SlideShare una empresa de Scribd logo
1 de 40
Descargar para leer sin conexión
A PRACTICAL TRAINING REPORT 
ON 
132 KV G.S.S. 
Taken at 
Jalore 
Submitted in partial fulfillment 
for the award of the degree of 
BACHELOR OF TECHNOLOGY 
(Rajasthan Technical University, Kota) 
IN 
ELECTRICAL ENGINEERING 
SESSION (2013-2014) 
SSSSUUUUBBBBMMMMIIIITTTTTTTTEEEEDDDD TTTTOOOO:::: SSSSUUUUBBBBMMMMIIIITTTTTTTTEEEEDDDD BBBBYYYY:::: 
Mr. Vaibhav Jain Pritam solanki 
(HOD) EE&7th Sem 
Electrical Department 10EPCEE092, 4th Year 
DEPARTMENT OF ELECTRICAL ENGINEERING 
POORNIMA COLLEGE OF ENGINEERING 
ISI-6, RIICO INSTITUTIONAL AREA 
SITAPURA, JAIPUR-302022(RAJASTHAN)
DEPARTMENT OF ELECTRICAL ENGINEERING 
POORNIMA COLLEGE OF ENGINEERING 
This is to certify that report on “Jalore 
the degree of Bachelor of Technology in 132 KV G.S.S. Jalore” has been carried out by Mr. Pritam Solanki under my guidance in partial fulfil 
Electrical Engineering 
of Rajasthan Technical University, Kota, during the academic year 2012 
the best of my knowledge and belief this work has not been submitted elsewhere for the award of any other degree. The work ha 
satisfactory and is approved for submission. 
Mr. Vaibhav Jain 
HOD (E.E.) 
(Asst. Prof.), E.E. (P.C.E) 
JAIPUR -302022 
CERTIFICATE 
Mr. Trilock Chand Sony 
Seminar Guide 
(Asst. Prof.), E.E. (P.C.E) 
i 
fulfillment of 
ring 2012-13 To 
has been found 
Dr. R.P.RAJORIA 
Campus director 
(P.C.E.)
TABLE OF CONTENT pg.no. 
CHAPTERS i 
LIST OF FIGURE iii 
LIST OF TABLE iv 
TRAINING CERTIFICATE 
CERTIFICATE 
ACKNOWLEDGMENT v 
ABSTRACT 1 
i 
CHAPTERS 
CHAPTER 1 
1.1 INTRODUCTION [SUB STATION] 2 
CHAPTER 2 
2.1 SINGLE LINE DIAGRAM OF 132 KV G.S.S. 5 
2.2 BUS BARS 6 
2.2.1 DOUBLE BUS BAR CONTAINING MAIN BUS I 
WITH MAIN BUS II 
2.2.2 DOUBLE BUS BAR ARRANGEMENTS 
CONTAINS MAIN BUS WITH AUXILIARY BUS 
2.3 ISOLATORS 7 
2.4 INSULATORS 8 
2.4.1 Pin type 
2.4.2 Suspension type insulator 
2.4.3 Strain insulator 
2.5 PROTECTIVE RELAYS 11 
2.5.1 Principal of relay 
2.5.2 Differential Relays 
2.5.3 Buchholz Relay 
2.5.3.1 CONSTRUCTION 
2.5.3.2 OPERATION 
2.5.3.3 ADVANTAGE 
2.5.3.4 DISADVANTAGES 
2.5.4 Overcurrent Relays 
2.6 CIRCUIT BREAKERS 13 
2.6.1 Operating Principal 
2.6.2 Arc Phenomenon 
2.6.3 Classification of the Circuit Breakers 
2.6.3.1 Sulphur Hexaflouride (SF6) Circuit 
2.6.3.1.1 Construction 
2.6.3.1.2 Working
2.6.3.1.3 Advantages of SF6 Ckt Breaker 
2.6.3.1.4 Demerits of SF6 Ckt Breaker 
2.7 POWER TRANSFORMER 17 
ii 
2.7.1 Principal of Transformer 
2.7.2 BASIC PARTS OF TRANSFORMER 
2.7.3 Description of Plant 
2.7.4 Rating Datas 
2.8 CURRENT TRANSFORMER 21 
2.8.1 POTENTIAL TRANSFORMER 
2.9 CAPACITIVE VOLTAGE TRANSFORMER 22 
2.9.1 Application 
2.10 TRANSFORMER OIL & ITS TESTING 24 
2.10.1 Breakdown Voltage 
2.10.2 Flash Point 
2.11 TRANSFORMER TANδ TESTING 24 
2.11.1 Principal 
2.12 LIGHTNING ARRESTORS 25 
2.12.1 Thyrite Type 
CHAPTER 3 
2.13 CONTROL ROOM 27 
2.14 EARTHING OF THE SYSTEM 29 
2.14.1 Procedure of Earthing 
2.14.2 Neutral Earthing 
2.15 POWER LINE CARRIER COMMUNICATION 30 
2.16 CORONA 31 
2.16.1 Factors Affecting Corona 
2.16.2 Advantages and Disadvantages of Corona 
CONCLUSION 33 
REFERENCES 34
iii 
LIST OF FIGURE 
Figure No. Figure Name pg.no. 
1.01 132 KV G.S.S. JALORE 2 
2.01 single line diagram of 132 KV G.S.S. 5 
2.02 132 KV BUS BARS 6 
2.03 Isolator 8 
2.04 Pin type insulator 9 
2.05 Suspension type insulator 10 
2.06 Strain insulator 10 
2.07 Diagram of Relay 11 
2.08 SF6 Circuit Breaker 14 
2.09 Construction view of SF6 Circuit Breaker 16 
2.10 Arrangement of a simple Transformer 18 
2.11 Transformer 19 
2.12 Ratings of Transformers 20 
2.13 Current Transformers 21 
2.14 Potential Transformers 22 
2.15 Capacitive Voltage Transformer 23 
2.16 Principal of TANδ tasting Transformers 25 
2.17 Lighting Arresters 26 
3.01 Control Room-1 27 
3.02 Control Room-2 28 
3.03 Control Room-3 28 
3.04 EARTHING OF THE SYSTEM 29 
3.05 POWER LINE CARRIER COMMUNICATION SYSTEM 31
iv 
LIST OF TABLE 
Table No. Table Name pg.no. 
1.01 Details of Circuit Breaker 3 
1.02 Details of Current Transformer 4
AKNOWLEDGEMENT 
This is opportunity to express my heartfelt words for the people who were part of this training in 
numerous ways, people who gave me unending support right from beginning of the training. 
I am grateful to training incharge Mr. Hari Ram Meena for giving guidelines to make the training 
successful. 
I want to give sincere thanks to the Campus Director, Dr. R.P. Rajoria and the principal, Dr. 
Om Prakash Sharma for his valuable support. 
I extend my thanks to Mr. Vaibhav Jain Head of the Department for his cooperation and 
guidance. 
v 
Yours Sincerely 
Pritam solanki
1 | P a g e 
ABSTRACT 
This is training of 30 days, during these days my training place was 132 KV G.S.S. Jalore 
(Rajasthan). G.S.S. is the mean of connection between generating station and 
consumer by providing safety and reliability of system in case of default. 
This substation step down the incoming voltage power transmission to the required valve and 
then is supplied to the consumer feeder or GSS done by connecting auto transformer operation 
and requirement of various equipment have been include in detail , further in case of report is 
the bus bar. 
In our substation there is two main parts 132KV and 33 KV which is a part of substation. First 
we receive the power 132 KV from Leta, and then we step down the voltage at 33 KV and 
distributed to the no. of feeders. 
We have three main transformers which converts 132 KV to 33KV. Two transformers are rating 
of 12.5 KVA (BHEL-EMCO) and the last one having rating of 25 KVA (IMP). So the total 
capacity of our substation is 55 MVA. 
Arrangement of different feeder level and switch yards included information of bus bar 
arrangement of different level isolator and growing substation also power transformer circuit 
breaker oil, filtration plant, and compression protection control room 
and place are leveled. 
While making this training report every care has been taken to avoid any mistake. In short I hope 
to provide concise sight of four weeks of my training period through this report. 
I was lucky to have my training from 132 KV G.S.S., Jalore that gave me an all round 
knowledge that an electrical engineer should know. During 30 days of my training Session at 
G.S.S. I got knowledge about power distribution, power transmission and power line carrier 
communication.
2 | P a g e 
CHAPTER 1 
1.1 INTRODUCTION [SUB STATION] 
Electric power is generated, transmitted and distributed in the form of alternating current. The 
electric power produced at the power stations is delivered to the consumers through a large 
network of transmission & distribution. The transmission network is inevitable long and high 
power lines are necessary to maintain a huge block of power from source of generation to the 
load centers to inter connected. Power house for increased reliability of supply greater. The 
assembly of apparatus used to change some characteristics (e.g. voltage, ac to dc, frequency, 
power factor etc.) of electric supply keeping the power constant is called a sub-station. 
Depending on the constructional feature, the high voltage sub-station may be further 
subdivided: 
a) Outdoor substation 
b) Indoor substation 
c) Basement or Underground substation 
132 KV G.S.S. is an outdoor type station. It is primary as well as distribution substation. The 
power mainly comes from JALORE-1 and JALORE-2 from Leta. 
Fig (1): 132 KV G.S.S. JALORE
Table of Circuit Breaker 
S.NO. NAME OF BREAKER MAKE 
1. 132 KV I/C JALORE-1 BHEL 
2. 132 KV I/C JALORE-2 ABB 
3. 132 KV Tr.(BHEL-EMCO) CG 
4. 132 KV Tr.(IMP) HBB 
5. 132 KV BUS COUPLER HBB 
6. 33 KV I/C-1(EMCO) SIEMENS 
7. 33 KV I/C-2(BHEL) SIEMENS 
8. 33 KV I/C-3(IMP) CG 
9. 33 KV O/G FN.1 KASHWANA BHEL 
10. 33 KV O/G FN.2 JALORE MEGAWIN 
11. 33 KV O/G FN.3 SAYLA MEGAWIN 
12. 33 KV O/G FN.4 AHORE EASUN REVOLLE 
13. 33 KV O/G FN.5 GODAN CG 
14. 33 KV O/G FN.6 RICCO MEGAWIN 
15. 33 KV CAP. BANK-1 SIEMENS 
16. 33 KV CAP. BANK-2 BHEL 
17. 33 KV CAP. BANK-3 SIEMENS 
18. 33/11 KV Tr. MEI 
19. 11 KV I/C-1 BHEL 
20. 11 KV O/G FN.1 TO FN.6 NGEF 
3 | P a g e 
Table (1.01): Details of Circuit Breaker
Table of Current Transformer 
S.NO. NAME OF CT MAKE 
1. 132 KV I/C JALORE-1 BHEL 
2. 132 KV I/C JALORE-2 HBB 
3. 132 KV Tr.(BHEL-EMCO) EASUN 
4. 132 KV Tr.(IMP) TELK 
5. 132 KV BUS COUPLER AMEI 
6. 33 KV I/C-1(EMCO) TATA 
7. 33 KV I/C-2(BHEL) AMEI 
8. 33 KV I/C-3(IMP) HEI 
9. 33 KV O/G FN.1 KASHWANA CG 
10. 33 KV O/G FN.2 JALORE CG 
11. 33 KV O/G FN.3 SAYLA AEI 
12. 33 KV O/G FN.4 AHORE UNIVERSAL 
13. 33 KV O/G FN.5 GODAN CG 
14. 33 KV O/G FN.6 RICCO AEI 
15. 33 KV CAP. BANK-1 BHEL 
16. 33 KV CAP. BANK-2 BHEL 
17. 33 KV CAP. BANK-3 ATE 
18. 33/11 KV Tr. AEI 
4 | P a g e 
Table (1.02): Details of Current Transformer
2.2 BUS BARS 
Bus Bars are common electrical component through which a large no. of feeders operating at 
same voltage have to be connected. If the bus bars are of rigid type 
(Aluminum types) the structure height 
s required. While in 
case of strain type of bus bars suitable ACSR conductors are strung / tensioned by 
insulator discs according to system voltages. In the widely used strain type bus bars stringing 
tension is about 500-900 kg depending 
effect the clearances when it swings while over tensioning may damage i 
even effect the supporting structures in low temperature conditions. The clamping should be 
proper, as loose clamp would s 
BUS BAR ARRANGEMENT MAY BE FOLLOWING TYPES: 
Which are being adopted by R.R.V.P.N.L. 
1. Single Bus Bar arrangement 
2. Double Bus Bar arrangement 
3. Double Bus Bar arrangement with auxiliary bu 
2.2.1 DOUBLE BUS BAR CONTAINING MAIN BUS I WITH MAIN BUS II 
1. Each load may be fed from either bus. 
6 | P a g e 
heights are low and minimum clearance is 
upon the size of conductor used. Loose Bus Bars would 
spark under in full load condition damaging the bus bars itself. 
TYPES:- 
bus 
Fig (2.2): 132 KV BUS BARS 
tension 
. insulators. Clamps or 
park II:
2. The load circuits may be divided in two separate groups if needed from operational 
consideration. Two supplies from different sources can be put on each bus separately. 
3. Either bus bar may be taken out from maintenance and cleaning of insulators. This 
arrangement has been quite frequently adopted where the loads and continuity of supply is 
necessary. 
In such a scheme a bus coupler breaker is mostly provided as it enables on load change over 
from one bus bar to other. The normal bus selection isolators cannot be used for breaking load 
currents. The arrangement does not permit breaker maintenance without causing stoppage of 
supply. 
2.2.2 DOUBLE BUS BAR ARRANGEMENTS CONTAINS MAIN BUS 
WITHAUXILIARY BUS: 
The double bus bar arrangement provides facility to change over to either bus to carry out 
maintenance on the other but provide no facility to carry over breaker maintenance. The main 
and transfer bus works the other way round .It provides facility for carrying out breaker 
maintenance but does not permit bus maintenance. Wherever maintenance is required on any 
breaker the circuit is changed over to the transfer bus and is controlled through bus coupler 
breaker. 
2.3 ISOLATORS 
Isolators which are also called disconnect switches or air break switches after the assembly as 
per drawings on the leveled structures the adjustment of connecting pipes, moving and fixed 
contacts is done so that all the three phase of the isolator close and open simultaneously and 
there is a full surface contact between moving and fixed contacts. Such switches are generally 
used on both sides of equipment in order that repairs and replacement of the equipment can be 
made without any danger. They should never be opened until the equipment in the same circuit 
has been turned off and should always be closed before the equipment is turned on. The 
adjustment of the tendon pipes leveling of post insulator, stop Holts in the fixed contacts etc. is 
done for smooth operation of insulator. Following type of isolators are being used in R.S.E.B.- 
a) Isolator without earth blades. 
b) Isolator with earth blades. 
c) Tendon isolator 
7| P a g e
Fig (2.3): ISOLATOR 
2.4 INSULATORS 
The insulators for the overhead lines provide insulation to the power conductors from the ground 
so that currents from conductors do not flow to earth through supports. The insulators are 
connected to the cross arm of supporting structure and the power conductors passes through the 
clamp of the insulator. The insulators provide necessary insulation between line conductors and 
supports and thus prevent any leakage current from conductors to earth. In general, the insulators 
should have the following desirable properties: 1) High mechanical strength in order to withstand 
conductor load, wind load etc. 2) High electrical resistance of insulator material in order to avoid 
leakage currents to earth. 3) High relative permittivity of insulator material in order that 
dielectric strength is high. 4) The insulator material should be non porous, free from impurities 
and cracks otherwise the permittivity will be lowered. 5) High ratio of puncture strength to flash 
over. These insulators are generally made of glazed porcelain or toughened glass. Porcelain type 
8| P a g e
insulators [solid core] are also being supplied in place of hast insulators if available 
indigenously. The design of the insulator is such that the stress due to contraction and expansion 
in any part of the insulator does not lead to any defect. It is desirable not to allow porcelain to 
come in direct contact with a hard metal screw thread. 
Insulators are available in three types: 
2.4.1 Pin type:- pin type insulator consists of a single or multiple shells adapted to be 
mounted on a spindle to be fixed to the cross arm of the supporting structure. When the upper 
most shell is wet due to rain the lower shells are dry and provide sufficient leakage resistance. 
These are used for transmission and distribution of electric power at voltage up to 33KV the pin 
type insulators thus become too bulky and hence uneconomical. 
Fig (2.4): pin type insulator 
2.4.2 Suspension type insulator:- suspension type insulators consists of a number of 
porcelain disc connected in series by metal links in the form of a string. Its working voltage is 
66KV. Each disc is designed for low voltage for 11KV. 
9| P a g e
Fig (2.5): suspension type insulator 
2.4.3 Strain insulator:- Strain insulators are exactly identical in shape with the suspension 
insulators these strings are placed in the horizontal plane rather than the vertical plane. 
These insulators are used where line is subjected to greater tension. For low voltage lines shackle 
insulators are used as strain insulator. 
Fig (2.6): strain insulator 
10| P a g e
2.5 PROTECTIVE RELAYS 
A protective relay is a device that detects the fault and initiates the operation of the circuit 
breaker to isolator the defective element from the rest of the system. The relays detect the 
abnormal condition in the electrical circuits by constantly measuring the electrical quantities i.e. 
voltage, current, frequency, phase angle which are different under normal and fault conditions. 
Having detected the fault, the relay operates to close the trip circuit of the breaker, which results 
in opening of the breaker and disconnection of the faulty circuit. Relays circuit connections can 
be divided in three parts: 
1) Primary winding of C.T. that is connected in series with the line to be protected. 
2) Secondary winding of C.T. and the relay operating coil 
3) Tripping circuit (either ac or dc) 
Fig (2.7): Diagram of Relay 
11| P a g e
2.5.1 Principal of relay:-when a short circuit occurs at any point F on the transmission line 
the current increases to enormous value. This results in a heavy current flow through the relay 
coil, causing the relay to operate by closing its contacts. This in turn closes the trip circuit of the 
breaker, making the C.B. open and isolating the family section from the rest of the system. In 
this way, relay ensures the safety of the circuit equipment from damage and normal working of 
the healthy portion of the system. Basic qualities that a protective relay must possess are: 
· Selectivity 
· Speed 
· Sensitivity 
· Reliability 
· Simplicity 
· Economy 
Type of relays:- 
2.5.2 Differential Relays:- A differential relays is one that operates when the phasor 
difference of two or more similar electrical quantities exceeds a predetermined value. Thus the 
current differential relay is one that compares the current entering and current leaving the 
section. Under normal operating conditions, the two currents are equal but as soon as fault 
occurs, this condition is no longer applied. The difference between the incoming and outgoing 
currents is arranged to flow through the operating coil of the relay. If this differential current is 
equal to or greater than the pickup value, the relay will operate and open the C.B. to isolate the 
faulty section. 
2.5.3 Buchholz Relay:- It is a gas-actuated relay installed in oil immersed transformers for 
protection against all kinds of faults. It is used to give an alarm in case of incipient (i.e. slow 
developing) faults in the transformer and to disconnect the transformer from the supply in the 
event of severe internal faults. It is usually installed in the pipe connecting the conservator to 
main tank. It is a universal practice to use buchholz relay on all such oil immersed transformers 
having ratings in excess of 750KVA. 
2.5.3.1 CONSTRUCTION:-It takes the form of a domed vessel pipe between the main 
tank and the conservator. The device has two elements. The upper element consists of a mercury 
type switch attached to a float. The lower element contains a mercury switch mounted on a 
hinged type flap located in the direct path of the flow of oil from the transformer to the 
conservator. The upper element closes an alarm circuit during incipient faults whereas the lower 
element is arranged to trip the circuit breaker in case of server internal faults. 
12| P a g e
2.5.3.2 OPERATION:-The operation of Buchholz relay is as follows: (i) In case of incipient 
faults within the transformer, the heat due to fault causes the decomposition of some transformer 
oil in the main tank the products of decomposition contain more than 70% of hydrogen gas. The 
hydrogen gas being light tries to go into the conservator and in the process gets entrapped in the 
upper part of the relay chamber. When a pre determined amount of gas gets accumulated, it 
exerts sufficient pressure on the float to cause it tilt and close the contacts of the mercury switch 
attached tom it. This completes the alarm circuits to sound an alarm. (ii)If a serious fault occurs 
in the transformer, enormous amount of gas is generated in the main tank. The oil in the main 
tank rushes to the conservator via the Buchholz relay and in doing so tilts the flap to close the 
contacts of the mercury switch. This completes the trip circuit to open the circuit breaker 
controlling the transformer. 
2.5.3.3 ADVANTAGE:- 
(i) It is the simplest form of transformer protection. 
(ii) It detects the incipient faults at a stage much earlier than possible with other forms of 
protection. 
2.5.3.4 DISADVANTAGES:- 
(i) It can only be used with oil immersed transformers equipped with conservator tanks. 
(ii) The device can detect only faults below oil level in the transformer. Therefore separate 
protection is needed for connecting cables. 
2.5.4 Overcurrent Relays:- 
an Overcurrent relay is a relay which sense the high current. When a short ckt occurs, high 
current flows if this current is equal or greater than pick up current then Overcurrent relay trip 
the ckt breaker. 
2.6 CIRCUIT BREAKERS 
Thus circuit breakers are used for switching & protection of various parts of power system. 
Circuit breaker is a piece of equipment, which can 
1) Make or break a circuit either manually or automatically under normal condition. 
2) Break a circuit automatically under fault condition. 
3) Make a circuit either manually or by remote control under fault conditions. 
13| P a g e
Fig (2.8): SF6 Circuit Breaker 
2.6.1 OPERATING PRINCIPLES: - A C.B. consists of fixed and moving contacts 
called electrodes. Under normal operating conditions, these contacts remain closed and will not 
open automatically until and unless the system becomes faulty. When a fault occurs on any part 
of the system, the trip coils of the circuit breaker get energized and the moving contacts are 
pulled apart, thereby opening the circuit. When the contacts of the C.B. are separated under fault 
conditions, an arc is struck between them. The current is thus able to continue until the discharge 
ceases. The production of arc not only delays the current interruption process but it also 
generates enormous heat which may cause damage to the system or to the C.B. It is thus 
necessary to extinguish the arc within the shortest possible time so that the heat generated by it 
may not reach a dangerous value. 
2.6.2 ARC PHENOMENON:- When a short circuit occurs, a heavy current flow through 
the contacts of the C.B. before they are opened by the protective system. At the instant when the 
contacts begin to separate, the contact area decreases rapidly and large fault current causes 
increased current density and hence rise in temperature. The heat produced in the medium 
14| P a g e
between contacts is sufficient to ionize the arc or vaporize and ionize the oil. The ionized air or 
vapour acts as conductor and an arc is set between the contacts. The potential difference between 
the contacts is quite small and is sufficient to maintain the arc. The arc provides a low resistance 
path and as a result the current in the circuit remains uninterrupted so long as the arc persists. 
During the arcing period the current flowing between the contacts depends on the arc resistance. 
The greater the arc resistance, the smaller the current that flows between the contacts. The arc 
resistance depends upon: 
(i) Degree of ionization. 
(ii) Length of arc. 
(iii) Cross section of arc. 
2.6.3 CLASSIFICATION OF THE CIRCUIT BREAKERS 
There are several ways of classifying the circuit breakers. However, the most general way of 
classification is on the basis of medium used for arc extinction. The medium used for arc 
extinction is usually oil, air, sulphur hexafluoride (SF6) or vacuum. Accordingly, circuit breakers 
may be classified into:-They are generally classified on the basis of the medium used for arc 
elimination. 
(i) Oil circuit breakers, which employ some insulating oil for arc extinction. 
(ii) Air-blast circuit breakers in which high pressure air blast is used for extinguishing the arc. 
(iii) Sulphur hexa fluroide C.B. in which SF6 gas is used for arc extinction. 
(iv) Vacuum C.B. in which vacuum is used for arc extinction. 
2.6.3.1 SULPHUR HEXAFLOURIDE (SF6) CIRCUIT 
BREAKER In such breakers, sulphur hexa flouride (SF6) gas is used as the arc quenching 
medium. The sf6 is an electro-negative gas and has a strong tendency to absorb free electrons. 
The SF6 circuit breakers have been found to be very effective for high power and high voltage 
service. 
2.6.3.1.1 CONSTRUCTION 
The cylindrical large size steel tanks are mounted horizontally parallel to each other. Each tank 
consists of SF6 under pressure. The interruption is of multibreak type & is placed along the axis 
of each tank. The interruption assembly is supported inside the tank by the vertical bushing, 
which are mounted near the end of each tank. Gas at high pressure is supplied to the interrupter 
from a gas reservoir. The bushings are also insulated with SF6 the conductor is in the form of 
copper tube supported at both end by porcelain shields. SF6 gas is supplied from the high 
pressure tanks. Shields are provided with gasket seals to eliminate leakage of gas from 
beginnings. 
15| P a g e
Fig (2.9): Construction view of SF6 Circuit Breaker. 
2.6.3.1.2 WORKING:- In the closed position of the breaker the contacts remain surrounded 
by SF6 gas at a pressure of about 2.8 kg/sq cm. When the breaker operates, the moving contact is 
pulled apart and an arc is struck between the contacts. The movement of the moving contact is 
synchronized with the opening of a valve which permits SF6 gas at 14kg/sq cm pressure from the 
reservoir to the arc interruption chamber. The high pressure flow of SF6 rapidly absorbs the free 
electrons in the arc path to form immobile negative ions which are ineffective as charge carriers. 
The result is that the medium between the contacts quickly builds up high dielectric strength and 
16| P a g e
causes the extinction of the arc. After the breaker operation the valve is closed by the action of a 
set of springs. 
2.6.3.1.3 ADVANTAGES OF SF6 CIRCUIT BREAKER: 
1. Due to the superior arc quenching property of SF6, such circuit breakers have very short 
arching time. 
2. Since the dielectric strength of SF6 gas is 2 to 3 times that of air, such breakers can interrupt 
much larger currents. 
3. The SF6 circuit breakers gives noiseless operation due to its closed gas circuit and no exhaust 
to the atmosphere unlike the air blast circuit breaker. 
4. The closest gas enclosure keeps the interior dry so that there is no moisture problem. 
5. There is on risk of fire in such breakers because SF6 gas is not inflammable. There are no 
carbon deposits so that tracking and insulation problems are eliminated. 
6. The SF6 breakers have low maintenance cost, light foundation requirement and minimum 
auxiliary equipment. 
7. Since SF6 breakers are totally enclosed and sealed from atmosphere they are particularly 
suitable where explosion hazard exists. 
2.6.3.1.4 DEMERITS OF SF6 CIRCUIT BREAKER: 
1. Sealing problems arise due to the type of the construction used. 
2. The presence of moisture in the system is very dangerous to SF6 circuit breaker. 
3. Arced Sf6 gas is poisonous & should not be let out. 
4. The double pressure SF6 CB is cost liner due to complex gas system. 
5. The internal parts should be cleaned thoroughly during periodic maintenance under clean dry 
environment. 
6. Dust of Teflon & sulfide should be removed. 
7. Special facilities are needed for transporting the gas. 
2.7 POWER TRANSFORMER 
2.7.1 Principal of Transformer: The transformer is a static apparatus, which receives 
power/energy at it, one circuit and transmits it to other circuit without changing the frequency. 
With this basic conception we can use the voltages at our desired level while utilizing the power. 
As, the voltage used to generate at modern power houses at 11 KV or so and afterwards we get it 
step up at a level of 33 KV, 66 KV, 132 V, 220 KV or 400KV, 750 KV for transmission to 
minimize the distribution losses. Again we get it step down with the help of transformer to use at 
our wishes at 11 KV, 6.6 KV or even 415, 230 volts at our houses. 
17| P a g e
Fig (2.10): Arrangement of a simple Transformer 
2.7.2 BASIC PARTS OF TRANSFORMER: - The following are the inherent parts of a modern 
day transformer. 
1. Primary and secondary coils (circuit) or windings. 
2. Core 
3. Main Tank 
4. Conservator 
5. Breather 
6. Radiator 
7. Buchholz relay 
8. Explosive vent 
9. Bushings (HT & LT) (Primary or secondary) 
10. Cooling fans 
11. Tap changer (on load and off load) 
12. NGR (Neutral Grounding Resistance) to minimize the earth fault current 
18| P a g e
Fig (2.11): Transformer 
2.7.3 DESCRIPTION OF PLANT 
The three transformers are oil immersed with rating of 12.5 MVA& one with 25 MVA. However 
a synchronous loading of 55 MVA at 0.98 power factor. The transformer is also provided with a 
separate bank of radiation, fans, and associated control equipments. The control equipments are 
housed in a tank mounted miscalling. 
19| P a g e
2.7.4 RATING DATAS 
20| P a g e 
Fig (2.12): Ratings of Transformers
2.8 CURRENT TRANSFORMER 
These transformers are used with low range ammeter to measure currents in high voltage 
alternating current circuits where it is not practicable to connect instruments and meters directly 
to lines. In addition to insulating the instrument from the high voltage line, they step down the 
current in the known ratio. The current (or series) transformers has a primary coil of 1 or more 
turns of thick wires connected in series with the line whose current is to be measured. The 
secondary consist of a large number of turns of fine wire and is connected across the ammeter 
terminals (usually of 5 amp bracket should be removed or 1 amp range. 
Fig (2.13): Current Transformers 
21| P a g e
2.8.1 POTENTIAL TRANSFORMER 
These transformers are extremely accurate ratio step down transformers and are used in 
conjunction with standard low range voltmeter (usually 150 volt) whose deflection when divided 
by voltage transformation ratio, gives the true voltage on the high voltage side. In general, they 
are of the shell type and do not differ much from the ordinary two winding transformer, except 
that their power rating is extremely small. Up to voltage of 5000 potential transformers are 
usually of dry type, between 5000 and 13800 volts, they may be either dry type or oil immersed 
type, although for voltage above 13800 they are oil type. Since their secondary windings are 
required to operate instruments or relays or pilot lights, their ratings are usually 42 to 100 watts. 
Fig (2.14): Potential Transformers 
2.9 CAPACITIVE VOLTAGE TRANSFORMERS (CVT) 
Capacitive voltage transformers are special kind of power transformers using capacitors to step 
down the voltage. The capacitive voltage transformer comprises of a capacitor divider with its 
associated electromagnetic unit. The divider provides an accurate proportioned voltage, while the 
magnetic unit transforms this voltage, in both magnitude and phase to convenient levels suitable 
for measuring, metering, protection etc. all WSI capacitor units has 
metallic bellows to compensate the volumetric expansion of oil inside. The porcelain in multi 
22| P a g e
Fig (2.15): CAPACITIVE VOLTAGE TRANSFORMERS 
unit stack, all the potential points are electrically tied and suitably shielded to overcome the 
effect of corona RIV etc. 
2.9.1 APPLICATION: 
1. Capacitive voltage transformers can be effectively as potential sources for measuring, 
metering, protection, carrier communication and other vital functions of an electrical network. 
2. CVT is constructed in single or multi unit porcelain housing with there associated magnetic 
units. For EHV system cuts are always supplied in multi unit construction. 
3. In case of EHV cuts the multi unit system has many advantage easy to transport and storing, 
convenience in handling. 
23| P a g e
2.10 TRANSFORMER OIL & ITS TESTING 
The prime function of oil is to convey the heat from the core and winding to the tank where it 
can be dissipated. Besides these, the oil provides additional insulation between primary and 
secondary windings. So, the oil must be completely free from dirt, moisture and other un-wanted 
solid matter. The oil used in the transformer is natural mineral oil and should undergo the 
following tests if required: 
2.10.1 BREAKDOWN VOLTAGE:- 
The voltage at which the oil breaks down when subjected to an electric field. 
2.10.2 FLASH POINT:- 
The temperature, at which the oil gives off so many vapors, when mixed with air forms an 
ignitable mixture and gives a momentary flash with small pilot flame. 
2.11 TRANSFORMER TANδ TESTING: 
TANδ testing is a diagnostic test conducted on the insulation of cables and windings. It is used to 
measure the deterioration in the cable. It also gives an idea of the aging process in the cable and 
enables us to predict the remaining life of 
the cable. It is alternatively known as the loss angle test or the dissipation factor test. 
2.11.1 PRINCIPLE:- 
The TANδ test works on the principle that any insulation in its pure state acts as a capacitor. The 
test involves applying a very low frequency AC voltage. The voltage is generally double the 
rated voltage of the cable or winding. 
A low frequency causes a higher value of capacitive reactance which leads to lesser power 
requirement during the test besides currents will be limited. 
24| P a g e
Fig (2.1 
2.12 LIGHTENING ARRESTORS 
An electric discharge between cloud and earth, between cloud and the charge centers of the same 
cloud is known as lightening. The earthing screens and the ground wires can well protect the 
electrical system against direct lightening 
strokes but they fail to provide protection against travelling waves which may reach the terminal 
apparatus. The lightening arrestors or the surge diverters provide protections against such surges. 
25| P a g e 
16): Principal of TANδ tasting Transformers 
Tanδ= / 
l
Fig (2.17): LIGHTENING ARRESTORS 
2.12.1 THYRITE TYPE: Ground wires run over the tower provides an adequate protection 
against lighting and reduces the induced electrostatic or electromagnetic voltage but such a 
shield is inadequate to protect any traveling wave, which reaches the terminal of the electrical 
equipment and such wave can cause the following damage: 
1. The high peak of the surge may cause a flashover in the internal wiring thus it may spoil the 
insulation of the winding. 
2. The steep wave front may cause internal flash over between their turns of transformer. 
3. The stop wave front resulting into resonance and high voltage may cause internal or external 
flashover causing building up the oscillator is the electrical operation. 
Lightening arrestors are provided between the line and earth provided the protection against 
traveling wave surge the thyrite lightening arrestor are provided at GSS. This type of LA has a 
basic cell made of thirties, which is particular type of clay, mixed with carborendum. Thirties has 
a particular property of being insulator one voltage At high voltage It will behave like a 
conducting material the electrical resistance of thyrite depends upon the voltage each time the 
voltage is made twice the resistance decrease in such a manner as to allow an increased current 
of 12.5 times the change in current is independent of rate of application voltage and its 
instantaneous value. The above law is followed by this material without any limit on the voltage 
increase and after the surge has passed the thyrite again retains its original property. 
26| P a g e
CHAPTER 3 
3.1 CONTROL ROOM 
Fig (3.1): control Room-1 
To remote control of power switch gear requires the provision of suitable control plates 
located at a suitable point remote from immediate vicinity of CB’s and other 
equipments. At "132 KV GSS Jalore" the separate control room provided for remote 
protection of 132KV switch yards transformer incoming feeder, outing feeders. Bus bar 
has their own control plant in their control rooms. The control panel carrier the appropriate 
relays. Necessary meters indicating lamp control switches and fuses. There are meters for 
reading purpose. A circuit concerning the panel is shown on the panel with standard co 
lour. 
On each panel a control switch is provided for remote operation of circuit breaker. There are 
two indicators which show that weather circuit breaker is closed or open. 
27| P a g e
Fig (3.2): Control Room-2 
Fig (3.3): Control Room-2 
28| P a g e
3.2 EARTHING OF THE SYSTEM 
The provision of an earthling system for an electric system is necessary by the following reason. 
1 In the event of over voltage on the system due to lightening discharge or other system fault. 
These parts of equipment, which are normally dead, as for as voltage, are concerned do not attain 
dangerously high potential. 2 In a three phase, circuit the neutral of the system is earthed in order 
to stabilize the potential of circuit with respect to earth. The resistance of earthling system is 
depending on: 
1. Shape and material of earth electrode used. 
2. Depth in the soil 
3. Specific resistance of soil surrounding in the neighborhood of system electrodes. 
Fig (3.4): EARTHING OF THE SYSTEM 
29| P a g e
3.3.1 PROCEDURE OF EARTHING: Technical consideration the current carrying path 
should have enough capacity to deal with more faults current. The resistance of earth and current 
path should below enough to prevent voltage rise between earth and neutral. The earth electrode 
must be driven into the ground to a sufficient depth to as to obtain lower value of earth 
resistance. To sufficient lowered earth resistance a number of electrodes are inserted in the earth 
to a depth they are connected together to form a mesh. The resistance of earth should be for the 
mesh in generally inserted in the earth at 0.5m depths the several point of mesh then connected to 
earth electrode or ground conduction. The earth electrode is metal plate copper is used for earth 
plate. 
3.3.2 Neutral Earthing: Neutral earthing of power transformer all power system operates 
with grounded neutral. Grounding of neutral offers several advantages the neutral point of 
generator transformer is connected to earth directly or through a reactance in some cases the 
neutral points is earthed through an adjustable reactor of reactance matched with the line. The 
earthling is one of the most important features of system design for switchgear protection neutral 
grounding is important because: 
1. The earth fault protection is based on the method of neutral earthling. 
2. The neutral earthling is associated switchgear. 
3. The neutral earthling is provided for the purpose of protection arcing grounds unbalanced 
voltages with respect to protection from lightening and for improvement of system. 
3.4 POWER LINE CARRIER COMMUNICATION 
As electronics plays a vital role in the industrial growth, communication is also a backbone of 
any power station, communication between various generating and receiving station is very 
essential for proper operation of power system. This is more so in case of a large interconnected 
system where a control load dispatch station has to coordinate the working of various units to see 
that the system is maintained in the optimum working condition, power line communication is 
the most economical and reliable method of communication for medium and long distance in a 
power network. 
30| P a g e
Fig (3.5): POWER LINE CARRIER COMMUNICATION SYSTEM 
3.5 CORONA EFFECT 
When an alternating potential difference is applied across two conductors whose spacing is as 
large as compared to their diameters, there is no apparent change in the condition of atmospheric 
air surrounding the wires if the applied voltage is low. However when the applied voltage 
exceeds a certain value called critical disruptive voltage, the conductors are surrounded by a faint 
violet glow called corona. The phenomenon of corona is accompanied by a hissing sound, 
production of ozone, and power loss and radio interference. The higher the voltage is raised the 
31| P a g e
larger and higher the luminous envelope becomes, and greater are the sound, the power loss and 
the radio noise. If the applied voltage is increased to breakdown value, a flash over will occur 
between the conductors due to the breakdown of air insulation. The phenomenon of violet glow, 
hissing noise and production of ozone gas in an overhead transmission line is known as corona. 
If the conductors are polished and smooth, the corona glow will be uniform throughout the 
length of the conductors; otherwise the rough points will appear brighter. The positive wire has 
uniform glow about it, while the negative conductors has spotty glow. 
3.5.1 FACTORS AFFECTING CORONA:-The phenomenon of corona is affected by 
the physical state of the atmosphere as well as by the conditions of the line. The following are 
the factors on which corona depends: 
1. Atmosphere. In the stormy weather, the number of ions is more than normal and as such 
corona occurs at much less voltage as compared with fair weather. 
2. Conductor size. The rough and irregular surface will give rise to more corona because 
unevenness of the surface decreases the value of breakdown voltage. 
3. Spacing between conductors. Larger space between conductors reduces the electro-static 
stresses at the conductor surface, thus avoiding corona formation. 4. Line voltage. If the line 
voltage is low, there is no chance in the condition of air surrounding the conductors and hence no 
corona is formed. 
3.5.2 ADVANTAGES AND DISADVANTAGES OF CORONA:-Corona has 
many advantages and disadvantages. In the correct design of a high voltage overhead line, a 
balance should be struck between the advantages and disadvantages. 
Advantages:- 
1. Due to corona formation, the air surrounding the conductor becomes conducting and hence 
virtual diameter of the conductor is increased. The increased diameter reduces the electro-static 
stresses between the conductors. 
2. Corona reduces the effect of the transients produced by surges. 
Disadvantages:- 
1. Corona is accompanied by a loss of energy. This affects the transmission efficiency of the line. 
2. Ozone is produced by corona and may cause corrosion of the conductor due to chemical 
action. 
3. The current drawn by the line due to corona is non-sinusoidal and hence non-sinusoidal 
voltage drop occurs in the line. This may cause inductive interference with neighboring 
communication lines. 
32| P a g e
CONCLUSION & FUTURE SCOPE 
A technician needs to have not just theoretical but practical as well and so every student is 
supposed to undergo a practical training session after III year where I have imbibed the 
knowledge about transmission, distribution, generation and maintenance with economical issues 
related to it. During our 30 days training session we were acquainted with the repairing of the 
transformers and also the testing of oil which is a major component of transformer. At last I 
would like to say that practical training taken at 132KV GSS has broadened my knowledge and 
has widened my thinking as a professional. 
After our technical summer training we gained more knowledge. While making this training 
report every care has been taken to avoid any mistake. In short I hope to provide concise sight of 
four weeks of my training period through this report. 
I was lucky to have my training from 132 KV G.S.S., Jalore that gave me an all round 
knowledge that an electrical engineer should know. During 30 days of my training Session at 
G.S.S. I got knowledge about power distribution, power transmission and power line carrier 
communication. 
At last, I would like to say that practical training taken at Jalore has broadened my knowledge 
and has widened my thinking as a professional. 
Future scope of G.S.S. for PLCC system by which we connect other G.S.S. without any 
interrupting. 
33| P a g e
REFERENCES 
· Principles of Power System-by V.K.MEHTA 
· Electrical Power System-by C.L.WADHWA 
· REPORT BY- PRITAM SOLANKI (PCE), JAIPUR 
· http://en.wikipedia.org/wiki/Busbar 
· http://en.wikipedia.org/wiki/Line_trap 
· http://www.google.co.in/search?q=tan+delta+testing&bav=on.2%2Cor.r_qf.&bvm=bv.50 
768961%2Cd.bmk%2Cpv.xjs.s.en_US.8oipRXAmOwI.O&biw=1360&bih=683&um=1 
&hl=en&tbm=isch&tab=wi&oq=tan+delta+testing&gs_l=img.3..0i24l7.14609.20823.0.2 
1551.17.17.0.0.0.0.733.4507.2j5j3j1j0j1j3.15.0....0...1c.1.24.img..9.8.1437.U6YsSGpbA 
Bw 
· http://www.google.co.in/search?q=EARTHING+OF+THE+SYSTEM+for+substations& 
bav=on.2%2Cor.r_qf.&bvm=bv.50768961%2Cd.bmk%2Cpv.xjs.s.en_US.8oipRXAmO 
wI.O&biw=1360&bih=667&um=1&hl=en&tbm=isch&tab=wi&oq=EARTHING+OF+T 
HE+SYSTEM+for+substations&gs_l=img.3...17442.24055.0.24263.16.16.0.0.0.0.316.13 
56.0j3j0j3.6.0....0...1c.1.24.img..16.0.0.6UAoegVSbhA 
· ““Electrical technology- by B.L. Thareja 
· Generation of Electrical power- by B.R.Gupta. 
· http://www.google.co.in/imgres?imgurl=http://www.vacuum-circuit-breakers. 
com/photo/pl421370- 
zw32_12kv_vacuum_circuit_breaker_for_substation_mining_rated_current_630_1250_a. 
jpg&imgrefurl=http://www.vacuum-circuit-breakers.com/china-zw32_ 
12kv_vacuum_circuit_breaker_for_substation_mining_rated_current_630_1250_a 
-298741.html&usg=__F_0RzmP6idI-PnSqgfeDhYTnfQs=& 
h=389&w=538&sz=28&hl=en&start=5&zoom=1&tbnid=QNUG 
SdFRzrhYdM:&tbnh=95&tbnw=132&ei=hhgNUq7wNMjVrQec3oGwBg&prev=/search 
%3Fq%3DCIRCUIT%2BBREAKERS%2Bfor%2Bsubstation%26um%3D1%26biw%3D 
1360%26bih%3D667%26hl%3Den%26tbm%3Disch&um=1&itbs=1&sa=X&ved=0CD 
QQrQMwBA 
· www.engineersgarage.com/articles/plcc-power-line-carrier-communication 
34| P a g e

Más contenido relacionado

La actualidad más candente

Industrial summer training
Industrial summer trainingIndustrial summer training
Industrial summer trainingShubham Patel
 
Report on visiting 132/33 kv substation teliarganj allahabad
Report on visiting 132/33 kv substation teliarganj allahabad Report on visiting 132/33 kv substation teliarganj allahabad
Report on visiting 132/33 kv substation teliarganj allahabad ADARSH KUMAR
 
substation internship report
substation internship report substation internship report
substation internship report Arun Thapa
 
Uttar pradesh power corparation ltd. training report
Uttar pradesh power corparation ltd. training reportUttar pradesh power corparation ltd. training report
Uttar pradesh power corparation ltd. training report19saurabh89
 
Electrical substations: 132 KV
Electrical substations: 132 KV Electrical substations: 132 KV
Electrical substations: 132 KV Girish Gupta
 
220KV Substation Training Report
220KV Substation Training Report220KV Substation Training Report
220KV Substation Training ReportSWAPNILKUMARGUPTA
 
PPt on 220 kV substation
PPt on 220 kV substationPPt on 220 kV substation
PPt on 220 kV substationIshank Ranjan
 
132 KV Grid Station Intern ship training report
132 KV Grid Station Intern ship training report132 KV Grid Station Intern ship training report
132 KV Grid Station Intern ship training reportMuntazir Mehdi
 
PPT on 33/11 sub-station uppcl
PPT on 33/11 sub-station uppclPPT on 33/11 sub-station uppcl
PPT on 33/11 sub-station uppclVISHAL VERMA
 
Summer internship at pgcil
Summer internship at pgcilSummer internship at pgcil
Summer internship at pgcilAnurag Savarn
 
Industrial summer training on 220 kv substation ppt
Industrial summer training on 220 kv substation pptIndustrial summer training on 220 kv substation ppt
Industrial summer training on 220 kv substation pptAshutosh Srivastava
 
Resonant Converter
Resonant ConverterResonant Converter
Resonant Converterpilurout
 
220 kV GSS Mansarovar Jaipur (RVPNL) Training PPT SM54
220 kV GSS Mansarovar Jaipur (RVPNL) Training PPT SM54220 kV GSS Mansarovar Jaipur (RVPNL) Training PPT SM54
220 kV GSS Mansarovar Jaipur (RVPNL) Training PPT SM54Subhash Mahla
 
substation 220 kv
substation 220 kv substation 220 kv
substation 220 kv student
 
Training report-in-a-132-k-v-substation
Training report-in-a-132-k-v-substationTraining report-in-a-132-k-v-substation
Training report-in-a-132-k-v-substationankesh kumar
 

La actualidad más candente (20)

Industrial summer training
Industrial summer trainingIndustrial summer training
Industrial summer training
 
Report on visiting 132/33 kv substation teliarganj allahabad
Report on visiting 132/33 kv substation teliarganj allahabad Report on visiting 132/33 kv substation teliarganj allahabad
Report on visiting 132/33 kv substation teliarganj allahabad
 
substation internship report
substation internship report substation internship report
substation internship report
 
Uttar pradesh power corparation ltd. training report
Uttar pradesh power corparation ltd. training reportUttar pradesh power corparation ltd. training report
Uttar pradesh power corparation ltd. training report
 
Electrical substations: 132 KV
Electrical substations: 132 KV Electrical substations: 132 KV
Electrical substations: 132 KV
 
220KV Substation Training Report
220KV Substation Training Report220KV Substation Training Report
220KV Substation Training Report
 
PPt on 220 kV substation
PPt on 220 kV substationPPt on 220 kV substation
PPt on 220 kV substation
 
132 KV Grid Station Intern ship training report
132 KV Grid Station Intern ship training report132 KV Grid Station Intern ship training report
132 KV Grid Station Intern ship training report
 
PPT on 33/11 sub-station uppcl
PPT on 33/11 sub-station uppclPPT on 33/11 sub-station uppcl
PPT on 33/11 sub-station uppcl
 
33/11 KV SUBSTATION
33/11 KV SUBSTATION33/11 KV SUBSTATION
33/11 KV SUBSTATION
 
Summer internship at pgcil
Summer internship at pgcilSummer internship at pgcil
Summer internship at pgcil
 
Industrial summer training on 220 kv substation ppt
Industrial summer training on 220 kv substation pptIndustrial summer training on 220 kv substation ppt
Industrial summer training on 220 kv substation ppt
 
220 kv gss
220 kv gss220 kv gss
220 kv gss
 
Resonant Converter
Resonant ConverterResonant Converter
Resonant Converter
 
220 kV GSS Mansarovar Jaipur (RVPNL) Training PPT SM54
220 kV GSS Mansarovar Jaipur (RVPNL) Training PPT SM54220 kV GSS Mansarovar Jaipur (RVPNL) Training PPT SM54
220 kV GSS Mansarovar Jaipur (RVPNL) Training PPT SM54
 
substation 220 kv
substation 220 kv substation 220 kv
substation 220 kv
 
33kv substation
33kv substation33kv substation
33kv substation
 
Training report-in-a-132-k-v-substation
Training report-in-a-132-k-v-substationTraining report-in-a-132-k-v-substation
Training report-in-a-132-k-v-substation
 
132kV GSS ppt
132kV GSS ppt132kV GSS ppt
132kV GSS ppt
 
220 kv gss renwal ppt
220 kv gss renwal ppt220 kv gss renwal ppt
220 kv gss renwal ppt
 

Similar a 132kv G.S.S. Jalore

Training report of secl , khairha coal mine , sohagpur area for electrical
Training report of secl , khairha coal mine , sohagpur area for electricalTraining report of secl , khairha coal mine , sohagpur area for electrical
Training report of secl , khairha coal mine , sohagpur area for electricalPiyush Dwivedi
 
BSES - Maintaince of EHV Equipments
BSES - Maintaince of EHV Equipments BSES - Maintaince of EHV Equipments
BSES - Maintaince of EHV Equipments Anuj Gupta
 
132 33kv substation documentation
132 33kv substation documentation132 33kv substation documentation
132 33kv substation documentationRajashekar Gurrala
 
132 KV GSS NPH jodhpur treaning report
132 KV GSS NPH jodhpur treaning report 132 KV GSS NPH jodhpur treaning report
132 KV GSS NPH jodhpur treaning report imkanhaiyalal
 
Trainingreport 120930165750-phpapp01
Trainingreport 120930165750-phpapp01Trainingreport 120930165750-phpapp01
Trainingreport 120930165750-phpapp01Vinay Vashisht
 
132 kv sub-station, power transmission
132 kv sub-station, power transmission132 kv sub-station, power transmission
132 kv sub-station, power transmissionprasantakcs
 
220 kv g.s.s, report
 220 kv g.s.s, report 220 kv g.s.s, report
220 kv g.s.s, reportpanna rayal
 
33-11-kv-substation-training-report (1) (1).pdf
33-11-kv-substation-training-report (1) (1).pdf33-11-kv-substation-training-report (1) (1).pdf
33-11-kv-substation-training-report (1) (1).pdfSagarRana91
 
Industrial training report on dlw varanasi for Main Receiving Substation, Tra...
Industrial training report on dlw varanasi for Main Receiving Substation, Tra...Industrial training report on dlw varanasi for Main Receiving Substation, Tra...
Industrial training report on dlw varanasi for Main Receiving Substation, Tra...Devendra Kumar
 
final year project report
final year project reportfinal year project report
final year project reportAnuj Kumar
 
Internship doc 33 11 kv substation
Internship doc 33 11 kv substation  Internship doc 33 11 kv substation
Internship doc 33 11 kv substation Madeen Kumar
 
Trainingreport 132 KV
Trainingreport 132 KVTrainingreport 132 KV
Trainingreport 132 KVAbrar Ahamed
 
400 kV GSS RRVPNL , Surpura jodhpur
400 kV GSS RRVPNL , Surpura jodhpur400 kV GSS RRVPNL , Surpura jodhpur
400 kV GSS RRVPNL , Surpura jodhpurMANISH BISHNOI
 
MWAPE KAMPILIMBA FINAL REPORT
MWAPE KAMPILIMBA FINAL REPORTMWAPE KAMPILIMBA FINAL REPORT
MWAPE KAMPILIMBA FINAL REPORTKampilimba Mwape
 
Summer Training Report Ntpc barh (ajeet)
Summer Training Report Ntpc barh (ajeet)Summer Training Report Ntpc barh (ajeet)
Summer Training Report Ntpc barh (ajeet)Ajeet Chaurasia
 
Durgapur Projects Limited: Vocational training presentation
Durgapur Projects Limited: Vocational training presentationDurgapur Projects Limited: Vocational training presentation
Durgapur Projects Limited: Vocational training presentationSaumyadip Moitra
 

Similar a 132kv G.S.S. Jalore (20)

Training report of secl , khairha coal mine , sohagpur area for electrical
Training report of secl , khairha coal mine , sohagpur area for electricalTraining report of secl , khairha coal mine , sohagpur area for electrical
Training report of secl , khairha coal mine , sohagpur area for electrical
 
BSES - Maintaince of EHV Equipments
BSES - Maintaince of EHV Equipments BSES - Maintaince of EHV Equipments
BSES - Maintaince of EHV Equipments
 
33 kv substation vt report
33 kv substation vt report33 kv substation vt report
33 kv substation vt report
 
132 33kv substation documentation
132 33kv substation documentation132 33kv substation documentation
132 33kv substation documentation
 
132 KV GSS NPH jodhpur treaning report
132 KV GSS NPH jodhpur treaning report 132 KV GSS NPH jodhpur treaning report
132 KV GSS NPH jodhpur treaning report
 
Trainingreport 120930165750-phpapp01
Trainingreport 120930165750-phpapp01Trainingreport 120930165750-phpapp01
Trainingreport 120930165750-phpapp01
 
132 kv sub-station, power transmission
132 kv sub-station, power transmission132 kv sub-station, power transmission
132 kv sub-station, power transmission
 
220 kv g.s.s, report
 220 kv g.s.s, report 220 kv g.s.s, report
220 kv g.s.s, report
 
33-11-kv-substation-training-report (1) (1).pdf
33-11-kv-substation-training-report (1) (1).pdf33-11-kv-substation-training-report (1) (1).pdf
33-11-kv-substation-training-report (1) (1).pdf
 
DPL Training .doc file
DPL Training .doc file DPL Training .doc file
DPL Training .doc file
 
finalseminar.docx
finalseminar.docxfinalseminar.docx
finalseminar.docx
 
Industrial training report on dlw varanasi for Main Receiving Substation, Tra...
Industrial training report on dlw varanasi for Main Receiving Substation, Tra...Industrial training report on dlw varanasi for Main Receiving Substation, Tra...
Industrial training report on dlw varanasi for Main Receiving Substation, Tra...
 
final year project report
final year project reportfinal year project report
final year project report
 
Internship doc 33 11 kv substation
Internship doc 33 11 kv substation  Internship doc 33 11 kv substation
Internship doc 33 11 kv substation
 
Trainingreport 132 KV
Trainingreport 132 KVTrainingreport 132 KV
Trainingreport 132 KV
 
400 kV GSS RRVPNL , Surpura jodhpur
400 kV GSS RRVPNL , Surpura jodhpur400 kV GSS RRVPNL , Surpura jodhpur
400 kV GSS RRVPNL , Surpura jodhpur
 
400 kv nelmangala
400 kv nelmangala400 kv nelmangala
400 kv nelmangala
 
MWAPE KAMPILIMBA FINAL REPORT
MWAPE KAMPILIMBA FINAL REPORTMWAPE KAMPILIMBA FINAL REPORT
MWAPE KAMPILIMBA FINAL REPORT
 
Summer Training Report Ntpc barh (ajeet)
Summer Training Report Ntpc barh (ajeet)Summer Training Report Ntpc barh (ajeet)
Summer Training Report Ntpc barh (ajeet)
 
Durgapur Projects Limited: Vocational training presentation
Durgapur Projects Limited: Vocational training presentationDurgapur Projects Limited: Vocational training presentation
Durgapur Projects Limited: Vocational training presentation
 

Último

Computer Lecture 01.pptxIntroduction to Computers
Computer Lecture 01.pptxIntroduction to ComputersComputer Lecture 01.pptxIntroduction to Computers
Computer Lecture 01.pptxIntroduction to ComputersMairaAshraf6
 
S1S2 B.Arch MGU - HOA1&2 Module 3 -Temple Architecture of Kerala.pptx
S1S2 B.Arch MGU - HOA1&2 Module 3 -Temple Architecture of Kerala.pptxS1S2 B.Arch MGU - HOA1&2 Module 3 -Temple Architecture of Kerala.pptx
S1S2 B.Arch MGU - HOA1&2 Module 3 -Temple Architecture of Kerala.pptxSCMS School of Architecture
 
Unleashing the Power of the SORA AI lastest leap
Unleashing the Power of the SORA AI lastest leapUnleashing the Power of the SORA AI lastest leap
Unleashing the Power of the SORA AI lastest leapRishantSharmaFr
 
A CASE STUDY ON CERAMIC INDUSTRY OF BANGLADESH.pptx
A CASE STUDY ON CERAMIC INDUSTRY OF BANGLADESH.pptxA CASE STUDY ON CERAMIC INDUSTRY OF BANGLADESH.pptx
A CASE STUDY ON CERAMIC INDUSTRY OF BANGLADESH.pptxmaisarahman1
 
Block diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.pptBlock diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.pptNANDHAKUMARA10
 
Bridge Jacking Design Sample Calculation.pptx
Bridge Jacking Design Sample Calculation.pptxBridge Jacking Design Sample Calculation.pptx
Bridge Jacking Design Sample Calculation.pptxnuruddin69
 
Tamil Call Girls Bhayandar WhatsApp +91-9930687706, Best Service
Tamil Call Girls Bhayandar WhatsApp +91-9930687706, Best ServiceTamil Call Girls Bhayandar WhatsApp +91-9930687706, Best Service
Tamil Call Girls Bhayandar WhatsApp +91-9930687706, Best Servicemeghakumariji156
 
Hostel management system project report..pdf
Hostel management system project report..pdfHostel management system project report..pdf
Hostel management system project report..pdfKamal Acharya
 
Air Compressor reciprocating single stage
Air Compressor reciprocating single stageAir Compressor reciprocating single stage
Air Compressor reciprocating single stageAbc194748
 
Engineering Drawing focus on projection of planes
Engineering Drawing focus on projection of planesEngineering Drawing focus on projection of planes
Engineering Drawing focus on projection of planesRAJNEESHKUMAR341697
 
+97470301568>> buy weed in qatar,buy thc oil qatar,buy weed and vape oil in d...
+97470301568>> buy weed in qatar,buy thc oil qatar,buy weed and vape oil in d...+97470301568>> buy weed in qatar,buy thc oil qatar,buy weed and vape oil in d...
+97470301568>> buy weed in qatar,buy thc oil qatar,buy weed and vape oil in d...Health
 
A Study of Urban Area Plan for Pabna Municipality
A Study of Urban Area Plan for Pabna MunicipalityA Study of Urban Area Plan for Pabna Municipality
A Study of Urban Area Plan for Pabna MunicipalityMorshed Ahmed Rahath
 
Rums floating Omkareshwar FSPV IM_16112021.pdf
Rums floating Omkareshwar FSPV IM_16112021.pdfRums floating Omkareshwar FSPV IM_16112021.pdf
Rums floating Omkareshwar FSPV IM_16112021.pdfsmsksolar
 
School management system project Report.pdf
School management system project Report.pdfSchool management system project Report.pdf
School management system project Report.pdfKamal Acharya
 
kiln thermal load.pptx kiln tgermal load
kiln thermal load.pptx kiln tgermal loadkiln thermal load.pptx kiln tgermal load
kiln thermal load.pptx kiln tgermal loadhamedmustafa094
 
Online food ordering system project report.pdf
Online food ordering system project report.pdfOnline food ordering system project report.pdf
Online food ordering system project report.pdfKamal Acharya
 
Learn the concepts of Thermodynamics on Magic Marks
Learn the concepts of Thermodynamics on Magic MarksLearn the concepts of Thermodynamics on Magic Marks
Learn the concepts of Thermodynamics on Magic MarksMagic Marks
 
scipt v1.pptxcxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx...
scipt v1.pptxcxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx...scipt v1.pptxcxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx...
scipt v1.pptxcxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx...HenryBriggs2
 

Último (20)

Computer Lecture 01.pptxIntroduction to Computers
Computer Lecture 01.pptxIntroduction to ComputersComputer Lecture 01.pptxIntroduction to Computers
Computer Lecture 01.pptxIntroduction to Computers
 
S1S2 B.Arch MGU - HOA1&2 Module 3 -Temple Architecture of Kerala.pptx
S1S2 B.Arch MGU - HOA1&2 Module 3 -Temple Architecture of Kerala.pptxS1S2 B.Arch MGU - HOA1&2 Module 3 -Temple Architecture of Kerala.pptx
S1S2 B.Arch MGU - HOA1&2 Module 3 -Temple Architecture of Kerala.pptx
 
Unleashing the Power of the SORA AI lastest leap
Unleashing the Power of the SORA AI lastest leapUnleashing the Power of the SORA AI lastest leap
Unleashing the Power of the SORA AI lastest leap
 
A CASE STUDY ON CERAMIC INDUSTRY OF BANGLADESH.pptx
A CASE STUDY ON CERAMIC INDUSTRY OF BANGLADESH.pptxA CASE STUDY ON CERAMIC INDUSTRY OF BANGLADESH.pptx
A CASE STUDY ON CERAMIC INDUSTRY OF BANGLADESH.pptx
 
Block diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.pptBlock diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.ppt
 
Bridge Jacking Design Sample Calculation.pptx
Bridge Jacking Design Sample Calculation.pptxBridge Jacking Design Sample Calculation.pptx
Bridge Jacking Design Sample Calculation.pptx
 
Tamil Call Girls Bhayandar WhatsApp +91-9930687706, Best Service
Tamil Call Girls Bhayandar WhatsApp +91-9930687706, Best ServiceTamil Call Girls Bhayandar WhatsApp +91-9930687706, Best Service
Tamil Call Girls Bhayandar WhatsApp +91-9930687706, Best Service
 
Hostel management system project report..pdf
Hostel management system project report..pdfHostel management system project report..pdf
Hostel management system project report..pdf
 
Air Compressor reciprocating single stage
Air Compressor reciprocating single stageAir Compressor reciprocating single stage
Air Compressor reciprocating single stage
 
Engineering Drawing focus on projection of planes
Engineering Drawing focus on projection of planesEngineering Drawing focus on projection of planes
Engineering Drawing focus on projection of planes
 
+97470301568>> buy weed in qatar,buy thc oil qatar,buy weed and vape oil in d...
+97470301568>> buy weed in qatar,buy thc oil qatar,buy weed and vape oil in d...+97470301568>> buy weed in qatar,buy thc oil qatar,buy weed and vape oil in d...
+97470301568>> buy weed in qatar,buy thc oil qatar,buy weed and vape oil in d...
 
A Study of Urban Area Plan for Pabna Municipality
A Study of Urban Area Plan for Pabna MunicipalityA Study of Urban Area Plan for Pabna Municipality
A Study of Urban Area Plan for Pabna Municipality
 
Rums floating Omkareshwar FSPV IM_16112021.pdf
Rums floating Omkareshwar FSPV IM_16112021.pdfRums floating Omkareshwar FSPV IM_16112021.pdf
Rums floating Omkareshwar FSPV IM_16112021.pdf
 
School management system project Report.pdf
School management system project Report.pdfSchool management system project Report.pdf
School management system project Report.pdf
 
kiln thermal load.pptx kiln tgermal load
kiln thermal load.pptx kiln tgermal loadkiln thermal load.pptx kiln tgermal load
kiln thermal load.pptx kiln tgermal load
 
Online food ordering system project report.pdf
Online food ordering system project report.pdfOnline food ordering system project report.pdf
Online food ordering system project report.pdf
 
Call Girls in South Ex (delhi) call me [🔝9953056974🔝] escort service 24X7
Call Girls in South Ex (delhi) call me [🔝9953056974🔝] escort service 24X7Call Girls in South Ex (delhi) call me [🔝9953056974🔝] escort service 24X7
Call Girls in South Ex (delhi) call me [🔝9953056974🔝] escort service 24X7
 
Learn the concepts of Thermodynamics on Magic Marks
Learn the concepts of Thermodynamics on Magic MarksLearn the concepts of Thermodynamics on Magic Marks
Learn the concepts of Thermodynamics on Magic Marks
 
scipt v1.pptxcxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx...
scipt v1.pptxcxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx...scipt v1.pptxcxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx...
scipt v1.pptxcxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx...
 
FEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced Loads
FEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced LoadsFEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced Loads
FEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced Loads
 

132kv G.S.S. Jalore

  • 1. A PRACTICAL TRAINING REPORT ON 132 KV G.S.S. Taken at Jalore Submitted in partial fulfillment for the award of the degree of BACHELOR OF TECHNOLOGY (Rajasthan Technical University, Kota) IN ELECTRICAL ENGINEERING SESSION (2013-2014) SSSSUUUUBBBBMMMMIIIITTTTTTTTEEEEDDDD TTTTOOOO:::: SSSSUUUUBBBBMMMMIIIITTTTTTTTEEEEDDDD BBBBYYYY:::: Mr. Vaibhav Jain Pritam solanki (HOD) EE&7th Sem Electrical Department 10EPCEE092, 4th Year DEPARTMENT OF ELECTRICAL ENGINEERING POORNIMA COLLEGE OF ENGINEERING ISI-6, RIICO INSTITUTIONAL AREA SITAPURA, JAIPUR-302022(RAJASTHAN)
  • 2. DEPARTMENT OF ELECTRICAL ENGINEERING POORNIMA COLLEGE OF ENGINEERING This is to certify that report on “Jalore the degree of Bachelor of Technology in 132 KV G.S.S. Jalore” has been carried out by Mr. Pritam Solanki under my guidance in partial fulfil Electrical Engineering of Rajasthan Technical University, Kota, during the academic year 2012 the best of my knowledge and belief this work has not been submitted elsewhere for the award of any other degree. The work ha satisfactory and is approved for submission. Mr. Vaibhav Jain HOD (E.E.) (Asst. Prof.), E.E. (P.C.E) JAIPUR -302022 CERTIFICATE Mr. Trilock Chand Sony Seminar Guide (Asst. Prof.), E.E. (P.C.E) i fulfillment of ring 2012-13 To has been found Dr. R.P.RAJORIA Campus director (P.C.E.)
  • 3. TABLE OF CONTENT pg.no. CHAPTERS i LIST OF FIGURE iii LIST OF TABLE iv TRAINING CERTIFICATE CERTIFICATE ACKNOWLEDGMENT v ABSTRACT 1 i CHAPTERS CHAPTER 1 1.1 INTRODUCTION [SUB STATION] 2 CHAPTER 2 2.1 SINGLE LINE DIAGRAM OF 132 KV G.S.S. 5 2.2 BUS BARS 6 2.2.1 DOUBLE BUS BAR CONTAINING MAIN BUS I WITH MAIN BUS II 2.2.2 DOUBLE BUS BAR ARRANGEMENTS CONTAINS MAIN BUS WITH AUXILIARY BUS 2.3 ISOLATORS 7 2.4 INSULATORS 8 2.4.1 Pin type 2.4.2 Suspension type insulator 2.4.3 Strain insulator 2.5 PROTECTIVE RELAYS 11 2.5.1 Principal of relay 2.5.2 Differential Relays 2.5.3 Buchholz Relay 2.5.3.1 CONSTRUCTION 2.5.3.2 OPERATION 2.5.3.3 ADVANTAGE 2.5.3.4 DISADVANTAGES 2.5.4 Overcurrent Relays 2.6 CIRCUIT BREAKERS 13 2.6.1 Operating Principal 2.6.2 Arc Phenomenon 2.6.3 Classification of the Circuit Breakers 2.6.3.1 Sulphur Hexaflouride (SF6) Circuit 2.6.3.1.1 Construction 2.6.3.1.2 Working
  • 4. 2.6.3.1.3 Advantages of SF6 Ckt Breaker 2.6.3.1.4 Demerits of SF6 Ckt Breaker 2.7 POWER TRANSFORMER 17 ii 2.7.1 Principal of Transformer 2.7.2 BASIC PARTS OF TRANSFORMER 2.7.3 Description of Plant 2.7.4 Rating Datas 2.8 CURRENT TRANSFORMER 21 2.8.1 POTENTIAL TRANSFORMER 2.9 CAPACITIVE VOLTAGE TRANSFORMER 22 2.9.1 Application 2.10 TRANSFORMER OIL & ITS TESTING 24 2.10.1 Breakdown Voltage 2.10.2 Flash Point 2.11 TRANSFORMER TANδ TESTING 24 2.11.1 Principal 2.12 LIGHTNING ARRESTORS 25 2.12.1 Thyrite Type CHAPTER 3 2.13 CONTROL ROOM 27 2.14 EARTHING OF THE SYSTEM 29 2.14.1 Procedure of Earthing 2.14.2 Neutral Earthing 2.15 POWER LINE CARRIER COMMUNICATION 30 2.16 CORONA 31 2.16.1 Factors Affecting Corona 2.16.2 Advantages and Disadvantages of Corona CONCLUSION 33 REFERENCES 34
  • 5. iii LIST OF FIGURE Figure No. Figure Name pg.no. 1.01 132 KV G.S.S. JALORE 2 2.01 single line diagram of 132 KV G.S.S. 5 2.02 132 KV BUS BARS 6 2.03 Isolator 8 2.04 Pin type insulator 9 2.05 Suspension type insulator 10 2.06 Strain insulator 10 2.07 Diagram of Relay 11 2.08 SF6 Circuit Breaker 14 2.09 Construction view of SF6 Circuit Breaker 16 2.10 Arrangement of a simple Transformer 18 2.11 Transformer 19 2.12 Ratings of Transformers 20 2.13 Current Transformers 21 2.14 Potential Transformers 22 2.15 Capacitive Voltage Transformer 23 2.16 Principal of TANδ tasting Transformers 25 2.17 Lighting Arresters 26 3.01 Control Room-1 27 3.02 Control Room-2 28 3.03 Control Room-3 28 3.04 EARTHING OF THE SYSTEM 29 3.05 POWER LINE CARRIER COMMUNICATION SYSTEM 31
  • 6. iv LIST OF TABLE Table No. Table Name pg.no. 1.01 Details of Circuit Breaker 3 1.02 Details of Current Transformer 4
  • 7. AKNOWLEDGEMENT This is opportunity to express my heartfelt words for the people who were part of this training in numerous ways, people who gave me unending support right from beginning of the training. I am grateful to training incharge Mr. Hari Ram Meena for giving guidelines to make the training successful. I want to give sincere thanks to the Campus Director, Dr. R.P. Rajoria and the principal, Dr. Om Prakash Sharma for his valuable support. I extend my thanks to Mr. Vaibhav Jain Head of the Department for his cooperation and guidance. v Yours Sincerely Pritam solanki
  • 8. 1 | P a g e ABSTRACT This is training of 30 days, during these days my training place was 132 KV G.S.S. Jalore (Rajasthan). G.S.S. is the mean of connection between generating station and consumer by providing safety and reliability of system in case of default. This substation step down the incoming voltage power transmission to the required valve and then is supplied to the consumer feeder or GSS done by connecting auto transformer operation and requirement of various equipment have been include in detail , further in case of report is the bus bar. In our substation there is two main parts 132KV and 33 KV which is a part of substation. First we receive the power 132 KV from Leta, and then we step down the voltage at 33 KV and distributed to the no. of feeders. We have three main transformers which converts 132 KV to 33KV. Two transformers are rating of 12.5 KVA (BHEL-EMCO) and the last one having rating of 25 KVA (IMP). So the total capacity of our substation is 55 MVA. Arrangement of different feeder level and switch yards included information of bus bar arrangement of different level isolator and growing substation also power transformer circuit breaker oil, filtration plant, and compression protection control room and place are leveled. While making this training report every care has been taken to avoid any mistake. In short I hope to provide concise sight of four weeks of my training period through this report. I was lucky to have my training from 132 KV G.S.S., Jalore that gave me an all round knowledge that an electrical engineer should know. During 30 days of my training Session at G.S.S. I got knowledge about power distribution, power transmission and power line carrier communication.
  • 9. 2 | P a g e CHAPTER 1 1.1 INTRODUCTION [SUB STATION] Electric power is generated, transmitted and distributed in the form of alternating current. The electric power produced at the power stations is delivered to the consumers through a large network of transmission & distribution. The transmission network is inevitable long and high power lines are necessary to maintain a huge block of power from source of generation to the load centers to inter connected. Power house for increased reliability of supply greater. The assembly of apparatus used to change some characteristics (e.g. voltage, ac to dc, frequency, power factor etc.) of electric supply keeping the power constant is called a sub-station. Depending on the constructional feature, the high voltage sub-station may be further subdivided: a) Outdoor substation b) Indoor substation c) Basement or Underground substation 132 KV G.S.S. is an outdoor type station. It is primary as well as distribution substation. The power mainly comes from JALORE-1 and JALORE-2 from Leta. Fig (1): 132 KV G.S.S. JALORE
  • 10. Table of Circuit Breaker S.NO. NAME OF BREAKER MAKE 1. 132 KV I/C JALORE-1 BHEL 2. 132 KV I/C JALORE-2 ABB 3. 132 KV Tr.(BHEL-EMCO) CG 4. 132 KV Tr.(IMP) HBB 5. 132 KV BUS COUPLER HBB 6. 33 KV I/C-1(EMCO) SIEMENS 7. 33 KV I/C-2(BHEL) SIEMENS 8. 33 KV I/C-3(IMP) CG 9. 33 KV O/G FN.1 KASHWANA BHEL 10. 33 KV O/G FN.2 JALORE MEGAWIN 11. 33 KV O/G FN.3 SAYLA MEGAWIN 12. 33 KV O/G FN.4 AHORE EASUN REVOLLE 13. 33 KV O/G FN.5 GODAN CG 14. 33 KV O/G FN.6 RICCO MEGAWIN 15. 33 KV CAP. BANK-1 SIEMENS 16. 33 KV CAP. BANK-2 BHEL 17. 33 KV CAP. BANK-3 SIEMENS 18. 33/11 KV Tr. MEI 19. 11 KV I/C-1 BHEL 20. 11 KV O/G FN.1 TO FN.6 NGEF 3 | P a g e Table (1.01): Details of Circuit Breaker
  • 11. Table of Current Transformer S.NO. NAME OF CT MAKE 1. 132 KV I/C JALORE-1 BHEL 2. 132 KV I/C JALORE-2 HBB 3. 132 KV Tr.(BHEL-EMCO) EASUN 4. 132 KV Tr.(IMP) TELK 5. 132 KV BUS COUPLER AMEI 6. 33 KV I/C-1(EMCO) TATA 7. 33 KV I/C-2(BHEL) AMEI 8. 33 KV I/C-3(IMP) HEI 9. 33 KV O/G FN.1 KASHWANA CG 10. 33 KV O/G FN.2 JALORE CG 11. 33 KV O/G FN.3 SAYLA AEI 12. 33 KV O/G FN.4 AHORE UNIVERSAL 13. 33 KV O/G FN.5 GODAN CG 14. 33 KV O/G FN.6 RICCO AEI 15. 33 KV CAP. BANK-1 BHEL 16. 33 KV CAP. BANK-2 BHEL 17. 33 KV CAP. BANK-3 ATE 18. 33/11 KV Tr. AEI 4 | P a g e Table (1.02): Details of Current Transformer
  • 12. 2.2 BUS BARS Bus Bars are common electrical component through which a large no. of feeders operating at same voltage have to be connected. If the bus bars are of rigid type (Aluminum types) the structure height s required. While in case of strain type of bus bars suitable ACSR conductors are strung / tensioned by insulator discs according to system voltages. In the widely used strain type bus bars stringing tension is about 500-900 kg depending effect the clearances when it swings while over tensioning may damage i even effect the supporting structures in low temperature conditions. The clamping should be proper, as loose clamp would s BUS BAR ARRANGEMENT MAY BE FOLLOWING TYPES: Which are being adopted by R.R.V.P.N.L. 1. Single Bus Bar arrangement 2. Double Bus Bar arrangement 3. Double Bus Bar arrangement with auxiliary bu 2.2.1 DOUBLE BUS BAR CONTAINING MAIN BUS I WITH MAIN BUS II 1. Each load may be fed from either bus. 6 | P a g e heights are low and minimum clearance is upon the size of conductor used. Loose Bus Bars would spark under in full load condition damaging the bus bars itself. TYPES:- bus Fig (2.2): 132 KV BUS BARS tension . insulators. Clamps or park II:
  • 13. 2. The load circuits may be divided in two separate groups if needed from operational consideration. Two supplies from different sources can be put on each bus separately. 3. Either bus bar may be taken out from maintenance and cleaning of insulators. This arrangement has been quite frequently adopted where the loads and continuity of supply is necessary. In such a scheme a bus coupler breaker is mostly provided as it enables on load change over from one bus bar to other. The normal bus selection isolators cannot be used for breaking load currents. The arrangement does not permit breaker maintenance without causing stoppage of supply. 2.2.2 DOUBLE BUS BAR ARRANGEMENTS CONTAINS MAIN BUS WITHAUXILIARY BUS: The double bus bar arrangement provides facility to change over to either bus to carry out maintenance on the other but provide no facility to carry over breaker maintenance. The main and transfer bus works the other way round .It provides facility for carrying out breaker maintenance but does not permit bus maintenance. Wherever maintenance is required on any breaker the circuit is changed over to the transfer bus and is controlled through bus coupler breaker. 2.3 ISOLATORS Isolators which are also called disconnect switches or air break switches after the assembly as per drawings on the leveled structures the adjustment of connecting pipes, moving and fixed contacts is done so that all the three phase of the isolator close and open simultaneously and there is a full surface contact between moving and fixed contacts. Such switches are generally used on both sides of equipment in order that repairs and replacement of the equipment can be made without any danger. They should never be opened until the equipment in the same circuit has been turned off and should always be closed before the equipment is turned on. The adjustment of the tendon pipes leveling of post insulator, stop Holts in the fixed contacts etc. is done for smooth operation of insulator. Following type of isolators are being used in R.S.E.B.- a) Isolator without earth blades. b) Isolator with earth blades. c) Tendon isolator 7| P a g e
  • 14. Fig (2.3): ISOLATOR 2.4 INSULATORS The insulators for the overhead lines provide insulation to the power conductors from the ground so that currents from conductors do not flow to earth through supports. The insulators are connected to the cross arm of supporting structure and the power conductors passes through the clamp of the insulator. The insulators provide necessary insulation between line conductors and supports and thus prevent any leakage current from conductors to earth. In general, the insulators should have the following desirable properties: 1) High mechanical strength in order to withstand conductor load, wind load etc. 2) High electrical resistance of insulator material in order to avoid leakage currents to earth. 3) High relative permittivity of insulator material in order that dielectric strength is high. 4) The insulator material should be non porous, free from impurities and cracks otherwise the permittivity will be lowered. 5) High ratio of puncture strength to flash over. These insulators are generally made of glazed porcelain or toughened glass. Porcelain type 8| P a g e
  • 15. insulators [solid core] are also being supplied in place of hast insulators if available indigenously. The design of the insulator is such that the stress due to contraction and expansion in any part of the insulator does not lead to any defect. It is desirable not to allow porcelain to come in direct contact with a hard metal screw thread. Insulators are available in three types: 2.4.1 Pin type:- pin type insulator consists of a single or multiple shells adapted to be mounted on a spindle to be fixed to the cross arm of the supporting structure. When the upper most shell is wet due to rain the lower shells are dry and provide sufficient leakage resistance. These are used for transmission and distribution of electric power at voltage up to 33KV the pin type insulators thus become too bulky and hence uneconomical. Fig (2.4): pin type insulator 2.4.2 Suspension type insulator:- suspension type insulators consists of a number of porcelain disc connected in series by metal links in the form of a string. Its working voltage is 66KV. Each disc is designed for low voltage for 11KV. 9| P a g e
  • 16. Fig (2.5): suspension type insulator 2.4.3 Strain insulator:- Strain insulators are exactly identical in shape with the suspension insulators these strings are placed in the horizontal plane rather than the vertical plane. These insulators are used where line is subjected to greater tension. For low voltage lines shackle insulators are used as strain insulator. Fig (2.6): strain insulator 10| P a g e
  • 17. 2.5 PROTECTIVE RELAYS A protective relay is a device that detects the fault and initiates the operation of the circuit breaker to isolator the defective element from the rest of the system. The relays detect the abnormal condition in the electrical circuits by constantly measuring the electrical quantities i.e. voltage, current, frequency, phase angle which are different under normal and fault conditions. Having detected the fault, the relay operates to close the trip circuit of the breaker, which results in opening of the breaker and disconnection of the faulty circuit. Relays circuit connections can be divided in three parts: 1) Primary winding of C.T. that is connected in series with the line to be protected. 2) Secondary winding of C.T. and the relay operating coil 3) Tripping circuit (either ac or dc) Fig (2.7): Diagram of Relay 11| P a g e
  • 18. 2.5.1 Principal of relay:-when a short circuit occurs at any point F on the transmission line the current increases to enormous value. This results in a heavy current flow through the relay coil, causing the relay to operate by closing its contacts. This in turn closes the trip circuit of the breaker, making the C.B. open and isolating the family section from the rest of the system. In this way, relay ensures the safety of the circuit equipment from damage and normal working of the healthy portion of the system. Basic qualities that a protective relay must possess are: · Selectivity · Speed · Sensitivity · Reliability · Simplicity · Economy Type of relays:- 2.5.2 Differential Relays:- A differential relays is one that operates when the phasor difference of two or more similar electrical quantities exceeds a predetermined value. Thus the current differential relay is one that compares the current entering and current leaving the section. Under normal operating conditions, the two currents are equal but as soon as fault occurs, this condition is no longer applied. The difference between the incoming and outgoing currents is arranged to flow through the operating coil of the relay. If this differential current is equal to or greater than the pickup value, the relay will operate and open the C.B. to isolate the faulty section. 2.5.3 Buchholz Relay:- It is a gas-actuated relay installed in oil immersed transformers for protection against all kinds of faults. It is used to give an alarm in case of incipient (i.e. slow developing) faults in the transformer and to disconnect the transformer from the supply in the event of severe internal faults. It is usually installed in the pipe connecting the conservator to main tank. It is a universal practice to use buchholz relay on all such oil immersed transformers having ratings in excess of 750KVA. 2.5.3.1 CONSTRUCTION:-It takes the form of a domed vessel pipe between the main tank and the conservator. The device has two elements. The upper element consists of a mercury type switch attached to a float. The lower element contains a mercury switch mounted on a hinged type flap located in the direct path of the flow of oil from the transformer to the conservator. The upper element closes an alarm circuit during incipient faults whereas the lower element is arranged to trip the circuit breaker in case of server internal faults. 12| P a g e
  • 19. 2.5.3.2 OPERATION:-The operation of Buchholz relay is as follows: (i) In case of incipient faults within the transformer, the heat due to fault causes the decomposition of some transformer oil in the main tank the products of decomposition contain more than 70% of hydrogen gas. The hydrogen gas being light tries to go into the conservator and in the process gets entrapped in the upper part of the relay chamber. When a pre determined amount of gas gets accumulated, it exerts sufficient pressure on the float to cause it tilt and close the contacts of the mercury switch attached tom it. This completes the alarm circuits to sound an alarm. (ii)If a serious fault occurs in the transformer, enormous amount of gas is generated in the main tank. The oil in the main tank rushes to the conservator via the Buchholz relay and in doing so tilts the flap to close the contacts of the mercury switch. This completes the trip circuit to open the circuit breaker controlling the transformer. 2.5.3.3 ADVANTAGE:- (i) It is the simplest form of transformer protection. (ii) It detects the incipient faults at a stage much earlier than possible with other forms of protection. 2.5.3.4 DISADVANTAGES:- (i) It can only be used with oil immersed transformers equipped with conservator tanks. (ii) The device can detect only faults below oil level in the transformer. Therefore separate protection is needed for connecting cables. 2.5.4 Overcurrent Relays:- an Overcurrent relay is a relay which sense the high current. When a short ckt occurs, high current flows if this current is equal or greater than pick up current then Overcurrent relay trip the ckt breaker. 2.6 CIRCUIT BREAKERS Thus circuit breakers are used for switching & protection of various parts of power system. Circuit breaker is a piece of equipment, which can 1) Make or break a circuit either manually or automatically under normal condition. 2) Break a circuit automatically under fault condition. 3) Make a circuit either manually or by remote control under fault conditions. 13| P a g e
  • 20. Fig (2.8): SF6 Circuit Breaker 2.6.1 OPERATING PRINCIPLES: - A C.B. consists of fixed and moving contacts called electrodes. Under normal operating conditions, these contacts remain closed and will not open automatically until and unless the system becomes faulty. When a fault occurs on any part of the system, the trip coils of the circuit breaker get energized and the moving contacts are pulled apart, thereby opening the circuit. When the contacts of the C.B. are separated under fault conditions, an arc is struck between them. The current is thus able to continue until the discharge ceases. The production of arc not only delays the current interruption process but it also generates enormous heat which may cause damage to the system or to the C.B. It is thus necessary to extinguish the arc within the shortest possible time so that the heat generated by it may not reach a dangerous value. 2.6.2 ARC PHENOMENON:- When a short circuit occurs, a heavy current flow through the contacts of the C.B. before they are opened by the protective system. At the instant when the contacts begin to separate, the contact area decreases rapidly and large fault current causes increased current density and hence rise in temperature. The heat produced in the medium 14| P a g e
  • 21. between contacts is sufficient to ionize the arc or vaporize and ionize the oil. The ionized air or vapour acts as conductor and an arc is set between the contacts. The potential difference between the contacts is quite small and is sufficient to maintain the arc. The arc provides a low resistance path and as a result the current in the circuit remains uninterrupted so long as the arc persists. During the arcing period the current flowing between the contacts depends on the arc resistance. The greater the arc resistance, the smaller the current that flows between the contacts. The arc resistance depends upon: (i) Degree of ionization. (ii) Length of arc. (iii) Cross section of arc. 2.6.3 CLASSIFICATION OF THE CIRCUIT BREAKERS There are several ways of classifying the circuit breakers. However, the most general way of classification is on the basis of medium used for arc extinction. The medium used for arc extinction is usually oil, air, sulphur hexafluoride (SF6) or vacuum. Accordingly, circuit breakers may be classified into:-They are generally classified on the basis of the medium used for arc elimination. (i) Oil circuit breakers, which employ some insulating oil for arc extinction. (ii) Air-blast circuit breakers in which high pressure air blast is used for extinguishing the arc. (iii) Sulphur hexa fluroide C.B. in which SF6 gas is used for arc extinction. (iv) Vacuum C.B. in which vacuum is used for arc extinction. 2.6.3.1 SULPHUR HEXAFLOURIDE (SF6) CIRCUIT BREAKER In such breakers, sulphur hexa flouride (SF6) gas is used as the arc quenching medium. The sf6 is an electro-negative gas and has a strong tendency to absorb free electrons. The SF6 circuit breakers have been found to be very effective for high power and high voltage service. 2.6.3.1.1 CONSTRUCTION The cylindrical large size steel tanks are mounted horizontally parallel to each other. Each tank consists of SF6 under pressure. The interruption is of multibreak type & is placed along the axis of each tank. The interruption assembly is supported inside the tank by the vertical bushing, which are mounted near the end of each tank. Gas at high pressure is supplied to the interrupter from a gas reservoir. The bushings are also insulated with SF6 the conductor is in the form of copper tube supported at both end by porcelain shields. SF6 gas is supplied from the high pressure tanks. Shields are provided with gasket seals to eliminate leakage of gas from beginnings. 15| P a g e
  • 22. Fig (2.9): Construction view of SF6 Circuit Breaker. 2.6.3.1.2 WORKING:- In the closed position of the breaker the contacts remain surrounded by SF6 gas at a pressure of about 2.8 kg/sq cm. When the breaker operates, the moving contact is pulled apart and an arc is struck between the contacts. The movement of the moving contact is synchronized with the opening of a valve which permits SF6 gas at 14kg/sq cm pressure from the reservoir to the arc interruption chamber. The high pressure flow of SF6 rapidly absorbs the free electrons in the arc path to form immobile negative ions which are ineffective as charge carriers. The result is that the medium between the contacts quickly builds up high dielectric strength and 16| P a g e
  • 23. causes the extinction of the arc. After the breaker operation the valve is closed by the action of a set of springs. 2.6.3.1.3 ADVANTAGES OF SF6 CIRCUIT BREAKER: 1. Due to the superior arc quenching property of SF6, such circuit breakers have very short arching time. 2. Since the dielectric strength of SF6 gas is 2 to 3 times that of air, such breakers can interrupt much larger currents. 3. The SF6 circuit breakers gives noiseless operation due to its closed gas circuit and no exhaust to the atmosphere unlike the air blast circuit breaker. 4. The closest gas enclosure keeps the interior dry so that there is no moisture problem. 5. There is on risk of fire in such breakers because SF6 gas is not inflammable. There are no carbon deposits so that tracking and insulation problems are eliminated. 6. The SF6 breakers have low maintenance cost, light foundation requirement and minimum auxiliary equipment. 7. Since SF6 breakers are totally enclosed and sealed from atmosphere they are particularly suitable where explosion hazard exists. 2.6.3.1.4 DEMERITS OF SF6 CIRCUIT BREAKER: 1. Sealing problems arise due to the type of the construction used. 2. The presence of moisture in the system is very dangerous to SF6 circuit breaker. 3. Arced Sf6 gas is poisonous & should not be let out. 4. The double pressure SF6 CB is cost liner due to complex gas system. 5. The internal parts should be cleaned thoroughly during periodic maintenance under clean dry environment. 6. Dust of Teflon & sulfide should be removed. 7. Special facilities are needed for transporting the gas. 2.7 POWER TRANSFORMER 2.7.1 Principal of Transformer: The transformer is a static apparatus, which receives power/energy at it, one circuit and transmits it to other circuit without changing the frequency. With this basic conception we can use the voltages at our desired level while utilizing the power. As, the voltage used to generate at modern power houses at 11 KV or so and afterwards we get it step up at a level of 33 KV, 66 KV, 132 V, 220 KV or 400KV, 750 KV for transmission to minimize the distribution losses. Again we get it step down with the help of transformer to use at our wishes at 11 KV, 6.6 KV or even 415, 230 volts at our houses. 17| P a g e
  • 24. Fig (2.10): Arrangement of a simple Transformer 2.7.2 BASIC PARTS OF TRANSFORMER: - The following are the inherent parts of a modern day transformer. 1. Primary and secondary coils (circuit) or windings. 2. Core 3. Main Tank 4. Conservator 5. Breather 6. Radiator 7. Buchholz relay 8. Explosive vent 9. Bushings (HT & LT) (Primary or secondary) 10. Cooling fans 11. Tap changer (on load and off load) 12. NGR (Neutral Grounding Resistance) to minimize the earth fault current 18| P a g e
  • 25. Fig (2.11): Transformer 2.7.3 DESCRIPTION OF PLANT The three transformers are oil immersed with rating of 12.5 MVA& one with 25 MVA. However a synchronous loading of 55 MVA at 0.98 power factor. The transformer is also provided with a separate bank of radiation, fans, and associated control equipments. The control equipments are housed in a tank mounted miscalling. 19| P a g e
  • 26. 2.7.4 RATING DATAS 20| P a g e Fig (2.12): Ratings of Transformers
  • 27. 2.8 CURRENT TRANSFORMER These transformers are used with low range ammeter to measure currents in high voltage alternating current circuits where it is not practicable to connect instruments and meters directly to lines. In addition to insulating the instrument from the high voltage line, they step down the current in the known ratio. The current (or series) transformers has a primary coil of 1 or more turns of thick wires connected in series with the line whose current is to be measured. The secondary consist of a large number of turns of fine wire and is connected across the ammeter terminals (usually of 5 amp bracket should be removed or 1 amp range. Fig (2.13): Current Transformers 21| P a g e
  • 28. 2.8.1 POTENTIAL TRANSFORMER These transformers are extremely accurate ratio step down transformers and are used in conjunction with standard low range voltmeter (usually 150 volt) whose deflection when divided by voltage transformation ratio, gives the true voltage on the high voltage side. In general, they are of the shell type and do not differ much from the ordinary two winding transformer, except that their power rating is extremely small. Up to voltage of 5000 potential transformers are usually of dry type, between 5000 and 13800 volts, they may be either dry type or oil immersed type, although for voltage above 13800 they are oil type. Since their secondary windings are required to operate instruments or relays or pilot lights, their ratings are usually 42 to 100 watts. Fig (2.14): Potential Transformers 2.9 CAPACITIVE VOLTAGE TRANSFORMERS (CVT) Capacitive voltage transformers are special kind of power transformers using capacitors to step down the voltage. The capacitive voltage transformer comprises of a capacitor divider with its associated electromagnetic unit. The divider provides an accurate proportioned voltage, while the magnetic unit transforms this voltage, in both magnitude and phase to convenient levels suitable for measuring, metering, protection etc. all WSI capacitor units has metallic bellows to compensate the volumetric expansion of oil inside. The porcelain in multi 22| P a g e
  • 29. Fig (2.15): CAPACITIVE VOLTAGE TRANSFORMERS unit stack, all the potential points are electrically tied and suitably shielded to overcome the effect of corona RIV etc. 2.9.1 APPLICATION: 1. Capacitive voltage transformers can be effectively as potential sources for measuring, metering, protection, carrier communication and other vital functions of an electrical network. 2. CVT is constructed in single or multi unit porcelain housing with there associated magnetic units. For EHV system cuts are always supplied in multi unit construction. 3. In case of EHV cuts the multi unit system has many advantage easy to transport and storing, convenience in handling. 23| P a g e
  • 30. 2.10 TRANSFORMER OIL & ITS TESTING The prime function of oil is to convey the heat from the core and winding to the tank where it can be dissipated. Besides these, the oil provides additional insulation between primary and secondary windings. So, the oil must be completely free from dirt, moisture and other un-wanted solid matter. The oil used in the transformer is natural mineral oil and should undergo the following tests if required: 2.10.1 BREAKDOWN VOLTAGE:- The voltage at which the oil breaks down when subjected to an electric field. 2.10.2 FLASH POINT:- The temperature, at which the oil gives off so many vapors, when mixed with air forms an ignitable mixture and gives a momentary flash with small pilot flame. 2.11 TRANSFORMER TANδ TESTING: TANδ testing is a diagnostic test conducted on the insulation of cables and windings. It is used to measure the deterioration in the cable. It also gives an idea of the aging process in the cable and enables us to predict the remaining life of the cable. It is alternatively known as the loss angle test or the dissipation factor test. 2.11.1 PRINCIPLE:- The TANδ test works on the principle that any insulation in its pure state acts as a capacitor. The test involves applying a very low frequency AC voltage. The voltage is generally double the rated voltage of the cable or winding. A low frequency causes a higher value of capacitive reactance which leads to lesser power requirement during the test besides currents will be limited. 24| P a g e
  • 31. Fig (2.1 2.12 LIGHTENING ARRESTORS An electric discharge between cloud and earth, between cloud and the charge centers of the same cloud is known as lightening. The earthing screens and the ground wires can well protect the electrical system against direct lightening strokes but they fail to provide protection against travelling waves which may reach the terminal apparatus. The lightening arrestors or the surge diverters provide protections against such surges. 25| P a g e 16): Principal of TANδ tasting Transformers Tanδ= / l
  • 32. Fig (2.17): LIGHTENING ARRESTORS 2.12.1 THYRITE TYPE: Ground wires run over the tower provides an adequate protection against lighting and reduces the induced electrostatic or electromagnetic voltage but such a shield is inadequate to protect any traveling wave, which reaches the terminal of the electrical equipment and such wave can cause the following damage: 1. The high peak of the surge may cause a flashover in the internal wiring thus it may spoil the insulation of the winding. 2. The steep wave front may cause internal flash over between their turns of transformer. 3. The stop wave front resulting into resonance and high voltage may cause internal or external flashover causing building up the oscillator is the electrical operation. Lightening arrestors are provided between the line and earth provided the protection against traveling wave surge the thyrite lightening arrestor are provided at GSS. This type of LA has a basic cell made of thirties, which is particular type of clay, mixed with carborendum. Thirties has a particular property of being insulator one voltage At high voltage It will behave like a conducting material the electrical resistance of thyrite depends upon the voltage each time the voltage is made twice the resistance decrease in such a manner as to allow an increased current of 12.5 times the change in current is independent of rate of application voltage and its instantaneous value. The above law is followed by this material without any limit on the voltage increase and after the surge has passed the thyrite again retains its original property. 26| P a g e
  • 33. CHAPTER 3 3.1 CONTROL ROOM Fig (3.1): control Room-1 To remote control of power switch gear requires the provision of suitable control plates located at a suitable point remote from immediate vicinity of CB’s and other equipments. At "132 KV GSS Jalore" the separate control room provided for remote protection of 132KV switch yards transformer incoming feeder, outing feeders. Bus bar has their own control plant in their control rooms. The control panel carrier the appropriate relays. Necessary meters indicating lamp control switches and fuses. There are meters for reading purpose. A circuit concerning the panel is shown on the panel with standard co lour. On each panel a control switch is provided for remote operation of circuit breaker. There are two indicators which show that weather circuit breaker is closed or open. 27| P a g e
  • 34. Fig (3.2): Control Room-2 Fig (3.3): Control Room-2 28| P a g e
  • 35. 3.2 EARTHING OF THE SYSTEM The provision of an earthling system for an electric system is necessary by the following reason. 1 In the event of over voltage on the system due to lightening discharge or other system fault. These parts of equipment, which are normally dead, as for as voltage, are concerned do not attain dangerously high potential. 2 In a three phase, circuit the neutral of the system is earthed in order to stabilize the potential of circuit with respect to earth. The resistance of earthling system is depending on: 1. Shape and material of earth electrode used. 2. Depth in the soil 3. Specific resistance of soil surrounding in the neighborhood of system electrodes. Fig (3.4): EARTHING OF THE SYSTEM 29| P a g e
  • 36. 3.3.1 PROCEDURE OF EARTHING: Technical consideration the current carrying path should have enough capacity to deal with more faults current. The resistance of earth and current path should below enough to prevent voltage rise between earth and neutral. The earth electrode must be driven into the ground to a sufficient depth to as to obtain lower value of earth resistance. To sufficient lowered earth resistance a number of electrodes are inserted in the earth to a depth they are connected together to form a mesh. The resistance of earth should be for the mesh in generally inserted in the earth at 0.5m depths the several point of mesh then connected to earth electrode or ground conduction. The earth electrode is metal plate copper is used for earth plate. 3.3.2 Neutral Earthing: Neutral earthing of power transformer all power system operates with grounded neutral. Grounding of neutral offers several advantages the neutral point of generator transformer is connected to earth directly or through a reactance in some cases the neutral points is earthed through an adjustable reactor of reactance matched with the line. The earthling is one of the most important features of system design for switchgear protection neutral grounding is important because: 1. The earth fault protection is based on the method of neutral earthling. 2. The neutral earthling is associated switchgear. 3. The neutral earthling is provided for the purpose of protection arcing grounds unbalanced voltages with respect to protection from lightening and for improvement of system. 3.4 POWER LINE CARRIER COMMUNICATION As electronics plays a vital role in the industrial growth, communication is also a backbone of any power station, communication between various generating and receiving station is very essential for proper operation of power system. This is more so in case of a large interconnected system where a control load dispatch station has to coordinate the working of various units to see that the system is maintained in the optimum working condition, power line communication is the most economical and reliable method of communication for medium and long distance in a power network. 30| P a g e
  • 37. Fig (3.5): POWER LINE CARRIER COMMUNICATION SYSTEM 3.5 CORONA EFFECT When an alternating potential difference is applied across two conductors whose spacing is as large as compared to their diameters, there is no apparent change in the condition of atmospheric air surrounding the wires if the applied voltage is low. However when the applied voltage exceeds a certain value called critical disruptive voltage, the conductors are surrounded by a faint violet glow called corona. The phenomenon of corona is accompanied by a hissing sound, production of ozone, and power loss and radio interference. The higher the voltage is raised the 31| P a g e
  • 38. larger and higher the luminous envelope becomes, and greater are the sound, the power loss and the radio noise. If the applied voltage is increased to breakdown value, a flash over will occur between the conductors due to the breakdown of air insulation. The phenomenon of violet glow, hissing noise and production of ozone gas in an overhead transmission line is known as corona. If the conductors are polished and smooth, the corona glow will be uniform throughout the length of the conductors; otherwise the rough points will appear brighter. The positive wire has uniform glow about it, while the negative conductors has spotty glow. 3.5.1 FACTORS AFFECTING CORONA:-The phenomenon of corona is affected by the physical state of the atmosphere as well as by the conditions of the line. The following are the factors on which corona depends: 1. Atmosphere. In the stormy weather, the number of ions is more than normal and as such corona occurs at much less voltage as compared with fair weather. 2. Conductor size. The rough and irregular surface will give rise to more corona because unevenness of the surface decreases the value of breakdown voltage. 3. Spacing between conductors. Larger space between conductors reduces the electro-static stresses at the conductor surface, thus avoiding corona formation. 4. Line voltage. If the line voltage is low, there is no chance in the condition of air surrounding the conductors and hence no corona is formed. 3.5.2 ADVANTAGES AND DISADVANTAGES OF CORONA:-Corona has many advantages and disadvantages. In the correct design of a high voltage overhead line, a balance should be struck between the advantages and disadvantages. Advantages:- 1. Due to corona formation, the air surrounding the conductor becomes conducting and hence virtual diameter of the conductor is increased. The increased diameter reduces the electro-static stresses between the conductors. 2. Corona reduces the effect of the transients produced by surges. Disadvantages:- 1. Corona is accompanied by a loss of energy. This affects the transmission efficiency of the line. 2. Ozone is produced by corona and may cause corrosion of the conductor due to chemical action. 3. The current drawn by the line due to corona is non-sinusoidal and hence non-sinusoidal voltage drop occurs in the line. This may cause inductive interference with neighboring communication lines. 32| P a g e
  • 39. CONCLUSION & FUTURE SCOPE A technician needs to have not just theoretical but practical as well and so every student is supposed to undergo a practical training session after III year where I have imbibed the knowledge about transmission, distribution, generation and maintenance with economical issues related to it. During our 30 days training session we were acquainted with the repairing of the transformers and also the testing of oil which is a major component of transformer. At last I would like to say that practical training taken at 132KV GSS has broadened my knowledge and has widened my thinking as a professional. After our technical summer training we gained more knowledge. While making this training report every care has been taken to avoid any mistake. In short I hope to provide concise sight of four weeks of my training period through this report. I was lucky to have my training from 132 KV G.S.S., Jalore that gave me an all round knowledge that an electrical engineer should know. During 30 days of my training Session at G.S.S. I got knowledge about power distribution, power transmission and power line carrier communication. At last, I would like to say that practical training taken at Jalore has broadened my knowledge and has widened my thinking as a professional. Future scope of G.S.S. for PLCC system by which we connect other G.S.S. without any interrupting. 33| P a g e
  • 40. REFERENCES · Principles of Power System-by V.K.MEHTA · Electrical Power System-by C.L.WADHWA · REPORT BY- PRITAM SOLANKI (PCE), JAIPUR · http://en.wikipedia.org/wiki/Busbar · http://en.wikipedia.org/wiki/Line_trap · http://www.google.co.in/search?q=tan+delta+testing&bav=on.2%2Cor.r_qf.&bvm=bv.50 768961%2Cd.bmk%2Cpv.xjs.s.en_US.8oipRXAmOwI.O&biw=1360&bih=683&um=1 &hl=en&tbm=isch&tab=wi&oq=tan+delta+testing&gs_l=img.3..0i24l7.14609.20823.0.2 1551.17.17.0.0.0.0.733.4507.2j5j3j1j0j1j3.15.0....0...1c.1.24.img..9.8.1437.U6YsSGpbA Bw · http://www.google.co.in/search?q=EARTHING+OF+THE+SYSTEM+for+substations& bav=on.2%2Cor.r_qf.&bvm=bv.50768961%2Cd.bmk%2Cpv.xjs.s.en_US.8oipRXAmO wI.O&biw=1360&bih=667&um=1&hl=en&tbm=isch&tab=wi&oq=EARTHING+OF+T HE+SYSTEM+for+substations&gs_l=img.3...17442.24055.0.24263.16.16.0.0.0.0.316.13 56.0j3j0j3.6.0....0...1c.1.24.img..16.0.0.6UAoegVSbhA · ““Electrical technology- by B.L. Thareja · Generation of Electrical power- by B.R.Gupta. · http://www.google.co.in/imgres?imgurl=http://www.vacuum-circuit-breakers. com/photo/pl421370- zw32_12kv_vacuum_circuit_breaker_for_substation_mining_rated_current_630_1250_a. jpg&imgrefurl=http://www.vacuum-circuit-breakers.com/china-zw32_ 12kv_vacuum_circuit_breaker_for_substation_mining_rated_current_630_1250_a -298741.html&usg=__F_0RzmP6idI-PnSqgfeDhYTnfQs=& h=389&w=538&sz=28&hl=en&start=5&zoom=1&tbnid=QNUG SdFRzrhYdM:&tbnh=95&tbnw=132&ei=hhgNUq7wNMjVrQec3oGwBg&prev=/search %3Fq%3DCIRCUIT%2BBREAKERS%2Bfor%2Bsubstation%26um%3D1%26biw%3D 1360%26bih%3D667%26hl%3Den%26tbm%3Disch&um=1&itbs=1&sa=X&ved=0CD QQrQMwBA · www.engineersgarage.com/articles/plcc-power-line-carrier-communication 34| P a g e