ME 6404 – THERMAL ENGINEERING
UNIT – V – REFRIGERATION
Presented by
A. SANKARA NARAYANA MURTHY,
Assistant Professor,
Dept. of Mechanical Engineering,
Kamaraj College of Engineeriechnology,
Virudhunagar
REFRIGERATOR
• The transfer of heat from a low-temperature
region to a high-temperature one requires
special devices called refrigerators.
• The objective of a refrigerator is to remove
heat (QL) from the cold medium; the objective
of a heat pump is to supply heat (QH) to a
warm medium.
HEAT PUMP
• Heat pump supplies heat to the higher-temperature
region from lower temperature by giving work as
input.
• Heat pumps and refrigerators are essentially the
same devices; they differ in their objectives only.
for fixed values of QL and QH
TYPES OF REFRIGERATION
SYSTEM
• Vapour Compression Refrigeration
(VCR): uses mechanical energy
• Vapour Absorption Refrigeration (VAR):
uses thermal energy
• Steam Jet Refrigeration system
• Liquid N2 bath
• Ice bunk cooling system
• Etc…
THE PRESSURE-ENTHALPY DIAGRAM

The process of the vapor
compression refrigeration cycle may
conveniently be displayed on a
diagram having pressure and specific
enthalpy as coordinates.

Below the critical point (CP) the
saturated liquid line (SL) and
saturated vapor line (SV) enclose a
two-phase (wet) region between them.

To the left of the saturated liquid line
lie states which have lower
temperature than the saturation
temperature at a given pressure.

These are states of sub-cooled liquid.
THE PRESSURE-ENTHALPY DIAGRAM

To the right of the saturated vapor line lie states which have higher
temperature than the saturation temperature at a given pressure.

These are states of superheated vapor.

The area to the left of the liquid line is called the subcooled liquid region,
and the area to the right of the vapor line is called the superheated vapor
region.

Within the two-phase region the horizontal lines of constant pressure are
also lines of constant temperature

In the superheat region the lines of constant temperature leave the
saturation line as indicated.

As the pressure diminishes in the superheat region, the lines of constant
temperature tend to become lines of constant enthalpy, i.e. vertical on
the diagram, indicating that the vapor is beginning to behave like an ideal
gas with its enthalpy independent of pressure.

Lines of constant specific entropy and lines of constant specific volume ,
are shown in the superheat region.
REFRIGERANT IN VAPOR
COMPRESSION REFRIGERATION

The working substance in a refrigeration system is called the refrigerant.

There are lots of refrigerants, including gas, liquid and solid refrigerants.

There are many natural and artificial substances have been used in mechanical
driven and thermal driven vapor compression refrigeration systems.
 In lithium bromide vapor absorption refrigeration system, H2O is used as a
refrigerant and LiBr is an absorbent ; in NH3 vapor absorption refrigeration
system, NH3 is a refrigerant; is an absorbent.
 Water H2O is also used as a refrigerant both in vapor adsorption and in vapor
jet refrigeration cycles. In mechanical driven vapor compression refrigeration,
NH3, CO2, chlorofluorocarbons (CFCs), hydro chloro fluoro carbons (HCFCs),
hydro fluoro carbons (HFCs), azeotropic and zeotropic mixtures, inorganic
compounds, hydrocarbons, and others are used as refrigerants.
REFRIGERATION CHARACTERISTICS
OF REFRIGERANTS

The pressure- enthalpy diagram
is the usual graphic means of
presenting refrigerant properties
and its cycles.

A typical vapor compression
refrigeration cycle has been
shown in figure
REFRIGERANT PROPERTIES
1. Appropriate temperature and pressure characteristics

The saturated pressure with temperature is an important property
of refrigerant.
1) It is desired for the pressure at evaporating temperature to be
above atmospheric, to avoid inward leakage of air.
2)The pressure at the corresponding condensing temperature
should not be excessive, so that extra strength high-side equipment
is not required.
3) Low compression ratio is desirable, because the degree of
complication and difficulty of a compressor increases directly with
the compression ratio.
4) Discharge temperature of compressor should not be excessive,
to avoid problems as breakdown or dilution of the lubricating oil,
decomposition of the refrigerant, or formation of contaminants
such as sludge or acids. All of these can lead to compressor damage.
REFRIGERANT PROPERTIES
2. High latent heat of vaporization and low specific
volume of the refrigerant at the entry to compressor

A high latent heat of vaporization and a low specific volume of
the refrigerant at entry to the compressor are desirable for
smaller equipment and pipe size at given cooling capacity.

High latent heat means there is a high refrigeration effect.

For example, R11 has a much larger specific volume of suction
vapor of compressor than those of refrigerants of R22, R502 and
R717.

That means it requires a higher volumetric flow rate to produce
the same amount of cooling capacity.

Therefore, R11 is usually used with centrifugal compressors
because they are good at handing large volumetric flow rate.
REFRIGERANT PROPERTIES
3. Lower compression work

In order to get high COP, both high refrigeration effect and
low compression work must be considered in combination.
 For example, R717 (ammonia ) has a refrigerating effect q1 much
larger than other refrigerants, but its compression work w is
also high, as a result, COP of ammonia has the same order of
magnitude as that of the other refrigerants.
REFRIGERANT PROPERTIES
4. Some Important Physical/Chemical Properties of
Refrigerants

Any substance which has appropriate thermal properties can be
used as a refrigerant, but in practice the choice is limited by
many factors such as toxicity, flammability, chemical stability,
and the behaviors of the refrigerant with lubricating oil, water
and construction materials.
VAPOR-COMPRESSION REFRIGERATION
(VCR) CYCLE
The vapor-compression refrigeration
cycle has four components:
1. Evaporator,
2. Compressor,
3. Condenser, and
4. Expansion (or throttle) valve

In a basic vapor-compression
refrigeration cycle, the refrigerant
enters the compressor as a saturated
vapor and is cooled to the saturated
liquid state in the condenser.

It is then throttled to the evaporator
pressure and vaporizes as it absorbs
heat from the refrigerated space
VCR - Cycle
VCR - Cycle

The principal work and heat transfer that
occurs in the system are shown below,
these quantities being taken as positive in
the directions indicated by the arrows in
the Fig. 6.4.

In the analyses, each component is first
separately considered.

The evaporator, in which the desired
refrigeration effect is achieved, will be
considered first.

Considering a control volume enclosing
the refrigerant side of the evaporator,
conservation of mass and energy applied
to this control volume together give the
rate of heat transfer per unit mass of
refrigerant flow in the evaporator as:
1 4
e
e
Q
q h h
m
= = −
VCR - Cycle

Next consider the compressor.

It is usually adequate to assume that there is no heat transfer to or
from the compressor.

Conservation of mass and energy rate applied to a control volume
enclosing the compressor then give:

For a control volume enclosing the refrigerant side of the condenser,
the rate of heat transfer from the refrigerant per unit mass of
refrigerant is:
2 1
i
i
W
w h h
m
= = −
2 3
c
c
Q
q h h
m
= = −
VCR - Cycle

Finally, the refrigerant at state 3 enters the expansion valve and
expands to the evaporator pressure.

This process is usually modeled as a throttling process in which there
is no heat transfer, i.e., for which

In the vapor-compression system, the net power input is equal to the
compressor power, the expansion valve involving no power input or
output.

Using the quantities and expressions introduced above, the coefficient of
performance, COP, of the vapor- compression refrigeration system is
given by:
34 hh =
1 4
2 1
/
/
e e
i i
q Q m h h
COP
w W m h h
−
= = =
−
LIQUID SUBCOOING

In practice some degree of subcooling
may be acquired, and the point 3 moves
to the left of the saturated liquid on the
pressure-enthalpy diagram, as shown in
Figure.

Subcooling is the process of cooling
condensed gas beyond what is required
for the condensation process.

Subcooling is sensible heat and is
measured in degrees.

If it was possible to further cool down the
liquid to some lower value, say upto 3’,
then the net refrigeration effect will be
increased by
1 4' 1 4 4 4' 3 3'( ) ( )h h h h h h h h− − − = − = −
Subcooling of the liquid and superheating
of the vapor
LIQUID SUBCOOING

The volume refrigerating effect is of course increased by subcooling in
the same way as the specific refrigerating effect.

Since the specific work of compression remains the same, the
coefficient of performance is improved.

The subcooling may be achieved by any of the following methods:

(i) By passing the liquid refrigerant from condenser through a heat
exchanger through which the cold vapor at suction from the
evaporator is allowed to flow in the reversed direction.

(ii) By making use of enough quantity of cooling water so that the
liquid refrigerant is further cooled below the temperature of
saturation.
VAPOR SUPERHEATING

If the vapor at the compressor entry is in the
superheated state 1’, which is produced due to
higher heat absorption in the evaporator, then
the refrigerating effect is increased as

The specific work of reversible adiabatic
compression is increased by superheat. This is
indicated in Figure by the decreased gradient of
the line of constant entropy though point 1’ in
the superheat region compared with the
gradient of the line though point 1.

Although the specific work of reversible
adiabatic compression is increased by superheat,
so is the specific refrigerating effect, however,
their ratio, COP, may increase, decrease or
remain unchanged depending upon the range of
pressure of the cycle.
Subcooling of the liquid and
superheating of the vapor
1' 4 1 4 1' 1( ) ( )h h h h h h− − − = −
VAPOR SUPERHEATING

Here, it is necessary to consider the effect of heat transfer to the
refrigerant vapor in the suction pipe from the evaporator to the
compressor.

The suction line usually passes though warm surroundings, then heat
transfer to the vapor can take place, which will cause the temperature
increase.

This will cause a part of refrigerating capacity loss to refrigerate
engine room, so it will be called “useless refrigerant capacity”.

And the capacity used to refrigerate things which need refrigeration
will be called “useful refrigerant capacity”.

In practice, useless refrigerant capacity loss should be decreased, and
should increase useful capacity as possible.
CASCADE REFRIGERATION SYSTEMS
• Very low temperatures can be achieved by operating two or more vapor-
compression systems in series, called cascading. The COP of a refrigeration
system also increases as a result of cascading.
MULTISTAGE COMPRESSION
REFRIGERATION SYSTEMS
•When the fluid used throughout the cascade refrigeration system is the same, the heat
exchanger between the stages can be replaced by a mixing chamber (called a flash
chamber) since it has better heat transfer characteristics.
VAPOUR ABSORPTION
REFRIGERATION (VAR) SYSTEM
• When there is a source of
inexpensive thermal energy at a
temperature of 100 to 200°C is
absorption refrigeration.
• Some examples include
geothermal energy, solar energy,
and waste heat from cogeneration
or process steam plants, and even
natural gas when it is at a
relatively low price.
• Vapour Absorption refrigeration
(VAR) systems involve the
absorption of a refrigerant by a
transport medium.
• The most widely used system is
the ammonia–water system, where
ammonia (NH3) serves as the
refrigerant and water (H2O) as the
transport medium.
VAR SYSTEM
• Other systems include water–lithium bromide and water–lithium chloride
systems, where water serves as the refrigerant. These systems are limited to
applications such as A-C where the minimum temperature is above the
freezing point of water.
• Compared with vapor-compression systems, ARS have one major advantage: A
liquid is compressed instead of a vapor and as a result the work input is very
small (on the order of one percent of the heat supplied to the generator) and
often neglected in the cycle analysis.
• ARS are often classified as heat-driven systems.
• ARS are much more expensive than the vapor-compression refrigeration
systems. They are more complex and occupy more space, they are much less
efficient thus requiring much larger cooling towers to reject the waste heat,
and they are more difficult to service since they are less common.
• Therefore, ARS should be considered only when the unit cost of thermal
energy is low and is projected to remain low relative to electricity.
• ARS are primarily used in large commercial and industrial installations.
VAR SYSTEM
VAR SYSTEM
The COP of actual absorption refrigeration
systems is usually less than 1.
Air-conditioning systems based on
absorption refrigeration, called absorption
chillers, perform best when the heat source
can supply heat at a high temperature with
little temperature drop.
VCR CYCLE COMPONENTS
• Refrigerant
• Evaporator/Chiller
• Compressor
• Condenser
• Receiver
• Thermostatic expansion valve
(TXV)
REFRIGERANT
• Desirable properties:
– High latent heat of vaporization - max cooling
– Non-toxicity (no health hazard)
– Desirable saturation temp (for operating pressure)
– Chemical stability (non-flammable/non-explosive)
– Ease of leak detection
– Low cost
– Readily available
29
LOW SIDE OPERATION
• Refrigerants have low boiling points
• When liquid boils, it absorbs large amounts of heat
• Amount of heat absorbed in evaporator is proportional to
amount of refrigerant boiled
• High side Components
• Expansion device
• Evaporator
• Accumulator (if equipped)
30
EXPANSION DEVICES
• The expansion device separates the high side from the low
side and provides a restriction for the compressor to pump
against.
• There are two styles of expansion devices:
• The TXV can open or close to change flow. It is controlled
by the superheat spring, thermal bulb that senses
evaporator outlet temperature, and evaporator pressure
• Most OTs have a fixed diameter orifice
A TXV controls the
refrigerant flow from
the high pressure side
to the evaporator. A
receiver dryer is
mounted in the liquid
line of all TXV systems.
TXV SYSTEM
An OT controls the
refrigerant flow from the high
pressure side to the
evaporator. An accumulator is
mounted in the suction line of
all OT systems.
OT SYSTEM
33
THERMAL EXPANSION VALVES,
TXVs
•The three major types of expansion valves:
•Internally balanced TXVs are the most
common.
•Externally balanced TXVs are used on some
larger evaporators.
•Block valves route the refrigerant leaving
the evaporator past the thermal sensing
diaphragm so a thermal bulb is not needed.
Internally
Balanced
Externally
Balanced
Block Valve
34
THERMAL EXPANSION VALVES,
TXVS
• Variable valve that can change size of opening in response to
system load
• Opens or closes depending on evaporator pressure and
temperature
35
EVAPORATOR OPERATION
Hot, liquid refrigerant flows through
the expansion device in the low side to
become a fine mist.
Refrigerant boils or evaporates to
become a gas inside the evaporator.
The boiling refrigerant absorbs heat
from the air during this change of state.
EVAPORATOR/CHILLER
• Located in space to be refrigerated
• Cooling coil acts as an indirect heat exchanger
• Absorbs heat from surroundings and vaporizes
– Latent Heat of Vaporization
– Sensible Heat of surroundings
• Slightly superheated (10°F) ensures no liquid carryover into compressor
37
ACCUMULATORS
Accumulators are used in the suction line of all OT
systems.
The accumulator:
•separates liquid refrigerant so only gas flows to
the compressor.
•Allows oil in the bottom of the accumulator to
return to the compressor.
•provides storage for a refrigerant reserve.
•contains the desiccant bag for water removal.
•provides a place to mount low pressure switches
and sensors.
38
HIGH SIDE OPERATION
• Takes low pressure vapor from evaporator and returns high
pressure liquid to expansion device
• Must increase vapor temperature above ambient temperature for
heat transfer to occur resulting in change of state from vapor to
liquid
• High side Components
• High begins at compressor and ends at expansion device
• Compressor
• Condenser
• Receiver-drier (if equipped)
39
COMPRESSORS
There is a large variety of compressors.
Some of variations are:
The compressor manufacturer
Piston, vane, or scroll type
The piston and cylinder arrangement
How the compressor is mounted
Style and position of ports
Type and number of drive belts
Compressor displacement
Fixed or variable displacement
40
SCOTCH YOKE COMPRESSORS
A Scotch yoke compressor has two pairs of
pistons that are driven by a slider block on
the crankshaft. The pistons are connected
by a yoke.
Pistons Yoke
Discharge Reed
Suction Reed
41
CONDENSER OPERATION
Hot, high pressure gas is pumped from the compressor to enter the condenser.
The gas gives up its
heat to the air passing through the condenser. Removing heat from the hot gas causes it
to change state and become liquid.
42
CONDENSER TYPES
Condensers A and C are round
tube, serpentine condensers.
Condenser B is an oval/flat tube,
serpentine condenser.
Condenser D is an oval/flat tube,
parallel flow condenser.
Flat tube condensers are more
efficient.
43
SERPENTINE CONDENSER
Refrigerant flows from the
upper inlet to the bottom
outlet through two tubes.
These tubes wind back and
forth though the condenser.
44
PARALLEL FLOW CONDENSER
Refrigerant flows from the upper inlet to the
bottom outlet through groups of parallel
tubes. Some carry refrigerant from the right
to the left, and others move it back to the
right side.
45
HEAT EXCHANGERS
 Condensers have to move heat from the refrigerant to the air.
 Evaporators must move heat from air to the refrigerant.
 Both require a lot of contact area for both air and refrigerant.
 Both require free movement of air and refrigerant.
46
RECEIVER DRYERS
A receiver dryer is mounted in the liquid line of a
TXV system. It is used to:
•to store a reserve of refrigerant.
•hold the desiccant bag that removes water from
the refrigerant.
•filter the refrigerant and remove debris particles.
•provide a sight glass so refrigerant flow can be
observed.
•provide a location for switch mounting.
Barb
Connections,
Note Sight
Glass
Male Flare
Connections
Male O-ring
Connections,
Note Switch
PROBLEM-1
An ideal vapor-compression refrigeration cycle operates at steady state
with Refrigerant 134a as the working fluid. Saturated vapor enters the
compressor at 2 bar, and saturated liquid exits the condenser at 8 bar.
The mass flow rate of refrigerant is 7 kg/min. Determine
a)the compressor power, in kW
b)the refrigerating capacity, in tons
c)the coefficient of performance
Analyzing vapor-Compression
Refrigeration Systems
Ideal Refrigeration Cycle
An ideal cycle has no irreversibilities within the evaporator and
condenser, and there are no frictional pressure drops. Compression
is isentropic. The T-s diagram is shown on the next slide.
Process 1-2s: Isentropic compression of the refrigerant;
Process 2s-3: Heat transfer from refrigerant to outside air, at
constant pressure;
Process 3-4: Throttling process to a two-phase mixture at lower
pressure;
Process 4-1: Heat transfer to the refrigerant as it flows at constant
pressure through the evaporator;
Analyzing vapor-Compression
Refrigeration Systems
As the refrigerant passes through the evaporator, the heat
transfer per unit mass of refrigerant flowing is:
A ton of refrigeration is equal to 200 Btu/min or 211 kJ/min.
Work done by compressor per unit mass flow of refrigerant is
flowmasstrefrigeranismhh
m
Qin



);( 41 −=
);( 12 hh
m
Wc
−=


Analyzing vapor-Compression
Refrigeration Systems
Heat rejected by the refrigerant:
Expansion valve:
Coefficient of performance:
);( 32 hh
m
Qout
−=


34 hh =
;
)(
)(
12
41
hh
hh
m
W
m
Q
c
in
−
−
==




β
SOLUTION
Let us first get the properties at each state in the cycle.
State 1: p1 = 2 bar, sat vapor. h1 = 241.30 kJ/kg, s1 = 0.9253
kJ/kg.K
State 2: p2 = 8 bar, s2 = s1, h2 = 269.92 kJ/kg
State 3: p3 = 8 bar, sat. liquid, h3 = 93.42 kJ/kg
State 4: Throttling process, h4 = h3 = 93.42 kJ/kg
a)The compressor power is:
CW m h h kg s kJ kg kW( ) ( / )( . . ) / .= − = − =2 1
7
269 92 241 30 3 34
60
 
Solution
b) The refrigerating capacity is
c)The coefficient of performance is
inQ m h h kg kJ kg tons kJ
tons
( ) ( /min)( . . ) / / / /min
.
= − = −
=
1 4 7 241 30 93 42 211
4 91
 
h h
h h
( ) ( . . )
.
( ) ( . . )
− −
β = = =
− −
1 4
2 1
241 30 93 42
5 17
269 92 241 30
• Problem-2
• A refrigerator uses refrigerant-134a as the working fluid and
operates on an ideal vapor-compression refrigeration cycle
between 0.12 and 0.7 MPa. The mass flow rate of the refrigerant
is 0.05 kg/s. Show the cycle on a T-s diagram with respect to
saturation lines. Determine:
• a) the rate of heat removal from the refrigerated space,
• b) the power input to the compressor,
• c) the rate of heat rejection to the environment, and
• d) the coefficient of performance.
Solution
Answers: (a) 7.41 kW, 1.83 kW, (b) 9.23 kW, (c)
4.06
Problem-3
Consider an ideal refrigeration cycle which uses R-12 as
the working fluid. The temperature of the refrigerant in
the evaporator is –20°C and in the condenser it is 40°C.
The refrigerant is circulated at the rate of 0.03kg/s.
Determine the coefficient of performance and the
capacity of the plant in rate of refrigeration.
For each control volume analyzed, the thermodynamic
model is the R-12 tables. Each process is SSSF with no
change in kinetic or potential energy.
Control volume: Compressor.
Inlet state: T1 known, saturated vapor; state fixed.
Exit state: P2 known(saturation pressure at T3).
At T3=40°C
2 1
2 1
cw h h
s s
= −
=
2
1
1 2
2
2
2 1
0.9607
178.61 /
0.7082
50.8
211.38 /
32.77 /
g
o
c
P P MPa
h kJ kg
s s
T C
h kJ kg
w h h kJ kg
= =
=
= =
=
=
= − =
Control volume: Expansion valve.
Inlet state: T3 known, saturated liquid; state fixed.
Exit state: T4 known.
Control volume: Evaporator.
Inlet state: State 4 known.
Exit state: State 1 known.
3 4 74.53 /h h kJ kg= =
1 4 104.08 /
3.18
3.12
L
L
c
q h h kJ kg
q
w
Capacity kW
β
= − =
= =
=
• Problem-3
Consider a 300 kJ/min refrigeration system that operates on an ideal
vapor-compression refrigeration cycle with refrigerant-134a as the
working fluid. The refrigerant enters the compressor as saturated
vapor at 140 kPa and is compressed to 800 kPa. Show the cycle on a T-
s diagram with respect to saturation lines, and determine the:
a) quality of the refrigerant at evaporator inlet,
b) coefficient of performance, and
c) power input to the compressor.

Más contenido relacionado

La actualidad más candente

Aircraft refrigeration system (air cooling system)
Aircraft refrigeration system (air cooling system)Aircraft refrigeration system (air cooling system)
Aircraft refrigeration system (air cooling system)Ripuranjan Singh
 
Air refrigeration systems
Air refrigeration systemsAir refrigeration systems
Air refrigeration systemsSuhail Bhatia
 
Refrigeration and-air-conditioning-notes
Refrigeration and-air-conditioning-notesRefrigeration and-air-conditioning-notes
Refrigeration and-air-conditioning-notesOlumide Daniel
 
Basics of Refrigerartion
Basics of RefrigerartionBasics of Refrigerartion
Basics of RefrigerartionKonal Singh
 
Refrigeration & air conditioning
Refrigeration & air conditioningRefrigeration & air conditioning
Refrigeration & air conditioningNirav Jadav
 
Presentation on Expansion Devices
Presentation on Expansion DevicesPresentation on Expansion Devices
Presentation on Expansion DevicesVivek Yadav
 
Refrigeration system (1)
Refrigeration system (1)Refrigeration system (1)
Refrigeration system (1)Prakash Kumawat
 
Psychrometric chart and process
Psychrometric chart and processPsychrometric chart and process
Psychrometric chart and processSANDEEPPS24
 
Refrigeration and Air conditioning
Refrigeration and Air conditioningRefrigeration and Air conditioning
Refrigeration and Air conditioningSLA1987
 
Refrigeration cycle
Refrigeration cycleRefrigeration cycle
Refrigeration cyclezubi0585
 
Psychrometry and air conditioning
Psychrometry and air conditioningPsychrometry and air conditioning
Psychrometry and air conditioningnitin184shukla
 
Refrigerant condenser and its types
Refrigerant condenser and its typesRefrigerant condenser and its types
Refrigerant condenser and its typesvaibhav tailor
 
Vapour compression refrigeration system
Vapour compression refrigeration systemVapour compression refrigeration system
Vapour compression refrigeration systemnaphis ahamad
 
Applications of Refrigeration and Air Conditioning & Refrigerants
Applications of Refrigeration and Air Conditioning & RefrigerantsApplications of Refrigeration and Air Conditioning & Refrigerants
Applications of Refrigeration and Air Conditioning & RefrigerantsNITIN AHER
 
Aircraft refrigeration system
Aircraft refrigeration systemAircraft refrigeration system
Aircraft refrigeration systemAnkur Sachdeva
 
Presentation on evaporators
Presentation on evaporatorsPresentation on evaporators
Presentation on evaporatorsAnshumaan Tiwari
 

La actualidad más candente (20)

Refrigerant compressors
Refrigerant compressorsRefrigerant compressors
Refrigerant compressors
 
Aircraft refrigeration system (air cooling system)
Aircraft refrigeration system (air cooling system)Aircraft refrigeration system (air cooling system)
Aircraft refrigeration system (air cooling system)
 
Air refrigeration systems
Air refrigeration systemsAir refrigeration systems
Air refrigeration systems
 
Refrigeration and-air-conditioning-notes
Refrigeration and-air-conditioning-notesRefrigeration and-air-conditioning-notes
Refrigeration and-air-conditioning-notes
 
Basics of Refrigerartion
Basics of RefrigerartionBasics of Refrigerartion
Basics of Refrigerartion
 
Refrigeration systems
Refrigeration systemsRefrigeration systems
Refrigeration systems
 
Refrigeration & air conditioning
Refrigeration & air conditioningRefrigeration & air conditioning
Refrigeration & air conditioning
 
Presentation on Expansion Devices
Presentation on Expansion DevicesPresentation on Expansion Devices
Presentation on Expansion Devices
 
Refrigeration system (1)
Refrigeration system (1)Refrigeration system (1)
Refrigeration system (1)
 
Psychrometric chart and process
Psychrometric chart and processPsychrometric chart and process
Psychrometric chart and process
 
Refrigeration and Air conditioning
Refrigeration and Air conditioningRefrigeration and Air conditioning
Refrigeration and Air conditioning
 
Refrigeration cycle
Refrigeration cycleRefrigeration cycle
Refrigeration cycle
 
Secondary refrigerants
Secondary refrigerantsSecondary refrigerants
Secondary refrigerants
 
Psychrometry and air conditioning
Psychrometry and air conditioningPsychrometry and air conditioning
Psychrometry and air conditioning
 
Refrigeration system
Refrigeration systemRefrigeration system
Refrigeration system
 
Refrigerant condenser and its types
Refrigerant condenser and its typesRefrigerant condenser and its types
Refrigerant condenser and its types
 
Vapour compression refrigeration system
Vapour compression refrigeration systemVapour compression refrigeration system
Vapour compression refrigeration system
 
Applications of Refrigeration and Air Conditioning & Refrigerants
Applications of Refrigeration and Air Conditioning & RefrigerantsApplications of Refrigeration and Air Conditioning & Refrigerants
Applications of Refrigeration and Air Conditioning & Refrigerants
 
Aircraft refrigeration system
Aircraft refrigeration systemAircraft refrigeration system
Aircraft refrigeration system
 
Presentation on evaporators
Presentation on evaporatorsPresentation on evaporators
Presentation on evaporators
 

Similar a Refrigeration

R&AC NOTES (2).pdf
R&AC NOTES (2).pdfR&AC NOTES (2).pdf
R&AC NOTES (2).pdfAdugnaGosa1
 
K11019(samant singh)rac
K11019(samant singh)racK11019(samant singh)rac
K11019(samant singh)raccpume
 
7_Refrigeration_Cycle_UNIT_2_REFRIGERATI.pdf
7_Refrigeration_Cycle_UNIT_2_REFRIGERATI.pdf7_Refrigeration_Cycle_UNIT_2_REFRIGERATI.pdf
7_Refrigeration_Cycle_UNIT_2_REFRIGERATI.pdfDr. Ahamed Saleel C
 
7 Refrigeration Cycle UNIT 2 REFRIGERATION CYCLE
7 Refrigeration Cycle UNIT 2 REFRIGERATION CYCLE7 Refrigeration Cycle UNIT 2 REFRIGERATION CYCLE
7 Refrigeration Cycle UNIT 2 REFRIGERATION CYCLEJim Webb
 
Chapter 3 Vapour Compression Refrigeration Systems.pdf
Chapter 3 Vapour Compression Refrigeration Systems.pdfChapter 3 Vapour Compression Refrigeration Systems.pdf
Chapter 3 Vapour Compression Refrigeration Systems.pdfAnupKashyap10
 
VCRS PPT.pptxhdjdhdjskznznbxkxijzjsjskskamms
VCRS PPT.pptxhdjdhdjskznznbxkxijzjsjskskammsVCRS PPT.pptxhdjdhdjskznznbxkxijzjsjskskamms
VCRS PPT.pptxhdjdhdjskznznbxkxijzjsjskskammsPrashantKuwar
 
Refrigeration cycle
Refrigeration cycleRefrigeration cycle
Refrigeration cyclevidya Alex
 
EME Module 3 REFRIGERATION AND AIR CONDITIONING PART-1
EME Module 3 REFRIGERATION AND AIR CONDITIONING  PART-1 EME Module 3 REFRIGERATION AND AIR CONDITIONING  PART-1
EME Module 3 REFRIGERATION AND AIR CONDITIONING PART-1 Rajashekar Matpathi
 
DOC-20231017-WA0003..pptx
DOC-20231017-WA0003..pptxDOC-20231017-WA0003..pptx
DOC-20231017-WA0003..pptxKarthik029CSK
 
LU5 - Refrigeration.pptx
LU5 - Refrigeration.pptxLU5 - Refrigeration.pptx
LU5 - Refrigeration.pptxGeeDeville
 
Basic refrigeration cycle .
Basic refrigeration cycle .Basic refrigeration cycle .
Basic refrigeration cycle .JISHNU U
 
Refrigeration and Heat Pump Systems
Refrigeration and Heat Pump SystemsRefrigeration and Heat Pump Systems
Refrigeration and Heat Pump SystemsSalman Jailani
 
Chapter_11.ppt RAC REFRIGERATOR.ppt
Chapter_11.ppt RAC REFRIGERATOR.pptChapter_11.ppt RAC REFRIGERATOR.ppt
Chapter_11.ppt RAC REFRIGERATOR.pptGeoffreyMichael1
 
Let ref & aircondirtioning
Let  ref & aircondirtioningLet  ref & aircondirtioning
Let ref & aircondirtioningJocelyn Gallegos
 
ch-3 Lecture-2-Refrigeration-Cycles.pptx
ch-3 Lecture-2-Refrigeration-Cycles.pptxch-3 Lecture-2-Refrigeration-Cycles.pptx
ch-3 Lecture-2-Refrigeration-Cycles.pptxabinetadugnaawukew
 

Similar a Refrigeration (20)

Refrigeration
RefrigerationRefrigeration
Refrigeration
 
R&AC NOTES (2).pdf
R&AC NOTES (2).pdfR&AC NOTES (2).pdf
R&AC NOTES (2).pdf
 
K11019(samant singh)rac
K11019(samant singh)racK11019(samant singh)rac
K11019(samant singh)rac
 
7_Refrigeration_Cycle_UNIT_2_REFRIGERATI.pdf
7_Refrigeration_Cycle_UNIT_2_REFRIGERATI.pdf7_Refrigeration_Cycle_UNIT_2_REFRIGERATI.pdf
7_Refrigeration_Cycle_UNIT_2_REFRIGERATI.pdf
 
7 Refrigeration Cycle UNIT 2 REFRIGERATION CYCLE
7 Refrigeration Cycle UNIT 2 REFRIGERATION CYCLE7 Refrigeration Cycle UNIT 2 REFRIGERATION CYCLE
7 Refrigeration Cycle UNIT 2 REFRIGERATION CYCLE
 
Chapter 3 Vapour Compression Refrigeration Systems.pdf
Chapter 3 Vapour Compression Refrigeration Systems.pdfChapter 3 Vapour Compression Refrigeration Systems.pdf
Chapter 3 Vapour Compression Refrigeration Systems.pdf
 
VCRS PPT.pptxhdjdhdjskznznbxkxijzjsjskskamms
VCRS PPT.pptxhdjdhdjskznznbxkxijzjsjskskammsVCRS PPT.pptxhdjdhdjskznznbxkxijzjsjskskamms
VCRS PPT.pptxhdjdhdjskznznbxkxijzjsjskskamms
 
CHAPTER 11.pdf
CHAPTER 11.pdfCHAPTER 11.pdf
CHAPTER 11.pdf
 
Refrigeration cycle
Refrigeration cycleRefrigeration cycle
Refrigeration cycle
 
CH-3.pptx
CH-3.pptxCH-3.pptx
CH-3.pptx
 
Refrigeration Senator Libya
Refrigeration  Senator LibyaRefrigeration  Senator Libya
Refrigeration Senator Libya
 
EME Module 3 REFRIGERATION AND AIR CONDITIONING PART-1
EME Module 3 REFRIGERATION AND AIR CONDITIONING  PART-1 EME Module 3 REFRIGERATION AND AIR CONDITIONING  PART-1
EME Module 3 REFRIGERATION AND AIR CONDITIONING PART-1
 
DOC-20231017-WA0003..pptx
DOC-20231017-WA0003..pptxDOC-20231017-WA0003..pptx
DOC-20231017-WA0003..pptx
 
LU5 - Refrigeration.pptx
LU5 - Refrigeration.pptxLU5 - Refrigeration.pptx
LU5 - Refrigeration.pptx
 
Basic refrigeration cycle .
Basic refrigeration cycle .Basic refrigeration cycle .
Basic refrigeration cycle .
 
Refrigeration and Heat Pump Systems
Refrigeration and Heat Pump SystemsRefrigeration and Heat Pump Systems
Refrigeration and Heat Pump Systems
 
Chapter_11.ppt RAC REFRIGERATOR.ppt
Chapter_11.ppt RAC REFRIGERATOR.pptChapter_11.ppt RAC REFRIGERATOR.ppt
Chapter_11.ppt RAC REFRIGERATOR.ppt
 
Let ref & aircondirtioning
Let  ref & aircondirtioningLet  ref & aircondirtioning
Let ref & aircondirtioning
 
Refrigiration and air conditioning by abhishek singh
Refrigiration and air conditioning by abhishek singhRefrigiration and air conditioning by abhishek singh
Refrigiration and air conditioning by abhishek singh
 
ch-3 Lecture-2-Refrigeration-Cycles.pptx
ch-3 Lecture-2-Refrigeration-Cycles.pptxch-3 Lecture-2-Refrigeration-Cycles.pptx
ch-3 Lecture-2-Refrigeration-Cycles.pptx
 

Último

Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingrakeshbaidya232001
 
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur EscortsCall Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
Online banking management system project.pdf
Online banking management system project.pdfOnline banking management system project.pdf
Online banking management system project.pdfKamal Acharya
 
Russian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur Escorts
Russian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur EscortsRussian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur Escorts
Russian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...roncy bisnoi
 
UNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its PerformanceUNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its Performancesivaprakash250
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escortsranjana rawat
 
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...Call Girls in Nagpur High Profile
 
Glass Ceramics: Processing and Properties
Glass Ceramics: Processing and PropertiesGlass Ceramics: Processing and Properties
Glass Ceramics: Processing and PropertiesPrabhanshu Chaturvedi
 
Extrusion Processes and Their Limitations
Extrusion Processes and Their LimitationsExtrusion Processes and Their Limitations
Extrusion Processes and Their Limitations120cr0395
 
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINEMANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINESIVASHANKAR N
 
Introduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxIntroduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxupamatechverse
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
AKTU Computer Networks notes --- Unit 3.pdf
AKTU Computer Networks notes ---  Unit 3.pdfAKTU Computer Networks notes ---  Unit 3.pdf
AKTU Computer Networks notes --- Unit 3.pdfankushspencer015
 
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Call Girls in Nagpur High Profile
 
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Christo Ananth
 
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSMANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSSIVASHANKAR N
 
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
Introduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxIntroduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxupamatechverse
 

Último (20)

Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writing
 
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur EscortsCall Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
 
Online banking management system project.pdf
Online banking management system project.pdfOnline banking management system project.pdf
Online banking management system project.pdf
 
Russian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur Escorts
Russian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur EscortsRussian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur Escorts
Russian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur Escorts
 
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
 
UNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its PerformanceUNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its Performance
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
 
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...
 
Glass Ceramics: Processing and Properties
Glass Ceramics: Processing and PropertiesGlass Ceramics: Processing and Properties
Glass Ceramics: Processing and Properties
 
Extrusion Processes and Their Limitations
Extrusion Processes and Their LimitationsExtrusion Processes and Their Limitations
Extrusion Processes and Their Limitations
 
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINEMANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
 
Introduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxIntroduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptx
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
AKTU Computer Networks notes --- Unit 3.pdf
AKTU Computer Networks notes ---  Unit 3.pdfAKTU Computer Networks notes ---  Unit 3.pdf
AKTU Computer Networks notes --- Unit 3.pdf
 
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
 
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
 
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSMANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
 
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
Introduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxIntroduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptx
 

Refrigeration

  • 1. ME 6404 – THERMAL ENGINEERING UNIT – V – REFRIGERATION Presented by A. SANKARA NARAYANA MURTHY, Assistant Professor, Dept. of Mechanical Engineering, Kamaraj College of Engineeriechnology, Virudhunagar
  • 2. REFRIGERATOR • The transfer of heat from a low-temperature region to a high-temperature one requires special devices called refrigerators. • The objective of a refrigerator is to remove heat (QL) from the cold medium; the objective of a heat pump is to supply heat (QH) to a warm medium.
  • 3. HEAT PUMP • Heat pump supplies heat to the higher-temperature region from lower temperature by giving work as input. • Heat pumps and refrigerators are essentially the same devices; they differ in their objectives only. for fixed values of QL and QH
  • 4. TYPES OF REFRIGERATION SYSTEM • Vapour Compression Refrigeration (VCR): uses mechanical energy • Vapour Absorption Refrigeration (VAR): uses thermal energy • Steam Jet Refrigeration system • Liquid N2 bath • Ice bunk cooling system • Etc…
  • 5. THE PRESSURE-ENTHALPY DIAGRAM  The process of the vapor compression refrigeration cycle may conveniently be displayed on a diagram having pressure and specific enthalpy as coordinates.  Below the critical point (CP) the saturated liquid line (SL) and saturated vapor line (SV) enclose a two-phase (wet) region between them.  To the left of the saturated liquid line lie states which have lower temperature than the saturation temperature at a given pressure.  These are states of sub-cooled liquid.
  • 6. THE PRESSURE-ENTHALPY DIAGRAM  To the right of the saturated vapor line lie states which have higher temperature than the saturation temperature at a given pressure.  These are states of superheated vapor.  The area to the left of the liquid line is called the subcooled liquid region, and the area to the right of the vapor line is called the superheated vapor region.  Within the two-phase region the horizontal lines of constant pressure are also lines of constant temperature  In the superheat region the lines of constant temperature leave the saturation line as indicated.  As the pressure diminishes in the superheat region, the lines of constant temperature tend to become lines of constant enthalpy, i.e. vertical on the diagram, indicating that the vapor is beginning to behave like an ideal gas with its enthalpy independent of pressure.  Lines of constant specific entropy and lines of constant specific volume , are shown in the superheat region.
  • 7. REFRIGERANT IN VAPOR COMPRESSION REFRIGERATION  The working substance in a refrigeration system is called the refrigerant.  There are lots of refrigerants, including gas, liquid and solid refrigerants.  There are many natural and artificial substances have been used in mechanical driven and thermal driven vapor compression refrigeration systems.  In lithium bromide vapor absorption refrigeration system, H2O is used as a refrigerant and LiBr is an absorbent ; in NH3 vapor absorption refrigeration system, NH3 is a refrigerant; is an absorbent.  Water H2O is also used as a refrigerant both in vapor adsorption and in vapor jet refrigeration cycles. In mechanical driven vapor compression refrigeration, NH3, CO2, chlorofluorocarbons (CFCs), hydro chloro fluoro carbons (HCFCs), hydro fluoro carbons (HFCs), azeotropic and zeotropic mixtures, inorganic compounds, hydrocarbons, and others are used as refrigerants.
  • 8. REFRIGERATION CHARACTERISTICS OF REFRIGERANTS  The pressure- enthalpy diagram is the usual graphic means of presenting refrigerant properties and its cycles.  A typical vapor compression refrigeration cycle has been shown in figure
  • 9. REFRIGERANT PROPERTIES 1. Appropriate temperature and pressure characteristics  The saturated pressure with temperature is an important property of refrigerant. 1) It is desired for the pressure at evaporating temperature to be above atmospheric, to avoid inward leakage of air. 2)The pressure at the corresponding condensing temperature should not be excessive, so that extra strength high-side equipment is not required. 3) Low compression ratio is desirable, because the degree of complication and difficulty of a compressor increases directly with the compression ratio. 4) Discharge temperature of compressor should not be excessive, to avoid problems as breakdown or dilution of the lubricating oil, decomposition of the refrigerant, or formation of contaminants such as sludge or acids. All of these can lead to compressor damage.
  • 10. REFRIGERANT PROPERTIES 2. High latent heat of vaporization and low specific volume of the refrigerant at the entry to compressor  A high latent heat of vaporization and a low specific volume of the refrigerant at entry to the compressor are desirable for smaller equipment and pipe size at given cooling capacity.  High latent heat means there is a high refrigeration effect.  For example, R11 has a much larger specific volume of suction vapor of compressor than those of refrigerants of R22, R502 and R717.  That means it requires a higher volumetric flow rate to produce the same amount of cooling capacity.  Therefore, R11 is usually used with centrifugal compressors because they are good at handing large volumetric flow rate.
  • 11. REFRIGERANT PROPERTIES 3. Lower compression work  In order to get high COP, both high refrigeration effect and low compression work must be considered in combination.  For example, R717 (ammonia ) has a refrigerating effect q1 much larger than other refrigerants, but its compression work w is also high, as a result, COP of ammonia has the same order of magnitude as that of the other refrigerants.
  • 12. REFRIGERANT PROPERTIES 4. Some Important Physical/Chemical Properties of Refrigerants  Any substance which has appropriate thermal properties can be used as a refrigerant, but in practice the choice is limited by many factors such as toxicity, flammability, chemical stability, and the behaviors of the refrigerant with lubricating oil, water and construction materials.
  • 13. VAPOR-COMPRESSION REFRIGERATION (VCR) CYCLE The vapor-compression refrigeration cycle has four components: 1. Evaporator, 2. Compressor, 3. Condenser, and 4. Expansion (or throttle) valve  In a basic vapor-compression refrigeration cycle, the refrigerant enters the compressor as a saturated vapor and is cooled to the saturated liquid state in the condenser.  It is then throttled to the evaporator pressure and vaporizes as it absorbs heat from the refrigerated space VCR - Cycle
  • 14. VCR - Cycle  The principal work and heat transfer that occurs in the system are shown below, these quantities being taken as positive in the directions indicated by the arrows in the Fig. 6.4.  In the analyses, each component is first separately considered.  The evaporator, in which the desired refrigeration effect is achieved, will be considered first.  Considering a control volume enclosing the refrigerant side of the evaporator, conservation of mass and energy applied to this control volume together give the rate of heat transfer per unit mass of refrigerant flow in the evaporator as: 1 4 e e Q q h h m = = −
  • 15. VCR - Cycle  Next consider the compressor.  It is usually adequate to assume that there is no heat transfer to or from the compressor.  Conservation of mass and energy rate applied to a control volume enclosing the compressor then give:  For a control volume enclosing the refrigerant side of the condenser, the rate of heat transfer from the refrigerant per unit mass of refrigerant is: 2 1 i i W w h h m = = − 2 3 c c Q q h h m = = −
  • 16. VCR - Cycle  Finally, the refrigerant at state 3 enters the expansion valve and expands to the evaporator pressure.  This process is usually modeled as a throttling process in which there is no heat transfer, i.e., for which  In the vapor-compression system, the net power input is equal to the compressor power, the expansion valve involving no power input or output.  Using the quantities and expressions introduced above, the coefficient of performance, COP, of the vapor- compression refrigeration system is given by: 34 hh = 1 4 2 1 / / e e i i q Q m h h COP w W m h h − = = = −
  • 17. LIQUID SUBCOOING  In practice some degree of subcooling may be acquired, and the point 3 moves to the left of the saturated liquid on the pressure-enthalpy diagram, as shown in Figure.  Subcooling is the process of cooling condensed gas beyond what is required for the condensation process.  Subcooling is sensible heat and is measured in degrees.  If it was possible to further cool down the liquid to some lower value, say upto 3’, then the net refrigeration effect will be increased by 1 4' 1 4 4 4' 3 3'( ) ( )h h h h h h h h− − − = − = − Subcooling of the liquid and superheating of the vapor
  • 18. LIQUID SUBCOOING  The volume refrigerating effect is of course increased by subcooling in the same way as the specific refrigerating effect.  Since the specific work of compression remains the same, the coefficient of performance is improved.  The subcooling may be achieved by any of the following methods:  (i) By passing the liquid refrigerant from condenser through a heat exchanger through which the cold vapor at suction from the evaporator is allowed to flow in the reversed direction.  (ii) By making use of enough quantity of cooling water so that the liquid refrigerant is further cooled below the temperature of saturation.
  • 19. VAPOR SUPERHEATING  If the vapor at the compressor entry is in the superheated state 1’, which is produced due to higher heat absorption in the evaporator, then the refrigerating effect is increased as  The specific work of reversible adiabatic compression is increased by superheat. This is indicated in Figure by the decreased gradient of the line of constant entropy though point 1’ in the superheat region compared with the gradient of the line though point 1.  Although the specific work of reversible adiabatic compression is increased by superheat, so is the specific refrigerating effect, however, their ratio, COP, may increase, decrease or remain unchanged depending upon the range of pressure of the cycle. Subcooling of the liquid and superheating of the vapor 1' 4 1 4 1' 1( ) ( )h h h h h h− − − = −
  • 20. VAPOR SUPERHEATING  Here, it is necessary to consider the effect of heat transfer to the refrigerant vapor in the suction pipe from the evaporator to the compressor.  The suction line usually passes though warm surroundings, then heat transfer to the vapor can take place, which will cause the temperature increase.  This will cause a part of refrigerating capacity loss to refrigerate engine room, so it will be called “useless refrigerant capacity”.  And the capacity used to refrigerate things which need refrigeration will be called “useful refrigerant capacity”.  In practice, useless refrigerant capacity loss should be decreased, and should increase useful capacity as possible.
  • 21. CASCADE REFRIGERATION SYSTEMS • Very low temperatures can be achieved by operating two or more vapor- compression systems in series, called cascading. The COP of a refrigeration system also increases as a result of cascading.
  • 22. MULTISTAGE COMPRESSION REFRIGERATION SYSTEMS •When the fluid used throughout the cascade refrigeration system is the same, the heat exchanger between the stages can be replaced by a mixing chamber (called a flash chamber) since it has better heat transfer characteristics.
  • 23. VAPOUR ABSORPTION REFRIGERATION (VAR) SYSTEM • When there is a source of inexpensive thermal energy at a temperature of 100 to 200°C is absorption refrigeration. • Some examples include geothermal energy, solar energy, and waste heat from cogeneration or process steam plants, and even natural gas when it is at a relatively low price. • Vapour Absorption refrigeration (VAR) systems involve the absorption of a refrigerant by a transport medium. • The most widely used system is the ammonia–water system, where ammonia (NH3) serves as the refrigerant and water (H2O) as the transport medium.
  • 24. VAR SYSTEM • Other systems include water–lithium bromide and water–lithium chloride systems, where water serves as the refrigerant. These systems are limited to applications such as A-C where the minimum temperature is above the freezing point of water. • Compared with vapor-compression systems, ARS have one major advantage: A liquid is compressed instead of a vapor and as a result the work input is very small (on the order of one percent of the heat supplied to the generator) and often neglected in the cycle analysis. • ARS are often classified as heat-driven systems. • ARS are much more expensive than the vapor-compression refrigeration systems. They are more complex and occupy more space, they are much less efficient thus requiring much larger cooling towers to reject the waste heat, and they are more difficult to service since they are less common. • Therefore, ARS should be considered only when the unit cost of thermal energy is low and is projected to remain low relative to electricity. • ARS are primarily used in large commercial and industrial installations.
  • 26. VAR SYSTEM The COP of actual absorption refrigeration systems is usually less than 1. Air-conditioning systems based on absorption refrigeration, called absorption chillers, perform best when the heat source can supply heat at a high temperature with little temperature drop.
  • 27. VCR CYCLE COMPONENTS • Refrigerant • Evaporator/Chiller • Compressor • Condenser • Receiver • Thermostatic expansion valve (TXV)
  • 28. REFRIGERANT • Desirable properties: – High latent heat of vaporization - max cooling – Non-toxicity (no health hazard) – Desirable saturation temp (for operating pressure) – Chemical stability (non-flammable/non-explosive) – Ease of leak detection – Low cost – Readily available
  • 29. 29 LOW SIDE OPERATION • Refrigerants have low boiling points • When liquid boils, it absorbs large amounts of heat • Amount of heat absorbed in evaporator is proportional to amount of refrigerant boiled • High side Components • Expansion device • Evaporator • Accumulator (if equipped)
  • 30. 30 EXPANSION DEVICES • The expansion device separates the high side from the low side and provides a restriction for the compressor to pump against. • There are two styles of expansion devices: • The TXV can open or close to change flow. It is controlled by the superheat spring, thermal bulb that senses evaporator outlet temperature, and evaporator pressure • Most OTs have a fixed diameter orifice
  • 31. A TXV controls the refrigerant flow from the high pressure side to the evaporator. A receiver dryer is mounted in the liquid line of all TXV systems. TXV SYSTEM
  • 32. An OT controls the refrigerant flow from the high pressure side to the evaporator. An accumulator is mounted in the suction line of all OT systems. OT SYSTEM
  • 33. 33 THERMAL EXPANSION VALVES, TXVs •The three major types of expansion valves: •Internally balanced TXVs are the most common. •Externally balanced TXVs are used on some larger evaporators. •Block valves route the refrigerant leaving the evaporator past the thermal sensing diaphragm so a thermal bulb is not needed. Internally Balanced Externally Balanced Block Valve
  • 34. 34 THERMAL EXPANSION VALVES, TXVS • Variable valve that can change size of opening in response to system load • Opens or closes depending on evaporator pressure and temperature
  • 35. 35 EVAPORATOR OPERATION Hot, liquid refrigerant flows through the expansion device in the low side to become a fine mist. Refrigerant boils or evaporates to become a gas inside the evaporator. The boiling refrigerant absorbs heat from the air during this change of state.
  • 36. EVAPORATOR/CHILLER • Located in space to be refrigerated • Cooling coil acts as an indirect heat exchanger • Absorbs heat from surroundings and vaporizes – Latent Heat of Vaporization – Sensible Heat of surroundings • Slightly superheated (10°F) ensures no liquid carryover into compressor
  • 37. 37 ACCUMULATORS Accumulators are used in the suction line of all OT systems. The accumulator: •separates liquid refrigerant so only gas flows to the compressor. •Allows oil in the bottom of the accumulator to return to the compressor. •provides storage for a refrigerant reserve. •contains the desiccant bag for water removal. •provides a place to mount low pressure switches and sensors.
  • 38. 38 HIGH SIDE OPERATION • Takes low pressure vapor from evaporator and returns high pressure liquid to expansion device • Must increase vapor temperature above ambient temperature for heat transfer to occur resulting in change of state from vapor to liquid • High side Components • High begins at compressor and ends at expansion device • Compressor • Condenser • Receiver-drier (if equipped)
  • 39. 39 COMPRESSORS There is a large variety of compressors. Some of variations are: The compressor manufacturer Piston, vane, or scroll type The piston and cylinder arrangement How the compressor is mounted Style and position of ports Type and number of drive belts Compressor displacement Fixed or variable displacement
  • 40. 40 SCOTCH YOKE COMPRESSORS A Scotch yoke compressor has two pairs of pistons that are driven by a slider block on the crankshaft. The pistons are connected by a yoke. Pistons Yoke Discharge Reed Suction Reed
  • 41. 41 CONDENSER OPERATION Hot, high pressure gas is pumped from the compressor to enter the condenser. The gas gives up its heat to the air passing through the condenser. Removing heat from the hot gas causes it to change state and become liquid.
  • 42. 42 CONDENSER TYPES Condensers A and C are round tube, serpentine condensers. Condenser B is an oval/flat tube, serpentine condenser. Condenser D is an oval/flat tube, parallel flow condenser. Flat tube condensers are more efficient.
  • 43. 43 SERPENTINE CONDENSER Refrigerant flows from the upper inlet to the bottom outlet through two tubes. These tubes wind back and forth though the condenser.
  • 44. 44 PARALLEL FLOW CONDENSER Refrigerant flows from the upper inlet to the bottom outlet through groups of parallel tubes. Some carry refrigerant from the right to the left, and others move it back to the right side.
  • 45. 45 HEAT EXCHANGERS  Condensers have to move heat from the refrigerant to the air.  Evaporators must move heat from air to the refrigerant.  Both require a lot of contact area for both air and refrigerant.  Both require free movement of air and refrigerant.
  • 46. 46 RECEIVER DRYERS A receiver dryer is mounted in the liquid line of a TXV system. It is used to: •to store a reserve of refrigerant. •hold the desiccant bag that removes water from the refrigerant. •filter the refrigerant and remove debris particles. •provide a sight glass so refrigerant flow can be observed. •provide a location for switch mounting. Barb Connections, Note Sight Glass Male Flare Connections Male O-ring Connections, Note Switch
  • 47. PROBLEM-1 An ideal vapor-compression refrigeration cycle operates at steady state with Refrigerant 134a as the working fluid. Saturated vapor enters the compressor at 2 bar, and saturated liquid exits the condenser at 8 bar. The mass flow rate of refrigerant is 7 kg/min. Determine a)the compressor power, in kW b)the refrigerating capacity, in tons c)the coefficient of performance
  • 49. Ideal Refrigeration Cycle An ideal cycle has no irreversibilities within the evaporator and condenser, and there are no frictional pressure drops. Compression is isentropic. The T-s diagram is shown on the next slide. Process 1-2s: Isentropic compression of the refrigerant; Process 2s-3: Heat transfer from refrigerant to outside air, at constant pressure; Process 3-4: Throttling process to a two-phase mixture at lower pressure; Process 4-1: Heat transfer to the refrigerant as it flows at constant pressure through the evaporator;
  • 50. Analyzing vapor-Compression Refrigeration Systems As the refrigerant passes through the evaporator, the heat transfer per unit mass of refrigerant flowing is: A ton of refrigeration is equal to 200 Btu/min or 211 kJ/min. Work done by compressor per unit mass flow of refrigerant is flowmasstrefrigeranismhh m Qin    );( 41 −= );( 12 hh m Wc −=  
  • 51. Analyzing vapor-Compression Refrigeration Systems Heat rejected by the refrigerant: Expansion valve: Coefficient of performance: );( 32 hh m Qout −=   34 hh = ; )( )( 12 41 hh hh m W m Q c in − − ==     β
  • 52. SOLUTION Let us first get the properties at each state in the cycle. State 1: p1 = 2 bar, sat vapor. h1 = 241.30 kJ/kg, s1 = 0.9253 kJ/kg.K State 2: p2 = 8 bar, s2 = s1, h2 = 269.92 kJ/kg State 3: p3 = 8 bar, sat. liquid, h3 = 93.42 kJ/kg State 4: Throttling process, h4 = h3 = 93.42 kJ/kg a)The compressor power is: CW m h h kg s kJ kg kW( ) ( / )( . . ) / .= − = − =2 1 7 269 92 241 30 3 34 60  
  • 53. Solution b) The refrigerating capacity is c)The coefficient of performance is inQ m h h kg kJ kg tons kJ tons ( ) ( /min)( . . ) / / / /min . = − = − = 1 4 7 241 30 93 42 211 4 91   h h h h ( ) ( . . ) . ( ) ( . . ) − − β = = = − − 1 4 2 1 241 30 93 42 5 17 269 92 241 30
  • 54. • Problem-2 • A refrigerator uses refrigerant-134a as the working fluid and operates on an ideal vapor-compression refrigeration cycle between 0.12 and 0.7 MPa. The mass flow rate of the refrigerant is 0.05 kg/s. Show the cycle on a T-s diagram with respect to saturation lines. Determine: • a) the rate of heat removal from the refrigerated space, • b) the power input to the compressor, • c) the rate of heat rejection to the environment, and • d) the coefficient of performance.
  • 55. Solution Answers: (a) 7.41 kW, 1.83 kW, (b) 9.23 kW, (c) 4.06
  • 56. Problem-3 Consider an ideal refrigeration cycle which uses R-12 as the working fluid. The temperature of the refrigerant in the evaporator is –20°C and in the condenser it is 40°C. The refrigerant is circulated at the rate of 0.03kg/s. Determine the coefficient of performance and the capacity of the plant in rate of refrigeration. For each control volume analyzed, the thermodynamic model is the R-12 tables. Each process is SSSF with no change in kinetic or potential energy.
  • 57. Control volume: Compressor. Inlet state: T1 known, saturated vapor; state fixed. Exit state: P2 known(saturation pressure at T3). At T3=40°C 2 1 2 1 cw h h s s = − = 2 1 1 2 2 2 2 1 0.9607 178.61 / 0.7082 50.8 211.38 / 32.77 / g o c P P MPa h kJ kg s s T C h kJ kg w h h kJ kg = = = = = = = = − =
  • 58. Control volume: Expansion valve. Inlet state: T3 known, saturated liquid; state fixed. Exit state: T4 known. Control volume: Evaporator. Inlet state: State 4 known. Exit state: State 1 known. 3 4 74.53 /h h kJ kg= = 1 4 104.08 / 3.18 3.12 L L c q h h kJ kg q w Capacity kW β = − = = = =
  • 59. • Problem-3 Consider a 300 kJ/min refrigeration system that operates on an ideal vapor-compression refrigeration cycle with refrigerant-134a as the working fluid. The refrigerant enters the compressor as saturated vapor at 140 kPa and is compressed to 800 kPa. Show the cycle on a T- s diagram with respect to saturation lines, and determine the: a) quality of the refrigerant at evaporator inlet, b) coefficient of performance, and c) power input to the compressor.

Notas del editor

  1. Evaporation From the expansion valve, Freon as a saturated mixture of liquid and vapor passes into the cooling coil, or evaporator, located in the freeze box to be cooled. The cooling coil acts as a heat exchanger. The boiling point of the refrigerant under the low pressure in the evaporator is extremely low - much lower than the temperature of the spaces in which the cooling coils are installed. The temperature differential between the -5°F refrigerant in the coils and the air in the freeze box slightly above 0°F causes heat to be transferred from the freeze box to the refrigerant. It absorbs its latent heat of vaporization from the surroundings, thereby cooling the space. The refrigerant continues to absorb heat until all the liquid has boiled and vaporized. To ensure all the refrigerant changes phase to vapor, the Freon must be slightly superheated. As a rule, 6° to 10°F of superheat is added to the Freon. The refrigerant leaves the evaporator as a low pressure superheated vapor, having cooled the freeze box by absorbing its unwanted heat. The remainder of the cycle is concerned with disposing of this heat and getting the refrigerant back into a liquid state so that it can again vaporize in the evaporator and thus again absorb heat from the freeze box.