2. Preface
JB-KR-TC5306 Combustible Gas Fire Alarm Control Panel is a new
generational controller after full investigation of fire protection market
demandandyearsofexperienceinfireprotectionengineering.
JB-KR-TC5306 Combustible Gas Fire Alarm Control Panel is a wall-
mountedandmodular-designcontrollerwithpowerful,reliableandflexible
function.ItisequippedacolorLCDandaprinteravailableforallinformation
when alarms, errors or other operations occur. JB-KR-TC5306 is the best
optionforfireprotectionengineering.
This manual should be charged by a special person for safekeeping and
subsequentreference.
4. PartOne:Overview
ChapterOne:BriefIntroduction
JB-KR-TC5306 Combustible Gas Fire Alarm Control Panel (FACP) is the new generational controller with
powerful,reliableandflexiblefunction.
Thecontrolpaneladoptsintelligentloopcontrolmode,withupto255alarmingnodes(addressabledetector)
ineachloop.Theloopisreliablewithstronganti-interferencecapability,convenientforcommissionandfield
operation.
1.1Colormenudisplayinterface
This control panel uses menu-style interface which displays clearly and intuitively. This control panel is
friendlytouse,simpleoperationachievingavarietyofsystemfunctions.
PartTwo:Structure,InstallationandCommission
ChapterTwo:StructureandConfiguration
JB-KR-TC5306CombustibleGasAlarmControlPanelInstallationandOperationManual Ver.1.0,August2015
1
6. JB-KR-TC5306CombustibleGasAlarmControlPanelInstallationandOperationManual Ver.1.0,August2015
3
●Mainpowerfault:Yellow.Itilluminates,whenAC220Vpowerisdamagedorpoweroff.Itgoesoutwhenmain
powersourceoperatesnormally,.
●Batteryfault:Yellow.Whenthestandbypowersourceisintrouble,thelightilluminates.Whenitoperates
normally,thelightgoesout.
●Disable: Yellow. When outside devices (detectors) are in trouble, they will be disabled. After fixing or
exchanging,enablethedevicesbacktonormal.ThisLEDilluminateswhenthereisdisablement.
●Manual:Green.Itilluminates,whenmanualoperationstarts.
●Auto:Green.Itilluminates,whenautooperationstarts.
●Loop fault: Yellow. It illuminates, when the loop is shorted or overloaded. It automatically goes out after
troubleshooting.
●Mute: Green. When the control panel alarms, press“Silence”
to silence loudspeakers and the LED
illuminates.Thecontrolpanelwillalarmagain,ifthereisanotherfireandtheLEDgoesout.
●Systemfault:Yellow.Itilluminates,whenthesystemfailstoworknormally.
2.3TheInternalConstructionandCabling
2.3.1IntroductionoftheInternalConstruction
The control box is the heat of control panel, consisting of three parts: main board, loop board and power
supply.
2.3.2ExternalTerminalsDescriptionofControlPanel
L,N,PE:AC220Vterminalsandthegroundterminal.
L+,L-:Loopterminalsofnon-polarizedloopsignal.
NC1,CM1,NO1:Theyrespectivelyarenormallyclosedcontact,sharingcontract,andnormallyopencontact
ofoutputrelayNo.1.
NC2,CM2,NO1:Theyrespectivelyarenormallyclosedcontact,sharingcontract,andnormallyopencontact
ofoutputrelayNo.2.
A1,B1:RS485terminals.A1istheA-endof485,B1theB-endof485(Theyareoptional).
A2,B2:TheRS485terminalstoconnectagraphicdisplaydeviceinafirecontrolroom.A1istheA-endof485,
B1theB-endof485(Theyareoptional).
CH,CL:PolarizedcontrollineofCANnetworkingofcontrolpanel.
JP2: It locates on the outsider networking terminal pins. When this device is the terminal of outside
networking,theshort-loopblockskipsto
“
On”
position.
24V,GND:DC24Vpowersupplyoutputterminals.
Fig.2-2
7. ChapterThree:InstallationandCommission
3.1OpenPackageInspection
Thefielddevicesneedtoinspectbeforeinstallation.
3.1.1ComponentsInspection
Checkwhetherthepackinglistofcontroldevicesmatchestheengineeringcomponentsoftheprojectornot.
Openpackingboxesandcheckthecontentsbasedonthepackinglist,whichincludesInstallationManualand
keys of the control panel. Then make the necessary checks of the appearance of the control panel. If there is
somethingnotmatchingtherequirements,pleaseconnectwithaftersalesdepartmentofourcompany.
3.1.2InternalComponentsandCablingInspection
Checkwhethertheconnectionsofinternalcomponentsarecorrectornot.Ifthereissomethinglikeconnecting
cables off, or something not matching with manuals or unclear signals, please connect with aftersales
departmentofourcompany.
3.2Installationconditions
Dimension(L×W×H):320mm×120mm×400mm
AmbientTemperature:0℃~+40℃
RelativeHumidity:≤95%,non-condensing
Structure:Wall-mounted
3.3StartChecking
Afterinstallation,thecontrolpanelshouldbepoweredonforstartchecking.Checkingpointsareatbelow.
●WhetherLCDscreenandLEDsworknormallyornot.
●Self-test operation. Check whether LEDs can all be illuminated and loudspeakers can alarm three times
loudlyandcontinuously.
●Inmonitoringstatus,checkwhetherthereisanyfaultofpowersupply,whetherkeypadcanbewellusedor
not,whetherprintercanoperatenormallyornot.
●Anythingabnormalisfoundinthosechecks,pleaseconnectaftersalesdepartmentofourcompany.
3.4OutsideDeviceInspection
3.4.1OutsideCablingInspection
Checktheloopconnectedwiththecontrolpanel.Measureinsulationresistancesbetweentheloopandearth,
whichshallbegreaterthan20MΩ(usinginsulationmetertomeasure).Theloadofloopsshallbegreaterthan
70kΩ(usingresistancegradeofmulti-metertomeasure).
3.4.2DevicesInspection
Inspecttheinstallationoffacilitiesmatchingthedesignrequirementornot.Eliminateallfaultsandprepareto
connectwiththesystem.
JB-KR-TC5306CombustibleGasAlarmControlPanelInstallationandOperationManual Ver.1.0,August2015
4
9. PartThree:SystemApplication
ChapterFour:UserManual
4.1Start,ShutdownandSelf-test
Aftercommission,userscanoperateasbelow:
●Powerontherelativedevices.
● Turn on the switches of the power and the
batteryofcontrolpanel.
The system will begin to initialize after the
operationsmentionedahead(refertoFig4-1).When
the initialization complicated, the system works in
monitoringstatus.Press“
Self-test”
onthekeypadof
co n t ro l pa n e l a n d t h e s y ste m sta r t to te st
automatically.
Shutdown is to close switches one by one as an
oppositeorderofstarting.Pleasenoticethattheswitchofbatterymustbeturnedoff,otherwiseitwilldamagethe
battery.
4.2Preparationbeforekeypadoperation
4.2.1Orderandcharacterfunctionofkeypad
Mostofkeypadsaredual-functionwiththeorderfunctioninthebottomhalfandthecharacterfunctioninthe
upper half. Order keys can only work under monitoring and most of order keys are limited by operation level.
Characterkeysareonlyavailableinthemenu.
4.2.2Datainput
Thescreenwillremindyoutoinputtheaddressandtherangeofthedateneeded.Afterprogrammingablock
ofdata,press“
Enter”
tosavealltheinputteddata.Press“
Cancel”
toexitfromthecurrentprogrammingstatus
andsavenothing.
4.2.3Queryinformation
Press
“
Query”
toquerythemenu.Pressthenumerickeypadtoentertherelativeinformation.
Underthedisplaystate,press
“
▲”
,
“
▼”
toscrollitembyitem.Press
“
Cancel”
togobacktothelastoperation
menuortothenormalworkingmenuofthesystem.
4.3OperationLevel
The control panel system is divided into three operation levels:“
Level Ⅰ”
,“
Level Ⅱ”
and“
Level Ⅲ”
. The
default setting of the control panel is“Level Ⅰ”
. Meanwhile“Mute”
,“Query”
and“Setup Query”
are in
operational status. The status showing at the bottom of LCD displays“
Operation Level: Level Ⅰ”
. Operations
available for Ⅱ Level are“
User setup”
,“
Self-test”
,“
Reset”
,“
Disable”
,“
Enable”
and“
Linkage”
. The Level Ⅲ
operationareavailablefor
“
Systemsetup”
“
, Networksetup”
and
“
Linkageprogram”
.
6
JB-KR-TC5306CombustibleGasAlarmControlPanelInstallationandOperationManual Ver.1.0,August2015
Fig.4-1
10. Press
“
OperationLevel”
andchooseoperationlevelbythenumerickeypad.Thenkeyinthepasswordasthe
systemasked.Thenpress
“
Enter”
togetthepermissionofrelativeoperationlevel.Thesystemwillautomatically
exitLevelⅠ,ifthereisnooperationover30s.
4.4Deviceregistrationandregistrationinquiry
4.4.1Deviceregistration
Press
“
Menu”
intomainmenu,thenpress
“
5”
into
“
5.Systemsetup”
→
“1.Deviceregistration”
.Press
“
Enter”
to
registry.Thesystemwillresetautomaticallyafterregistration.
4.4.2Registrationinquiry
Press
“
Test”
,theLCDwilldisplaythetotalamountofregistrations,faultsanddisablesofthecontrolpanel.
4.4.3Loopallocationinspection
Press“
Menu”
into main menu (Fig4-2). Then press“
1”
into“
1.System info.”
as Fig4-3 showing. This LCD
displayshowsthevarietiesandamountsofalldevices.
Thisinterfaceshowsthesumofregistereddevicedots,
loop current value and the reference voltage, which
displayswhetherthesystemisrunningnormallyornot.In
thedisplayofFig4-3,press“
F1”
intotheinterfaceofloop
device information to query the information of device.
RefertoFig4-4.
The interface of loop device information displays the
localaddressofdevices,registrationtypes,2ndcodeand
remark information (Refer to the chapter of Devices
Definitionfordetails).Press
“
▲”
,
“
▼”
toquerylastitemorthenextitem.TheregistrationtypeisFBS(FrontSide
Loop)equipment.
OnFig4-3,press“
F2”
andentertheinterfaceofloopstatustobrowsingloopstatus.Basedonthefeedback
currentdisplayedonthisinterface,wecaninspecttheworkingstatusofloops.
OnFig4-3,press
“
▼”
toquerythedesignedthresholdvalueandcurrentvalueofdevices.
7
JB-KR-TC5306CombustibleGasAlarmControlPanelInstallationandOperationManual Ver.1.0,August2015
Fig.4-2 Fig.4-3
Fig.4-4
11. 4.5Informationdisplayandrecord
4.5.1Informationdisplay
Thesystemcandisplayanykindinformationofalarming,starting,faultsanddisable.Ifmorethanonekind
informationtransformedatthesametime,thepriorityshowsasthepriorityofalarmingfaultstartingdisable.
“Test”
canhelptoswitchbetweeninterfaces.
4.5.2Queryhistorylog
Press
“
Menu”
intomainmenuandchoose
“
3”
toentertheinterfaceofhistorylog.RefertoFig4-5.
OntheinterfaceofFig4-5,press“
1”
tochooseAlarmlogandentertheinterfaceofalarmloghistory.Referto
Fig4-6.
Thesystemcandisplayhistorylogoffireandeverylogincludestime,loop,addressandremarkinformation.
4.6Mute
Whenfiresorfaultshappen,theloudspeakersofcontrolpanelwillbuzz.Press
“
Mute”
tosilenceloudspeakers
and extinguish the flash of indicators. If another new alarm happens, the mute indicator will flash and
loudspeakerswillalarmagain.
4.7Alarmandtroubleshooting
4.7.1Troubleshooting
Faultsaredividedintotwotypes,oneiscontrolsystemfaults,likefaultsofmainpower,backupbatteryor
loops. The other is faults of devices in field, like faults of detectors. When faults happen,
“Mute”
can stop
loudspeakers.
Ifthemainpowerisoutofpower,backupbatteriescansupplytherunningpower.Pleasenoticethatthetotal
timeofbackupbatteriesshouldnotbeover1.5h.Ifover1.5H,theswitchesshouldbeturnedoff(includingbackup
switch)toprotectbatteries.
If faults happen, devices must accept maintenance without delay. If shutdown is necessary, please keep
record.
Ifdevicesonthefieldfailtowork,theymustacceptmaintenancewithoutdelay.Iffaultscannotbecleared
immediatelybecauseofsomespecialreasons,thisdeviceshouldbeisolatedbytheisolationfunction.Afterthe
troubleshooting,cancelisolationandresetthedevice.