Fire Safety Program
New York State's Cigarette Fire Safety Program
 

High Challenge Warehouse case study

  • 1. rechter Rand right margin marge droite margine destra High challenge warehouse case study – Summary February 19, 2010 Richard Gallagher Michael Gollner Zurich Services Corporation
  • 2. Objectives Review the results of the high challenge warehouse workshop Recognize participants Explain the project background Review case Given information Question Summarize the eight presentations Recap the overall findings
  • 3. Case study participants Schirmer Engineering Dan O’Connor, Garner Palenske Rolf Jensen and Associates Richard Bukowski FPI Consortium Warde Comeaux Telgian Tracy Bellamy Summit Fire Protection Sean Merkel, Ryan Bierwerth Hughes Associates Jerry Back, Joe Scheffey, Dan Gottuk UCSD Michael Gollner WPI Ali Rangawala Creative FPE Solutions Jonathan Perricone XL GAPS John Frank
  • 4. Background NFPA 13 basis: Automatic sprinklers control or suppression a fire Final fire extinguishment by the fire service Today’s warehouses High challenges to both sprinklers and fire service Recent fire experience Not always reasonable to expect manual intervention Foundation Addressing research to support potential changes to NFPA standards.
  • 5. Workshop approach Basis for workshop Theoretical Case Study Presentations Six leading FPE companies share innovative design concepts One presentation on novel approach to manual fire suppression One presentation addressing need to step back further and understand commodities and storage Format 20 minute presentations Panel Q&A
  • 6. Case Study Warehouse 6 2/4/2010 High Challenge Warehouse Case Study
  • 7. 2/4/2010 7 High Challenge Warehouse Case Study General conditions Who - XYZ Company What - New warehouse Where - Rural region of US
  • 8. 2/4/2010 8 High Challenge Warehouse Case Study Facility parameters Two attached buildings Low Bay 100’ x 150’ x 35’ tall High Bay 55’ x 150’ x 65’ tall
  • 9. 2/4/2010 9 High Challenge Warehouse Case Study Facility construction Roof –Noncombustible steel deck on steel bar joist High bay rack supported roof Exterior walls – Insulated metal panel Interior walls Between Low Bay and High Bay 150’ long Reinforced concrete block Up to Low Bay roof Floors – Reinforced concrete
  • 10. 2/4/2010 10 High Challenge Warehouse Case Study Public protection Public fire service Volunteer department XYZ Company is first storage facility in district Public water Extending main 3 miles to site Limited flow 60 psi static / 20 psi residual / 800 gpm flowing
  • 11. 2/4/2010 11 High Challenge Warehouse Case Study Private protection Water supply Two fire pumps – one electric, one diesel Ground water suction tank Detached fire pump house 300 feet from building
  • 12. 2/4/2010 12 High Challenge Warehouse Case Study Storage commodity Group A plastics Unexpanded In cartons Nonencapsulated Conventional wood pallets Pallet loads 4’ x 4’ x 4’
  • 13. 2/4/2010 13 High Challenge Warehouse Case Study Storage configuration Workshop focus The High Bay warehouse High bay Multiple row rack (4 pallets deep) flanked by double row racks Racks are separated aisles 5 ft wide Array 23 pallets long & 13 pallets high Nominal 6” flues around each pallet load Tiers 5’ tall Elevation View
  • 14. 2/4/2010 14 High Challenge Warehouse Case Study Stock handling Low Bay Industrial trucks High Bay Automatic storage and retrieval system (ASRS) Two ASRS systems Operate in 5 ft wide aisles Photo source: FEMA
  • 15. 2/4/2010 15 High Challenge Warehouse Case Study The challenge Local fire chief has made it clear that in the event of a fire - Will enter building to save people Will not enter building to save property Question: As the fire protection engineer of record, what fire protection design will be proposed to achieve final fire extinguishment without fire service intervention? Photo source: FEMA
  • 16. Summary of case study presentations
  • 17. Summary format Ignition - Sources of ignition Agent - Extinguishing media Detection/ Release - Method of detection and release ASRS - Uses for ASRS Failure - Noted failure concerns for method Comments - Additional comments Where no data provided – marked “NA” and grayed-out
  • 18. Schirmer Engineering Ignition - Arson, electrical, etc. Agent - Water - ESFR high zone at intersection of flues & over aisles ESFR low zone at intersection of flues One level in-racks in each zone 1600 gpm either zone Horizontal barrier between high and low zones CO2 - Low zone for redundancy (higher exposure area) Local application, can pipe long distances, can handle flammable liquids and electrical fires, no pumps, Use a 30-60 second discharge Divide low zone into sections (CO2 volume calculations) Detection/ Release - Sprinkler fusible element, In-rack linear/spot heat detection ASRS - NA Failure - NA Comments - Test ESFR configuration, locate in flues, avoid water ricochet Test low zone detection concept Develop CO2 nozzle Technology proven and can implement today
  • 19. Rolf Jensen and Associates Ignition - NA Agent - Water mist Zoned vertically (vertical risers) Spray either side of pallet and one side of adjacent pallet High velocity exhaust fans on outside walls - Produce airflow perpendicular to aisles to distribute water mist - Maintain visibility Detection/ Release - In-rack linear heat detection to locate fire ASRS - Use self-contained foam skid IR camera guided nozzle Not for primary suppression due to response time Failure - NA Comments - Low bay is typical for ESFR Critical to maintain longitudinal and transverse flues High bay ceiling sprinklers to protect building
  • 20. FPI Consortium Ignition - ASRS (lights not usually in use) electrical rails top and bottom, fires involve ASRS unit and spreads to storage Agent - High expansion foam – submerge in 4 min 13 foam generators 30 minute duration 100,000 gallons water for 30 minutes Detection/ - Heat detection - ceiling & in-rack spot heat detection Release Ceiling 15’ x 15’, in-rack 10’ vertical & 8’ horizontal ASRS - Not used, returned to home base and shutdown Failure - Doors and openings must close False release of foam (cross-zone possible) Comments - Sprinklers not considered due to environment impact
  • 21. Telgian Ignition - ASRS or lighting at elevated location Agent - Water Design an in-rack sprinklers, quick response Need horizontal barriers above in-racks, perhaps each tier Use waterflow to locate fire vertically Detection/ Release - Fusible sprinkler elements ASRS - Locate fire using thermal imaging Relocate stock to safe area Handle wet and damaged loads (enclosed unit) Failure - NA Comments - Need in-rack sprinkler design guidance - In-rack response time - In-rack water distribution
  • 22. Summit Fire Protection Ignition - NA Agent - Water Develop suppression mode in-racks Increased clearance for larger orifice in-rack sprinklers Fire barriers to provide fire confinement 300,000 gallons – 2 hour duration Detection/ Release - Fusible sprinklers elements ASRS - Under fire conditions, ASRS not available Failure - NA Comments - Introduce ESRF into racks Evaluate all changes over time (personnel turnover, commodities, maintenance, etc.
  • 23. Hughes Associates Ignition - NA Agent - High expansion foam Zoned system, 4 quadrants, barriers wire mesh/noncombustible fabric Curtains strips to allow ASRS passage Safety factors of 2+ compared to NFPA requirements 20,000 gallons water – 30 minute duration Detection/ - In-rack linear heat detection Release Flame detection for open spaces ASRS - Apply skid mounted fire suppression system Remove pallets of stock around fire Evaluate extinguishment – video monitoring Remove pallets of damaged stock Failure - Fire at zone interface, Openings between zones, Collateral damage to stock remote from fire Comments - Goals include low complexity, reasonable cost, rapid control, extinguishment, minimum fire damage, and minimum collateral damage
  • 24. WPI, UCSD, Creative FPE Solutions Ignition - NA Agent - NA Detection Release - NA ASRS - NA Failure - NA Comments - Must start at a more fundamental level Develop method to quantify warehouse fire control, suppression, or extinguishment Limits to “modeling” and “small scale testing” Need new intermediate-scale test - Determine water application rate for suppression - Will discuss further in a few slides
  • 25. XL GAPS Ignition - NA Agent - Water Mobilize remote special fire fighting team Need 12 hours (remote response, size-up, extinguish, overhaul) Sprinklers controlling fire during this time Need 900,000 gallons water Detection/ Release - Fusible sprinkler elements ASRS - Fire fighter access to upper tiers Failure - NA Comments - Interim solution until an engineered solution available Specialized fire team responding from central location Similar to private emergency services such as urban search and rescue, oil wells, oil tanks Skills to verify building stability, locate fire, work vertically, apply agent
  • 26. Summary of work Ignition scenarios Proposed solutions Design challenges Gaps Manual intervention
  • 27. Identified ignition scenarios ASRS equipment Power rails top and bottom Power on stacker crane Can introduce ignition source at any level Lighting Ignition exposure at roof Arson Anticipate low level exposure 2/4/2010 27 High Challenge Warehouse Case Study
  • 28. Solutions Manual fire suppression – an immediate solution XL Gaps Test & validate current sprinkler suppression practices WPI, UCSD, Edinburgh, and Creative FPE Solutions. Sprinklers – modify current designs – ESFR inracks Summit Fire Protection Telgian Sprinklers (2 levels ESFR) & CO2 Schirmer High expansion foam FPI Consortium Hughes Associates Water mist RJA 2/4/2010 28 High Challenge Warehouse Case Study
  • 29. Design challenges Water sources Reliability / redundancy Volume / duration Cost of system due to rural location Environmental concerns Release of contaminated water Recycling of used water Hazard of commodity Defining the hazard of a commodity Commodities changing or introducing unknown commodities In-rack sprinkler placement and type (ESFR) highly specific to fuel type, configuration Avoiding complex designs Can collateral damage be limited to limit business impact 2/4/2010 29 High Challenge Warehouse Case Study
  • 30. GapsTest methodologies There are no methods, currently, to quantify warehouse fire control, suppression or extinguishment. A test methodology is needed to ensure adequacy of current and new design concepts How much suppressant? Length of discharge? Limitations in full scale, small scale testing and modeling demand a new approach – small scale commodity classification verified by intermediate scale testing and large scale modeling/testing for validation
  • 31. GapsDesign approach – WPI et al 2/4/2010 31 High Challenge Warehouse Case Study 2. SprinklerFlow Characterization Determine limits of current sprinkler protection systems Analyze the warehouse fire problem in pieces 1. Characterize sprinkler spray 2. Droplet losses from geometry, plume, radiation, etc. 3. Suppression/Extinction interaction between film/drops and fire Benefits: Design fixed system to provide suppression or extinction for any tested materials Utilize current sprinkler infrastructure and modify deficient systems if necessary Sprinkler Spray PLUME 1. Classification of Commodity FIRE
  • 32. Gaps Design approach – WPI et al Engineering Approach to Warehouse Fire Protection Design 32
  • 33. GapsTechnology In-rack sprinkler design No sprinkler designed to respond quickly in a rack No sprinkler designed to distribute water in a rack No suppression mode in-rack sprinkler Hardening of ASRS for use during fire event Carry self-contained extinguishing system skid Identify fire location within array Verify fire control/suppression progress Remove adjacent stock to isolate fire Remove wet or damaged stock
  • 34. GapsManual intervention - the immediate solution Water supplies Are durations sufficient (2 hours vs. 12 hours) Thorough pre-emergency planning Safe work plan
  • 35. Questions or comments? 2/4/2010 35 High Challenge Warehouse Case Study