SlideShare una empresa de Scribd logo
1 de 75
Welcome
     T APR SE AIONON
      O E NT T
INSULATION- CO-ORDINATION
            BY
   A.SAI PRASAD SARMA
INSULATION CO-ORDINATION
•    It is selection of suitable insulation levels of various
     components in any electrical system and their rational
     arrangement.
•    It is required to ensure
3)   Insulation shall withstand all normal stresses and
     majority of abnormal ones
4)   Efficient discharge of over voltages due to internal
     /external causes



5)   B/D shall be only due to external causes
6)   B/D shall be at such places where least damage is
     caused
Determination of Insulation
      coordination – contd.
 Steps in the determination of Insulation
    coordination
• Determination of live Insulation
• Selection of BIL and Insulation levels of
  other equipment
• Selection of Lightning Arrestors.
Definition:- Flash over voltages
• Dry flash over voltage (Dry for) Power frequency voltage.
  Which will cause flashover of the Insulation.
• Wet flash over voltage:- Power frequency voltage.
  Which will cause flash- over when sprayed with water of
  a resistance 9000-11000 ohm-cms drawn from a source
  of supply at a temp within 10°c of the ambient
  temperature in the neighbour- hood of insulation under
  testing and directed at an angle of 45° the volume of
  water being equivalent to precipitation of 0.305 cm /min
Definition:- Flash over voltages
 Impulse flash over voltage:-
• The voltage which will cause flash over of
  an Insulation When subjected to a
  1.2x50µs impulse
• (British standards1x50µ sec)
• (American standards 1.5 x 40µsec)
Definition:- Flash over voltages
• Basic Insulation level :-
  The crest voltage of standard wave that will not
  cause flashover of the insulation is referred to as
  “Basic insulation level”
  (Basic impulse insulation voltages are levels
  expressed in impulse crest voltage with a
  standard wave not longer than 1.2x50 µs (Indian
  standards)
  Equipment insulation as tested shall be equal or
  above the BIL
Impulse spark over volt- time
         characteristic
•     This characteristic is obtained by plotting
    --Time which elapses between the moment the voltage
      wave is applied and the moment of spark over -- on
      abscissa
     -Voltage at the movement of spark over
       (i) Occurring on the wave front
      (ii) Occurring on the wave peaks
      (iii) Crest of the voltage for spark over
           occurring on the wave tail
Impulse spark over volt- time
      characteristic -contd.
• This characteristic is established by
  means of a 1/50 impulse wave
• A line drawn meeting the three B/D
  values is the characteristic
• Proper insulation co-ordination will ensure
  that the voltage time Curve of any
  equipment will lie above the volt -time
  curve of the protective equipment, say,
  Lightning arrestor.
LINE INSULATION
•  Extra high voltage line can be made lightning
   proof by
2 Efficient shielding
3 Low tower footing resistance equal to or less
   than 10 ohms
   shielding angle
Transmission lines up to 220kV      30°
400 kV at and above                  20°
Line insulation -contd.
• Line insulation shall be sufficient to
  prevent a flashover from the power-
  frequency over voltages and Switching
  Surges.
• It shall take into consideration the local un
  favourable circumstances which decrease
  the flash over voltage (rain, dirt, Insulation
  pollution etc.,)
OVER VOLTAGE FACTORS


Line      Switching       Power frequency flash
Voltages  Surge flash     over (Dry & Wet)
          over
220kV     6.5 V pn        0.3
400kV     5.0 V pn        3.3
Vpn = Phase to Neutral Voltage (rms)
Add one or two more Insulators for each string.
OVER VOLTAGE FACTORS—
          Contd.
-To take care of one disc in the string
 becoming defective.
 -Facilitate hot line maintenance
 Up to 220 kV Line – 1 disc for each
 string
 400 kV Line – 2 discs for each string
FLASH OVER VOLATAGE(FOV)
    OF DISCS 254 X 145 mm
NO    DRY FOV   WET FOV Impulse
OF              ( kV rms) FOV
DISCS                     (Standard
                          full wave)
9    540        375       860
10   590        415       945
14   785        565       1265
15   830        600       1345
25   1280       900       2145
RECOMMENDED INSULATION
       LEVEL OF LINE
Normal Vpn       Switching over No of
system In kV     volt. (Wet) kV * discs
Voltage (Vph/√3)                  required


132kV 76         76 x6.5=495   5
220kV 127        127x6.5=825 9
400kV 231        231x5=1755    13
* Compared with Impulse FOV (Value)
RECOMMENDED INSULATION
   LEVEL OF LINE—contd.
Normal     Vpn    Power freq.    No. No. of As per
system    In kV    over volt      of   discs practice
Voltage              (wet)      discs recom.
                   (kVrms)      req.

132kV      76     76x3=228       6      7      9/10

220kV     127     127x3=381      10     11    13/14

400kV     231     231x3=762      20     22    23/24
• Tower forting resistance 10ohms
• severest lightning discharge 50kA (rms)
• Impulse strength of
  Insulation=√2x50x10³x10=700kV
• As per the table for 7 discs, the impulse
  FOV ( kVp =695kVp)
• For better performance tower forting
  resistance shall be brought down.
• For 132kV best is 7 ohms
Co-ordination of line Insulation and
      Sub-Station Insulation
•   Line Insulation is not directly related to the
    Insulation of equipment within the Sub-Station.
•   Impulse flash over voltage of line Insulation
    determine the highest surge voltage that can
    travel into the sub-station.
•   Current through lighting arrestor can be
    calculated from
4   Surge impudence of line
5   Surge voltage arriving over the line
Co-ordination of line Insulation and
      Sub-Station Insulation
• Discharge voltage of the LA on that
  current is the basic protective level of the
  substation equipment.
• Discharge voltage across LA varies with
  surge current.
BASIC INSULATION LEVEL AS
         PER IS (2165 – 1962)
Nominal   Highest   Impulse withstand     One minute power
system    system    volt kVp for test     frequent volt kV (rms)
volt kV   volt kV   Full        Reduced Full           Reduced
(rms)     (rms)     insulation insulation insulation insulation
132 kV 145          650         550       275          230
220 kV 245          1050        900       460          395
400 kV 420                      1550                   680
                                1425                   630
Reduced insulation is used where system is effectively earthed.
INSULATION LEVELS OF
           EQUIPMENT
• Transformers, Isolators, Instrument
  Transformers are manufactured for the standard
  Insulation level.
• Some times transformers, are manufactured for
  one step lower insulation level for the sake of
  economy. (LAs will be designed for a still lower
  level)
• Where LAs are provided right on the top of the
  transformer, some of the equipment may lie well
  out side the protective zone of the LA.
INSULATION LEVELS OF
           EQUIPMENT
• Protective zone is determined based on
A    With stand level of equipment
B    Discharge volt of LA
C    Distance between LA and equipment.
• Such equipment shall be designed for one step
  higher Bill.
• Generally BILL of substation equipment other
  than transformer are designed for10% higher
  BIL than that of Transformer .
INSULATION LEVELS OF
          EQUIPMENT

• BIL of Open poles of a disconnect switch
  shall be 10 to 15% higher than that
  provided between poles and earth.
• EHV system must be designed to operate under
  stresses associated not only with normal
  operating power frequency voltage but also
  those caused by transient over voltage.
• These transient over voltage rise principally
  from lightning over voltage and switching
  operations
• The former is predominant in system at 100 kV
  and below.
• Switching over voltage are of concern in system
  at 220 kV and above
INSULATION CO-ORDINATION
         Over Voltage
• Let Un = line to line normal RMS voltage
• Let Um = Rated highest system voltage rms line
  to line
• √2 Un / √ 3 = Peak of rms voltage phase to
  ground for nominal system voltage
• √2 Um / √ 3 = Peak of rms voltage phase to
  ground voltage for highest system voltage
• Any voltage higher than √ 2/ √ 3 Um is called
  over voltage
Over voltages
•   In addition, temporary over voltages also occur
    at power and harmonic frequencies at times for
    considerable time under certain conditions.
•   The insulation strength and characteristics of
    various components of a system (including
    those of voltage limiting devices) must be
    selected relating to those stresses.
    i. To reduce frequency of supply interruptions
    ii. To reduce component failures
•    The selected level of voltage shall be low
    enough to be operationally and economically
    acceptable
• IEC 71 covers “ Insulation Co-ordination”
• IEC -71- Part-I definition, principles
• IEC 71- Part – II Guidance for selection of rules
  (i) electric strength of the plant, (ii) electric
  strength of LAs or protective spark gaps
IEC 71-3
     • Phase to phase insulation co-ordination
     • Complimentary to part I & II
     • Standard phase to phase insulation level for voltages up to
       and above 300 kV
     • Voltage stresses In service and clearances in air
Data required:
2. Field data on lightning induced and
   switching surges appearing on the
   system
3. Establishing insulation strength of
   various insulating components of the
   system through lab tests
Causes of over voltage:
• Phase to earth faults ( it is assumed that resulting
  temporary voltages will not exceed
     –1.4 Pu for solidly earthed networks
     –1.7 Pu for resistance earthed networks
     –2.0 Pu for reactance earthed networks
• Load rejection (supplying capacitive current through a
  large inductive reactance ex. A smaller generator
  connected to a long cable or over head line)
• Ferro resonance ( inter change of stored energy for
  series or parallel combination of inductive and capacitive
  reactance)
Causes of over voltage: contd.
• Ferranti effect: (receiving end voltage greater
  than sending end voltage under no load or light
  load conditions)
• By care full design and natural earthing
  sustained over voltages involving resonance and
  arcing ground faults are eliminated
• Below 145 kV method of earthing will normally
  determine the level temporary over voltages.
Switching surges
• They are of short duration and irregular form
• Typical switching impulse standard form is the 250/2500
   sec. ( time to crest/ time to half value way)
• The magnitude of internally operated switching surges is
  related to the system operating voltage
• In a system where CBS are not subjected to multi re
  striking the switching surges will rarely exceed 3 pu
• 2.5 pu would be typical maximum based on which the
  discharge duty of LA is assessed
• However in systems above 300 kV, it may be necessary
  to suppress maximum switching surges to 2 pu or less
  by the installation of a shunt reactor and/or closing
  resistors on the circuit breakers
Resonance effects
•    For voltage level below 300 kV.
     Resonance effects occur
    i. When switching transformer
    ii. When switching cable and overhead line
         combination
    iii. Between lumped capacitive and reactive
         elements and over head lines
    iv. Charging long lines without shunt reactor
         compensation
Resonance effects-- contd
• Ferro resonance encountered on a transformer
  feeder greater than 5 to 10 Km in length
• When one feeder/transformer on a double circuit
  is switched out but parallel feeder remains
  energized, the dead circuit draws energy by
  captive coupling from the parallel line circuit
  which resonates with transformer impedance at
  a sub harmonic frequency
• (operation procedure such as opening the line
  isolator at the transformer end on the
  disconnected circuit will eliminate the problem)
Mode of action of flash over on a
                  line

•    A lightning flash can impress over
     voltage on a over head line by
    a) Induction when it discharges to earth close
       to line
    b) By direct contact on the line either to the
       earthed structure or to the phase conductor
Induced Voltage Surge
– A close flash to ground up to about 14 m away
  can induce a voltage rise on phase conductors
– The highest amplitude normally associated is
  in the region of 200 kV
– Significant in case of low voltage lines
– At 11 kV estimated that it accounts for some
  90% of all faults
– Little significance on lines of 275 kV and above
Direct stroke

• A direct stroke can be to the earthed tower
  top or on phase conductor
• Stroke on earthed lower top, for
  transmission of shielded design, is
  innocuous
• Raise in potential caused by passage of
  current through tower impedance to earth
  will be less than with stand strength of line
Direct stroke—contd.

• However the rise in potential can be
  severe and exceed with stand capability, if
  – Tower footing resistance is high
  – Rate of rise of current exceeds a certain level
• Flashover may occur
• Through the system voltage, losses is the
  frequency of flash over
Direct stroke—contd.
• Direct stroke on phase conductor
• May occur if there is a shielding failure i.e. stroke avoids
  earth wire and lands on line conductor.
• Discharge current flows equally in both directions.
• Impedance to earth is half the surge impedance (Z0) of the
  conductor. IN a 400 kV line Z0 = 175 ohms
• Voltage rise is sufficient to cause failure of line insulation
• Minimum critical current for flash over Ic = 2 V I0
                                                   Z0
   VI0 = minimum flash over voltage for 1/50 Wave

• At flash over the impedance through which the discharge
  current flows drops abruptly from Z0/2 to impedance of
  tower, x -arm, tower footing
Surge propagation:

• Surge waves are propagated at the velocity of
  light along the conductor
• On arrival at substation, equipment there in get
  stressed.
• Rod gaps and surge arrestors provide necessary
  protection
• Waves      are    subjected    to   considerable
  attenuations due to losses both in the conductor
  (ohmic losses) and corona losses
Lightning discharges
• Clarification of lightning discharges
  stroke (A)
  stroke (B)
  Stroke (A) : produced by the charged cloud which induces
  a charge on the stationery objects such as high buildings
  etc.
• Charge distribution causes concentration of potential at the
  top most point
• Electro static stress being great at that point ionization of
  surrounding atmosphere takes place
• Dielectric strength of surrounding air decreases giving an
  easy path to lightning stroke.
• Decrease in dielectric strength of surrounding air takes
  considerable time
Lightning discharges
Stroke B:
• A, B & C are three clouds with A and C positively
  charged and B negatively charged
• When there is a stroke between (A) and (B) the charge
  on (C) becomes free and immediately and
  indiscriminately strikes on any object on the ground
• For stroke (B) there is no time lag
• Stroke (B) may completely ignore highest building and
  strike bare ground.
• No protection can be arranged against stroke `B`
• Stroke `A` can be made safe by channelising the charge
  through a lightning conductor placed on the top of the
  building
Static induced charges
• An over head conductor accumulates statically
  induced charge when a charged cloud comes
  above
     • When the cloud is swept away charge on
       the conductor is released
     • The charge travels on either side giving
       rise to two travelling waves
     • The earth wire does not prevent such
       surges
Lightning strokes
• Over voltage due to lightning strokes
  surge impedance of the line = Zs
  Discharge current             = Id
  Over voltage due to direct stroke = Vd = Id x Zs
  However current travels in both directions
 over voltage = Vd = Id x Zs
                        2
  when lightning strikes over earth wire or a tower
Over voltage = Id x Ze + Lc di
                             dt
  Ze = impedance of earth wire
  Lc is the inductance of the line conductor
Protection against lightning
1. Protection of transmission lines
   from direct strokes
2. Protection of power stations and
   substations from direct strokes
3. Protection of electrical equipment
   from traveling waves
Protection of transmission lines
Against the direct strokes :
• Most harmful
• Effective protection required shielding to
  prevent lightning from striking the electrical
  conductors.
• There shall be adequate drain facilities so
  that the charge can be grounded without
  affecting Insulators or line conductors.
Design of transmission line against
                 lightning
•   Design shall consists of
 (a) General wire of adequate mechanical strength to provide
    shielding for line conductor. They shall also be non –corrosive
   Resistance of ground wire shall be low for better protection
    against direct stroke.
(b) Adequate clearance between
    1. Line conductor and tower
    2. Line conductor and earth
    3. Clearance between line conductor and ground wire all
        through the span including mid Span or point of lowest sag.
(c) Tower footing resistance shall be low
 (d) Angle of protection (shielding angle) angle between the
    normal passing through the ground wire and line joining the
    supported center points of outer conductor and ground wire.
    It shall be 30° for 132 & 220 kV lines 20 ° for 400 kV lines
Effect of number of earth wires
• In the absence of a ground wire:
• When there is a charge cloud over a transmission line
  without any ground wire
• There will be two capacitances
   (1) Between cloud and conductor C2
   (2) Between conductor and earth C1
   Induced voltage on the line
   V L1 =       C1    x Ec
               C1+C2
• When ground wire is present it increases capacitance
  between conductor and earth i.e. C1 Decreases induced
  voltage on the line.
• It is observed that presence of a ground wire reduces
  induced voltage on line to half.
• For two ground wires the induced voltage comes down to
  one third
• Presence of two ground wires also provides better shielding
Earth wires
• Disadvantages with ground wire:
 (a) higher line cost
  (b) Probable direct shorting between line
   conductor and ground wire when the later
   gets cut
   In 400kV system transmission line towers
   will have twu earth wires.
Alternative method of line
               protection
• Even after providing ground and reducing the
  likely induced voltages, harmful voltages can still
  develop
• Lightning arrestors act as additional protective
  devisees by by-passing the surges to ground
• Protector tube is a fiber tube with electrode at
  earth end.
• Fitted directly below the conductor
• The arc type electrode on the top of the tube
  forms a series gap with conductor
Alternative method of line
               protection
• The lower electrode is solidly grounded
• In case of surge on the conductor, an arc
  develops between conductor and top electrode
  of the tube.
• Arc shifts within the tube and vaporises some of
  the fiber of tube wall to emit gases which will
  quench the arc
• This tube successfully prevents re-striking
• The break down voltage of tube shall be less
  than flash over voltage of the insulation.
Protection against traveling waves
The traveling waves cause the following damages:
     i.   High peak voltage of surge may cause flash over in
          the internal winding or external flashover between
          the terminals of the equipment.
     ii. steep wave front may cause internal flash over
          between turns of the transformer
     iii. Steep wave front resulting into resonance and high
           voltage may cause internal or external flash over
          causing building up of oscillations in the equipment
•         Protective equipment : LAs and Surge
          diverters
•         They are connected between line and earth
Action of the Surge diverter
• A traveling wave reaches surge diverter and
  attains a prefixed voltage
• A spark is formed across the gap
• The diversion provides a low impedance path to
  earth
• The surge impedance of the line limits the
  amplitude of the current flowing to earth to prevent
  break down of insulation
• Important aspect is that the surge diverter shall
  provide low impedance path to earth only when
  traveling surge reaches the surge diverters
Action of the Surge diverter
• It shall absorb any current during normal
  operation for over voltage surges.
• It means that it shall not function at power
  frequencies but function only when abnormal
  frequencies are applied
• When there is a discharge through them they
  shall be capable of carrying the discharge current
  for some time interval.
• After the over voltage discharge it must be
  capable interrupting normal frequency current
  from flowing to earth as soon as the voltage
  reaches below the break down value
Switching over voltage protection in
           a substation
• Operation of breakers causes transient over voltages
• Over voltage value varying between 1.1 Pu to 6 Pu
  based on switching duty and the type of circuit breaker
• Over voltage occurs mainly due to exchange of energy
  between system inductance ½ LI2 and system
  capacitance ½ CV2
• Over voltage occurs during the opening of circuits and
  closing of long EHV lines
• Most severe over voltages occurs during the closing
  unloaded transmission line
• Preventive measure
   – Provision of Pre insertion resistors ( 400 to 800 ohms
     per phase)
• Simultaneous closing of lines at both ends
• Using shunt reactors, surge arresters etc.
Switching Over voltages in Substations
Switching duty of           Applications and             Phenomena
C.B.                        Remedial Actions

Opening of capacitor        Switching of shunt           Re strike in circuit
bank currents, cable        capacitor banks used for breakers giving over
charging circuits, filter   p.f. correction.             voltage.
banks                       - Use of re strike free C.B.
                            for capacitor switching
                            duty.
EHV lines                   * Long EHV transmission.     Traveling waves
* Closing unloaded           - Use of pre-closing        travel to and fro
lines                       resistors with circuit       giving rise to a
                            breakers. Use of lightning   switching surge.
* Closing charged
lines                       arresters. Use of shunt
                            reactors in transmission
* Auto re closing of
C.B.                        lines.
Methods of Reducing Switching
          Over Voltages
Switching operation       Method to reduce
causing over voltage      switching over voltage
Energising an uncharged   High voltage shunt reactors
line                      are connected to line to
                          reduce power frequency
                          over voltages.
Elimination of trapped    Line shunting after opening
charged on the line       by means of earthing switch
Reduction of current      Opening resistors
chopping                  ( Resistance switching with
                          CB) used only with ABCB
Methods of Reducing Switching
           Over Voltages
Switching operation                Method to reduce
causing over voltage               switching over voltage
Reducing the switching over        Single stage pre closing resistor
voltages due to closing            insertion with CB.
                                   Two stage pre closing resistor
                                   insertion with CB.
                                   Closing resistors in between circuit
                                   breaker and shunt reactor
Reducing switching over voltages   Synchronous switching of three
by improved switching sequence     poles.
                                   Simultaneous operation of circuit
                                   breakers at both ends of line,
Use of surge arrestors             While closing of line
                                   While disconnecting reactor
Rod gaps or coordinating gaps
• They are used on insulators, equipment and
  bushings
• Conducting rods are provided between line
  terminal and earth terminal with an adjustable gap
  ( Air insulation)
• Rods are of 12mm dia approx.
• The gap is adjusted to break down at about 20%
  below the flash over voltage of the insulation.
• Spark over causes dead Short circuit
• Voltage of phase with respect to ground falls very
  low
• The rod gaps are no more used consequent to
  development of surge arrestors.
Over-voltage in Network and Remedies
Phenomena Causes                          Effect                  Remedies

Surges      Lightning strokes on          Line insulation flash   -Use of Ground
            overhead lines or             over or puncture.       wire
            substation                    The traveling wave      - Surge Diverters
                                          reaches substations.    -Earthing of
                                          The insulation of       towers
                                          equipment is
                                                                  -Lightning Masts
                                          stressed by impulse
                                          surge

Switching   Breaking inductive circuit,   Wave travels from       -Use of opening
surges      the energy stored             C.B. to both sides      resistors with C.B.
            inductance gives rise a       Transmission line       - Use of restrike
            voltage rise across           insulator, stressed.    free C.B.
            capacitor.                    Terminal apparatus      -Use pre-insertion
            Switching of capacitive,      insulation stressed     resistors with C.B.
            line charging currents give
            rise to a over voltage due
            to restrike. Closing of EHV
            lines
Over-voltage in Network and Remedies
Phenomena           Causes                 Effect            Remedies

Resonance The fault causing          Very high, voltage   Filters to
          resonance between          surges occur.        eliminate
          inductance and             Insulation failure   harmonics
          capacitance in a part of   likely to occur.
          the circuit
Traveling   High voltage waves get Reflected waves      -Proper
waves       reflected – on reaching gets superimposed switching
            a junction or end.      for initial wave.   sequence.
                                    Voltage may rise
                                    to several time the
                                    normal voltage.
Sustained   Poor voltage control    Failure of          -Proper Voltage
Power                               transformers and    control
frequency                           Rotating Machines
over
voltage
Protective Devices Against Lightning Over
                       voltages
        Device             Where applied                 Remarks
Rod gaps               Across insulator string,   -Difficult to coordinate
                       bushing insulators         -Create dead short
                                                  circuit
                                                  -Cheap
Overhead Ground        -Above overhead lines      -Provide effective
Wires (earthed)        -Above the substation      protection against
                       area                       direct strokes on line
                                                  conductors towers sub
                                                  station equipment
Vertical Masts in      -- in sub stations         -instead of providing
substations                                       overhead shielding
                                                  wires
Lightning Masts/Rods   - Above tall buildings     Protect buildings
(earthed)                                         against direct strokes.
                                                  Angle of Protection
                                                     œ = 300
Protective Devices Against Lightning Over
                       voltages
     Device             Where applied                 Remarks

Surge Arresters   -- on incoming lines in     -- Diverts over voltage to
                  each substation             earth without causing
                  -Near terminals of          short circuit
                  Transformers and            -Used at every voltage
                  generators                  level in every sub-
                  -Near motor and             station and for each line.
                  generators terminals
Surge Absorbers   -- near rotating machines   -Resistance
                  connected between phase     Capacitance
                  and ground                  Combination absorbs
                                              the over voltage surge
                                              and reduces steepness
                                              of wave
Lightning arrester selection
•   1. To determine the magnitude of the power frequency phase to ground
    voltage expected at the proposed arrester location during phase to ground
    fault, or other abnormal conditions which cause higher voltages to ground
    than normal.
•   2. To make a tentative selection of the power frequency voltage rating of the
    arrester. This selection may have to be reconsidered after step (6) is
    completed.
•   3. To select the impulse current likely to be discharged through the arrester.
•   4. To determine the maximum arrester discharge voltage for the impulse
    current and type of arrester selected.
•   5. To establish the full-wave impulse voltage withstand level of the
    equipment to be protected.
•   6. To make certain that the maximum arrester discharge voltage is below
    the full wave impulse, withstand level of the equipment insulation to be
    protected, by adequate margin.
•   7. To establish the separation limit between the arrester and the equipment
    to be protected.
Types of Earthing
• For purpose of selection of voltage rating of a LA
   three types of earthing are considered
(I) Effective earthed system: a system is effectively
   earthed if under any fault condition the line to
   earth voltages of healthy phases do not exceed 80
   % of the system line to line voltage
• If in a system all transformers have star connected
   winding with neutrally solidly earthed then the
   system is effectively earthed
• However if only few transformers are earthed like
   that, it is not effectively earthed system
Types of Earthing - conted.
(II) Non effectively earthed system:
        a) if the line to earth voltage in healthy phases in case
   of a fault exceed 80% of the line to line voltage but does
   not exceed 100% of it, the system is called non effectively
   earthed system
        b) System with few solidly earthed neutrals
        c) Systems with neutral Earthed through resistors or
   reactors of low ohmic value or arc suppression coil

(III) Isolated or un earthed neutral systems :-
 system neutrals are not earthed. Line to earth voltage of
    healthy phases exceed 100% of the line to line voltage.
Selection of lightening arrestors
• Tentative selection of arrestor Voltage:
• Arrestor Voltage rating shall not be less
  than product of system highest voltage x
  co-efficient of earthing
• Co-efficient of earthing :
  – Effectively earthed system       – 80%
  – Non effectively earthed system   - 100 %
    and isolated earth system
Selection of lightening arrestors
• In a 220 kV effectively earthed system
  – Highest system voltage =       245 kV
  – Co-efficient of earthing =     80%
  – Arrestor voltage rating >= 245x0.8 = 196 kV
  – As per IS 3070 (part –I) 1965 the rating is
    198 kV
• By going for a higher voltage rating for a
  surge arrestor, the degree of protection for
  equipment gets reduced.
Selection of arrestor discharge
               current
•    This can be calculated from
    (a) Spark over voltage of transmission line insulation
    (b) Surge impedance of the line
    (c) Residual discharge voltage of LA
              Ia = 2E- Ea
                      Z
    Ia = Arrestor discharge current
    E = Magnitude of incoming surge voltage
    Ea = Residual discharge voltage of an arrestor
    Z = Surge impedance of the line
Selection of arrestor discharge
               current
• In a 220 kV system using 11 insulators
  Transmission line will not permit a traveling wave
  of a value more than 1025 kVp
• As per IS 3010 (Part 1) -1965 the residual
  voltages of LA at a discharge current of 10kA is
  649 kV.
• Considering the surge impedance as 450 ohms
• Maximum value of discharge current of LA =
            2(1025000)-649000       = 3100 Amps
                  450
• The LAs normally in 200 kV system have a
  discharge current rating of 10 kA.
Selection of arrestor discharge Voltage
• Most important characteristic of LA determining the
  protection level being offered
• The arrestor discharge voltage shall be less than BIL of
  equipment for effective protection
• Discharge voltage depends on
  (I) discharge current
  (II) rate of rise of current applied
  (III) Wave shape of current applied
• Discharge voltage of LA increases with discharge current.
  But increase is much restricted due to non –linear
  resistance property.
• Increase in discharge from 5 kA to 20 kA produces only
  25% rise in discharge voltage.
• Increase in rate of current from 1000 to 5000 Amps per
  micro second increases discharge voltage by only 35%.
Protective margin of LA
• Protective margin of LA = BIL of the equipment---
                                  maximum discharge
   voltage of LA
• While determining protection level offered by a LA 10%
   allowances towards drop in lead length and
   manufacturing tolerance shall be allowed.
• Protective margin shall be 20% of the BIL of the
   equipment when closely located
• In a 220 kV system
Discharge voltage of LA = 649 kV
Allowing 10 % margin protection level = 713 kV
BIL of equipment = 900 kVp
Protection margin = 900-713 = 187 kVp
 There is more than 20 % of the BIL of 180 kV
Protective margin of LA-Continue.
• In American system
  Average discharge voltage x 1.25 +40 kV
  = BIL protected
  When adequate margin is not available
  LAs with lower rating shall be chosen
  taking risk.
Insulation Co-ordination Scheme
•   For 220 KV system.
•    L.A. Voltage rating=system highest voltage x co-efficient of earthing =245x.8=196Kv.
•    Selecting standard rating from Table 12.1 column 1,L.A. voltage rating=198 Kv
•   Discharge current rating= 10KA (assumed)
•    Residual voltage, from column 3 of table 12.1,=649Kv (peak)
•   Protection level of the L.A. =649x1.1=714Kv
•   For a margin of 20% between the B.I.L. and the protection level of L.A., the B.I.L.
    should be =714x1.2=857Kv.
•   Choose standard B.I.L. Table 14.3 (b) Col. 4=900 Kv,
•   The corresponding power freq. I minute test voltage =395kv
•   Switching surge flashover voltage =220 x6.5=825kv
•                                          √3
•   Check it is less than B.I.L. of 900kv.
•   Power frequency over voltage=220x3=228kv rms
                                     √3
•   This is less than 395kv.
•   B.I.L. of CBs, instrument transformer, disconnect switches etc,.=900x1.1=990kv.
•   Choose standard B.I.L.=1175kv.
The L.A. voltage rating
Rated system   Highest system Arrester rating
voltage KV     voltage KV     in KV
132            145             120/132
220            245             198/216
400            420             336
Establishment of Separation Limit
•    When arrestor are to be located away from equipment.
•    A traveling wave coming into the station to location to the discharge voltage of the
     arrestor.
• Proximity to transformer or breakers.
     - Transformer is most expensive price.
       - Repair to transformer is costly and with higher revenue loss.
       - Transformers are always at the end of a circuit where voltage regulation.
. For circuit breakers and disconnecting switches flash over distance between terminals
     when in open position in grater than between terminals and ground.
. Surge in excess to insulation strength will flash over to ground with out damaging the
     equipment.
. At best there can be only outage .
. By reducing BIL of transformer savings in the cost of insulation can be obtained.
. Not possible incase of CB or disconnections switches.
. Hence a set of LAS shall be closer to transformers.
Location of Lightning Arresters:
•    The electrical circuit length between L.A. and the transformer
    bushing terminal (inclusive of lead length in metes for effectively
    earthed) should not exceed the limits given below:

       Rated syst.         BIL KV             Max.
       voltage KV          Peak               distance
       132kV               550                35.0
                           650                45.0
       220kV               900/1050           Closer
       400kV               1425/1550          to
                                              Trans.

Más contenido relacionado

La actualidad más candente

Protection against over voltage
Protection against over voltageProtection against over voltage
Protection against over voltageMuhammedArifTanoli
 
Power quality disturbances
Power quality disturbancesPower quality disturbances
Power quality disturbancesManasKumarPatro
 
Distribution System Voltage Drop and Power Loss Calculation
Distribution System Voltage Drop and Power Loss CalculationDistribution System Voltage Drop and Power Loss Calculation
Distribution System Voltage Drop and Power Loss CalculationAmeen San
 
Switchgear and protection 3
Switchgear and protection 3Switchgear and protection 3
Switchgear and protection 3Md Irshad Ahmad
 
Power systems voltage and power control
Power systems voltage and power controlPower systems voltage and power control
Power systems voltage and power controlCaner Göksel Sonuzun
 
Switch Gear & Protection (2170908) (Generator Protection)
Switch Gear & Protection (2170908) (Generator Protection)Switch Gear & Protection (2170908) (Generator Protection)
Switch Gear & Protection (2170908) (Generator Protection)Abhishek Choksi
 
Differential relay
Differential relayDifferential relay
Differential relayChetan Patil
 
Extra high voltage long ac transmission lines
Extra high voltage long ac transmission linesExtra high voltage long ac transmission lines
Extra high voltage long ac transmission linesShivagee Raj
 
PROTECTION AGAINST OVER VOLTAGE AND GROUNDING Part 1
PROTECTION AGAINST OVER VOLTAGE AND GROUNDING Part 1PROTECTION AGAINST OVER VOLTAGE AND GROUNDING Part 1
PROTECTION AGAINST OVER VOLTAGE AND GROUNDING Part 1Dr. Rohit Babu
 
Basic types of facts controllers
Basic types of facts controllersBasic types of facts controllers
Basic types of facts controllersAyyarao T S L V
 
EDS Unit 4 (Protection and Coordination).pptx
EDS Unit 4 (Protection and Coordination).pptxEDS Unit 4 (Protection and Coordination).pptx
EDS Unit 4 (Protection and Coordination).pptxDr. Rohit Babu
 
60232804 ppt-compensation-techniques-in-ac-transmission-system-using-c
60232804 ppt-compensation-techniques-in-ac-transmission-system-using-c60232804 ppt-compensation-techniques-in-ac-transmission-system-using-c
60232804 ppt-compensation-techniques-in-ac-transmission-system-using-cABHISHEK RAI
 
Power System Protection basics
Power System Protection basicsPower System Protection basics
Power System Protection basicsRajan Singh Tanwar
 

La actualidad más candente (20)

Protection against over voltage
Protection against over voltageProtection against over voltage
Protection against over voltage
 
Power quality disturbances
Power quality disturbancesPower quality disturbances
Power quality disturbances
 
Distribution System Voltage Drop and Power Loss Calculation
Distribution System Voltage Drop and Power Loss CalculationDistribution System Voltage Drop and Power Loss Calculation
Distribution System Voltage Drop and Power Loss Calculation
 
Out of step
Out of stepOut of step
Out of step
 
Switchgear and protection 3
Switchgear and protection 3Switchgear and protection 3
Switchgear and protection 3
 
Power systems voltage and power control
Power systems voltage and power controlPower systems voltage and power control
Power systems voltage and power control
 
Switch Gear & Protection (2170908) (Generator Protection)
Switch Gear & Protection (2170908) (Generator Protection)Switch Gear & Protection (2170908) (Generator Protection)
Switch Gear & Protection (2170908) (Generator Protection)
 
Differential relay
Differential relayDifferential relay
Differential relay
 
Extra high voltage long ac transmission lines
Extra high voltage long ac transmission linesExtra high voltage long ac transmission lines
Extra high voltage long ac transmission lines
 
Introduction
IntroductionIntroduction
Introduction
 
Lightning arresters
Lightning arrestersLightning arresters
Lightning arresters
 
PROTECTION AGAINST OVER VOLTAGE AND GROUNDING Part 1
PROTECTION AGAINST OVER VOLTAGE AND GROUNDING Part 1PROTECTION AGAINST OVER VOLTAGE AND GROUNDING Part 1
PROTECTION AGAINST OVER VOLTAGE AND GROUNDING Part 1
 
Basic types of facts controllers
Basic types of facts controllersBasic types of facts controllers
Basic types of facts controllers
 
Lightning Arrestar
Lightning ArrestarLightning Arrestar
Lightning Arrestar
 
Corona effect
Corona effectCorona effect
Corona effect
 
EDS Unit 4 (Protection and Coordination).pptx
EDS Unit 4 (Protection and Coordination).pptxEDS Unit 4 (Protection and Coordination).pptx
EDS Unit 4 (Protection and Coordination).pptx
 
Reactive power compensation
Reactive power compensationReactive power compensation
Reactive power compensation
 
Ac voltage
Ac voltageAc voltage
Ac voltage
 
60232804 ppt-compensation-techniques-in-ac-transmission-system-using-c
60232804 ppt-compensation-techniques-in-ac-transmission-system-using-c60232804 ppt-compensation-techniques-in-ac-transmission-system-using-c
60232804 ppt-compensation-techniques-in-ac-transmission-system-using-c
 
Power System Protection basics
Power System Protection basicsPower System Protection basics
Power System Protection basics
 

Destacado

Mitsubishi - substation insulation coordination studies-sparacino
Mitsubishi - substation insulation coordination studies-sparacinoMitsubishi - substation insulation coordination studies-sparacino
Mitsubishi - substation insulation coordination studies-sparacinoGilberto Mejía
 
Protection against overvoltages
Protection against overvoltagesProtection against overvoltages
Protection against overvoltagesMaryam Nawaz
 
Le.h insulation coordination - Digsilent
Le.h insulation coordination - DigsilentLe.h insulation coordination - Digsilent
Le.h insulation coordination - DigsilentGilberto Mejía
 
Presentation on Over-/under-voltage protection of electrical appliance
Presentation on Over-/under-voltage protection of electrical appliancePresentation on Over-/under-voltage protection of electrical appliance
Presentation on Over-/under-voltage protection of electrical applianceNishant Kumar
 
Ppt of ehv ac transmission
Ppt of ehv ac transmissionPpt of ehv ac transmission
Ppt of ehv ac transmissionSumit Kumar
 
High Voltage Dc (HVDC) transmission
High Voltage Dc (HVDC) transmissionHigh Voltage Dc (HVDC) transmission
High Voltage Dc (HVDC) transmissionZunAib Ali
 
Insulation PPT
Insulation PPTInsulation PPT
Insulation PPTISF
 
ATI's Grounding and Shielding for EMC Technical Training Short Course Sampler
ATI's Grounding and Shielding for EMC Technical Training Short Course SamplerATI's Grounding and Shielding for EMC Technical Training Short Course Sampler
ATI's Grounding and Shielding for EMC Technical Training Short Course SamplerJim Jenkins
 
Types of Insulation
Types of InsulationTypes of Insulation
Types of Insulationcam600
 
WEIDMANN Integrated Services
WEIDMANN Integrated ServicesWEIDMANN Integrated Services
WEIDMANN Integrated Servicespontetto
 
How to conduct the test on the linearity of impulse voltage divider? (www.him...
How to conduct the test on the linearity of impulse voltage divider? (www.him...How to conduct the test on the linearity of impulse voltage divider? (www.him...
How to conduct the test on the linearity of impulse voltage divider? (www.him...Fang Sam
 
1 hvdc systems_in_india
1 hvdc systems_in_india1 hvdc systems_in_india
1 hvdc systems_in_indiaganesh g
 

Destacado (20)

Mitsubishi - substation insulation coordination studies-sparacino
Mitsubishi - substation insulation coordination studies-sparacinoMitsubishi - substation insulation coordination studies-sparacino
Mitsubishi - substation insulation coordination studies-sparacino
 
Protection against overvoltages
Protection against overvoltagesProtection against overvoltages
Protection against overvoltages
 
Insulation
InsulationInsulation
Insulation
 
Overvoltages 1
Overvoltages 1Overvoltages 1
Overvoltages 1
 
Le.h insulation coordination - Digsilent
Le.h insulation coordination - DigsilentLe.h insulation coordination - Digsilent
Le.h insulation coordination - Digsilent
 
Presentation on Over-/under-voltage protection of electrical appliance
Presentation on Over-/under-voltage protection of electrical appliancePresentation on Over-/under-voltage protection of electrical appliance
Presentation on Over-/under-voltage protection of electrical appliance
 
Ppt of ehv ac transmission
Ppt of ehv ac transmissionPpt of ehv ac transmission
Ppt of ehv ac transmission
 
Lighting arrester
Lighting arresterLighting arrester
Lighting arrester
 
HVDC
HVDC HVDC
HVDC
 
HVDC vs HVAC ppt
HVDC vs HVAC pptHVDC vs HVAC ppt
HVDC vs HVAC ppt
 
High Voltage Dc (HVDC) transmission
High Voltage Dc (HVDC) transmissionHigh Voltage Dc (HVDC) transmission
High Voltage Dc (HVDC) transmission
 
Insulation PPT
Insulation PPTInsulation PPT
Insulation PPT
 
ATI's Grounding and Shielding for EMC Technical Training Short Course Sampler
ATI's Grounding and Shielding for EMC Technical Training Short Course SamplerATI's Grounding and Shielding for EMC Technical Training Short Course Sampler
ATI's Grounding and Shielding for EMC Technical Training Short Course Sampler
 
Crazy idea competition 2015
Crazy idea competition 2015Crazy idea competition 2015
Crazy idea competition 2015
 
Types of Insulation
Types of InsulationTypes of Insulation
Types of Insulation
 
WEIDMANN Integrated Services
WEIDMANN Integrated ServicesWEIDMANN Integrated Services
WEIDMANN Integrated Services
 
How to conduct the test on the linearity of impulse voltage divider? (www.him...
How to conduct the test on the linearity of impulse voltage divider? (www.him...How to conduct the test on the linearity of impulse voltage divider? (www.him...
How to conduct the test on the linearity of impulse voltage divider? (www.him...
 
Radio interference
Radio interferenceRadio interference
Radio interference
 
10.1.1.125.8882
10.1.1.125.888210.1.1.125.8882
10.1.1.125.8882
 
1 hvdc systems_in_india
1 hvdc systems_in_india1 hvdc systems_in_india
1 hvdc systems_in_india
 

Similar a 6654882 presentation-on-insulation-co ordination

Insulation co cordination design
Insulation co cordination designInsulation co cordination design
Insulation co cordination designNaresh Surisetti
 
SUBSTATION DESIGN powerpoint presentation.pptx
SUBSTATION DESIGN powerpoint presentation.pptxSUBSTATION DESIGN powerpoint presentation.pptx
SUBSTATION DESIGN powerpoint presentation.pptxHimanshuShrivastava74
 
Insulation coordination
Insulation coordinationInsulation coordination
Insulation coordinationsarunkutti
 
Surge and Lightning Protection Oct 2020
Surge and Lightning Protection Oct 2020Surge and Lightning Protection Oct 2020
Surge and Lightning Protection Oct 2020RekaNext Capital
 
Generator grounding
Generator groundingGenerator grounding
Generator groundingmichaeljmack
 
Pamphlet on important psi parameters rdso
Pamphlet on important psi parameters rdsoPamphlet on important psi parameters rdso
Pamphlet on important psi parameters rdsosonu200186
 
KEMET Webinar - Using varistors for circuit protection
KEMET Webinar - Using varistors for circuit protectionKEMET Webinar - Using varistors for circuit protection
KEMET Webinar - Using varistors for circuit protectionIvana Ivanovska
 
Bil and insulation coordination ppt
Bil and insulation coordination pptBil and insulation coordination ppt
Bil and insulation coordination pptBILAL ALAM
 
PPT_1_Electrical services_By group no. 1.pptx
PPT_1_Electrical services_By group no. 1.pptxPPT_1_Electrical services_By group no. 1.pptx
PPT_1_Electrical services_By group no. 1.pptxayazkhan261
 
PPT_1_Electrical services_By group no. 1.pptx
PPT_1_Electrical services_By group no. 1.pptxPPT_1_Electrical services_By group no. 1.pptx
PPT_1_Electrical services_By group no. 1.pptxayazkhan261
 
1502957304lectrure_1 [Autosaved].pptx
1502957304lectrure_1 [Autosaved].pptx1502957304lectrure_1 [Autosaved].pptx
1502957304lectrure_1 [Autosaved].pptxTajmun1
 
1502957304lectrure_1.pptx
1502957304lectrure_1.pptx1502957304lectrure_1.pptx
1502957304lectrure_1.pptxTajmun1
 
Introduction to power transformers
Introduction to power transformersIntroduction to power transformers
Introduction to power transformersLeonardo ENERGY
 
Lightning impulse test in precise
Lightning impulse test in  preciseLightning impulse test in  precise
Lightning impulse test in preciseMuthar Hussain
 
Fire Pump Short Circuit and WIC Considerations
Fire Pump Short Circuit and WIC ConsiderationsFire Pump Short Circuit and WIC Considerations
Fire Pump Short Circuit and WIC ConsiderationsJames S Nasby
 

Similar a 6654882 presentation-on-insulation-co ordination (20)

Turkey hv
Turkey hvTurkey hv
Turkey hv
 
Insulation co cordination design
Insulation co cordination designInsulation co cordination design
Insulation co cordination design
 
SUBSTATION DESIGN powerpoint presentation.pptx
SUBSTATION DESIGN powerpoint presentation.pptxSUBSTATION DESIGN powerpoint presentation.pptx
SUBSTATION DESIGN powerpoint presentation.pptx
 
Insulation coordination
Insulation coordinationInsulation coordination
Insulation coordination
 
Surge and Lightning Protection Oct 2020
Surge and Lightning Protection Oct 2020Surge and Lightning Protection Oct 2020
Surge and Lightning Protection Oct 2020
 
Generator grounding
Generator groundingGenerator grounding
Generator grounding
 
Pamphlet on important psi parameters rdso
Pamphlet on important psi parameters rdsoPamphlet on important psi parameters rdso
Pamphlet on important psi parameters rdso
 
KEMET Webinar - Using varistors for circuit protection
KEMET Webinar - Using varistors for circuit protectionKEMET Webinar - Using varistors for circuit protection
KEMET Webinar - Using varistors for circuit protection
 
Bil and insulation coordination ppt
Bil and insulation coordination pptBil and insulation coordination ppt
Bil and insulation coordination ppt
 
Aşırı Gerilim Koruma
Aşırı Gerilim KorumaAşırı Gerilim Koruma
Aşırı Gerilim Koruma
 
PPT_1_Electrical services_By group no. 1.pptx
PPT_1_Electrical services_By group no. 1.pptxPPT_1_Electrical services_By group no. 1.pptx
PPT_1_Electrical services_By group no. 1.pptx
 
PPT_1_Electrical services_By group no. 1.pptx
PPT_1_Electrical services_By group no. 1.pptxPPT_1_Electrical services_By group no. 1.pptx
PPT_1_Electrical services_By group no. 1.pptx
 
Introduction to mv switchgear
Introduction to mv switchgearIntroduction to mv switchgear
Introduction to mv switchgear
 
Deltatron or Engetron
Deltatron or EngetronDeltatron or Engetron
Deltatron or Engetron
 
1502957304lectrure_1 [Autosaved].pptx
1502957304lectrure_1 [Autosaved].pptx1502957304lectrure_1 [Autosaved].pptx
1502957304lectrure_1 [Autosaved].pptx
 
1502957304lectrure_1.pptx
1502957304lectrure_1.pptx1502957304lectrure_1.pptx
1502957304lectrure_1.pptx
 
Introduction to power transformers
Introduction to power transformersIntroduction to power transformers
Introduction to power transformers
 
Lightning impulse test in precise
Lightning impulse test in  preciseLightning impulse test in  precise
Lightning impulse test in precise
 
Fire Pump Short Circuit and WIC Considerations
Fire Pump Short Circuit and WIC ConsiderationsFire Pump Short Circuit and WIC Considerations
Fire Pump Short Circuit and WIC Considerations
 
Substation overview
Substation overviewSubstation overview
Substation overview
 

Último

Pooja 9892124323, Call girls Services and Mumbai Escort Service Near Hotel Hy...
Pooja 9892124323, Call girls Services and Mumbai Escort Service Near Hotel Hy...Pooja 9892124323, Call girls Services and Mumbai Escort Service Near Hotel Hy...
Pooja 9892124323, Call girls Services and Mumbai Escort Service Near Hotel Hy...Pooja Nehwal
 
Recommendable # 971589162217 # philippine Young Call Girls in Dubai By Marina...
Recommendable # 971589162217 # philippine Young Call Girls in Dubai By Marina...Recommendable # 971589162217 # philippine Young Call Girls in Dubai By Marina...
Recommendable # 971589162217 # philippine Young Call Girls in Dubai By Marina...home
 
Tapestry Clothing Brands: Collapsing the Funnel
Tapestry Clothing Brands: Collapsing the FunnelTapestry Clothing Brands: Collapsing the Funnel
Tapestry Clothing Brands: Collapsing the Funneljen_giacalone
 
Case Study of Hotel Taj Vivanta, Pune
Case Study of Hotel Taj Vivanta, PuneCase Study of Hotel Taj Vivanta, Pune
Case Study of Hotel Taj Vivanta, PuneLukeKholes
 
Design Inspiration for College by Slidesgo.pptx
Design Inspiration for College by Slidesgo.pptxDesign Inspiration for College by Slidesgo.pptx
Design Inspiration for College by Slidesgo.pptxTusharBahuguna2
 
call girls in Dakshinpuri (DELHI) 🔝 >༒9953056974 🔝 genuine Escort Service 🔝✔️✔️
call girls in Dakshinpuri  (DELHI) 🔝 >༒9953056974 🔝 genuine Escort Service 🔝✔️✔️call girls in Dakshinpuri  (DELHI) 🔝 >༒9953056974 🔝 genuine Escort Service 🔝✔️✔️
call girls in Dakshinpuri (DELHI) 🔝 >༒9953056974 🔝 genuine Escort Service 🔝✔️✔️9953056974 Low Rate Call Girls In Saket, Delhi NCR
 
VVIP CALL GIRLS Lucknow 💓 Lucknow < Renuka Sharma > 7877925207 Escorts Service
VVIP CALL GIRLS Lucknow 💓 Lucknow < Renuka Sharma > 7877925207 Escorts ServiceVVIP CALL GIRLS Lucknow 💓 Lucknow < Renuka Sharma > 7877925207 Escorts Service
VVIP CALL GIRLS Lucknow 💓 Lucknow < Renuka Sharma > 7877925207 Escorts Servicearoranaina404
 
CALL ON ➥8923113531 🔝Call Girls Kalyanpur Lucknow best Female service 🧵
CALL ON ➥8923113531 🔝Call Girls Kalyanpur Lucknow best Female service  🧵CALL ON ➥8923113531 🔝Call Girls Kalyanpur Lucknow best Female service  🧵
CALL ON ➥8923113531 🔝Call Girls Kalyanpur Lucknow best Female service 🧵anilsa9823
 
AMBER GRAIN EMBROIDERY | Growing folklore elements | Root-based materials, w...
AMBER GRAIN EMBROIDERY | Growing folklore elements |  Root-based materials, w...AMBER GRAIN EMBROIDERY | Growing folklore elements |  Root-based materials, w...
AMBER GRAIN EMBROIDERY | Growing folklore elements | Root-based materials, w...BarusRa
 
Best VIP Call Girls Noida Sector 44 Call Me: 8448380779
Best VIP Call Girls Noida Sector 44 Call Me: 8448380779Best VIP Call Girls Noida Sector 44 Call Me: 8448380779
Best VIP Call Girls Noida Sector 44 Call Me: 8448380779Delhi Call girls
 
Escorts Service Nagavara ☎ 7737669865☎ Book Your One night Stand (Bangalore)
Escorts Service Nagavara ☎ 7737669865☎ Book Your One night Stand (Bangalore)Escorts Service Nagavara ☎ 7737669865☎ Book Your One night Stand (Bangalore)
Escorts Service Nagavara ☎ 7737669865☎ Book Your One night Stand (Bangalore)amitlee9823
 
call girls in Vasundhra (Ghaziabad) 🔝 >༒8448380779 🔝 genuine Escort Service 🔝...
call girls in Vasundhra (Ghaziabad) 🔝 >༒8448380779 🔝 genuine Escort Service 🔝...call girls in Vasundhra (Ghaziabad) 🔝 >༒8448380779 🔝 genuine Escort Service 🔝...
call girls in Vasundhra (Ghaziabad) 🔝 >༒8448380779 🔝 genuine Escort Service 🔝...Delhi Call girls
 
Brookefield Call Girls: 🍓 7737669865 🍓 High Profile Model Escorts | Bangalore...
Brookefield Call Girls: 🍓 7737669865 🍓 High Profile Model Escorts | Bangalore...Brookefield Call Girls: 🍓 7737669865 🍓 High Profile Model Escorts | Bangalore...
Brookefield Call Girls: 🍓 7737669865 🍓 High Profile Model Escorts | Bangalore...amitlee9823
 
DragonBall PowerPoint Template for demo.pptx
DragonBall PowerPoint Template for demo.pptxDragonBall PowerPoint Template for demo.pptx
DragonBall PowerPoint Template for demo.pptxmirandajeremy200221
 
Peaches App development presentation deck
Peaches App development presentation deckPeaches App development presentation deck
Peaches App development presentation decktbatkhuu1
 
RT Nagar Call Girls Service: 🍓 7737669865 🍓 High Profile Model Escorts | Bang...
RT Nagar Call Girls Service: 🍓 7737669865 🍓 High Profile Model Escorts | Bang...RT Nagar Call Girls Service: 🍓 7737669865 🍓 High Profile Model Escorts | Bang...
RT Nagar Call Girls Service: 🍓 7737669865 🍓 High Profile Model Escorts | Bang...amitlee9823
 
VVIP Pune Call Girls Hadapsar (7001035870) Pune Escorts Nearby with Complete ...
VVIP Pune Call Girls Hadapsar (7001035870) Pune Escorts Nearby with Complete ...VVIP Pune Call Girls Hadapsar (7001035870) Pune Escorts Nearby with Complete ...
VVIP Pune Call Girls Hadapsar (7001035870) Pune Escorts Nearby with Complete ...Call Girls in Nagpur High Profile
 
Pastel Portfolio _ by Slidesgo.pptx. Xxx
Pastel Portfolio _ by Slidesgo.pptx. XxxPastel Portfolio _ by Slidesgo.pptx. Xxx
Pastel Portfolio _ by Slidesgo.pptx. XxxSegundoManuelFaichin1
 
VIP Model Call Girls Kalyani Nagar ( Pune ) Call ON 8005736733 Starting From ...
VIP Model Call Girls Kalyani Nagar ( Pune ) Call ON 8005736733 Starting From ...VIP Model Call Girls Kalyani Nagar ( Pune ) Call ON 8005736733 Starting From ...
VIP Model Call Girls Kalyani Nagar ( Pune ) Call ON 8005736733 Starting From ...SUHANI PANDEY
 

Último (20)

Pooja 9892124323, Call girls Services and Mumbai Escort Service Near Hotel Hy...
Pooja 9892124323, Call girls Services and Mumbai Escort Service Near Hotel Hy...Pooja 9892124323, Call girls Services and Mumbai Escort Service Near Hotel Hy...
Pooja 9892124323, Call girls Services and Mumbai Escort Service Near Hotel Hy...
 
Recommendable # 971589162217 # philippine Young Call Girls in Dubai By Marina...
Recommendable # 971589162217 # philippine Young Call Girls in Dubai By Marina...Recommendable # 971589162217 # philippine Young Call Girls in Dubai By Marina...
Recommendable # 971589162217 # philippine Young Call Girls in Dubai By Marina...
 
Tapestry Clothing Brands: Collapsing the Funnel
Tapestry Clothing Brands: Collapsing the FunnelTapestry Clothing Brands: Collapsing the Funnel
Tapestry Clothing Brands: Collapsing the Funnel
 
Case Study of Hotel Taj Vivanta, Pune
Case Study of Hotel Taj Vivanta, PuneCase Study of Hotel Taj Vivanta, Pune
Case Study of Hotel Taj Vivanta, Pune
 
Design Inspiration for College by Slidesgo.pptx
Design Inspiration for College by Slidesgo.pptxDesign Inspiration for College by Slidesgo.pptx
Design Inspiration for College by Slidesgo.pptx
 
call girls in Dakshinpuri (DELHI) 🔝 >༒9953056974 🔝 genuine Escort Service 🔝✔️✔️
call girls in Dakshinpuri  (DELHI) 🔝 >༒9953056974 🔝 genuine Escort Service 🔝✔️✔️call girls in Dakshinpuri  (DELHI) 🔝 >༒9953056974 🔝 genuine Escort Service 🔝✔️✔️
call girls in Dakshinpuri (DELHI) 🔝 >༒9953056974 🔝 genuine Escort Service 🔝✔️✔️
 
VVIP CALL GIRLS Lucknow 💓 Lucknow < Renuka Sharma > 7877925207 Escorts Service
VVIP CALL GIRLS Lucknow 💓 Lucknow < Renuka Sharma > 7877925207 Escorts ServiceVVIP CALL GIRLS Lucknow 💓 Lucknow < Renuka Sharma > 7877925207 Escorts Service
VVIP CALL GIRLS Lucknow 💓 Lucknow < Renuka Sharma > 7877925207 Escorts Service
 
CALL ON ➥8923113531 🔝Call Girls Kalyanpur Lucknow best Female service 🧵
CALL ON ➥8923113531 🔝Call Girls Kalyanpur Lucknow best Female service  🧵CALL ON ➥8923113531 🔝Call Girls Kalyanpur Lucknow best Female service  🧵
CALL ON ➥8923113531 🔝Call Girls Kalyanpur Lucknow best Female service 🧵
 
AMBER GRAIN EMBROIDERY | Growing folklore elements | Root-based materials, w...
AMBER GRAIN EMBROIDERY | Growing folklore elements |  Root-based materials, w...AMBER GRAIN EMBROIDERY | Growing folklore elements |  Root-based materials, w...
AMBER GRAIN EMBROIDERY | Growing folklore elements | Root-based materials, w...
 
Best VIP Call Girls Noida Sector 44 Call Me: 8448380779
Best VIP Call Girls Noida Sector 44 Call Me: 8448380779Best VIP Call Girls Noida Sector 44 Call Me: 8448380779
Best VIP Call Girls Noida Sector 44 Call Me: 8448380779
 
Escorts Service Nagavara ☎ 7737669865☎ Book Your One night Stand (Bangalore)
Escorts Service Nagavara ☎ 7737669865☎ Book Your One night Stand (Bangalore)Escorts Service Nagavara ☎ 7737669865☎ Book Your One night Stand (Bangalore)
Escorts Service Nagavara ☎ 7737669865☎ Book Your One night Stand (Bangalore)
 
call girls in Vasundhra (Ghaziabad) 🔝 >༒8448380779 🔝 genuine Escort Service 🔝...
call girls in Vasundhra (Ghaziabad) 🔝 >༒8448380779 🔝 genuine Escort Service 🔝...call girls in Vasundhra (Ghaziabad) 🔝 >༒8448380779 🔝 genuine Escort Service 🔝...
call girls in Vasundhra (Ghaziabad) 🔝 >༒8448380779 🔝 genuine Escort Service 🔝...
 
Brookefield Call Girls: 🍓 7737669865 🍓 High Profile Model Escorts | Bangalore...
Brookefield Call Girls: 🍓 7737669865 🍓 High Profile Model Escorts | Bangalore...Brookefield Call Girls: 🍓 7737669865 🍓 High Profile Model Escorts | Bangalore...
Brookefield Call Girls: 🍓 7737669865 🍓 High Profile Model Escorts | Bangalore...
 
DragonBall PowerPoint Template for demo.pptx
DragonBall PowerPoint Template for demo.pptxDragonBall PowerPoint Template for demo.pptx
DragonBall PowerPoint Template for demo.pptx
 
Peaches App development presentation deck
Peaches App development presentation deckPeaches App development presentation deck
Peaches App development presentation deck
 
RT Nagar Call Girls Service: 🍓 7737669865 🍓 High Profile Model Escorts | Bang...
RT Nagar Call Girls Service: 🍓 7737669865 🍓 High Profile Model Escorts | Bang...RT Nagar Call Girls Service: 🍓 7737669865 🍓 High Profile Model Escorts | Bang...
RT Nagar Call Girls Service: 🍓 7737669865 🍓 High Profile Model Escorts | Bang...
 
Call Girls Service Mukherjee Nagar @9999965857 Delhi 🫦 No Advance VVIP 🍎 SER...
Call Girls Service Mukherjee Nagar @9999965857 Delhi 🫦 No Advance  VVIP 🍎 SER...Call Girls Service Mukherjee Nagar @9999965857 Delhi 🫦 No Advance  VVIP 🍎 SER...
Call Girls Service Mukherjee Nagar @9999965857 Delhi 🫦 No Advance VVIP 🍎 SER...
 
VVIP Pune Call Girls Hadapsar (7001035870) Pune Escorts Nearby with Complete ...
VVIP Pune Call Girls Hadapsar (7001035870) Pune Escorts Nearby with Complete ...VVIP Pune Call Girls Hadapsar (7001035870) Pune Escorts Nearby with Complete ...
VVIP Pune Call Girls Hadapsar (7001035870) Pune Escorts Nearby with Complete ...
 
Pastel Portfolio _ by Slidesgo.pptx. Xxx
Pastel Portfolio _ by Slidesgo.pptx. XxxPastel Portfolio _ by Slidesgo.pptx. Xxx
Pastel Portfolio _ by Slidesgo.pptx. Xxx
 
VIP Model Call Girls Kalyani Nagar ( Pune ) Call ON 8005736733 Starting From ...
VIP Model Call Girls Kalyani Nagar ( Pune ) Call ON 8005736733 Starting From ...VIP Model Call Girls Kalyani Nagar ( Pune ) Call ON 8005736733 Starting From ...
VIP Model Call Girls Kalyani Nagar ( Pune ) Call ON 8005736733 Starting From ...
 

6654882 presentation-on-insulation-co ordination

  • 1. Welcome T APR SE AIONON O E NT T INSULATION- CO-ORDINATION BY A.SAI PRASAD SARMA
  • 2. INSULATION CO-ORDINATION • It is selection of suitable insulation levels of various components in any electrical system and their rational arrangement. • It is required to ensure 3) Insulation shall withstand all normal stresses and majority of abnormal ones 4) Efficient discharge of over voltages due to internal /external causes 5) B/D shall be only due to external causes 6) B/D shall be at such places where least damage is caused
  • 3. Determination of Insulation coordination – contd. Steps in the determination of Insulation coordination • Determination of live Insulation • Selection of BIL and Insulation levels of other equipment • Selection of Lightning Arrestors.
  • 4. Definition:- Flash over voltages • Dry flash over voltage (Dry for) Power frequency voltage. Which will cause flashover of the Insulation. • Wet flash over voltage:- Power frequency voltage. Which will cause flash- over when sprayed with water of a resistance 9000-11000 ohm-cms drawn from a source of supply at a temp within 10°c of the ambient temperature in the neighbour- hood of insulation under testing and directed at an angle of 45° the volume of water being equivalent to precipitation of 0.305 cm /min
  • 5. Definition:- Flash over voltages Impulse flash over voltage:- • The voltage which will cause flash over of an Insulation When subjected to a 1.2x50µs impulse • (British standards1x50µ sec) • (American standards 1.5 x 40µsec)
  • 6. Definition:- Flash over voltages • Basic Insulation level :- The crest voltage of standard wave that will not cause flashover of the insulation is referred to as “Basic insulation level” (Basic impulse insulation voltages are levels expressed in impulse crest voltage with a standard wave not longer than 1.2x50 µs (Indian standards) Equipment insulation as tested shall be equal or above the BIL
  • 7. Impulse spark over volt- time characteristic • This characteristic is obtained by plotting --Time which elapses between the moment the voltage wave is applied and the moment of spark over -- on abscissa -Voltage at the movement of spark over (i) Occurring on the wave front (ii) Occurring on the wave peaks (iii) Crest of the voltage for spark over occurring on the wave tail
  • 8. Impulse spark over volt- time characteristic -contd. • This characteristic is established by means of a 1/50 impulse wave • A line drawn meeting the three B/D values is the characteristic • Proper insulation co-ordination will ensure that the voltage time Curve of any equipment will lie above the volt -time curve of the protective equipment, say, Lightning arrestor.
  • 9. LINE INSULATION • Extra high voltage line can be made lightning proof by 2 Efficient shielding 3 Low tower footing resistance equal to or less than 10 ohms shielding angle Transmission lines up to 220kV 30° 400 kV at and above 20°
  • 10. Line insulation -contd. • Line insulation shall be sufficient to prevent a flashover from the power- frequency over voltages and Switching Surges. • It shall take into consideration the local un favourable circumstances which decrease the flash over voltage (rain, dirt, Insulation pollution etc.,)
  • 11. OVER VOLTAGE FACTORS Line Switching Power frequency flash Voltages Surge flash over (Dry & Wet) over 220kV 6.5 V pn 0.3 400kV 5.0 V pn 3.3 Vpn = Phase to Neutral Voltage (rms) Add one or two more Insulators for each string.
  • 12. OVER VOLTAGE FACTORS— Contd. -To take care of one disc in the string becoming defective. -Facilitate hot line maintenance Up to 220 kV Line – 1 disc for each string 400 kV Line – 2 discs for each string
  • 13. FLASH OVER VOLATAGE(FOV) OF DISCS 254 X 145 mm NO DRY FOV WET FOV Impulse OF ( kV rms) FOV DISCS (Standard full wave) 9 540 375 860 10 590 415 945 14 785 565 1265 15 830 600 1345 25 1280 900 2145
  • 14. RECOMMENDED INSULATION LEVEL OF LINE Normal Vpn Switching over No of system In kV volt. (Wet) kV * discs Voltage (Vph/√3) required 132kV 76 76 x6.5=495 5 220kV 127 127x6.5=825 9 400kV 231 231x5=1755 13 * Compared with Impulse FOV (Value)
  • 15. RECOMMENDED INSULATION LEVEL OF LINE—contd. Normal Vpn Power freq. No. No. of As per system In kV over volt of discs practice Voltage (wet) discs recom. (kVrms) req. 132kV 76 76x3=228 6 7 9/10 220kV 127 127x3=381 10 11 13/14 400kV 231 231x3=762 20 22 23/24
  • 16. • Tower forting resistance 10ohms • severest lightning discharge 50kA (rms) • Impulse strength of Insulation=√2x50x10³x10=700kV • As per the table for 7 discs, the impulse FOV ( kVp =695kVp) • For better performance tower forting resistance shall be brought down. • For 132kV best is 7 ohms
  • 17. Co-ordination of line Insulation and Sub-Station Insulation • Line Insulation is not directly related to the Insulation of equipment within the Sub-Station. • Impulse flash over voltage of line Insulation determine the highest surge voltage that can travel into the sub-station. • Current through lighting arrestor can be calculated from 4 Surge impudence of line 5 Surge voltage arriving over the line
  • 18. Co-ordination of line Insulation and Sub-Station Insulation • Discharge voltage of the LA on that current is the basic protective level of the substation equipment. • Discharge voltage across LA varies with surge current.
  • 19. BASIC INSULATION LEVEL AS PER IS (2165 – 1962) Nominal Highest Impulse withstand One minute power system system volt kVp for test frequent volt kV (rms) volt kV volt kV Full Reduced Full Reduced (rms) (rms) insulation insulation insulation insulation 132 kV 145 650 550 275 230 220 kV 245 1050 900 460 395 400 kV 420 1550 680 1425 630 Reduced insulation is used where system is effectively earthed.
  • 20. INSULATION LEVELS OF EQUIPMENT • Transformers, Isolators, Instrument Transformers are manufactured for the standard Insulation level. • Some times transformers, are manufactured for one step lower insulation level for the sake of economy. (LAs will be designed for a still lower level) • Where LAs are provided right on the top of the transformer, some of the equipment may lie well out side the protective zone of the LA.
  • 21. INSULATION LEVELS OF EQUIPMENT • Protective zone is determined based on A With stand level of equipment B Discharge volt of LA C Distance between LA and equipment. • Such equipment shall be designed for one step higher Bill. • Generally BILL of substation equipment other than transformer are designed for10% higher BIL than that of Transformer .
  • 22. INSULATION LEVELS OF EQUIPMENT • BIL of Open poles of a disconnect switch shall be 10 to 15% higher than that provided between poles and earth.
  • 23. • EHV system must be designed to operate under stresses associated not only with normal operating power frequency voltage but also those caused by transient over voltage. • These transient over voltage rise principally from lightning over voltage and switching operations • The former is predominant in system at 100 kV and below. • Switching over voltage are of concern in system at 220 kV and above
  • 24. INSULATION CO-ORDINATION Over Voltage • Let Un = line to line normal RMS voltage • Let Um = Rated highest system voltage rms line to line • √2 Un / √ 3 = Peak of rms voltage phase to ground for nominal system voltage • √2 Um / √ 3 = Peak of rms voltage phase to ground voltage for highest system voltage • Any voltage higher than √ 2/ √ 3 Um is called over voltage
  • 25. Over voltages • In addition, temporary over voltages also occur at power and harmonic frequencies at times for considerable time under certain conditions. • The insulation strength and characteristics of various components of a system (including those of voltage limiting devices) must be selected relating to those stresses. i. To reduce frequency of supply interruptions ii. To reduce component failures • The selected level of voltage shall be low enough to be operationally and economically acceptable
  • 26. • IEC 71 covers “ Insulation Co-ordination” • IEC -71- Part-I definition, principles • IEC 71- Part – II Guidance for selection of rules (i) electric strength of the plant, (ii) electric strength of LAs or protective spark gaps IEC 71-3 • Phase to phase insulation co-ordination • Complimentary to part I & II • Standard phase to phase insulation level for voltages up to and above 300 kV • Voltage stresses In service and clearances in air
  • 27. Data required: 2. Field data on lightning induced and switching surges appearing on the system 3. Establishing insulation strength of various insulating components of the system through lab tests
  • 28. Causes of over voltage: • Phase to earth faults ( it is assumed that resulting temporary voltages will not exceed –1.4 Pu for solidly earthed networks –1.7 Pu for resistance earthed networks –2.0 Pu for reactance earthed networks • Load rejection (supplying capacitive current through a large inductive reactance ex. A smaller generator connected to a long cable or over head line) • Ferro resonance ( inter change of stored energy for series or parallel combination of inductive and capacitive reactance)
  • 29. Causes of over voltage: contd. • Ferranti effect: (receiving end voltage greater than sending end voltage under no load or light load conditions) • By care full design and natural earthing sustained over voltages involving resonance and arcing ground faults are eliminated • Below 145 kV method of earthing will normally determine the level temporary over voltages.
  • 30. Switching surges • They are of short duration and irregular form • Typical switching impulse standard form is the 250/2500 sec. ( time to crest/ time to half value way) • The magnitude of internally operated switching surges is related to the system operating voltage • In a system where CBS are not subjected to multi re striking the switching surges will rarely exceed 3 pu • 2.5 pu would be typical maximum based on which the discharge duty of LA is assessed • However in systems above 300 kV, it may be necessary to suppress maximum switching surges to 2 pu or less by the installation of a shunt reactor and/or closing resistors on the circuit breakers
  • 31. Resonance effects • For voltage level below 300 kV. Resonance effects occur i. When switching transformer ii. When switching cable and overhead line combination iii. Between lumped capacitive and reactive elements and over head lines iv. Charging long lines without shunt reactor compensation
  • 32. Resonance effects-- contd • Ferro resonance encountered on a transformer feeder greater than 5 to 10 Km in length • When one feeder/transformer on a double circuit is switched out but parallel feeder remains energized, the dead circuit draws energy by captive coupling from the parallel line circuit which resonates with transformer impedance at a sub harmonic frequency • (operation procedure such as opening the line isolator at the transformer end on the disconnected circuit will eliminate the problem)
  • 33. Mode of action of flash over on a line • A lightning flash can impress over voltage on a over head line by a) Induction when it discharges to earth close to line b) By direct contact on the line either to the earthed structure or to the phase conductor
  • 34. Induced Voltage Surge – A close flash to ground up to about 14 m away can induce a voltage rise on phase conductors – The highest amplitude normally associated is in the region of 200 kV – Significant in case of low voltage lines – At 11 kV estimated that it accounts for some 90% of all faults – Little significance on lines of 275 kV and above
  • 35. Direct stroke • A direct stroke can be to the earthed tower top or on phase conductor • Stroke on earthed lower top, for transmission of shielded design, is innocuous • Raise in potential caused by passage of current through tower impedance to earth will be less than with stand strength of line
  • 36. Direct stroke—contd. • However the rise in potential can be severe and exceed with stand capability, if – Tower footing resistance is high – Rate of rise of current exceeds a certain level • Flashover may occur • Through the system voltage, losses is the frequency of flash over
  • 37. Direct stroke—contd. • Direct stroke on phase conductor • May occur if there is a shielding failure i.e. stroke avoids earth wire and lands on line conductor. • Discharge current flows equally in both directions. • Impedance to earth is half the surge impedance (Z0) of the conductor. IN a 400 kV line Z0 = 175 ohms • Voltage rise is sufficient to cause failure of line insulation • Minimum critical current for flash over Ic = 2 V I0 Z0 VI0 = minimum flash over voltage for 1/50 Wave • At flash over the impedance through which the discharge current flows drops abruptly from Z0/2 to impedance of tower, x -arm, tower footing
  • 38. Surge propagation: • Surge waves are propagated at the velocity of light along the conductor • On arrival at substation, equipment there in get stressed. • Rod gaps and surge arrestors provide necessary protection • Waves are subjected to considerable attenuations due to losses both in the conductor (ohmic losses) and corona losses
  • 39. Lightning discharges • Clarification of lightning discharges stroke (A) stroke (B) Stroke (A) : produced by the charged cloud which induces a charge on the stationery objects such as high buildings etc. • Charge distribution causes concentration of potential at the top most point • Electro static stress being great at that point ionization of surrounding atmosphere takes place • Dielectric strength of surrounding air decreases giving an easy path to lightning stroke. • Decrease in dielectric strength of surrounding air takes considerable time
  • 40. Lightning discharges Stroke B: • A, B & C are three clouds with A and C positively charged and B negatively charged • When there is a stroke between (A) and (B) the charge on (C) becomes free and immediately and indiscriminately strikes on any object on the ground • For stroke (B) there is no time lag • Stroke (B) may completely ignore highest building and strike bare ground. • No protection can be arranged against stroke `B` • Stroke `A` can be made safe by channelising the charge through a lightning conductor placed on the top of the building
  • 41. Static induced charges • An over head conductor accumulates statically induced charge when a charged cloud comes above • When the cloud is swept away charge on the conductor is released • The charge travels on either side giving rise to two travelling waves • The earth wire does not prevent such surges
  • 42. Lightning strokes • Over voltage due to lightning strokes surge impedance of the line = Zs Discharge current = Id Over voltage due to direct stroke = Vd = Id x Zs However current travels in both directions over voltage = Vd = Id x Zs 2 when lightning strikes over earth wire or a tower Over voltage = Id x Ze + Lc di dt Ze = impedance of earth wire Lc is the inductance of the line conductor
  • 43. Protection against lightning 1. Protection of transmission lines from direct strokes 2. Protection of power stations and substations from direct strokes 3. Protection of electrical equipment from traveling waves
  • 44. Protection of transmission lines Against the direct strokes : • Most harmful • Effective protection required shielding to prevent lightning from striking the electrical conductors. • There shall be adequate drain facilities so that the charge can be grounded without affecting Insulators or line conductors.
  • 45. Design of transmission line against lightning • Design shall consists of (a) General wire of adequate mechanical strength to provide shielding for line conductor. They shall also be non –corrosive Resistance of ground wire shall be low for better protection against direct stroke. (b) Adequate clearance between 1. Line conductor and tower 2. Line conductor and earth 3. Clearance between line conductor and ground wire all through the span including mid Span or point of lowest sag. (c) Tower footing resistance shall be low (d) Angle of protection (shielding angle) angle between the normal passing through the ground wire and line joining the supported center points of outer conductor and ground wire. It shall be 30° for 132 & 220 kV lines 20 ° for 400 kV lines
  • 46. Effect of number of earth wires • In the absence of a ground wire: • When there is a charge cloud over a transmission line without any ground wire • There will be two capacitances (1) Between cloud and conductor C2 (2) Between conductor and earth C1 Induced voltage on the line V L1 = C1 x Ec C1+C2 • When ground wire is present it increases capacitance between conductor and earth i.e. C1 Decreases induced voltage on the line. • It is observed that presence of a ground wire reduces induced voltage on line to half. • For two ground wires the induced voltage comes down to one third • Presence of two ground wires also provides better shielding
  • 47. Earth wires • Disadvantages with ground wire: (a) higher line cost (b) Probable direct shorting between line conductor and ground wire when the later gets cut In 400kV system transmission line towers will have twu earth wires.
  • 48. Alternative method of line protection • Even after providing ground and reducing the likely induced voltages, harmful voltages can still develop • Lightning arrestors act as additional protective devisees by by-passing the surges to ground • Protector tube is a fiber tube with electrode at earth end. • Fitted directly below the conductor • The arc type electrode on the top of the tube forms a series gap with conductor
  • 49. Alternative method of line protection • The lower electrode is solidly grounded • In case of surge on the conductor, an arc develops between conductor and top electrode of the tube. • Arc shifts within the tube and vaporises some of the fiber of tube wall to emit gases which will quench the arc • This tube successfully prevents re-striking • The break down voltage of tube shall be less than flash over voltage of the insulation.
  • 50. Protection against traveling waves The traveling waves cause the following damages: i. High peak voltage of surge may cause flash over in the internal winding or external flashover between the terminals of the equipment. ii. steep wave front may cause internal flash over between turns of the transformer iii. Steep wave front resulting into resonance and high voltage may cause internal or external flash over causing building up of oscillations in the equipment • Protective equipment : LAs and Surge diverters • They are connected between line and earth
  • 51. Action of the Surge diverter • A traveling wave reaches surge diverter and attains a prefixed voltage • A spark is formed across the gap • The diversion provides a low impedance path to earth • The surge impedance of the line limits the amplitude of the current flowing to earth to prevent break down of insulation • Important aspect is that the surge diverter shall provide low impedance path to earth only when traveling surge reaches the surge diverters
  • 52. Action of the Surge diverter • It shall absorb any current during normal operation for over voltage surges. • It means that it shall not function at power frequencies but function only when abnormal frequencies are applied • When there is a discharge through them they shall be capable of carrying the discharge current for some time interval. • After the over voltage discharge it must be capable interrupting normal frequency current from flowing to earth as soon as the voltage reaches below the break down value
  • 53. Switching over voltage protection in a substation • Operation of breakers causes transient over voltages • Over voltage value varying between 1.1 Pu to 6 Pu based on switching duty and the type of circuit breaker • Over voltage occurs mainly due to exchange of energy between system inductance ½ LI2 and system capacitance ½ CV2 • Over voltage occurs during the opening of circuits and closing of long EHV lines • Most severe over voltages occurs during the closing unloaded transmission line • Preventive measure – Provision of Pre insertion resistors ( 400 to 800 ohms per phase) • Simultaneous closing of lines at both ends • Using shunt reactors, surge arresters etc.
  • 54. Switching Over voltages in Substations Switching duty of Applications and Phenomena C.B. Remedial Actions Opening of capacitor Switching of shunt Re strike in circuit bank currents, cable capacitor banks used for breakers giving over charging circuits, filter p.f. correction. voltage. banks - Use of re strike free C.B. for capacitor switching duty. EHV lines * Long EHV transmission. Traveling waves * Closing unloaded - Use of pre-closing travel to and fro lines resistors with circuit giving rise to a breakers. Use of lightning switching surge. * Closing charged lines arresters. Use of shunt reactors in transmission * Auto re closing of C.B. lines.
  • 55. Methods of Reducing Switching Over Voltages Switching operation Method to reduce causing over voltage switching over voltage Energising an uncharged High voltage shunt reactors line are connected to line to reduce power frequency over voltages. Elimination of trapped Line shunting after opening charged on the line by means of earthing switch Reduction of current Opening resistors chopping ( Resistance switching with CB) used only with ABCB
  • 56. Methods of Reducing Switching Over Voltages Switching operation Method to reduce causing over voltage switching over voltage Reducing the switching over Single stage pre closing resistor voltages due to closing insertion with CB. Two stage pre closing resistor insertion with CB. Closing resistors in between circuit breaker and shunt reactor Reducing switching over voltages Synchronous switching of three by improved switching sequence poles. Simultaneous operation of circuit breakers at both ends of line, Use of surge arrestors While closing of line While disconnecting reactor
  • 57. Rod gaps or coordinating gaps • They are used on insulators, equipment and bushings • Conducting rods are provided between line terminal and earth terminal with an adjustable gap ( Air insulation) • Rods are of 12mm dia approx. • The gap is adjusted to break down at about 20% below the flash over voltage of the insulation. • Spark over causes dead Short circuit • Voltage of phase with respect to ground falls very low • The rod gaps are no more used consequent to development of surge arrestors.
  • 58. Over-voltage in Network and Remedies Phenomena Causes Effect Remedies Surges Lightning strokes on Line insulation flash -Use of Ground overhead lines or over or puncture. wire substation The traveling wave - Surge Diverters reaches substations. -Earthing of The insulation of towers equipment is -Lightning Masts stressed by impulse surge Switching Breaking inductive circuit, Wave travels from -Use of opening surges the energy stored C.B. to both sides resistors with C.B. inductance gives rise a Transmission line - Use of restrike voltage rise across insulator, stressed. free C.B. capacitor. Terminal apparatus -Use pre-insertion Switching of capacitive, insulation stressed resistors with C.B. line charging currents give rise to a over voltage due to restrike. Closing of EHV lines
  • 59. Over-voltage in Network and Remedies Phenomena Causes Effect Remedies Resonance The fault causing Very high, voltage Filters to resonance between surges occur. eliminate inductance and Insulation failure harmonics capacitance in a part of likely to occur. the circuit Traveling High voltage waves get Reflected waves -Proper waves reflected – on reaching gets superimposed switching a junction or end. for initial wave. sequence. Voltage may rise to several time the normal voltage. Sustained Poor voltage control Failure of -Proper Voltage Power transformers and control frequency Rotating Machines over voltage
  • 60. Protective Devices Against Lightning Over voltages Device Where applied Remarks Rod gaps Across insulator string, -Difficult to coordinate bushing insulators -Create dead short circuit -Cheap Overhead Ground -Above overhead lines -Provide effective Wires (earthed) -Above the substation protection against area direct strokes on line conductors towers sub station equipment Vertical Masts in -- in sub stations -instead of providing substations overhead shielding wires Lightning Masts/Rods - Above tall buildings Protect buildings (earthed) against direct strokes. Angle of Protection œ = 300
  • 61. Protective Devices Against Lightning Over voltages Device Where applied Remarks Surge Arresters -- on incoming lines in -- Diverts over voltage to each substation earth without causing -Near terminals of short circuit Transformers and -Used at every voltage generators level in every sub- -Near motor and station and for each line. generators terminals Surge Absorbers -- near rotating machines -Resistance connected between phase Capacitance and ground Combination absorbs the over voltage surge and reduces steepness of wave
  • 62. Lightning arrester selection • 1. To determine the magnitude of the power frequency phase to ground voltage expected at the proposed arrester location during phase to ground fault, or other abnormal conditions which cause higher voltages to ground than normal. • 2. To make a tentative selection of the power frequency voltage rating of the arrester. This selection may have to be reconsidered after step (6) is completed. • 3. To select the impulse current likely to be discharged through the arrester. • 4. To determine the maximum arrester discharge voltage for the impulse current and type of arrester selected. • 5. To establish the full-wave impulse voltage withstand level of the equipment to be protected. • 6. To make certain that the maximum arrester discharge voltage is below the full wave impulse, withstand level of the equipment insulation to be protected, by adequate margin. • 7. To establish the separation limit between the arrester and the equipment to be protected.
  • 63. Types of Earthing • For purpose of selection of voltage rating of a LA three types of earthing are considered (I) Effective earthed system: a system is effectively earthed if under any fault condition the line to earth voltages of healthy phases do not exceed 80 % of the system line to line voltage • If in a system all transformers have star connected winding with neutrally solidly earthed then the system is effectively earthed • However if only few transformers are earthed like that, it is not effectively earthed system
  • 64. Types of Earthing - conted. (II) Non effectively earthed system: a) if the line to earth voltage in healthy phases in case of a fault exceed 80% of the line to line voltage but does not exceed 100% of it, the system is called non effectively earthed system b) System with few solidly earthed neutrals c) Systems with neutral Earthed through resistors or reactors of low ohmic value or arc suppression coil (III) Isolated or un earthed neutral systems :- system neutrals are not earthed. Line to earth voltage of healthy phases exceed 100% of the line to line voltage.
  • 65. Selection of lightening arrestors • Tentative selection of arrestor Voltage: • Arrestor Voltage rating shall not be less than product of system highest voltage x co-efficient of earthing • Co-efficient of earthing : – Effectively earthed system – 80% – Non effectively earthed system - 100 % and isolated earth system
  • 66. Selection of lightening arrestors • In a 220 kV effectively earthed system – Highest system voltage = 245 kV – Co-efficient of earthing = 80% – Arrestor voltage rating >= 245x0.8 = 196 kV – As per IS 3070 (part –I) 1965 the rating is 198 kV • By going for a higher voltage rating for a surge arrestor, the degree of protection for equipment gets reduced.
  • 67. Selection of arrestor discharge current • This can be calculated from (a) Spark over voltage of transmission line insulation (b) Surge impedance of the line (c) Residual discharge voltage of LA Ia = 2E- Ea Z Ia = Arrestor discharge current E = Magnitude of incoming surge voltage Ea = Residual discharge voltage of an arrestor Z = Surge impedance of the line
  • 68. Selection of arrestor discharge current • In a 220 kV system using 11 insulators Transmission line will not permit a traveling wave of a value more than 1025 kVp • As per IS 3010 (Part 1) -1965 the residual voltages of LA at a discharge current of 10kA is 649 kV. • Considering the surge impedance as 450 ohms • Maximum value of discharge current of LA = 2(1025000)-649000 = 3100 Amps 450 • The LAs normally in 200 kV system have a discharge current rating of 10 kA.
  • 69. Selection of arrestor discharge Voltage • Most important characteristic of LA determining the protection level being offered • The arrestor discharge voltage shall be less than BIL of equipment for effective protection • Discharge voltage depends on (I) discharge current (II) rate of rise of current applied (III) Wave shape of current applied • Discharge voltage of LA increases with discharge current. But increase is much restricted due to non –linear resistance property. • Increase in discharge from 5 kA to 20 kA produces only 25% rise in discharge voltage. • Increase in rate of current from 1000 to 5000 Amps per micro second increases discharge voltage by only 35%.
  • 70. Protective margin of LA • Protective margin of LA = BIL of the equipment--- maximum discharge voltage of LA • While determining protection level offered by a LA 10% allowances towards drop in lead length and manufacturing tolerance shall be allowed. • Protective margin shall be 20% of the BIL of the equipment when closely located • In a 220 kV system Discharge voltage of LA = 649 kV Allowing 10 % margin protection level = 713 kV BIL of equipment = 900 kVp Protection margin = 900-713 = 187 kVp There is more than 20 % of the BIL of 180 kV
  • 71. Protective margin of LA-Continue. • In American system Average discharge voltage x 1.25 +40 kV = BIL protected When adequate margin is not available LAs with lower rating shall be chosen taking risk.
  • 72. Insulation Co-ordination Scheme • For 220 KV system. • L.A. Voltage rating=system highest voltage x co-efficient of earthing =245x.8=196Kv. • Selecting standard rating from Table 12.1 column 1,L.A. voltage rating=198 Kv • Discharge current rating= 10KA (assumed) • Residual voltage, from column 3 of table 12.1,=649Kv (peak) • Protection level of the L.A. =649x1.1=714Kv • For a margin of 20% between the B.I.L. and the protection level of L.A., the B.I.L. should be =714x1.2=857Kv. • Choose standard B.I.L. Table 14.3 (b) Col. 4=900 Kv, • The corresponding power freq. I minute test voltage =395kv • Switching surge flashover voltage =220 x6.5=825kv • √3 • Check it is less than B.I.L. of 900kv. • Power frequency over voltage=220x3=228kv rms √3 • This is less than 395kv. • B.I.L. of CBs, instrument transformer, disconnect switches etc,.=900x1.1=990kv. • Choose standard B.I.L.=1175kv.
  • 73. The L.A. voltage rating Rated system Highest system Arrester rating voltage KV voltage KV in KV 132 145 120/132 220 245 198/216 400 420 336
  • 74. Establishment of Separation Limit • When arrestor are to be located away from equipment. • A traveling wave coming into the station to location to the discharge voltage of the arrestor. • Proximity to transformer or breakers. - Transformer is most expensive price. - Repair to transformer is costly and with higher revenue loss. - Transformers are always at the end of a circuit where voltage regulation. . For circuit breakers and disconnecting switches flash over distance between terminals when in open position in grater than between terminals and ground. . Surge in excess to insulation strength will flash over to ground with out damaging the equipment. . At best there can be only outage . . By reducing BIL of transformer savings in the cost of insulation can be obtained. . Not possible incase of CB or disconnections switches. . Hence a set of LAS shall be closer to transformers.
  • 75. Location of Lightning Arresters: • The electrical circuit length between L.A. and the transformer bushing terminal (inclusive of lead length in metes for effectively earthed) should not exceed the limits given below: Rated syst. BIL KV Max. voltage KV Peak distance 132kV 550 35.0 650 45.0 220kV 900/1050 Closer 400kV 1425/1550 to Trans.