3. PartOne:Overview
ChapterOne:BriefIntroduction
JB-DH-TC5600ElectricalFireMonitoringEquipment(EFME)andDH12A,DH01B,DH230electricalfiredetectors
composeanelectricalfiremonitoringsystemofloopcontrolcommunication.Anelectricalfiremonitoringdevice
uses a two-line loop to connect each detector with its own address, which is called communication. This
monitoringdevicesuppliespowertoeachsubdevices.Alarmsinformationwillbesenttocontrolpanelthrough
breakmode,effectiveandefficient.Opencircuits,shortcircuitsandcommunicationfaultsofanyloopcontrol
devicewillallreporttothecontrolpanel,whichprovidesanimportantbasisfornormaloperationofdevicesand
maintenanceoffollow-upsystem.
1.1JB-DH-TC5600ElectricalFireMonitoringEquipmenthasfollowingfeatures:
1.1.1Itiscompliedwithalarge-screencharacterLCDdisplay,throughwhichallinformationsuchasalarms,
faultsorstatuscanbedisplayedclearlyanddirectly.
1.1.2Thealarmingrangesofresidualcurrentdetectorsandheatdetectorsallcanbeadjustedwidely.They
adapttovarioussituations.
1.1.3Detectorsareaddressable,flexibleandconvenientforcommissionandinstallation.
1.1.4Alldeviceshavetheinterconnectionfunctionoffirealarmsystemwithourcompany
1.1.5Maximum2loops,withupto255electricalfiredetectorsofaloop.
1.1.6 The enclosure of EFME conforms to the rules of IP30 strictly, with all cracks and louvers smaller than
2.5mm.
JB-DH-TC5600ElectricalFireMonitoringEquipmentInstallationandOperationManual
1
5. 3
●Manual:Green.Itilluminates,whenmanualoperationstarts.
●Auto:Green.Itilluminates,whenautooperationstarts.
●Loopfault:Yellow.Itilluminates,whentheloopofcontrolpanelisshortedoroverloaded.Itautomatically
goesoutaftertroubleshooting.
●Communication fault: Yellow. It illuminates, when the control panel and CRT have troubles in
communication.Whenthecommunicationisbacktonormal,thelightgoesoutautomatically.
●Systemrunning:Green.Itflashes,whenthecontrolpanelrunsnormally.
●Disable: Yellow. When outside devices (detectors) are in trouble, they will be disabled. After fixing or
exchanging,enablethedevicesbacktonormal.ThisLEDilluminateswhenthereisdisablement.
●Self-test:Yellow.Itilluminates,whenloopdevicesistesting.Onceitfinished,theLEDgoesout.
●Silence: Green. When the control panel alarms, press“Mute”
to silence loudspeakers and the LED
illuminates.Thecontrolpanelwillalarmagain,ifthereisanotherfireandtheLEDgoesout.
2.3TheInternalConstruction
2.3.1IntroductionoftheInternalConstruction
The control box is the heat of control panel, consisting of three parts: main board, loop board and power
supply.
ShowasFig.2-2:
2.3.2ExternalTerminalsDescriptionofControlPanel
L,N,PE:AC220Vterminalsandthegroundterminal.
L+,L-:Controlterminalofnon-polarizedloopsignal.
NC1,CM1,NO1:Theyrespectivelyarenormallyclosedcontact,commonmode,andnormallyopencontactof
outputrelayNo.1.
NC2,CM2,NO1:Theyrespectivelyarenormallyclosedcontact,commonmode,andnormallyopencontactof
outputrelayNo.2.
A1,B1:RS485terminals.A1istheA-endof485,B1theB-endof485(reserved).
A2,B2:TheRS485terminalstoconnectagraphicdisplaydeviceinafirecontrolroom.
CH,CL:PolarizedcontrollineofCANnetworkingofcontrolpanel.
JP2: It locates on the outsider networking terminal pins. When this device is the terminal of outside
networking,theshort-loopblockskipsto
“
On”
position.
24V,GND:DC24Vpowersupplyoutputterminals(reserved).
Fig.2-2
JB-DH-TC5600ElectricalFireMonitoringEquipmentInstallationandOperationManual
8. PartThree:SystemOperation
ChapterFour:UserGuide
4.1Start,ShutdownandSelf-test
Whenfinishthecommission,userscanopenthe
machineaccordingtotheprocessasfollow:
4.1.1Poweronthecontrolpanel.
4.1.2Afterpoweron,thesystemstarttoinitialize
(refer to Fig.4-1 for the display) and enter to
monitoringstatus.Press“
Self-test”
onthekeypadof
controlpanel,thensystemstarttoself-testofsound
andstrobe.
4.2DescriptionofSystemMenu
4.2.1Mainmenu
ThemainmenushowsasFig.4-2:
The main menu displays all the function of the
system, each module of which will be described in
detailasbelow.
4.2.2Systeminformation
Please refer to Fig. 4-3 for system information
inquiry:
Thisdisplayshowsthesumofdevicesregistered
in the control panel. Press numerical keys 1-4 to
querytherelativeinformation.
6
Fig.4-1
JB-DH-TC5600ElectricalFireMonitoringEquipmentInstallationandOperationManual
ScientificandTechnologicalCreationEnsuretheSecurity
JB-DH-TC5600
ElectricalFireMonitoringEquipment
Systemrunningnormally!
China·Liaoning·YingkouTianchengFireProtectionEquipmentCo.,Ltd
Auto Manual Level:I
Mainmenu
Auto Manual Level:I
1.Systeminfo
5.Systemsetup 6.Networking
setup
7.Linkage
program
2.Setupinquiry 3.Historylog 4.Usersetup
8.Aboutdevice
Fig.4-2
Systeminfo
Detectorregsum:
245
DH01Bdetecto:
245
DH12Adetector:
000
DH230detector:
000
Auto Manual Level:I
1.Loop1info2.Loop2info3.Devicestatusinquiry
4.Query2ndcodeofloopdevice
Press1/2/3/4toqueryinfo
Fig.4-3
9. 4.2.2.1LoopInformation
Press
“
1”
anddisplayFig.4-4asfollow:
Querythesumofregistrationof2-loopandeach
kindofdevices,theinformationofloopcurrentand
referencevoltage.
Press“F1”
on this display to quer y the
informationof2ndcodeandnote,referringtoFig.4-
5.
Press“
F2”
toquerythedevicestatusoftheloop,
like online, offline or duplicated code, referring to
Fig.4-6:
4.2.2.2Devicestatusinquiry
Press
“
3”
,referringtoFig.4-7:
Inputtheinformationofloop,addressandtube
toquerythestatusofdevices,liketheinformationof
online/offline, tube type, device type, alarm pre-
valueandalarmsignalvalue.
Loop2info
Detectorregsum:
245
DH01Bdetecto:
245
DH12Adetector:
000
DH230detector:
000
Auto Manual Level:I
Loopstatus
Loopcurrent:108mAReferencevoltage:
12.3V
F1toquerydeviceF2forloopstatusbrowsing
7
JB-DH-TC5600ElectricalFireMonitoringEquipmentInstallationandOperationManual
Fig.4-4
Fig.4-5
Add.Type2ndcodeNote
12345678
DH01B
DH01B
DH01B
DH01B
DH01B
DH01B
DH01B
DH01B
2-loopdeviceinfo
0001
0002
0003
0004
0005
0006
0007
0008
Auto Manual Level:I
TianchengFireProtectionEquipmentCo,.Ltd
2-loopstatusbrowsing
Auto Manual Level:I
Fig.4-6
Loop:02Add.:
001Tube:01
Querystatus:
Refreshing
Devicestatus:
Online
Tubetype::
Leakage
Devicetype
Alarmpre-value
Alarmsignalvalue(real-time,autorefresh/3s)
CANCELtoreviseF1toexit
Devicestatusinquiry
Auto Manual Level:I
Fig.4-7
10. 4.2.2.32ndcodeinquiry
Press
“
4”
,referringtoFig.4-8:
Press“
1”
to query the sum of the 2nd codes of
tubes,referringtoFig.4-9asbelow.
Press“
2”
to query the single 2nd code of each
tube,referringtoFig.4-10asbelow.
4.2.3SetupInquiry
RefertoFig.4-11forinformationofsetupinquiry.
This page is to query all setup information of
devicesonthiscontrolpanel,referringtodetailson
thecontrolpanel.
8
JB-DH-TC5600ElectricalFireMonitoringEquipmentInstallationandOperationManual
1.Totalinquiryof2ndcode
2.Singleinquiryof2ncode
2ndcodeinquiry
Auto Manual Level:I
Fig.4-8
No.LoopAdd.Tube2ndcode
12345678
Totalinquiryof2ndcode.
000102000101
Auto Manual Level:I
Fig.4-9
Loop:02Add.:001Tube:01
2ndcode:12345678Result:Inquiryfinished
Singlesetupof2ndcode
ENTERtoqueryF2toexit
ESCtorevise
Auto Manual Level:I
Fig.4-10
1.Localadd.
2.Linkageprogram
3.Devicedisable
4.Printersetup
5.CAN-networkingmode
Totalinquiryof2ndcode.
Auto Manual Level:I
Fig.4-11
12. 4.2.5UserSetup
4.2.5.1DateSetup
“
DateSetup”
istosetthedateofcontrolpanel
includingyear,monthanddate.
4.2.5.2SoundSetup
“
SoundSetup”
istosetthekeysoundofcontrol
panel.
4.2.5.3PrinterSetup
“
PrinterSetup”
istosettheswitchoftheprinter,
referring to the description of control panel for
details.
4.2.6SystemSetup
Fig.4-17showsthedisplayofsystemsetup.
4.2.6.1RegistrationSetup
Press
“
1”
toregisteralldevicesontheloop.
4.2.6.2IlluminateOperationLight
Press“2”
to illuminate the operational light,
referringtoFig.4-18:
Locatingthedeviceonfieldandtroubleshooting
theproblemofduplicatedcodearemainlyrelayon
the operation of output loop, address and F1 to
illuminatetheoperationallight.
4.2.6.3PasswordSetup
Press“
3”
tosetthepassword,referringtoFig.4-
19:
10
JB-DH-TC5600ElectricalFireMonitoringEquipmentInstallationandOperationManual
Fig.4-16
1.Date
2.Sound
3.Printer
Usersetup
Auto Manual Level:I
1.Devicereg
2.Illuminateoperationlight
3.Passwordsetup
4.CRTtransmitsetup
5.Loopsumsetup
6.Loopcomponentsetup
7.Factorydefault
Systemsetup
Auto Manual Level:I
Fig.4-17
Inputloop(**),add.(***)
Loop:01Add.:001
Illuminateoperationlight
Orderhasbeensent.
F1-onF2-off
Function:Checkduplicatedcodeofdevices
Auto Manual Level:I
Fig.4-18
1.SetupLevelIIpassword
2.SetupLevelIIIpassword
Passwordsetup
Auto Manual Level:I
Fig.4-19
13. There are password setup of Level and Level .
Press“2”
to set password of Level . As Fig. 4-20
shows:
InputthenewpasswordtwiceandpressENTER
tosave.Thesameprocessappliesforthepassword
of Level . Please remember the changed password
forlateruse.
4.2.6.4CRTTransmitSetup
Press“
4”
to display the CRT Transmit Setup as
Fig.4-21showing:
When the control panel does not connect with
CRT, please choose F2-Don't connect with CTR.
OtherwisethesystemwillreportCRTcommunication
fault.
4.2.6.5LoopSumSetup
Press
“
5”
todisplayFig.4-22ofLoopSumSetup:
Choose to set the sum of loop based on the
hardware configuration of loops. If loop setup is
wrong,therewillbecommunicationfaultofloops.
4.2.6.6LoopComponentSetup
Press
“
6”
tosetloopcomponent,referringtoFig.
4-23:
●Press“
1”
on the display of component setup
andenterthedisplayofparametersetupasFig.4-24
displaying.
Afterinputtheloop,addressandtubecorrectly,
thesystemcanqueryautomaticallyanddisplaythe
11
JB-DH-TC5600ElectricalFireMonitoringEquipmentInstallationandOperationManual
Fig.4-20
Inputnewpassword(***):***
Inputnewpasswordagainandremember:***
ENTERtosaveandexit
LevelIIsetup
Auto Manual Level:I
CRTtransmitsetup
Auto Manual Level:I
Fig.4-21
Loopsumsetup
Loopsum:Current-2loops
Set-1loops
F1-AloopF2-2loops
ENTERtosave
Auto Manual Level:I
Fig.4-22
CRTconfiguration:current-notconfiguredwithCRT
Set-configuredwithCRT
F1-configuredwithCRTF2-notconfigurewithCRT
PressENTERtosave
1.Parameter
2.Tube2ndcode
3.Deletetube2ndcode
4.2ndcodeandnote
5.DH01Bbatchparameter
6.DH12Abatchparameter
7.DH230batchparameter
Componentsetup
Auto Manual Level:I
Fig.4-23
14. 12
inquiry result. We decide whether to modify some
parameter or not, based on the displayed result. If
modify, press the key of up or down to scroll the
option.PressCanceltomodifyandEntertosaveinto
thecontrolpanel.
●Onthedisplayofcomponentsetup,press
“
2”
to
enter the display of 2nd code setup of component
tube.RefertoFig.4-25:
●On the display of 2nd code setup, press“
1”
to
enter the display of single setup of 2nd code of
componenttube.RefertoFig.4-26:
Inputloop,address,tubeand2ndcodethatneed
to set, and press Enter to save. Tube 2nd code is
designed for linkage program. An appropriate 2nd
codesetupisconvenientfortheprogramoflinkage
formula.
●On the display of 2nd code setup, press“
2”
to
enter the display of mass setup of 2nd code of
componenttube.RefertoFig.4-27:
On this display, the 2nd codes are allotted
accordingtotheregistrationautomatically.Basedon
theorderofloop,thebeginningaddressshouldnot
begreaterthantheendingaddress.Itmeansthatthe
2ndcodeshouldbeprogrammedincrementallyfrom
thefirst2ndcode.
JB-DH-TC5600ElectricalFireMonitoringEquipmentInstallationandOperationManual
Fig.4-24
Parametersetup
Auto Manual Level:I
2ndcodesetup
Auto Manual Level:I
Fig.4-25
Singleinquiryof2ndcode
Loop:01Add.:001Tube:01
→2ndcode:12345678Result:Savesuccessfully
F1tocancelF2toexit
CANCELtoreviseENTERtosave
Auto Manual Level:I
Fig.4-26
1.Singlesetupof2ndcode
2.Set2ndcodebyloopbatch
Note:firsttoregister,thentoautoassign2ndcode
Loop:01(01-02)
Beginningadd.:001(001-255)
Endingadd.:255(001-255)
→Thefirst2ndcode:12345678(0-9)
Result:--------
F1toclearF2toexit
CANCELtoreviseENTERtogenerate
Masssetupof2ndcode
Auto Manual Level:I
Fig.4-27
Loop:
02add.:
001→channel:
01
status:onlinetype:electricleakagepresetvalue:
0900mA
devicetype:
DH01Bstatus:querycomplete
alarmsignalvalue:0000Ma(query)
0-offline1-onlineleakagerange
(0200-0900)
mA
presscancelkeytoalteroptiontemp.range
(0045-0140)
℃
pressenterkeytosendsetupF1-clearF2-exit
15. 13
JB-DH-TC5600ElectricalFireMonitoringEquipmentInstallationandOperationManual
●Onthedisplayofcomponentsetup,press
“
3”
to
enterthedisplayofdeleting2ndcodeofcomponent
tube.RefertoFig.4-28:
Press“
Enter”
to clear all 2nd codes, please be
cautiousbeforeoperation.
●Onthedisplayofcomponentsetup,press
“
4”
to
enterthedisplayofnotesetupofcomponent.Refer
toFig.4-29:
Inputtheinformationofloop,address,2ndcode
andnotethatneedtosetandpress“
Enter”
tosave.
But the 2nd code setup is useless for this moment
andcanbesetasanydata.Theinputinformationof
ChineseandEnglish(bothcapitalandsmallletters),
numbers, punctuation marks is accepted by the
system.
●Onthedisplayofcomponentsetup,press
“
5”
to
enter the display of pareameter setup of DH01B.
RefertoFig.4-30:
When more than one DH01B needs to set
parameter and the leakage tubes need to set the
sameparameter,thisfunctioncanrealizesetupfast.
If the parameter of each tube is different from each
other,usethefunctionofparametersetuptorealize.
●Onthedisplayofcomponentsetup,press
“
6”
to
enterthedisplayofparametersetupofDH12A.Refer
toFig.4-31:
When more than one DH12A needs to set
parameter and the leakage tubes and temperature
tube need to set the same parameter, this function
canrealizesetupfast.Iftheparameterofeachtubeis
different from each other, use the function of
parametersetuptorealize.
Fig.4-28
Clearalltube2ndcode,
pleasebecautiousbeforeoperation!!!
ENTERtodelete2ndcode
Tube2ndcodedelete
Auto Manual Level:I
Componentsetup
Auto Manual Level:I
Fig.4-29
Loop:01add.:0012ndcode:12345678
CHECKtoconfirm.F1,F2toselect/roll
ENTERtosaveandintothenext
DH01Bsetup
Loop:02(01-02)
Beginningadd.:001(001-255)
Endingadd.:005(001-255)
Tubestatus:Online(0-1)
→Leakagepre-value:0900mA(
0200-0900)
mA
Result:SetsuccessfullySuccess-005
F1toclearF2toexit
CANTELtoreviseENTERtoset
Auto Manual Level:I
Fig.4-30
DH12Asetup
Auto Manual Level:I
Fig.4-31
Loop:01(01-02)
Beginningadd.:001(001-255)
Endingadd.:255(001-255)
Tubestatus:Online(0-1)
Leakagepre-value:0900mA(
0200-0900)
mA
→Temp.pre-value:0140℃(
0045-0140)℃
Result:--------
F1toclearF2toexit
CANTELtoreviseENTERtoset
16. 14
JB-DH-TC5600ElectricalFireMonitoringEquipmentInstallationandOperationManual
●Onthedisplayofcomponentsetup,press
“
7”
to
enterthedisplayofparametersetupofDH230.Refer
toFig.4-32:
When more than one DH230 needs to set
parameter and the leakage tubes and temperature
tube need to set the same parameter, this function
canrealizesetupfast.Iftheparameterofeachtubeis
different from each other, use the function of
parametersetuptorealize.
4.2.6.7Factorydefault
Press“7”
into the display of factory default,
referringtoFig.4-33:
Press
“
Enter”
toresetallthesetupsofthecontrol
panel. Please be cautious before operating factory
default.
4.2.7Networkingsetup
Press
“
6”
onthemainmenuandenterthedisplay
ofnetworkingsetup,referringtoFig.4-34:
4.2.7.1Localaddresssetup
Press“
1”
tosetthelocaladdress,referringtoFig.
4-35:
Fig.4-32
DH230setup
Auto Manual Level:I
Loop:02(01-02)
Add.:001(001-255)
Tubestatus:Online(0-1)
Leakagepre-value:0200mA(
0200-0900)
mA
→Temp.pre-value:0045℃(
0045-0140)℃
Result:--------
F1toclearF2tocancel
CANTELtoreviseENTERtoset
Factorydefault
Auto Manual Level:I
Fig.4-33
Factorydefaultwillclearallsettings
Becautioustooperate!!!
ENTERforfactorydefault
Networkingsetup
1.Localadd.
2.CANnetworkingmode(CHCL)
Auto Manual Level:I
Fig.4-34
Inputadd.Zone-Range:
(001-255)
Currentadd.:001Set:005
ENTERtosave
Localadd.
Auto Manual Level:I
Fig.4-35