Generator protection
1.
2.
3.
4. ROTOR ELECTRICAL FAULTS
LOSS OF EXCITATION
LOSS OF SYNCHRONISM
FAILURE OF PRIME MOVER
LUBRICATION OIL FAILURE
OVER SPEEDING
CORE LAMINATION FAILURE
5. STATOR ELECTRICAL FAULTS
OVER LOADS
OVER VOLTAGE
UN BALANCED LOADING
OVER FLUXING
13. 13
Device Function
21
Distance Relay. Backup for system
and generator zone phase faults.
24
Volts/Hz protection for generator
over excitation.
32
Reverse power relay. Anti-
motoring protection.
40 Loss-of-field protection.
46
Negative sequence unbalance
current protection for the
generator.
ANSI DEVICE NUMBERS
14. 14
Device Function
49 Stator Thermal Protection.
51GN Time over current ground relay.
51TN Backup for ground faults.
51V
Voltage-controlled or voltage-
restrained time over current
relay. Backup for system and
generator phase faults.
59 Overvoltage protection.
59GN
Overvoltage relay. Stator ground
fault protection for a generator.
ANSI DEVICE NUMBERS
15. 15
Device Function
78 Loss-of-synchronism protection.
81
Frequency relay. Both
underfrequency protection.
86 Hand-reset lockout auxiliary relay.
87G
Differential relay. Primary phase-
fault protection for the generator.
87N Stator ground fault differential .
87T
Differential relay. Primary
protection for the transformer.
87U
Differential relay for overall
generator and transformer
protection.
ANSI DEVICE NUMBERS