Cable Construction
Introduction
This article gives a brief exposition on the construction of typical low voltage, medium / high voltage
and instrumentation cables. The focus is on thermoplastic and thermosetting insulated cables,
however the construction of other cables are similar. Although there is more than one way to
construct a cable and no one standard to which all vendors will adhere, most cables tend to have
common characteristics.
 Low voltage power and control cables pertain to electrical cables that typically have a voltage
grade of 0.6/1 kV or below.
 Low voltage instrumentation cables pertain to cables for use in instrument applications and
typically have a voltage grade of 450/750 V or below.
 Medium / High voltage cables pertain to cables used for electric power transmission at madium
and high voltage (usually from 1 to 33 kV are medium voltage cables and those over 50 kV are
high voltage cables).
Cable Parts
Here, we will take a short overview of the main and the most typical cable construction parts:
Conductor
Usually stranded copper (Cu) or aluminium (Al). Copper is densier and heavier, but more conductive
than aluminium. Electrically equivalent aluminium conductors have a cross-sectional area
approximately 1.6 times larger than copper, but are half the weight (which may save on material
cost).
Annealing – is the process of gradually heating and cooling the conductor material to make it more
malleable and less brittle.
Coating – surface coating (eg. tin, nickel, silver, lead alloy) of copper conductors is common to
prevent the insulation from attacking or adhering to the copper conductor and prevents deterioration
of copper at high temperatures. Tin coatings were used in the past to protect against corrosion from
rubber insulation, which contained traces of the sulfur used in the vulcanising process.
Conductor Screen
A semi-conducting tape to maintain a uniform electric field and minimise electrostatic stresses (for
MV/HV power cables).
Insulation
Commonly thermoplastic (eg. PVC) or thermosetting (eg. EPR, XLPE) type materials. Mineral insulation
is sometimes used, but the construction of MI cables are entirely different to normal plastic / rubber
insulated cables. Typically a thermosetting(eg. EPR, XLPE) or paper/lead insulation for cables under
22kV. Paper-based insulation in combination with oil or gas-filled cables are generally used for higher
voltages.
Plastics are one of the more commonly used types of insulating materials for electrical conductors. It
has good insulating, flexibility, and moisture-resistant qualities. Although there are many types of
plastic insulating materials, thermoplastic is one of the most common. With the use of thermoplastic,
the conductor temperature can be higher than with some other types of insulating materials without
damage to the insulating quality of the material. Plastic insulation is normally used for low- or
medium-range voltage.
The designators used with thermoplastics are much like those used with rubber insulators. The
following letters are used when dealing with NEC type designators for thermoplastics:
T - Thermoplastic
H - Heat-resistant
W - Moisture-resistant
A - Asbestos
N - Outer nylon jacket
M - Oil-resistant
Paper has little insulation value alone. However, when impregnated with a high grade of mineral oil, it
serves as a satisfactory insulation for extremely high-voltage cables. The oil has a high dielectric
strength, and tends to prevent breakdown of the paper insulation. The paper must be thoroughly
saturated with the oil. The thin paper tape is wrapped in many layers around the conductors, and then
soaked with oil.
Enamel: the wire used on the coils of meters, relays, small transformers, motor windings, and so
forth, is called magnet wire. This wire is insulated with an enamel coating. The enamel is a synthetic
compound of cellulose acetate (wood pulp and magnesium). In the manufacturing process, the bare
wire is passed through a solution of hot enamel and then cooled. This process is repeated until the
wire acquires from 6 to 10 coatings. Thickness for thickness, enamel has higher dielectric strength
than rubber. It is not practical for large wires because of the expense and because the insulation is
readily fractured when large wires are bent.
Mineral-insulated (MI) cable was developed to meet the needs of a noncombustible, high heat-
resistant, and water-resistant cable. MI cable has from one to seven electrical conductors. These
conductors are insulated in a highly compressed mineral, normally magnesium oxide, and sealed in a
liquidtight, gastight metallic tube, normally made of seamless copper.
Silk and Cotton: in certain types of circuits (for example, communications circuits), a large number
of conductors are needed, perhaps as many as several hundred. Because the insulation in this type of
cable is not subjected to high voltage, the use of thin layers of silk and cotton is satisfactory.
Silk and cotton insulation keeps the size of the cable small enough to be handled easily. The silk and
cotton threads are wrapped around the individual conductors in reverse directions. The covering is
then impregnated with a special wax compound.
Insulation Screen
A semi-conducting material that has a similar function as the conductor screen (ie. control of the
electric field for MV/HV power cables).
Conductor Sheath
A conductive sheath / shield, typically of copper tape or sometimes lead alloy, is used as a shield to
keep electromagnetic radiation in, and also provide a path for fault and leakage currents (sheaths are
earthed at one cable end). Lead sheaths are heavier and potentially more difficult to terminate than
copper tape, but generally provide better earth fault capacity.
Filler
The interstices of the insulated conductor bundle is sometimes filled, usually with a soft polymer
material.
Bedding / Inner Sheath
Typically a thermoplastic (eg. PVC) or thermosetting (eg. CSP) compound, the inner sheath is there to
keep the bundle together and to provide a bedding for the cable armour.
Individual Screen (Instrument Cables)
An individual screen is occasionally applied over each insulated conductor bundle for shielding against
noise / radiation and interference from other conductor bundles. Screens are usually a metallic
(copper, aluminium) or semi-metallic (PETP/Al) tape or braid. Typically used in instrument cables, but
not in power cables.
Drain Wire (Instrument Cables)
Each screen has an associated drain wire, which assists in the termination of the screen. Typically
used in instrument cables, but not in power cables.
Overall Screen (Instrument Cables)
An overall screen is applied over all the insulated conductor bundles for shielding against noise /
radiation, interference from other cables and surge / lightning protection. Screens are usually a
metallic (copper, aluminium) or semi-metallic (PETP/Al) tape or braid. Typically used in instrument
cables, but not in power cables.
Armour
For mechanical protection of the conductor bundle. Steel wire armour or braid is typically used.
Tinning or galvanising is used for rust prevention. Phosphor bronze or tinned copper braid is also used
when steel armour is not allowed.
 SWA - Steel wire armour, used in multi-core cables (magnetic),
 AWA - Aluminium wire armour, used in single-core cables (non-magnetic).
When an electric current passes through a cable it produces a magnetic field (the higher the
voltage the bigger the field). The magnetic field will induce an electric current in steel armour
(eddy currents), which can cause overheating in AC systems. The non-magnetic aluminium
armour prevents this from happening.
Outer Sheath
Applied over the armour for overall mechanical, weather, chemical and electrical protection.
Typically a thermoplastic (eg. PVC) or thermosetting(eg. CSP) compound, and often the same
material as the bedding. Outer sheath is normally colour coded to differentiate between LV, HV
and instrumentation cables. Manufacturer’s markings and length markings are also printed on
the outer sheath.
Termite Protection
For underground cables, a nylon jacket can be applied for termite protection, although
sometimes a phosphor bronze tape is used.
Conductor Protection (Appendix)
Wires and cables are generally subject to abuse. The type and amount of abuse depends on how
and where they are installed and the manner in which they are used. Cables buried directly in
the ground must resist moisture, chemical action, and abrasion. Wires installed in buildings must
be protected against mechanical injury and overloading. Wires strung on crossarms on poles
must be kept far enough apart so that the wires do not touch. Snow, ice, and strong winds make
it necessary to use conductors having high tensile strength and substantial frame structures.
Generally, except for overhead transmission lines, wires or cables are protected by some form of
covering. The covering may be some type of insulator like rubber or plastic. Over this, additional
layers of fibrous braid or tape may be used and then covered with a finish or saturated with a
protective coating. If the wire or cable is installed where it is likely to receive rough treatment, a
metallic coat should be added.
The materials used to make up the conductor protection for a wire or cable are grouped into one
of two categories: non-metallic or metallic.
Non-Metallic
The category of non-metallic protective coverings is divided into three areas. These areas are:
(1) according to the material used as the covering,
(2) according to the saturant in which the covering was impregnated, and
(3) according to the external finish on the wire or cable.
These three areas reflect three different methods of protecting the wire or cable. These
methods allow some wire or cable to be classified under more than one category. Most of
the time, however, the wire or cable will be classified based upon the material used as the
covering regardless of whether or not a saturant or finish is applied.
Many types of non-metallic materials are used to protect wires and cables. Fibrous braid is
by far the most common and will be discussed first.
Fibrous Braid
Fibrous braid is used extensively as a protective covering for cables. This braid is woven
over the insulation to form a continuous covering without joints. The braid is generally
saturated with asphalt, paint, or varnish to give added protection against moisture, flame,
weathering, oil, or acid. Additionally, the outside braid is often given a finish of stearin pitch
and mica flakes, paint, wax, lacquer, or varnish depending on the environment where the
cable is to be used.
Woven Covers
Woven covers, commonly called loom, are used when exceptional abrasion-resistant
qualities are required. These covers are composed of thick, heavy, long-fibered cotton yarns
woven around the cable in a circular loom, much like that used on a fire hose. They are not
braids, although braid covering are also woven; they are designated differently.
Rubber and Synthetic Coverings
Rubber and synthetic coverings are not standardized. Different manufactures have their
own special compounds designated by individual trade names. These compounds are
different from the rubber compounds used to insulate cable. These compounds have been
perfected not for insulation qualities but for resistance to abrasion, moisture, oil, gasoline,
acids, earth solutions, and alkalies. None of these coverings will provide protection against
all types of exposure. Each covering has its own particular limitations and qualifications.
Jute and Asphalt Coverings
Jute and asphalt coverings are commonly used as a cushion between cable insulation and
metallic armour. Frequently, they are also used as a corrosive-resistant covering over a
lead sheath or metallic armour. Jute and asphalt coverings consist of asphalt-impregnated
jute yarn heli-wrapped around the cable or of alternate layers of asphalt-impregnated jute
yarn. These coverings serve as a weatherproofing.
Unspun Felted Cotton
Unspun felted cotton is commonly used only in special classes of service. It is made as a
solid felted covering for a cable.
Metallic
Metallic protection is of two types: sheath or armour. As with all wires and cables, the type
of protection needed will depend on the environment where the wire or cable will be used.
Metallic Sheath
Cables or wires that are continually subjected to water must be protected by a watertight
cover. This watertight cover is either a continuous metal jacket or a rubber sheath molded
around the cable.
Lead-sheathed cable is one of three types currently being used: alloy lead, pure lead, and
reinforced lead. An alloy-lead sheath is much like a pure lead sheath but is manufactured
with 2-percent tin. This alloy is more resistant to gouging and abrasion during and after
installation. Reinforced lead sheath is used mainly for oil-filled cables where high internal
pressures can be expected. Reinforced lead sheath consists of a double lead sheath. A thin
tape of hard-drawn copper, bronze, or other elastic metal (preferably nonmagnetic) is
wrapped around the inner sheath. This tape gives considerable additional strength and
elasticity to the sheath, but must be protected from corrosion. For this reason, a second
lead sheath is applied over the tape.
Metallic Armour
Metallic armour provides a tough protective covering for wires and cables. The type,
thickness, and kind of metal used to make the armour depend on three factors:
(1) the use of the conductors,
(2) the environment where the conductors are to be used, and
(3) the amount of rough treatment that is expected.
1. Wire-braid armour
Wire-braid armour, also known as basket-weave armour, is used when light and
flexible protection is needed. Wire braid is constructed much like fibrous braid. The
metal is woven directly over the cable as the outer covering. The metal used in this
braid is galvanized steel, bronze, copper, or aluminum. Wire-braid armour is mainly
for shipboard use.
2. Steel tape
A second type of metallic armour is steel tape. Steel tape covering is wrapped around
the cable and then covered with a serving of jute. There are two types of steel tape
armour. The first is called interlocking armour. Interlocking armour is applied by
wrapping the tape around the cable so that each turn is overlapped by the next and is
locked in place. The second type is flat- band armour. Flat-band armour consists of
two layers of steel tape. The first layer is wrapped around the cable but is not
overlapped. The second layer is then wrapped around the cable covering the area that
was not covered by the first layer.
3. Wire armour
Wire armour is a layer of wound metal wire wrapped around the cable. Wire armour is
usually made of galvanized steel and can be used over a lead sheath (see view C of
the figure above). It can be used with the sheath as a buried cable where moisture is
a concern, or without the sheath when used in buildings.
4. Coaxial cable
Coaxial cable is defined as two concentric wires, cylindrical in shape, separated by a
dielectric of some type. One wire is the center conductor and the other is the outer
conductor. These conductors are covered by a protective jacket. The protective jacket
is then covered by an outer protective armour.
Coaxial cables are used as transmission lines and are constructed to provide protection
against outside signal interference.
Low Voltage Power and Control Cables
Low voltage power and control cables pertain to electrical cables that typically have a
voltage grade of 0.6/1 kV or below.
Armoured FAS Cable
An important item that is under the grouping known as 'Low Voltage Cables', is Type
FAS (Fire Alarm & Signal Cable). This 300-volt cable, is specifically designed for the
interconnection of security system elements, including fire protection signalling
devices such as smoke and fire detectors, fire alarms, and two-way emergency
communications systems.
Fire alarm installations in non-combustible buildings require mechanical protection,
consisting of interlock armour, metallic conduit, non-metallic conduit embedded in
concrete or installed under-ground. Armoured FAS Cable provided with an interlocking
aluminum armour, may be expected to have an appreciable cost advantage, compared
with cables installed in rigid conduit.
Other common cables are LVT (Low Voltage Thermoplastic) and ELC (Extra Low
Voltage Control), which are frequently used in residential installations for such items
as door bells and thermostats.
Low Voltage Instrumentation Cables
Instrumentation cables
Low voltage instrumentation cables pertain to cables for use in instrument applications
and typically have a voltage grade of 450/750 V or below.
Instrumentation Cables rated at 300 volts have copper conductors 0.33 mm2
(#22
AWG) to 2.08 mm2
(#14 AWG), while those rated at 600 volts have 0.82 mm2
(#18
AWG) to 5.26 mm2
(#10 AWG), and unarmoured and armoured types are available.
The cables may be an assembly of single conductors, pairs, triads or quads. The
conductors are stranded seven-wire tinned or bare copper. The insulation is usually a
PVC compound chosen dependant on the environment for which it is intended.
Insulated conductors are paired with staggered lays to prevent electromagnetic
coupling and crosstalk. When individual shielding is specified, each pair is
aluminum/polyester shielded with drain wire to eliminate electrostatic interference.
Armoured cables have an interlocked aluminum or galvanized steel armour. The
armouring is applied over an inner PVC jacket, followed by a PVC outer jacket.
Armoured cables are suitable for installation on cable trays in dry, damp and wet
locations, or direct earth burial.
Unarmoured Instrumentation Cables are intended for installation in raceways/conduit
(except cable trays) in dry, damp or wet locations, or direct earth buried. Unarmoured
Cable with Type TC (Tray Cable) designation, may be installed in cable trays.
Thermocouple Extension Cables
Thermocouple Extension Cables have a 300 volt rating, and are of similar construction
to Instrumentation Cables, but the metals/alloys used for the conductors are different.
Thermocouples measure temperature using the electric current created when heat is
applied to two dissimilar metals/alloys. The cable assembles may consist of as many
as 50 pairs, depending on the number of locations being temperature monitored.
Medium / High Voltage Power Cables
Medium or High Voltage power cables have voltage grade greater than 1 kV. Medium
voltage usually goes up to 46 kV and High voltage is considering all voltage levels
above 46 kV.
Medium Voltage distribution systems begin at substations and supply electricity to a
wide spectrum of power consumers. When selecting a cable, the basic aim is to safely
provide adequate electrical power, with continuous, trouble-free operation, in a system
that is able to withstand unexpected demands and overload conditions. Each
installation has particular requirements that must be considered. There are distinct
benefits from specifying a copper-conductor cable that has been manufactured under
rigid specification and quality control procedures. It will provide maximum
performance with minimum maintenance. There are seven types different by
construction for medium voltage copper power cables in the 1 kV to 46 kV range. Most
are available in single- and multi-core configurations. There are ranges of sizes and
design variations for each type.
The MV cable types are:
 Teck Cables,
 Shielded Cables,
 Concentric Neutral Cables,
 Paper-Insulated Lead-Covered Cables,
 Submarine Cables,
 Mining Cables,
 Aluminum-Sheathed Cables.
In the cable descriptions a number of insulation and sheath (jacket) materials have
been abbreviated as follows:
 Cross-Linked Polyethylene - XLPE,
 Ethylene-Propylene Rubber - EPR,
 Polyvinyl Chloride - PVC,
 Polyethylene - PE,
 Tree-Retardant Cross-Linked Polyethylene - TR-XLPE.
Teck Cables
Teck Cables were originally developed for use in mines, but they are now widely used
in primary and secondary industries, chemical plants, refineries and general factory
environments. They are also used in multi-storey and commercial buildings. They are
flexible, resistant to mechanical abuse, corrosion resistant, compact and reliable. A
modified Teck Cable construction may be used for vertical installations, such as in
mine shafts and multi-storey buildings, where the armour is locked-in-place to prevent
slippage of the inner core. There are many different combinations of conductor size,
voltage rating, armour type and so forth, available in Teck Cables to meet the
requirements of particular installations. Annealed, bare, copper is used for the
conductor (s), and they are usually compact stranded to reduce diameter. In multi-
conductor cables, the insulated conductors are cabled together, including the bare
copper bonding (grounding) conductor. In shielded multi-conductor cables, the
bonding (grounding) conductor is positioned to contact the copper shields. A PVC outer
jacket which may be colour-coded depending on the rating of the cable is applied.
Shielded Cables
Shielded Power Cable may be single-or three-conductor. The basic construction begins
with a conductor of annealed, bare, solid or concentric-stranded copper, which may be
compact or compressed. This is followed by a semi-conducting conductor shield,
insulation, and then a semi-conducting insulation shield. Metallic shielding follows,
which is usually either gapped or lapped copper tape. Other types of metallic shielding
are available, including concentric wires and longitudinally corrugated copper tape.
The outer jacket is either PVC or PE.
Concentric Neutral Cables
These power cables may be used in dry or wet locations, for a wide variety of types of
installations, and may be single- or three-conductor. The two standard constructions
are Unjacketed and Jacketed, the latter being most frequently used. The conductor is
typically annealed, bare, stranded copper, but tin-coated wire and solid conductors are
also available. The concentric neutral conductor, from which the cable derives its
name, is bare or tin-coated copper wire, applied helically over the insulation shield.
These wires act as the metallic component of the shield and the neutral, at the same
time.
Paper-Insulated Lead-Covered Cables (PILC)
PILC cables are used in power distribution and industrial applications, and they may be
installed exposed, in underground ducts or directly buried. Their design begins with
annealed, bare copper conductor(s) which may be round, concentric, compressed or
compact stranded, compact sector, and in larger sizes … Type M segmental stranded.
An example of compact sector conductors is shown in the illustration. The insulated
cable core is impregnated with a medium viscosity polybutene-based compound. The
combination of the excellent electrical and mechanical characteristics of the liquid and
the paper has resulted in a reliable and economic insulation, which now claims a
history of almost 100 years. It is little wonder why so many utilities and power-
consuming industries, still continue to specify PILC. To prevent the ingress of
moisture, a seamless lead-alloy sheath is applied. The outer jacket may be PVC or PE,
and if required by the application, armour is available.
Submarine Cables
For submarine installations, usually Self-Contained Liquid-Filled Cables (SCLF), or
Solid Dielectric Cables are selected, depending on voltage and power load. SCLF
Cables are capable of handling very high voltages. However, for medium-voltage
installations, a Solid Dielectric Cable can easily fulfil the electrical demands of the
system. A submarine Solid Dielectric Cable is shown in the illustration. Its construction
begins with a compact stranded, annealed, bare copper conductor, followed by a semi-
conducting conductor shield. A copper tape shield is helically applied, followed by a
lead-alloy sheath. Due to the severe environmental demands placed on submarine
cables, a lead-alloy sheath is often specified because of its compressibility, flexibility
and resistance to moisture and corrosion. The sheath is usually covered by a number
of outer layers, comprising a PE or PVC jacket and metal wire armouring.
Mining Cables
A number of different types of cables are used in mines. There are fixed mining cables
and portable mining cables, the latter being described here. The key requirements of
portable cables are flexibility, and resistance to mechanical abrasion and damage. Due
to the additional demands put on portable mining cables used for reeling and dereeling
applications, special design may be required. There are many types of portable mining
cables. They are available in ratings up to 25 kV, and may have as many as five
conductors. An example of SHD-GC Cable, is shown in the illustration. It has three
insulated, shielded conductors, two bare ground wires, a ground check wire, and an
overall jacket. The conductors for this cable are annealed, bare or tinned copper wires.
The braided shield may be tin-coated wires, or a tin-coated copper wire/textile
composite. The grounding conductor(s) annealed, bare or tinned, stranded copper
wires, and the ground check conductor is annealed, bare, stranded copper wires with
EPR insulation and nylon braid, elastomeric jacket holds the conductor assembly firmly
in place, to minimize snaking and cork-screwing during reeling and dereeling.
Aluminum-Sheathed Cables
These power cables are used for exposed and concealed wiring, in wet and dry
locations, and where exposed to the weather. They may be installed in ventilated,
unventilated and ladder-type cable-troughs, and ventilated flexible cableways.
Aluminum-Sheathed Power Cables may be single-,two-,three- or four-conductor, the
conductor(s) being annealed, bare, compressed-round stranded copper. The insulated
core is enclosed in a liquid- and vapour-tight solid corrugated aluminum sheath,
covered by a PVC jacket.
Teck Cable
overview
Shielded
Cable
overview
Concentric
Neutral Cable
overview
Paper-
Insulated
Lead-Covered
Cable
overview
Submarine
Cable
overview
Mining Cable
overview
Aluminum-
Sheathed
Cable
overview
Trivia
References
 http://metechakir.blogspot.de/
 http://coppercanada.ca/publications/pub27e/27e-section8.htm
 http://www.otds.co.uk/cables.php
Source:
http://www.openelectrical.org/wiki/index.php?title=Teck_Cable#Teck_Cables

Más contenido relacionado

La actualidad más candente

Pfisterer Cable Fittings 11kV 33kV 52kV - Pfisterer MV-CONNEX Inner Cone Plug...
Pfisterer Cable Fittings 11kV 33kV 52kV - Pfisterer MV-CONNEX Inner Cone Plug...Pfisterer Cable Fittings 11kV 33kV 52kV - Pfisterer MV-CONNEX Inner Cone Plug...
Pfisterer Cable Fittings 11kV 33kV 52kV - Pfisterer MV-CONNEX Inner Cone Plug...Thorne & Derrick International
 
RAYCHEM SAUDI ARABIA LTD. (TYCO ELECTRONICS) Raychem terminations for polymer...
RAYCHEM SAUDI ARABIA LTD. (TYCO ELECTRONICS) Raychem terminations for polymer...RAYCHEM SAUDI ARABIA LTD. (TYCO ELECTRONICS) Raychem terminations for polymer...
RAYCHEM SAUDI ARABIA LTD. (TYCO ELECTRONICS) Raychem terminations for polymer...AKBAR TRADING
 
Electrical Wiring:Types of wires and Cables and the circuit control on domest...
Electrical Wiring:Types of wires and Cables and the circuit control on domest...Electrical Wiring:Types of wires and Cables and the circuit control on domest...
Electrical Wiring:Types of wires and Cables and the circuit control on domest...maharshi solanki
 
Principles of Cable Selection
Principles of Cable SelectionPrinciples of Cable Selection
Principles of Cable SelectionLeonardo ENERGY
 
UNIT - 06 TRANSMISSION LINES AND SUBSTATIONS
UNIT - 06 TRANSMISSION LINES AND SUBSTATIONSUNIT - 06 TRANSMISSION LINES AND SUBSTATIONS
UNIT - 06 TRANSMISSION LINES AND SUBSTATIONSPremanandDesai
 
wiring Part 3: wires & cables
wiring Part 3: wires & cableswiring Part 3: wires & cables
wiring Part 3: wires & cablesvigyanashram
 
Power cable - Voltage drop
Power cable - Voltage dropPower cable - Voltage drop
Power cable - Voltage dropLeonardo ENERGY
 
Nexans Euromold K400TB 630A 24kV Bolted Tee Connectors 35-300sqmm - Nexans Eu...
Nexans Euromold K400TB 630A 24kV Bolted Tee Connectors 35-300sqmm - Nexans Eu...Nexans Euromold K400TB 630A 24kV Bolted Tee Connectors 35-300sqmm - Nexans Eu...
Nexans Euromold K400TB 630A 24kV Bolted Tee Connectors 35-300sqmm - Nexans Eu...Thorne & Derrick International
 
Equipments of power transmission
Equipments of power transmissionEquipments of power transmission
Equipments of power transmissionRasika Ghongade
 
Types of conductors in high termission lines
Types of conductors in high termission linesTypes of conductors in high termission lines
Types of conductors in high termission linesJeevn Ln Gowda
 

La actualidad más candente (20)

Pfisterer Cable Fittings 11kV 33kV 52kV - Pfisterer MV-CONNEX Inner Cone Plug...
Pfisterer Cable Fittings 11kV 33kV 52kV - Pfisterer MV-CONNEX Inner Cone Plug...Pfisterer Cable Fittings 11kV 33kV 52kV - Pfisterer MV-CONNEX Inner Cone Plug...
Pfisterer Cable Fittings 11kV 33kV 52kV - Pfisterer MV-CONNEX Inner Cone Plug...
 
RAYCHEM SAUDI ARABIA LTD. (TYCO ELECTRONICS) Raychem terminations for polymer...
RAYCHEM SAUDI ARABIA LTD. (TYCO ELECTRONICS) Raychem terminations for polymer...RAYCHEM SAUDI ARABIA LTD. (TYCO ELECTRONICS) Raychem terminations for polymer...
RAYCHEM SAUDI ARABIA LTD. (TYCO ELECTRONICS) Raychem terminations for polymer...
 
Cable
CableCable
Cable
 
Electrical wiring
Electrical wiringElectrical wiring
Electrical wiring
 
Basics of Wires and Cables
Basics of Wires and CablesBasics of Wires and Cables
Basics of Wires and Cables
 
Contents sre cable tray
Contents sre cable trayContents sre cable tray
Contents sre cable tray
 
Electrical Wiring:Types of wires and Cables and the circuit control on domest...
Electrical Wiring:Types of wires and Cables and the circuit control on domest...Electrical Wiring:Types of wires and Cables and the circuit control on domest...
Electrical Wiring:Types of wires and Cables and the circuit control on domest...
 
Principles of Cable Selection
Principles of Cable SelectionPrinciples of Cable Selection
Principles of Cable Selection
 
UNIT - 06 TRANSMISSION LINES AND SUBSTATIONS
UNIT - 06 TRANSMISSION LINES AND SUBSTATIONSUNIT - 06 TRANSMISSION LINES AND SUBSTATIONS
UNIT - 06 TRANSMISSION LINES AND SUBSTATIONS
 
wiring Part 3: wires & cables
wiring Part 3: wires & cableswiring Part 3: wires & cables
wiring Part 3: wires & cables
 
Power cable - Voltage drop
Power cable - Voltage dropPower cable - Voltage drop
Power cable - Voltage drop
 
Underground cable
Underground cableUnderground cable
Underground cable
 
Cable
CableCable
Cable
 
Nexans Euromold K400TB 630A 24kV Bolted Tee Connectors 35-300sqmm - Nexans Eu...
Nexans Euromold K400TB 630A 24kV Bolted Tee Connectors 35-300sqmm - Nexans Eu...Nexans Euromold K400TB 630A 24kV Bolted Tee Connectors 35-300sqmm - Nexans Eu...
Nexans Euromold K400TB 630A 24kV Bolted Tee Connectors 35-300sqmm - Nexans Eu...
 
cables y cadenas de maquinas de elevacion
cables y cadenas de maquinas de elevacioncables y cadenas de maquinas de elevacion
cables y cadenas de maquinas de elevacion
 
Underground cables (1)
Underground cables  (1)Underground cables  (1)
Underground cables (1)
 
Underground cables
Underground cablesUnderground cables
Underground cables
 
Conductores electricos
Conductores electricosConductores electricos
Conductores electricos
 
Equipments of power transmission
Equipments of power transmissionEquipments of power transmission
Equipments of power transmission
 
Types of conductors in high termission lines
Types of conductors in high termission linesTypes of conductors in high termission lines
Types of conductors in high termission lines
 

Similar a Cable construction

Module 04 - Cables.pptx
Module 04 - Cables.pptxModule 04 - Cables.pptx
Module 04 - Cables.pptxZahid Yousaf
 
cable,Different distribution lines and Insulator
cable,Different distribution lines and Insulatorcable,Different distribution lines and Insulator
cable,Different distribution lines and InsulatorSuryakant Morey
 
Power cables-160211193139
Power cables-160211193139Power cables-160211193139
Power cables-160211193139Bilal Jutt
 
Types of cables
Types of cables Types of cables
Types of cables Nisarg Amin
 
Under ground cables
Under ground cablesUnder ground cables
Under ground cablesMohsin Mulla
 
TTypes of cables
TTypes of cablesTTypes of cables
TTypes of cablesJAY THAKAR
 
Project on Cable and its classification
Project on Cable and its classificationProject on Cable and its classification
Project on Cable and its classificationSOMNATH DAS
 
Electrical wiring project
Electrical wiring projectElectrical wiring project
Electrical wiring projectsam zion
 
Types of wires and cables
Types of wires and cablesTypes of wires and cables
Types of wires and cablesDhruvit Kardani
 
Electrical installation & maintenance
Electrical installation & maintenanceElectrical installation & maintenance
Electrical installation & maintenancePenaflorida Roel
 
types of cables .pptx
types of cables                    .pptxtypes of cables                    .pptx
types of cables .pptxObaidRehman81
 
Cables and Wires
Cables and WiresCables and Wires
Cables and WiresChandan K B
 
T&D GP.ppt
T&D GP.pptT&D GP.ppt
T&D GP.ppt52VikasV
 
Basics of electrical engineering
Basics of electrical engineeringBasics of electrical engineering
Basics of electrical engineeringNishkam Dhiman
 
types-of-wires-and-cables-55d0a2978b93e.ppt
types-of-wires-and-cables-55d0a2978b93e.ppttypes-of-wires-and-cables-55d0a2978b93e.ppt
types-of-wires-and-cables-55d0a2978b93e.pptaroldy
 
Types of Wires and Cables
Types of Wires and CablesTypes of Wires and Cables
Types of Wires and CablesOsama Naseem
 

Similar a Cable construction (20)

Module 04 - Cables.pptx
Module 04 - Cables.pptxModule 04 - Cables.pptx
Module 04 - Cables.pptx
 
cable,Different distribution lines and Insulator
cable,Different distribution lines and Insulatorcable,Different distribution lines and Insulator
cable,Different distribution lines and Insulator
 
Power cables-160211193139
Power cables-160211193139Power cables-160211193139
Power cables-160211193139
 
Types of cables
Types of cables Types of cables
Types of cables
 
Under ground cables
Under ground cablesUnder ground cables
Under ground cables
 
TTypes of cables
TTypes of cablesTTypes of cables
TTypes of cables
 
Project on Cable and its classification
Project on Cable and its classificationProject on Cable and its classification
Project on Cable and its classification
 
Electrical wiring project
Electrical wiring projectElectrical wiring project
Electrical wiring project
 
Types of wires and cables
Types of wires and cablesTypes of wires and cables
Types of wires and cables
 
Types of cables
Types of cablesTypes of cables
Types of cables
 
A Study of Insulators
A Study of InsulatorsA Study of Insulators
A Study of Insulators
 
UNDERGROUND CABLE
UNDERGROUND CABLEUNDERGROUND CABLE
UNDERGROUND CABLE
 
Electrical installation & maintenance
Electrical installation & maintenanceElectrical installation & maintenance
Electrical installation & maintenance
 
types of cables .pptx
types of cables                    .pptxtypes of cables                    .pptx
types of cables .pptx
 
Types of wires and cables
Types of wires and cablesTypes of wires and cables
Types of wires and cables
 
Cables and Wires
Cables and WiresCables and Wires
Cables and Wires
 
T&D GP.ppt
T&D GP.pptT&D GP.ppt
T&D GP.ppt
 
Basics of electrical engineering
Basics of electrical engineeringBasics of electrical engineering
Basics of electrical engineering
 
types-of-wires-and-cables-55d0a2978b93e.ppt
types-of-wires-and-cables-55d0a2978b93e.ppttypes-of-wires-and-cables-55d0a2978b93e.ppt
types-of-wires-and-cables-55d0a2978b93e.ppt
 
Types of Wires and Cables
Types of Wires and CablesTypes of Wires and Cables
Types of Wires and Cables
 

Más de vishal laddha

Case study on EHTC.pdf
Case study on EHTC.pdfCase study on EHTC.pdf
Case study on EHTC.pdfvishal laddha
 
Super critcal_sub critical_higher capacity sets - Copy.pdf
Super critcal_sub critical_higher capacity sets - Copy.pdfSuper critcal_sub critical_higher capacity sets - Copy.pdf
Super critcal_sub critical_higher capacity sets - Copy.pdfvishal laddha
 
Real Python 🐍👨_💻-1.pdf
Real Python 🐍👨_💻-1.pdfReal Python 🐍👨_💻-1.pdf
Real Python 🐍👨_💻-1.pdfvishal laddha
 
Brief Writeup on BCVMS.pdf
Brief Writeup on BCVMS.pdfBrief Writeup on BCVMS.pdf
Brief Writeup on BCVMS.pdfvishal laddha
 
BASICS OF VIBRATION.ppt
BASICS OF VIBRATION.pptBASICS OF VIBRATION.ppt
BASICS OF VIBRATION.pptvishal laddha
 
EXCITATION SYSTEM.ppt
EXCITATION SYSTEM.pptEXCITATION SYSTEM.ppt
EXCITATION SYSTEM.pptvishal laddha
 
December'2022 Maintenance review1.pptx
December'2022 Maintenance review1.pptxDecember'2022 Maintenance review1.pptx
December'2022 Maintenance review1.pptxvishal laddha
 
Case Studies on Vibrations.ppt
Case Studies on Vibrations.pptCase Studies on Vibrations.ppt
Case Studies on Vibrations.pptvishal laddha
 
Assignment business comm
Assignment business commAssignment business comm
Assignment business commvishal laddha
 
Plant operation manual
Plant operation manualPlant operation manual
Plant operation manualvishal laddha
 
Cable fault-finding-guide
Cable fault-finding-guideCable fault-finding-guide
Cable fault-finding-guidevishal laddha
 

Más de vishal laddha (20)

Case study on EHTC.pdf
Case study on EHTC.pdfCase study on EHTC.pdf
Case study on EHTC.pdf
 
Super critcal_sub critical_higher capacity sets - Copy.pdf
Super critcal_sub critical_higher capacity sets - Copy.pdfSuper critcal_sub critical_higher capacity sets - Copy.pdf
Super critcal_sub critical_higher capacity sets - Copy.pdf
 
CMC.pptx
CMC.pptxCMC.pptx
CMC.pptx
 
Gun Kaizen.pptx
Gun Kaizen.pptxGun Kaizen.pptx
Gun Kaizen.pptx
 
MAR,23.pptx
MAR,23.pptxMAR,23.pptx
MAR,23.pptx
 
Real Python 🐍👨_💻-1.pdf
Real Python 🐍👨_💻-1.pdfReal Python 🐍👨_💻-1.pdf
Real Python 🐍👨_💻-1.pdf
 
Brief Writeup on BCVMS.pdf
Brief Writeup on BCVMS.pdfBrief Writeup on BCVMS.pdf
Brief Writeup on BCVMS.pdf
 
BASICS OF VIBRATION.ppt
BASICS OF VIBRATION.pptBASICS OF VIBRATION.ppt
BASICS OF VIBRATION.ppt
 
Flame Scanner.ppt
Flame Scanner.pptFlame Scanner.ppt
Flame Scanner.ppt
 
EXCITATION SYSTEM.ppt
EXCITATION SYSTEM.pptEXCITATION SYSTEM.ppt
EXCITATION SYSTEM.ppt
 
HR.pptx
HR.pptxHR.pptx
HR.pptx
 
battery.ppt
battery.pptbattery.ppt
battery.ppt
 
December'2022 Maintenance review1.pptx
December'2022 Maintenance review1.pptxDecember'2022 Maintenance review1.pptx
December'2022 Maintenance review1.pptx
 
Case Studies on Vibrations.ppt
Case Studies on Vibrations.pptCase Studies on Vibrations.ppt
Case Studies on Vibrations.ppt
 
Assignment business comm
Assignment business commAssignment business comm
Assignment business comm
 
Assignment accounts
Assignment  accountsAssignment  accounts
Assignment accounts
 
Assignment hrm
Assignment hrmAssignment hrm
Assignment hrm
 
Plant operation manual
Plant operation manualPlant operation manual
Plant operation manual
 
Hplpbp
HplpbpHplpbp
Hplpbp
 
Cable fault-finding-guide
Cable fault-finding-guideCable fault-finding-guide
Cable fault-finding-guide
 

Último

Thermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - VThermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - VDineshKumar4165
 
Unit 2- Effective stress & Permeability.pdf
Unit 2- Effective stress & Permeability.pdfUnit 2- Effective stress & Permeability.pdf
Unit 2- Effective stress & Permeability.pdfRagavanV2
 
notes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.pptnotes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.pptMsecMca
 
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Bookingdharasingh5698
 
KubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlyKubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlysanyuktamishra911
 
University management System project report..pdf
University management System project report..pdfUniversity management System project report..pdf
University management System project report..pdfKamal Acharya
 
chapter 5.pptx: drainage and irrigation engineering
chapter 5.pptx: drainage and irrigation engineeringchapter 5.pptx: drainage and irrigation engineering
chapter 5.pptx: drainage and irrigation engineeringmulugeta48
 
Work-Permit-Receiver-in-Saudi-Aramco.pptx
Work-Permit-Receiver-in-Saudi-Aramco.pptxWork-Permit-Receiver-in-Saudi-Aramco.pptx
Work-Permit-Receiver-in-Saudi-Aramco.pptxJuliansyahHarahap1
 
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdfONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdfKamal Acharya
 
Block diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.pptBlock diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.pptNANDHAKUMARA10
 
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Bookingdharasingh5698
 
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night StandCall Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Standamitlee9823
 
data_management_and _data_science_cheat_sheet.pdf
data_management_and _data_science_cheat_sheet.pdfdata_management_and _data_science_cheat_sheet.pdf
data_management_and _data_science_cheat_sheet.pdfJiananWang21
 
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance BookingCall Girls Wakad Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance Bookingroncy bisnoi
 
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXssuser89054b
 
2016EF22_0 solar project report rooftop projects
2016EF22_0 solar project report rooftop projects2016EF22_0 solar project report rooftop projects
2016EF22_0 solar project report rooftop projectssmsksolar
 
Unleashing the Power of the SORA AI lastest leap
Unleashing the Power of the SORA AI lastest leapUnleashing the Power of the SORA AI lastest leap
Unleashing the Power of the SORA AI lastest leapRishantSharmaFr
 

Último (20)

Thermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - VThermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - V
 
Unit 2- Effective stress & Permeability.pdf
Unit 2- Effective stress & Permeability.pdfUnit 2- Effective stress & Permeability.pdf
Unit 2- Effective stress & Permeability.pdf
 
(INDIRA) Call Girl Bhosari Call Now 8617697112 Bhosari Escorts 24x7
(INDIRA) Call Girl Bhosari Call Now 8617697112 Bhosari Escorts 24x7(INDIRA) Call Girl Bhosari Call Now 8617697112 Bhosari Escorts 24x7
(INDIRA) Call Girl Bhosari Call Now 8617697112 Bhosari Escorts 24x7
 
notes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.pptnotes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.ppt
 
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
 
KubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlyKubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghly
 
University management System project report..pdf
University management System project report..pdfUniversity management System project report..pdf
University management System project report..pdf
 
chapter 5.pptx: drainage and irrigation engineering
chapter 5.pptx: drainage and irrigation engineeringchapter 5.pptx: drainage and irrigation engineering
chapter 5.pptx: drainage and irrigation engineering
 
Work-Permit-Receiver-in-Saudi-Aramco.pptx
Work-Permit-Receiver-in-Saudi-Aramco.pptxWork-Permit-Receiver-in-Saudi-Aramco.pptx
Work-Permit-Receiver-in-Saudi-Aramco.pptx
 
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdfONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
 
Block diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.pptBlock diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.ppt
 
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
 
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak HamilCara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
 
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night StandCall Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
 
data_management_and _data_science_cheat_sheet.pdf
data_management_and _data_science_cheat_sheet.pdfdata_management_and _data_science_cheat_sheet.pdf
data_management_and _data_science_cheat_sheet.pdf
 
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance BookingCall Girls Wakad Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance Booking
 
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
 
2016EF22_0 solar project report rooftop projects
2016EF22_0 solar project report rooftop projects2016EF22_0 solar project report rooftop projects
2016EF22_0 solar project report rooftop projects
 
(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7
(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7
(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7
 
Unleashing the Power of the SORA AI lastest leap
Unleashing the Power of the SORA AI lastest leapUnleashing the Power of the SORA AI lastest leap
Unleashing the Power of the SORA AI lastest leap
 

Cable construction

  • 1. Cable Construction Introduction This article gives a brief exposition on the construction of typical low voltage, medium / high voltage and instrumentation cables. The focus is on thermoplastic and thermosetting insulated cables, however the construction of other cables are similar. Although there is more than one way to construct a cable and no one standard to which all vendors will adhere, most cables tend to have common characteristics.  Low voltage power and control cables pertain to electrical cables that typically have a voltage grade of 0.6/1 kV or below.  Low voltage instrumentation cables pertain to cables for use in instrument applications and typically have a voltage grade of 450/750 V or below.  Medium / High voltage cables pertain to cables used for electric power transmission at madium and high voltage (usually from 1 to 33 kV are medium voltage cables and those over 50 kV are high voltage cables). Cable Parts Here, we will take a short overview of the main and the most typical cable construction parts: Conductor Usually stranded copper (Cu) or aluminium (Al). Copper is densier and heavier, but more conductive than aluminium. Electrically equivalent aluminium conductors have a cross-sectional area approximately 1.6 times larger than copper, but are half the weight (which may save on material cost). Annealing – is the process of gradually heating and cooling the conductor material to make it more malleable and less brittle. Coating – surface coating (eg. tin, nickel, silver, lead alloy) of copper conductors is common to prevent the insulation from attacking or adhering to the copper conductor and prevents deterioration of copper at high temperatures. Tin coatings were used in the past to protect against corrosion from rubber insulation, which contained traces of the sulfur used in the vulcanising process. Conductor Screen A semi-conducting tape to maintain a uniform electric field and minimise electrostatic stresses (for MV/HV power cables). Insulation Commonly thermoplastic (eg. PVC) or thermosetting (eg. EPR, XLPE) type materials. Mineral insulation is sometimes used, but the construction of MI cables are entirely different to normal plastic / rubber insulated cables. Typically a thermosetting(eg. EPR, XLPE) or paper/lead insulation for cables under 22kV. Paper-based insulation in combination with oil or gas-filled cables are generally used for higher voltages. Plastics are one of the more commonly used types of insulating materials for electrical conductors. It has good insulating, flexibility, and moisture-resistant qualities. Although there are many types of plastic insulating materials, thermoplastic is one of the most common. With the use of thermoplastic, the conductor temperature can be higher than with some other types of insulating materials without
  • 2. damage to the insulating quality of the material. Plastic insulation is normally used for low- or medium-range voltage. The designators used with thermoplastics are much like those used with rubber insulators. The following letters are used when dealing with NEC type designators for thermoplastics: T - Thermoplastic H - Heat-resistant W - Moisture-resistant A - Asbestos N - Outer nylon jacket M - Oil-resistant Paper has little insulation value alone. However, when impregnated with a high grade of mineral oil, it serves as a satisfactory insulation for extremely high-voltage cables. The oil has a high dielectric strength, and tends to prevent breakdown of the paper insulation. The paper must be thoroughly saturated with the oil. The thin paper tape is wrapped in many layers around the conductors, and then soaked with oil. Enamel: the wire used on the coils of meters, relays, small transformers, motor windings, and so forth, is called magnet wire. This wire is insulated with an enamel coating. The enamel is a synthetic compound of cellulose acetate (wood pulp and magnesium). In the manufacturing process, the bare wire is passed through a solution of hot enamel and then cooled. This process is repeated until the wire acquires from 6 to 10 coatings. Thickness for thickness, enamel has higher dielectric strength than rubber. It is not practical for large wires because of the expense and because the insulation is readily fractured when large wires are bent. Mineral-insulated (MI) cable was developed to meet the needs of a noncombustible, high heat- resistant, and water-resistant cable. MI cable has from one to seven electrical conductors. These conductors are insulated in a highly compressed mineral, normally magnesium oxide, and sealed in a liquidtight, gastight metallic tube, normally made of seamless copper. Silk and Cotton: in certain types of circuits (for example, communications circuits), a large number of conductors are needed, perhaps as many as several hundred. Because the insulation in this type of cable is not subjected to high voltage, the use of thin layers of silk and cotton is satisfactory. Silk and cotton insulation keeps the size of the cable small enough to be handled easily. The silk and cotton threads are wrapped around the individual conductors in reverse directions. The covering is then impregnated with a special wax compound. Insulation Screen A semi-conducting material that has a similar function as the conductor screen (ie. control of the electric field for MV/HV power cables). Conductor Sheath A conductive sheath / shield, typically of copper tape or sometimes lead alloy, is used as a shield to keep electromagnetic radiation in, and also provide a path for fault and leakage currents (sheaths are earthed at one cable end). Lead sheaths are heavier and potentially more difficult to terminate than copper tape, but generally provide better earth fault capacity.
  • 3. Filler The interstices of the insulated conductor bundle is sometimes filled, usually with a soft polymer material. Bedding / Inner Sheath Typically a thermoplastic (eg. PVC) or thermosetting (eg. CSP) compound, the inner sheath is there to keep the bundle together and to provide a bedding for the cable armour. Individual Screen (Instrument Cables) An individual screen is occasionally applied over each insulated conductor bundle for shielding against noise / radiation and interference from other conductor bundles. Screens are usually a metallic (copper, aluminium) or semi-metallic (PETP/Al) tape or braid. Typically used in instrument cables, but not in power cables. Drain Wire (Instrument Cables) Each screen has an associated drain wire, which assists in the termination of the screen. Typically used in instrument cables, but not in power cables. Overall Screen (Instrument Cables) An overall screen is applied over all the insulated conductor bundles for shielding against noise / radiation, interference from other cables and surge / lightning protection. Screens are usually a metallic (copper, aluminium) or semi-metallic (PETP/Al) tape or braid. Typically used in instrument cables, but not in power cables. Armour For mechanical protection of the conductor bundle. Steel wire armour or braid is typically used. Tinning or galvanising is used for rust prevention. Phosphor bronze or tinned copper braid is also used when steel armour is not allowed.  SWA - Steel wire armour, used in multi-core cables (magnetic),  AWA - Aluminium wire armour, used in single-core cables (non-magnetic). When an electric current passes through a cable it produces a magnetic field (the higher the voltage the bigger the field). The magnetic field will induce an electric current in steel armour (eddy currents), which can cause overheating in AC systems. The non-magnetic aluminium armour prevents this from happening. Outer Sheath Applied over the armour for overall mechanical, weather, chemical and electrical protection. Typically a thermoplastic (eg. PVC) or thermosetting(eg. CSP) compound, and often the same material as the bedding. Outer sheath is normally colour coded to differentiate between LV, HV and instrumentation cables. Manufacturer’s markings and length markings are also printed on the outer sheath. Termite Protection For underground cables, a nylon jacket can be applied for termite protection, although sometimes a phosphor bronze tape is used.
  • 4. Conductor Protection (Appendix) Wires and cables are generally subject to abuse. The type and amount of abuse depends on how and where they are installed and the manner in which they are used. Cables buried directly in the ground must resist moisture, chemical action, and abrasion. Wires installed in buildings must be protected against mechanical injury and overloading. Wires strung on crossarms on poles must be kept far enough apart so that the wires do not touch. Snow, ice, and strong winds make it necessary to use conductors having high tensile strength and substantial frame structures. Generally, except for overhead transmission lines, wires or cables are protected by some form of covering. The covering may be some type of insulator like rubber or plastic. Over this, additional layers of fibrous braid or tape may be used and then covered with a finish or saturated with a protective coating. If the wire or cable is installed where it is likely to receive rough treatment, a metallic coat should be added. The materials used to make up the conductor protection for a wire or cable are grouped into one of two categories: non-metallic or metallic. Non-Metallic The category of non-metallic protective coverings is divided into three areas. These areas are: (1) according to the material used as the covering, (2) according to the saturant in which the covering was impregnated, and (3) according to the external finish on the wire or cable. These three areas reflect three different methods of protecting the wire or cable. These methods allow some wire or cable to be classified under more than one category. Most of the time, however, the wire or cable will be classified based upon the material used as the covering regardless of whether or not a saturant or finish is applied. Many types of non-metallic materials are used to protect wires and cables. Fibrous braid is by far the most common and will be discussed first. Fibrous Braid Fibrous braid is used extensively as a protective covering for cables. This braid is woven over the insulation to form a continuous covering without joints. The braid is generally saturated with asphalt, paint, or varnish to give added protection against moisture, flame, weathering, oil, or acid. Additionally, the outside braid is often given a finish of stearin pitch and mica flakes, paint, wax, lacquer, or varnish depending on the environment where the cable is to be used. Woven Covers Woven covers, commonly called loom, are used when exceptional abrasion-resistant qualities are required. These covers are composed of thick, heavy, long-fibered cotton yarns woven around the cable in a circular loom, much like that used on a fire hose. They are not braids, although braid covering are also woven; they are designated differently. Rubber and Synthetic Coverings Rubber and synthetic coverings are not standardized. Different manufactures have their own special compounds designated by individual trade names. These compounds are different from the rubber compounds used to insulate cable. These compounds have been perfected not for insulation qualities but for resistance to abrasion, moisture, oil, gasoline,
  • 5. acids, earth solutions, and alkalies. None of these coverings will provide protection against all types of exposure. Each covering has its own particular limitations and qualifications. Jute and Asphalt Coverings Jute and asphalt coverings are commonly used as a cushion between cable insulation and metallic armour. Frequently, they are also used as a corrosive-resistant covering over a lead sheath or metallic armour. Jute and asphalt coverings consist of asphalt-impregnated jute yarn heli-wrapped around the cable or of alternate layers of asphalt-impregnated jute yarn. These coverings serve as a weatherproofing. Unspun Felted Cotton Unspun felted cotton is commonly used only in special classes of service. It is made as a solid felted covering for a cable. Metallic Metallic protection is of two types: sheath or armour. As with all wires and cables, the type of protection needed will depend on the environment where the wire or cable will be used. Metallic Sheath Cables or wires that are continually subjected to water must be protected by a watertight cover. This watertight cover is either a continuous metal jacket or a rubber sheath molded around the cable. Lead-sheathed cable is one of three types currently being used: alloy lead, pure lead, and reinforced lead. An alloy-lead sheath is much like a pure lead sheath but is manufactured with 2-percent tin. This alloy is more resistant to gouging and abrasion during and after installation. Reinforced lead sheath is used mainly for oil-filled cables where high internal pressures can be expected. Reinforced lead sheath consists of a double lead sheath. A thin tape of hard-drawn copper, bronze, or other elastic metal (preferably nonmagnetic) is wrapped around the inner sheath. This tape gives considerable additional strength and elasticity to the sheath, but must be protected from corrosion. For this reason, a second lead sheath is applied over the tape. Metallic Armour Metallic armour provides a tough protective covering for wires and cables. The type, thickness, and kind of metal used to make the armour depend on three factors: (1) the use of the conductors, (2) the environment where the conductors are to be used, and (3) the amount of rough treatment that is expected. 1. Wire-braid armour Wire-braid armour, also known as basket-weave armour, is used when light and flexible protection is needed. Wire braid is constructed much like fibrous braid. The metal is woven directly over the cable as the outer covering. The metal used in this braid is galvanized steel, bronze, copper, or aluminum. Wire-braid armour is mainly for shipboard use. 2. Steel tape
  • 6. A second type of metallic armour is steel tape. Steel tape covering is wrapped around the cable and then covered with a serving of jute. There are two types of steel tape armour. The first is called interlocking armour. Interlocking armour is applied by wrapping the tape around the cable so that each turn is overlapped by the next and is locked in place. The second type is flat- band armour. Flat-band armour consists of two layers of steel tape. The first layer is wrapped around the cable but is not overlapped. The second layer is then wrapped around the cable covering the area that was not covered by the first layer. 3. Wire armour Wire armour is a layer of wound metal wire wrapped around the cable. Wire armour is usually made of galvanized steel and can be used over a lead sheath (see view C of the figure above). It can be used with the sheath as a buried cable where moisture is a concern, or without the sheath when used in buildings. 4. Coaxial cable Coaxial cable is defined as two concentric wires, cylindrical in shape, separated by a dielectric of some type. One wire is the center conductor and the other is the outer conductor. These conductors are covered by a protective jacket. The protective jacket is then covered by an outer protective armour. Coaxial cables are used as transmission lines and are constructed to provide protection against outside signal interference. Low Voltage Power and Control Cables Low voltage power and control cables pertain to electrical cables that typically have a voltage grade of 0.6/1 kV or below.
  • 7. Armoured FAS Cable An important item that is under the grouping known as 'Low Voltage Cables', is Type FAS (Fire Alarm & Signal Cable). This 300-volt cable, is specifically designed for the interconnection of security system elements, including fire protection signalling devices such as smoke and fire detectors, fire alarms, and two-way emergency communications systems. Fire alarm installations in non-combustible buildings require mechanical protection, consisting of interlock armour, metallic conduit, non-metallic conduit embedded in concrete or installed under-ground. Armoured FAS Cable provided with an interlocking aluminum armour, may be expected to have an appreciable cost advantage, compared with cables installed in rigid conduit. Other common cables are LVT (Low Voltage Thermoplastic) and ELC (Extra Low Voltage Control), which are frequently used in residential installations for such items as door bells and thermostats.
  • 8. Low Voltage Instrumentation Cables Instrumentation cables Low voltage instrumentation cables pertain to cables for use in instrument applications and typically have a voltage grade of 450/750 V or below. Instrumentation Cables rated at 300 volts have copper conductors 0.33 mm2 (#22 AWG) to 2.08 mm2 (#14 AWG), while those rated at 600 volts have 0.82 mm2 (#18 AWG) to 5.26 mm2 (#10 AWG), and unarmoured and armoured types are available. The cables may be an assembly of single conductors, pairs, triads or quads. The conductors are stranded seven-wire tinned or bare copper. The insulation is usually a PVC compound chosen dependant on the environment for which it is intended. Insulated conductors are paired with staggered lays to prevent electromagnetic coupling and crosstalk. When individual shielding is specified, each pair is aluminum/polyester shielded with drain wire to eliminate electrostatic interference. Armoured cables have an interlocked aluminum or galvanized steel armour. The armouring is applied over an inner PVC jacket, followed by a PVC outer jacket. Armoured cables are suitable for installation on cable trays in dry, damp and wet locations, or direct earth burial. Unarmoured Instrumentation Cables are intended for installation in raceways/conduit (except cable trays) in dry, damp or wet locations, or direct earth buried. Unarmoured Cable with Type TC (Tray Cable) designation, may be installed in cable trays. Thermocouple Extension Cables Thermocouple Extension Cables have a 300 volt rating, and are of similar construction to Instrumentation Cables, but the metals/alloys used for the conductors are different. Thermocouples measure temperature using the electric current created when heat is applied to two dissimilar metals/alloys. The cable assembles may consist of as many as 50 pairs, depending on the number of locations being temperature monitored.
  • 9. Medium / High Voltage Power Cables Medium or High Voltage power cables have voltage grade greater than 1 kV. Medium voltage usually goes up to 46 kV and High voltage is considering all voltage levels above 46 kV. Medium Voltage distribution systems begin at substations and supply electricity to a wide spectrum of power consumers. When selecting a cable, the basic aim is to safely provide adequate electrical power, with continuous, trouble-free operation, in a system that is able to withstand unexpected demands and overload conditions. Each installation has particular requirements that must be considered. There are distinct benefits from specifying a copper-conductor cable that has been manufactured under rigid specification and quality control procedures. It will provide maximum performance with minimum maintenance. There are seven types different by construction for medium voltage copper power cables in the 1 kV to 46 kV range. Most are available in single- and multi-core configurations. There are ranges of sizes and design variations for each type. The MV cable types are:  Teck Cables,  Shielded Cables,  Concentric Neutral Cables,  Paper-Insulated Lead-Covered Cables,  Submarine Cables,  Mining Cables,  Aluminum-Sheathed Cables. In the cable descriptions a number of insulation and sheath (jacket) materials have been abbreviated as follows:
  • 10.  Cross-Linked Polyethylene - XLPE,  Ethylene-Propylene Rubber - EPR,  Polyvinyl Chloride - PVC,  Polyethylene - PE,  Tree-Retardant Cross-Linked Polyethylene - TR-XLPE. Teck Cables Teck Cables were originally developed for use in mines, but they are now widely used in primary and secondary industries, chemical plants, refineries and general factory environments. They are also used in multi-storey and commercial buildings. They are flexible, resistant to mechanical abuse, corrosion resistant, compact and reliable. A modified Teck Cable construction may be used for vertical installations, such as in mine shafts and multi-storey buildings, where the armour is locked-in-place to prevent slippage of the inner core. There are many different combinations of conductor size, voltage rating, armour type and so forth, available in Teck Cables to meet the requirements of particular installations. Annealed, bare, copper is used for the conductor (s), and they are usually compact stranded to reduce diameter. In multi- conductor cables, the insulated conductors are cabled together, including the bare copper bonding (grounding) conductor. In shielded multi-conductor cables, the bonding (grounding) conductor is positioned to contact the copper shields. A PVC outer jacket which may be colour-coded depending on the rating of the cable is applied. Shielded Cables Shielded Power Cable may be single-or three-conductor. The basic construction begins with a conductor of annealed, bare, solid or concentric-stranded copper, which may be compact or compressed. This is followed by a semi-conducting conductor shield, insulation, and then a semi-conducting insulation shield. Metallic shielding follows, which is usually either gapped or lapped copper tape. Other types of metallic shielding are available, including concentric wires and longitudinally corrugated copper tape. The outer jacket is either PVC or PE. Concentric Neutral Cables These power cables may be used in dry or wet locations, for a wide variety of types of installations, and may be single- or three-conductor. The two standard constructions are Unjacketed and Jacketed, the latter being most frequently used. The conductor is typically annealed, bare, stranded copper, but tin-coated wire and solid conductors are also available. The concentric neutral conductor, from which the cable derives its name, is bare or tin-coated copper wire, applied helically over the insulation shield. These wires act as the metallic component of the shield and the neutral, at the same time. Paper-Insulated Lead-Covered Cables (PILC) PILC cables are used in power distribution and industrial applications, and they may be installed exposed, in underground ducts or directly buried. Their design begins with annealed, bare copper conductor(s) which may be round, concentric, compressed or compact stranded, compact sector, and in larger sizes … Type M segmental stranded. An example of compact sector conductors is shown in the illustration. The insulated cable core is impregnated with a medium viscosity polybutene-based compound. The combination of the excellent electrical and mechanical characteristics of the liquid and the paper has resulted in a reliable and economic insulation, which now claims a
  • 11. history of almost 100 years. It is little wonder why so many utilities and power- consuming industries, still continue to specify PILC. To prevent the ingress of moisture, a seamless lead-alloy sheath is applied. The outer jacket may be PVC or PE, and if required by the application, armour is available. Submarine Cables For submarine installations, usually Self-Contained Liquid-Filled Cables (SCLF), or Solid Dielectric Cables are selected, depending on voltage and power load. SCLF Cables are capable of handling very high voltages. However, for medium-voltage installations, a Solid Dielectric Cable can easily fulfil the electrical demands of the system. A submarine Solid Dielectric Cable is shown in the illustration. Its construction begins with a compact stranded, annealed, bare copper conductor, followed by a semi- conducting conductor shield. A copper tape shield is helically applied, followed by a lead-alloy sheath. Due to the severe environmental demands placed on submarine cables, a lead-alloy sheath is often specified because of its compressibility, flexibility and resistance to moisture and corrosion. The sheath is usually covered by a number of outer layers, comprising a PE or PVC jacket and metal wire armouring. Mining Cables A number of different types of cables are used in mines. There are fixed mining cables and portable mining cables, the latter being described here. The key requirements of portable cables are flexibility, and resistance to mechanical abrasion and damage. Due to the additional demands put on portable mining cables used for reeling and dereeling applications, special design may be required. There are many types of portable mining cables. They are available in ratings up to 25 kV, and may have as many as five conductors. An example of SHD-GC Cable, is shown in the illustration. It has three insulated, shielded conductors, two bare ground wires, a ground check wire, and an overall jacket. The conductors for this cable are annealed, bare or tinned copper wires. The braided shield may be tin-coated wires, or a tin-coated copper wire/textile composite. The grounding conductor(s) annealed, bare or tinned, stranded copper wires, and the ground check conductor is annealed, bare, stranded copper wires with EPR insulation and nylon braid, elastomeric jacket holds the conductor assembly firmly in place, to minimize snaking and cork-screwing during reeling and dereeling. Aluminum-Sheathed Cables These power cables are used for exposed and concealed wiring, in wet and dry locations, and where exposed to the weather. They may be installed in ventilated, unventilated and ladder-type cable-troughs, and ventilated flexible cableways. Aluminum-Sheathed Power Cables may be single-,two-,three- or four-conductor, the conductor(s) being annealed, bare, compressed-round stranded copper. The insulated core is enclosed in a liquid- and vapour-tight solid corrugated aluminum sheath, covered by a PVC jacket.
  • 13. Trivia References  http://metechakir.blogspot.de/  http://coppercanada.ca/publications/pub27e/27e-section8.htm  http://www.otds.co.uk/cables.php Source: http://www.openelectrical.org/wiki/index.php?title=Teck_Cable#Teck_Cables