IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE)
e-ISSN: 2278-1676,p-ISSN: 2320-3331, Volume 6, Issue 5 (Jul. - Aug. 2013), PP 24-29
www.iosrjournals.org
www.iosrjournals.org 24 | Page
Energy Auditing of a Typical Residential Building in Ibadan
Metropolis
*Diji, C.J and **Ganiyu, H.
* Ojoo Business Unit, Ibadan Electricity Distribution Company
** Department of Mechanical Engineering, University of Ibadan, Ibadan
Abstract: An electricity audit of a building is the process whereby an energy manager survey and analyzes how
energy is used in the building with the main objective of identifying opportunities for reducing the amount of
energy used and ensuring that available energy is used efficiently.
This study reports the outcome of an electricity audit on a typical residential building in a major
location of Ibadan metropolis. The audited building is a four – flat apartment where all the customers in the
building have different tariff plans. Two of the customers labeled Customer A and B are metered, while the
other two Customers labeled C and D are not metered.
The result of the audit showed that the metered customers were paying the actual estimated electricity
bills, while the non – metered customers were over billed by over 30 and 80% respectively. The study concluded
by recommending the metering of all residential apartments and the use of pre – paid meters as it not only
stimulate demand but also is more effective in the electricity billing process
Key Words: Electricity Audit, Residential Building, Ibadan
I. Introduction
Electricity is the main energy source used in most building. Indeed, electricity is required for the
operation of numerous appliances in all residential building. Residential or domestic load consists of lights, fans,
and appliances like radios, heaters, electric irons, refrigerators, coolers, electric water heaters, washing
machines, amongst others. The small residential electricity consumers may generally use all the light points
simultaneously given a demand factor of unity. For big houses, the demand factor may be only around 0.5.
The demand for electricity continues to rise as population grows. Electrical energy demand refers to the
maximum amount of electrical energy that is being consumed at a giving time. It is necessary, for system
planning and operation, to know the total electrical energy requirements and the duration of various loads in
residential apartments. This is necessary to give residential consumers and building owners a proper sense of
how much energy different appliances and activities consumed, because most people consistently overestimate
the impact of less energy consuming appliances and less effective conservation activities and under estimate the
impact of energy of more energy consuming appliances and more effective conservation activities (Kempton
et.al 1985).
Understanding the way electricity is billed in residential apartments could sometimes seem very
confusing, this is because unlike some other products, electrical energy cannot, in a practical sense, be stored.
Rather, it needs to be generated and supplied as various equipments and home appliances require it. Day or
night, the electricity utility provider must be able to meet the electricity requirements of its residential
customers.The demand for electricity, and the flexibility needed to supply this electricity during peak times
leads to “demand charges.”
An energy survey and audit of buildings is the process by which a building is inspected and analyzed
by an energy manager to determine how energy is used in it, with the goal of identifying opportunities for
reducing the amount needed to operate the building while maintaining comfort level (Thumann and Young
2003).
This study reports the outcome of an energy survey and audit of a typical residential apartment in a
typical residential area in Ibadan metropolis. The residential apartment is located at Onikoro area, Shasa, Ibadan.
It is made up of a four flat apartment with each flat consisting of three bedroom, sitting room, dinning, two
toilets, two bathrooms, kitchen, store, passage and corridor. It takes its source of electricity from Shasa 1
500KVA substation on Shasa 11KVA feeder.
The occupants of the apartment are on different electricity tariff plans. One of the occupants uses a
single phase prepaid meter, another an analogue meter while the remaining two flats are on no meter. The study
involves the interpretation and comparison of one of the monthly electricity bills of the different apartments in
the building. The interpretation and comparison is done to make appropriate recommendations to the occupants
of the building and the utility provider, the Power Holding Company of Nigeria (PHCN) on appropriate
electricity consumption and billing for future electricity planning purposes.
Energy Auditing of a Typical Residential Building in Ibadan Metropolis
www.iosrjournals.org 25 | Page
The study is divided into five sections. The first section includes the introduction; section two discusses
extensively the concept of energy survey and auditing in buildings, while the third section elaborates the
methodology used in conducting the study. Section four discusses the results of the study and section five
concludes.
II. ElectricityUse and Auditing in Buildings
Electrical loads refer to the power consumed by a circuit and they are classified by tariff schedules into
three major categories namely: industrial, commercial and residential loads. Industrial electricity customers
usually engage in the manufacture of certain product or commodities and or convert given raw materials into
partly processed or finished products basically different from the raw materials. The factories usually have a
large number of motor, heaters, oven, presses air conditioning equipment and other electrical appliances.
Assessing maximum electricity demands require a thorough knowledge of the industrial processes involved.
Residential electricity consumers are typified by normal domestic utilization of electric energy for lighting,
cooking, refrigeration and air conditioning, water heating, laundry and other miscellaneous applications. In
assessing maximum demands of this category of loads, special attention should be paid to the air conditioning
load and the standard of living of the occupier vis – a – vis the ability of the consumer to pay the electricity bills
which may arise as a result of load and diversity factors assured in assessing the maximum demands and
electricity requirements. Commercial electrical loads are all electrical loads that are neither residential nor
industrial, usually involving small scale business outfits that are involved in providing various services.
An electricity audit is simply an audit or calculation of how much electricity is being used in the home and of
where that electricity is going. An electricity audit can help to identify waste so that the causes of additional
electricity use can be eliminated thereby reducing the expenditure on electricity in the home and reducing
damages to the environment.
There are two different types of electricity audit. The first is simply a do – it – yourself audit; this
involves the use of a calculator to find out how much energy each appliance and activity is using in order to
identify where your money is going when you pay your electric bill. There are several online calculator tools
that can be used for this purpose, thereby allowing the consumer to do is own electricity audit.
The second type of energy audit involves hiring a professional energy auditor to come to your home to identify
where and how energy is being wasted. These energy professionals usual work for home improvement or
building companies, and usually assist the residential consumer in identifying leaks and other areas of inefficient
use of electricity. The outcome of their work is expected to assist the consumer to improve in efficient
utilization of electricity and reduction in electricity costs in the home.
2.1 Estimating Electricity Consumption and Cost of Domestic Appliances
Electricity consumption is measured in kilowatt-hours (kWh), and one kWh equals 1,000 watts of
electricity used during one hour. To determine the total electricity consumed in the home by an electrical
appliance over a given period of time, it is first important to determine the amount of power (watts) of the
appliance. Manufacturers typically indicate the wattage on the back of the appliance. If the wattage is not given,
look for the amperage (amps) and voltage (volts) listed on the appliance. The multiplication of the amperage
with the voltage of the appliance will give the power (Watts) rating of the appliance.
To determine the electrical consumption of the appliance for a month, simply multiply the wattage times the
number of hours the appliances is used and divide by 1000 to get the kWhs. For example if a 60 Watts bulb is
used for a 5 hour period per day for a 30 days month; then the total electrical consumption will be 9 kWh.
The power consumed by each appliance during the year depends on, amongst other factors:
1. The average watts per hour consumed by the appliance when in active use. For many appliances, this
is not the same as the rated power consumption of the appliance since most do not normally operate
continuously at their rated energy consumption.
2. The number of hours in active use of each appliance per year.
3. The power consumed by the appliance (standby power) when it is not in active use.
4. Year in which it was sold
5. The market mix of the appliances sold in that year (size, technology, supplier)
6. The mean energy efficiency of those appliances both in operation and standby.
To calculate the cost of your electricity, whether for a particular appliance or other device, you need to know the
rate of consumption and the price of the electricity. The former you can find either printed on the unit or in the
manual. In addition to the rate of power usage, the duration of usage is part of the calculation. For the cost or the
electric power, check your bill. The bill will show the price per power unit, the kilowatt-hour. That unit equals a
consumption rate of 1,000 watts, in operation for one hour.
Energy Auditing of a Typical Residential Building in Ibadan Metropolis
www.iosrjournals.org 26 | Page
2.2 Electricity Metering and Billing
An electric meter or energy meter is a device that measures the amount of electrical energy supplied to
a residence or business. These are the customers of an electric utility. Utilities record the values measured by
these meters to generate an invoice for the electricity consumed. The most common unit for measurement on the
electricity meter is the kilowatt-hour which is equal to the amount of energy used by a load of one kilowatt over
a period of one hour, or 3,600,000 joules.
Electrical metering is important because the performance of utilities at various points is judged by the
global metering at grid points. For efficiency, therefore, the metering should be cascaded to the individual
customer’s premises. The accuracy of billing largely depends on the accuracy of metering and the number of
metered premises. Thus there is the need to strive to provide meters to the customers not having meters and to
repair or replace the faulty meters in the system.
Modern electricity meters operate by continuously measuring the instantaneous voltage (volts) and
current (amperes) and findings the product of these to give instantaneous electrical power (watts) which is then
integrated against time to give energy used (joules, kilowatt-hours etc). The meters fall into two basic
categories: These are electromechanical and electronic meters.
Electricity billing is the process of converting the electric meter reading or estimation of the customer’s
consumption (and demand) to a bill using appropriate tariff. An electric bill is expected to indicate the
information provided in Table 1.
Table 1: Information on an Electricity Bill
S/N INFORMATION DETAILS
1. Customer Information
Account Number
Name
Service Centre
Type of Account
Meter Status/dials
Customer Type
Average Daily consumption
2.
Description of Charge
Energy charge (Where Applicable)
Fixed Charge
Meter Maintenance Charge
3. Transaction information
Previous Balance
Payments
Adjustments
Current Charges
Value Added Tax
Total Amount Due For Payment
4. Other Required Information LAR (Last Actual Reading) Date
Date of Last Payment/Amount Paid
Reconnection Fee Charges
Tariff Rate for Account Type
Due Date
Read Date
Tariff Code
Electricity bills are produced through three broad forms namely: meter reading, estimation and fixed
consumption (direct) modes. Meter reading involves the subtraction of the previous reading from the present
reading and the value obtained is used to bill the consumption of the customer, this mode of billing is the most
convenient and appropriate form of billing.
Estimation mode of billing is used when there is no access to the customer premises and in situations in which
the previous reading is observed to be higher than the present reading. The Fixed consumption mode of billing is
used in situations where the bills are produced on fixed consumption; this mode is applied in situations where
there is delayed meter installation, faulty meter or where the meter has been stolen.
III. Research Methodology
The study involved the energy survey and auditing of the selected area of research, which is the four –
flat apartment at the Onikoro area of Shasha area in Ibadan metropolis. The customers in the four flat as stated
earlier have different tariff plans and their energy bills are estimated differently. Each of the flats consists of
three bedroom, sitting room, dining room, two toilets, two bathrooms, kitchen, store, passage and corridor.
Energy Auditing of a Typical Residential Building in Ibadan Metropolis
www.iosrjournals.org 27 | Page
The four customers have been designated as Customer A, B, C and D. Customer A uses a pre – paid meter;
Customer B uses an analogue meter, while Customer C and D have no meters and their energy billing is
currently done by fixed consumption mode.
The complete energy audit of the apartment was conducted over a two week period and involved collection of
all necessary electrical appliances in each apartment. This included the identification of the electrical devices
used, their types, models, current ratings, voltage ratings, cautions on them, input and output powers, amongst
others. The audit also took into cognizance factors that could affect the effective distribution of electricity in the
apartment such as technical and commercial losses, as well as unforeseen emergencies of extra load.
The general procedure used in the audit involved the following:
1. Facility and Utility Data Analysis
2. Walk through survey
3. Administration of questionnaires
4. Data processing and production of final report
It must be noted that in performing the audit, several of the tasks under the procedures stated above have to
repeated, reduced in scope or even eliminated based on the findings of other tasks. Hence, an audit is often not a
linear process, but is rather an iterative one.
3.1 Facility and Utility Data Analysis
In this step, the characteristics and patterns of electricity usein the building apartment was established.
This involved the compilation and historical analysis of the utility bills of the apartment over a three months
period i.e. from December 2011 to February, 2012. This was done to see if there is any seasonal and weather
effects on the building electricity use. The monthly utility bills were obtained from the PHCN business unit in
Ojoo and from established customer data for the same period.
3.2 Walk through Survey
During the audit exercise, a walk through survey was conducted to estimate the electrical load for each of
the apartments and to identify potential energy saving measures that will eliminate wasteful usage of electricity.
The tasks carried out during the walk through survey included:
I. Identifying the customer concerns and needs.
II. Checking the current operating and maintenance procedures.
III. Determining the existing operating conditions of major energy-use equipment (lighting, HVAC
systems, etc.).
IV. Estimate the occupancy, equipment, and lighting (energy-use density and hours of operation).
3.4 Field Questionnaires
This was administered to each of the flats in the apartment to identify how electricity supply was received by
each flat, the appliances used and the number of hours there was electricity availability during February 2012.
3.5 Data Processing and Production of Final Report
The results of the walk through survey and the administered questionnaires were used to estimate the
connected load, maximum demand and demand factors of each flat and a full comparative energy use analysis
of the building was carried out with the identification of energy losses.
3.5.1 Connected load
The connected load of a customer means the sum of the continuous rating of all the devices and outlet
installed on all the distribution circuit. By calculating the Total Connected Load (TCL), it will be possible to
estimate the TCL for a particular area and for determining the sizing of cables. The TCL also makes it possible
to determine Maximum Demand (MD) for a customer or group of customers and provides the utility provider
useful information for the purpose of meter deposit and utility bill.
3.5.2 Maximum Demand (MD)
This is the maximum power that a circuit is likely to draw at a certain time. Thus the maximum demand
of a customer is always less than the connected load of a customer.The reason for this is that the connected loads
are used intermittently and usually does not operate at their full electrical ratings. Also the maximum load
demand cannot be calculated simply by adding the maximum demands of individual loads since the individual
maximum demands occur at deferent times
The Maximum Demand is connected to the TCL by the Demand Factor (DF). The DF is the ratio of the
MD of a system or part of a system, to the TCL on the system or part of the system under consideration. DF is
always less than 1 (one).
Energy Auditing of a Typical Residential Building in Ibadan Metropolis
www.iosrjournals.org 28 | Page
𝐷𝑒𝑚𝑎𝑛𝑑𝐹𝑎𝑐𝑡𝑜𝑟 𝐷𝐹 =
𝑀𝑎𝑥𝑖𝑚𝑢𝑚𝐷𝑒𝑚𝑎𝑛𝑑
𝑇𝑜𝑡𝑎𝑙𝐶𝑜𝑛𝑛𝑒𝑐𝑡𝑒𝑑𝐿𝑜𝑎𝑑
IV. Results and Discussion
Table 2 shows the preliminary results of the energy audit of the four apartments while Table 3 shows
the estimated connected load for the residential apartment and Table 4 shows actual energy consumption and
cost of electricity for the month of electricity and the electricity billing from the utility provider, the PHCN.
From the aforementioned tables, it is obvious that customer A with the pre- paid meters paid actual electricity
bills and paid over 4 times more than the other customers in the apartment. Customer B, who is analogue
metered and with a maximum demand of 2.9kW was also properly billed as there is little or no disparity
between the estimated cost of using electricity and the electricity billing from the utility company. In addition,
customer B is obviously the most energy efficient occupant of the building.
Customer C and D who pay a fixed monthly charge are overbilled by over 30% and 80% respectively, due to
non – availability of meters. This shows that fixed monthly charges will not be beneficial in the long run to most
residential electricity consumers. It is better for all residential customers to be metered.
With regards to the Electricity Utility company. It is obvious that the use of pre – paid meters will stimulate
consumption and bring more revenue to the company. The practice should be encouraged and sustained.
Table 2: Preliminary Results of Electricity Audit
S/N LOCATION Customer A Customer B Customer C Customer D
1
Master
Room 1No 60w bulb 1No 65w Standing
Fan 1No 64w TV 1No 60w
Laptop 2Nos 25w Energy Bulb
1No 60w Bulb 1No
65w Fan 2Nos 25w
Energy Bulb 1No
180w Portable
Fridge
1No 100w Bulb
1No 55w Ceiling
Fan 2Nos 25w
Energy Bulb 1No
45w Standing Fan
1No 60w Bulb 1No
55w Ceiling Fan
2Nos 25w Energy
Bulb
2 Master Toilet
Ino 100w Bulb
32 4Ft Fluorescent
tube 1No 40w 1No 60w Bulb 1No 100w Bulb
3 2nd Room 1No 100w Bulb 1No 55w
Standing Fan 2Nos 25w Energy
Bulb
1No 60w Bulb 1No
60w Laptop 1No
55w Ceiling Fan
2Nos 25w Energy
Bulb
1No 60w Bulb
1No 65w Fan
2Nos 25w Energy
Bulb
1No 60w Bulb 1No
55w Standing Fan
2Nos 25w Energy
Bulb
4 3rd Room
1No 60w Bulb 1No 65w Fan
2Nos 25w Energy Bulb
1No 60w Bulb 1No
65w Fan 2Nos 25w
Energy Bulb
1No 60w Bulb
1No 55w Ceiling
Fan 2Nos 25w
Energy Bulb
1No 60w Bulb 2Nos
25w Energy Bulb
5 2nd Toilet 1No 100w Bulb 1No 60w Bulb 1No 60w Bulb 1No 100w Bulb
6 Sitting Room
1No 100w T.V 1No 130w
Standing Fan 1No 190w DVD
Player 1No 25w DSTV Decoder
4Nos 25w Energy Bulb 1No 40w
32' 4Ft Fluorescent 1No 55w
Ceiling Fan 1No 2Hp
Airconditioning 1No 1000w
Stabilizer 1No 159w Computer
System (Monitor, System Unit,
Stabilizer & UPS) 1No 35w Radio
1No 75w T.V 1No
55w Ceiling Fan
1No 25w DSTV
Decoder 4No 25w
Energy Bulb 1No
1000w Stabilizer
1No 25w Radio 1No
40w 32' 4Ft
Fluorescent
1No 64w T.V 1No
55w Ceiling Fan
1No 190w DVD
Player 1No 35w
Radio 4Nos 25w
Energy Bulb 1No
100w Bulb 1No
1200w Pressing
Iron
1No 100w T.V 1No
130w Standing Fan
1No 25w DSTV
Decoder 1No 40w
32' 4 Ft Fluorescent
1No 1000w
Stabilizer 1No
Laptop 80w 4Nos
25w Energy Bulb
7
Dining
Room
2Nos 25w Energy Bulb 1No 60w
Bulb 1No 55w Ceiling Fan 1No
150w Refrigerator
1No1000w Stabilizer
2No 25w Energy
Bulb 1No 60w Bulb
1No 65w Standing
Fan
2Nos 25w Energy
Bulb 1No 60w
Bulb 1No 45w
Standing Fan
2No 25w Energy
Bulb 1No 100w Bulb
1No 55w Ceiling Fan
8 Kitchen
1No 200w Freezer 1No 100w
Bulb 1No 300w Fruit Extraction
1No 700w Toaster 1No 350w
Blender 1No 500w Stabilizer
1No 180w Freezer
1No 100w Bulb
1No 1000w
Stabilizer 1No
1600w Electric
Kettle
1No 60w Bulb
1No 300w Blender
1No 1000w
Hotplate 1No
1000w Boiling
Ring
1No 1000w Hotplate
1No 100w Bulb 1No
150w Refrigerator
9 Passage
1No 100w Bulb 1No 1200w
Pressing Iron
1No 40w 2' 4Ft
Fluorescent tube
1No 1200w Pressing
iron 1No 60w Bulb
1No 60w Bulb 1No
1000w Pressing Iron
10 Store 1No 100w Bulb 1No 60w Bulb 1No 100w Bulb 1No 100w Bulb
11 Surrounding 2Nos 100w Bulb 2Nos 100w Bulb 2Nos 100w Bulb 2Nos 100w Bulb
Energy Auditing of a Typical Residential Building in Ibadan Metropolis
www.iosrjournals.org 29 | Page
Table 3: Estimated Connected Load for Each Apartment
S/N LOCATION
Customer A
(Watts)
Customer B
(Watts)
Customer C
(Watts)
Customer D
(Watts)
1 Master Room 299 355 250 165
2 Master Toilet 100 40 60 100
3 2nd Room 205 225 175 165
4 3rd Room 175 175 165 110
5 2nd Toilet 100 60 60 100
6 Sitting Room 3299 1320 1744 1744
7 Dining Room 1315 175 155 155
8 Kitchen 2150 2880 2360 2360
9 Passage 2200 1240 60 1060
10 Store 100 60 60 60
11 Surrounding 200 200 200 200
TOTAL 10,143 6,730 5,289 4,680
Table 4: Actual Energy Consumed and Cost of Electricity Supplied
S/N ITEM
Customer A Customer B Customer C Customer D
1. Connected Load (kW) 10.14 6.73 5.29 4.68
2. Maximum demand (kW) 3.3 2.88 2.36 1.27
3. Demand Factor 0.33 0.43 0.45 0.36
3. Total Energy Consumed(kWh) 610.23 176.97 170 134.01
4. Cost of Energy consumed (N) 4,342 1,291.88 1,240.93 978.27
5. Energy Billing by PHCN for February,
2012 (N)
1,301.04 1,825 1,825
V. Conclusion
The paper examined the outcome of an electricity audit on four customers on different tariff plans in a
typical residential building in Ibadan metropolis. It is the conclusion of the study that the use of fixed charges
for electricity billing is not favourable to residential consumers of electricity and the use of pre – paid meters
will obviously stimulate electricity demand and consumption.
References
[1]. Electric Power Research Institute (1993) - Reduction cost by understanding your bill.
[2]. Ezeruigbo E. N (2001) - AT&C Loss reduction India Experience
[3]. Osideide, A. A. (2011) - Strategic electricity marketing Activities in distribution companies of Nigeria
[4]. PHCN(2011) - Commercial instruction manuals
[5]. Taylor Francis Group LLC, (2006) - Handbook of energy efficiency and renewable energy

Más contenido relacionado

La actualidad más candente

Feasibility analysis of an off-grid photovoltaic-battery energy system for a...
Feasibility analysis of an off-grid photovoltaic-battery  energy system for a...Feasibility analysis of an off-grid photovoltaic-battery  energy system for a...
Feasibility analysis of an off-grid photovoltaic-battery energy system for a...IJECEIAES
 
ADOPTING MEASURES TO REDUCE POWER OUTAGES
ADOPTING MEASURES TO REDUCE POWER OUTAGESADOPTING MEASURES TO REDUCE POWER OUTAGES
ADOPTING MEASURES TO REDUCE POWER OUTAGESelelijjournal
 
Intelligent home energy management system including renewable energy based on...
Intelligent home energy management system including renewable energy based on...Intelligent home energy management system including renewable energy based on...
Intelligent home energy management system including renewable energy based on...eSAT Journals
 
energy efficient india
energy efficient indiaenergy efficient india
energy efficient indiahorizon8586
 
Optimal Hybrid Energy System for Rural Electrification in India using HOMER S...
Optimal Hybrid Energy System for Rural Electrification in India using HOMER S...Optimal Hybrid Energy System for Rural Electrification in India using HOMER S...
Optimal Hybrid Energy System for Rural Electrification in India using HOMER S...IRJET Journal
 
IRJET- Energy Saving in Governmental Educational Buildings: Case Study
IRJET- Energy Saving in Governmental Educational Buildings: Case StudyIRJET- Energy Saving in Governmental Educational Buildings: Case Study
IRJET- Energy Saving in Governmental Educational Buildings: Case StudyIRJET Journal
 
ADOPTING MEASURES TO REDUCE POWER OUTAGES
ADOPTING MEASURES TO REDUCE POWER OUTAGESADOPTING MEASURES TO REDUCE POWER OUTAGES
ADOPTING MEASURES TO REDUCE POWER OUTAGESecij
 
Comparative Analysis of Solar Standalone and Solar-Biogas Hybrid Systems for ...
Comparative Analysis of Solar Standalone and Solar-Biogas Hybrid Systems for ...Comparative Analysis of Solar Standalone and Solar-Biogas Hybrid Systems for ...
Comparative Analysis of Solar Standalone and Solar-Biogas Hybrid Systems for ...IRJET Journal
 
Conservation of Energy: a Case Study on Energy Conservation in Campus Lightin...
Conservation of Energy: a Case Study on Energy Conservation in Campus Lightin...Conservation of Energy: a Case Study on Energy Conservation in Campus Lightin...
Conservation of Energy: a Case Study on Energy Conservation in Campus Lightin...IJMER
 
Power management of wind and solar dg
Power management of wind and solar dgPower management of wind and solar dg
Power management of wind and solar dgIAEME Publication
 
Saving energy
Saving energySaving energy
Saving energyTeo RV
 
The Effect of Building Direction and Natural Airing on Yearly Power Utilization
The Effect of Building Direction and Natural Airing on Yearly Power UtilizationThe Effect of Building Direction and Natural Airing on Yearly Power Utilization
The Effect of Building Direction and Natural Airing on Yearly Power UtilizationYogeshIJTSRD
 
Quantitative research in energy, availability, access and affordability, Papi...
Quantitative research in energy, availability, access and affordability, Papi...Quantitative research in energy, availability, access and affordability, Papi...
Quantitative research in energy, availability, access and affordability, Papi...ESD UNU-IAS
 
Integrated Energy Management of Residential Halls at University of Dhaka by U...
Integrated Energy Management of Residential Halls at University of Dhaka by U...Integrated Energy Management of Residential Halls at University of Dhaka by U...
Integrated Energy Management of Residential Halls at University of Dhaka by U...Dr. Amarjeet Singh
 
Awareness on energy management in residential buildings a case study in kajan...
Awareness on energy management in residential buildings a case study in kajan...Awareness on energy management in residential buildings a case study in kajan...
Awareness on energy management in residential buildings a case study in kajan...Basrah University for Oil and Gas
 

La actualidad más candente (18)

Feasibility analysis of an off-grid photovoltaic-battery energy system for a...
Feasibility analysis of an off-grid photovoltaic-battery  energy system for a...Feasibility analysis of an off-grid photovoltaic-battery  energy system for a...
Feasibility analysis of an off-grid photovoltaic-battery energy system for a...
 
ADOPTING MEASURES TO REDUCE POWER OUTAGES
ADOPTING MEASURES TO REDUCE POWER OUTAGESADOPTING MEASURES TO REDUCE POWER OUTAGES
ADOPTING MEASURES TO REDUCE POWER OUTAGES
 
seminar fianle
seminar fianleseminar fianle
seminar fianle
 
Intelligent home energy management system including renewable energy based on...
Intelligent home energy management system including renewable energy based on...Intelligent home energy management system including renewable energy based on...
Intelligent home energy management system including renewable energy based on...
 
energy efficient india
energy efficient indiaenergy efficient india
energy efficient india
 
Optimal Hybrid Energy System for Rural Electrification in India using HOMER S...
Optimal Hybrid Energy System for Rural Electrification in India using HOMER S...Optimal Hybrid Energy System for Rural Electrification in India using HOMER S...
Optimal Hybrid Energy System for Rural Electrification in India using HOMER S...
 
Electricityconservationtips
ElectricityconservationtipsElectricityconservationtips
Electricityconservationtips
 
IRJET- Energy Saving in Governmental Educational Buildings: Case Study
IRJET- Energy Saving in Governmental Educational Buildings: Case StudyIRJET- Energy Saving in Governmental Educational Buildings: Case Study
IRJET- Energy Saving in Governmental Educational Buildings: Case Study
 
ADOPTING MEASURES TO REDUCE POWER OUTAGES
ADOPTING MEASURES TO REDUCE POWER OUTAGESADOPTING MEASURES TO REDUCE POWER OUTAGES
ADOPTING MEASURES TO REDUCE POWER OUTAGES
 
Comparative Analysis of Solar Standalone and Solar-Biogas Hybrid Systems for ...
Comparative Analysis of Solar Standalone and Solar-Biogas Hybrid Systems for ...Comparative Analysis of Solar Standalone and Solar-Biogas Hybrid Systems for ...
Comparative Analysis of Solar Standalone and Solar-Biogas Hybrid Systems for ...
 
Conservation of Energy: a Case Study on Energy Conservation in Campus Lightin...
Conservation of Energy: a Case Study on Energy Conservation in Campus Lightin...Conservation of Energy: a Case Study on Energy Conservation in Campus Lightin...
Conservation of Energy: a Case Study on Energy Conservation in Campus Lightin...
 
15 palpandian
15 palpandian15 palpandian
15 palpandian
 
Power management of wind and solar dg
Power management of wind and solar dgPower management of wind and solar dg
Power management of wind and solar dg
 
Saving energy
Saving energySaving energy
Saving energy
 
The Effect of Building Direction and Natural Airing on Yearly Power Utilization
The Effect of Building Direction and Natural Airing on Yearly Power UtilizationThe Effect of Building Direction and Natural Airing on Yearly Power Utilization
The Effect of Building Direction and Natural Airing on Yearly Power Utilization
 
Quantitative research in energy, availability, access and affordability, Papi...
Quantitative research in energy, availability, access and affordability, Papi...Quantitative research in energy, availability, access and affordability, Papi...
Quantitative research in energy, availability, access and affordability, Papi...
 
Integrated Energy Management of Residential Halls at University of Dhaka by U...
Integrated Energy Management of Residential Halls at University of Dhaka by U...Integrated Energy Management of Residential Halls at University of Dhaka by U...
Integrated Energy Management of Residential Halls at University of Dhaka by U...
 
Awareness on energy management in residential buildings a case study in kajan...
Awareness on energy management in residential buildings a case study in kajan...Awareness on energy management in residential buildings a case study in kajan...
Awareness on energy management in residential buildings a case study in kajan...
 

Destacado

ENERGY QUESTIONNAIRE
ENERGY QUESTIONNAIREENERGY QUESTIONNAIRE
ENERGY QUESTIONNAIREEva Vovka
 
Energy Consumption Project - Ryan Miller
Energy Consumption Project - Ryan MillerEnergy Consumption Project - Ryan Miller
Energy Consumption Project - Ryan Millerryan miller
 
Renewable energy questionnaire
Renewable energy questionnaireRenewable energy questionnaire
Renewable energy questionnairecoreurope
 
Water questionnaire
Water questionnaireWater questionnaire
Water questionnaireEvelyn Kurg
 
Project Report On Electric Vehicles
Project Report On Electric VehiclesProject Report On Electric Vehicles
Project Report On Electric VehiclesPrashant Bagalore
 
Top 10 reasons to change your electricity provider
Top 10 reasons to change your electricity providerTop 10 reasons to change your electricity provider
Top 10 reasons to change your electricity providerMichael Underwood
 
ERIS Filter for Ethylene and Pathogen control during Transportation of Fruit,...
ERIS Filter for Ethylene and Pathogen control during Transportation of Fruit,...ERIS Filter for Ethylene and Pathogen control during Transportation of Fruit,...
ERIS Filter for Ethylene and Pathogen control during Transportation of Fruit,...Dimitrios Loutsaris
 
Wastage of natural_resources
Wastage of natural_resourcesWastage of natural_resources
Wastage of natural_resourcesmirza ibraheem
 
Renewals survey call center script 10.3
Renewals survey call center script 10.3Renewals survey call center script 10.3
Renewals survey call center script 10.3Jennifer Bocca
 
Wasting electricity powerpoint
Wasting electricity powerpointWasting electricity powerpoint
Wasting electricity powerpointlsammut
 
Renewable Energy Questionnaire Summary1
Renewable Energy Questionnaire Summary1Renewable Energy Questionnaire Summary1
Renewable Energy Questionnaire Summary1Stanley Tamele
 
Consumer perception towards solar products
Consumer perception towards solar productsConsumer perception towards solar products
Consumer perception towards solar productsIMRAN KHAN
 
Small Hybrid wind/solar market study project-report
Small Hybrid wind/solar  market study  project-reportSmall Hybrid wind/solar  market study  project-report
Small Hybrid wind/solar market study project-reportomtaneja
 
Term project on consumer behaviour towards solar power
Term project on consumer behaviour towards solar powerTerm project on consumer behaviour towards solar power
Term project on consumer behaviour towards solar powerIMRAN KHAN
 

Destacado (20)

ENERGY QUESTIONNAIRE
ENERGY QUESTIONNAIREENERGY QUESTIONNAIRE
ENERGY QUESTIONNAIRE
 
Questionnaire
QuestionnaireQuestionnaire
Questionnaire
 
Energy Consumption Project - Ryan Miller
Energy Consumption Project - Ryan MillerEnergy Consumption Project - Ryan Miller
Energy Consumption Project - Ryan Miller
 
Electricity ppt
Electricity pptElectricity ppt
Electricity ppt
 
Renewable energy questionnaire
Renewable energy questionnaireRenewable energy questionnaire
Renewable energy questionnaire
 
Water questionnaire
Water questionnaireWater questionnaire
Water questionnaire
 
Project Report On Electric Vehicles
Project Report On Electric VehiclesProject Report On Electric Vehicles
Project Report On Electric Vehicles
 
Top 10 reasons to change your electricity provider
Top 10 reasons to change your electricity providerTop 10 reasons to change your electricity provider
Top 10 reasons to change your electricity provider
 
IT Trends 2015
IT Trends 2015IT Trends 2015
IT Trends 2015
 
Wind Solar Electricity Report
Wind Solar Electricity ReportWind Solar Electricity Report
Wind Solar Electricity Report
 
ERIS Filter for Ethylene and Pathogen control during Transportation of Fruit,...
ERIS Filter for Ethylene and Pathogen control during Transportation of Fruit,...ERIS Filter for Ethylene and Pathogen control during Transportation of Fruit,...
ERIS Filter for Ethylene and Pathogen control during Transportation of Fruit,...
 
Wastage of natural_resources
Wastage of natural_resourcesWastage of natural_resources
Wastage of natural_resources
 
Renewals survey call center script 10.3
Renewals survey call center script 10.3Renewals survey call center script 10.3
Renewals survey call center script 10.3
 
Wasting electricity powerpoint
Wasting electricity powerpointWasting electricity powerpoint
Wasting electricity powerpoint
 
Renewable Energy Questionnaire Summary1
Renewable Energy Questionnaire Summary1Renewable Energy Questionnaire Summary1
Renewable Energy Questionnaire Summary1
 
Consumer perception towards solar products
Consumer perception towards solar productsConsumer perception towards solar products
Consumer perception towards solar products
 
Festival questionnaire
Festival questionnaireFestival questionnaire
Festival questionnaire
 
Water questionnaire
Water questionnaireWater questionnaire
Water questionnaire
 
Small Hybrid wind/solar market study project-report
Small Hybrid wind/solar  market study  project-reportSmall Hybrid wind/solar  market study  project-report
Small Hybrid wind/solar market study project-report
 
Term project on consumer behaviour towards solar power
Term project on consumer behaviour towards solar powerTerm project on consumer behaviour towards solar power
Term project on consumer behaviour towards solar power
 

Similar a Energy Auditing of a Typical Residential Building in Ibadan Metropolis

SUSTAINABLE ENERGY SYSTEMS 1 P a g e .docx
SUSTAINABLE ENERGY SYSTEMS  1  P a g e .docxSUSTAINABLE ENERGY SYSTEMS  1  P a g e .docx
SUSTAINABLE ENERGY SYSTEMS 1 P a g e .docxmabelf3
 
IRJET- Computing Electricity Consumption Profiles for the Appliances in a House
IRJET- Computing Electricity Consumption Profiles for the Appliances in a HouseIRJET- Computing Electricity Consumption Profiles for the Appliances in a House
IRJET- Computing Electricity Consumption Profiles for the Appliances in a HouseIRJET Journal
 
ADOPTING MEASURES TO REDUCE POWER OUTAGES
ADOPTING MEASURES TO REDUCE POWER OUTAGESADOPTING MEASURES TO REDUCE POWER OUTAGES
ADOPTING MEASURES TO REDUCE POWER OUTAGESecij
 
Presentation Demand Management
Presentation Demand ManagementPresentation Demand Management
Presentation Demand ManagementMaheshThombare9
 
Smart_Grid_WP_1124aFINAL
Smart_Grid_WP_1124aFINALSmart_Grid_WP_1124aFINAL
Smart_Grid_WP_1124aFINALWes Frye
 
Electrical energy auditing
Electrical energy auditingElectrical energy auditing
Electrical energy auditingPradeep DC
 
IRJET- Industrial Energy Audit
IRJET- Industrial Energy AuditIRJET- Industrial Energy Audit
IRJET- Industrial Energy AuditIRJET Journal
 
Evaluation of Electrical Services using Energy Efficient Load
Evaluation of Electrical Services using Energy Efficient LoadEvaluation of Electrical Services using Energy Efficient Load
Evaluation of Electrical Services using Energy Efficient LoadNajeem Olawale Adelakun
 
Time series data measurement on electricity consumption for selected domestic...
Time series data measurement on electricity consumption for selected domestic...Time series data measurement on electricity consumption for selected domestic...
Time series data measurement on electricity consumption for selected domestic...journalBEEI
 
Energy Conservation and Audit Exercise Book
Energy Conservation and Audit Exercise BookEnergy Conservation and Audit Exercise Book
Energy Conservation and Audit Exercise BookArnabSaha99
 
IRJET- Analysis of Energy - Efficient Measures for Architectural Building
IRJET- Analysis of Energy - Efficient Measures for Architectural BuildingIRJET- Analysis of Energy - Efficient Measures for Architectural Building
IRJET- Analysis of Energy - Efficient Measures for Architectural BuildingIRJET Journal
 
FEASIBILITY ANALYSIS OF A GRID-CONNECTED PV SYSTEM FOR HOME APPLICATION
FEASIBILITY ANALYSIS OF A GRID-CONNECTED PV SYSTEM FOR HOME APPLICATIONFEASIBILITY ANALYSIS OF A GRID-CONNECTED PV SYSTEM FOR HOME APPLICATION
FEASIBILITY ANALYSIS OF A GRID-CONNECTED PV SYSTEM FOR HOME APPLICATIONWayan Santika
 
Energy audit in Industry.pptx
Energy audit in Industry.pptxEnergy audit in Industry.pptx
Energy audit in Industry.pptxAyush51240
 
energy consumption calculator
energy consumption calculatorenergy consumption calculator
energy consumption calculatorNIRAV Gherwara
 
Energy Conservation By Mehfooz Qazi
Energy Conservation By Mehfooz QaziEnergy Conservation By Mehfooz Qazi
Energy Conservation By Mehfooz QaziIEEEP Karachi
 
Energy Auditing/ Energy conservation ppt by Varun Pratap Singh
Energy Auditing/ Energy conservation ppt by Varun Pratap SinghEnergy Auditing/ Energy conservation ppt by Varun Pratap Singh
Energy Auditing/ Energy conservation ppt by Varun Pratap SinghVarun Pratap Singh
 

Similar a Energy Auditing of a Typical Residential Building in Ibadan Metropolis (20)

T04404121128
T04404121128T04404121128
T04404121128
 
SUSTAINABLE ENERGY SYSTEMS 1 P a g e .docx
SUSTAINABLE ENERGY SYSTEMS  1  P a g e .docxSUSTAINABLE ENERGY SYSTEMS  1  P a g e .docx
SUSTAINABLE ENERGY SYSTEMS 1 P a g e .docx
 
IRJET- Computing Electricity Consumption Profiles for the Appliances in a House
IRJET- Computing Electricity Consumption Profiles for the Appliances in a HouseIRJET- Computing Electricity Consumption Profiles for the Appliances in a House
IRJET- Computing Electricity Consumption Profiles for the Appliances in a House
 
ADOPTING MEASURES TO REDUCE POWER OUTAGES
ADOPTING MEASURES TO REDUCE POWER OUTAGESADOPTING MEASURES TO REDUCE POWER OUTAGES
ADOPTING MEASURES TO REDUCE POWER OUTAGES
 
Energy audit.pdf
Energy audit.pdfEnergy audit.pdf
Energy audit.pdf
 
Presentation Demand Management
Presentation Demand ManagementPresentation Demand Management
Presentation Demand Management
 
Smart_Grid_WP_1124aFINAL
Smart_Grid_WP_1124aFINALSmart_Grid_WP_1124aFINAL
Smart_Grid_WP_1124aFINAL
 
Electrical energy auditing
Electrical energy auditingElectrical energy auditing
Electrical energy auditing
 
Reluctantly redundant the real cost of power
Reluctantly redundant the real cost of powerReluctantly redundant the real cost of power
Reluctantly redundant the real cost of power
 
IRJET- Industrial Energy Audit
IRJET- Industrial Energy AuditIRJET- Industrial Energy Audit
IRJET- Industrial Energy Audit
 
Evaluation of Electrical Services using Energy Efficient Load
Evaluation of Electrical Services using Energy Efficient LoadEvaluation of Electrical Services using Energy Efficient Load
Evaluation of Electrical Services using Energy Efficient Load
 
Time series data measurement on electricity consumption for selected domestic...
Time series data measurement on electricity consumption for selected domestic...Time series data measurement on electricity consumption for selected domestic...
Time series data measurement on electricity consumption for selected domestic...
 
Energy Conservation and Audit Exercise Book
Energy Conservation and Audit Exercise BookEnergy Conservation and Audit Exercise Book
Energy Conservation and Audit Exercise Book
 
IRJET- Analysis of Energy - Efficient Measures for Architectural Building
IRJET- Analysis of Energy - Efficient Measures for Architectural BuildingIRJET- Analysis of Energy - Efficient Measures for Architectural Building
IRJET- Analysis of Energy - Efficient Measures for Architectural Building
 
FEASIBILITY ANALYSIS OF A GRID-CONNECTED PV SYSTEM FOR HOME APPLICATION
FEASIBILITY ANALYSIS OF A GRID-CONNECTED PV SYSTEM FOR HOME APPLICATIONFEASIBILITY ANALYSIS OF A GRID-CONNECTED PV SYSTEM FOR HOME APPLICATION
FEASIBILITY ANALYSIS OF A GRID-CONNECTED PV SYSTEM FOR HOME APPLICATION
 
A1103020113
A1103020113A1103020113
A1103020113
 
Energy audit in Industry.pptx
Energy audit in Industry.pptxEnergy audit in Industry.pptx
Energy audit in Industry.pptx
 
energy consumption calculator
energy consumption calculatorenergy consumption calculator
energy consumption calculator
 
Energy Conservation By Mehfooz Qazi
Energy Conservation By Mehfooz QaziEnergy Conservation By Mehfooz Qazi
Energy Conservation By Mehfooz Qazi
 
Energy Auditing/ Energy conservation ppt by Varun Pratap Singh
Energy Auditing/ Energy conservation ppt by Varun Pratap SinghEnergy Auditing/ Energy conservation ppt by Varun Pratap Singh
Energy Auditing/ Energy conservation ppt by Varun Pratap Singh
 

Más de IOSR Journals (20)

A011140104
A011140104A011140104
A011140104
 
M0111397100
M0111397100M0111397100
M0111397100
 
L011138596
L011138596L011138596
L011138596
 
K011138084
K011138084K011138084
K011138084
 
J011137479
J011137479J011137479
J011137479
 
I011136673
I011136673I011136673
I011136673
 
G011134454
G011134454G011134454
G011134454
 
H011135565
H011135565H011135565
H011135565
 
F011134043
F011134043F011134043
F011134043
 
E011133639
E011133639E011133639
E011133639
 
D011132635
D011132635D011132635
D011132635
 
C011131925
C011131925C011131925
C011131925
 
B011130918
B011130918B011130918
B011130918
 
A011130108
A011130108A011130108
A011130108
 
I011125160
I011125160I011125160
I011125160
 
H011124050
H011124050H011124050
H011124050
 
G011123539
G011123539G011123539
G011123539
 
F011123134
F011123134F011123134
F011123134
 
E011122530
E011122530E011122530
E011122530
 
D011121524
D011121524D011121524
D011121524
 

Último

Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escortsranjana rawat
 
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSMANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSSIVASHANKAR N
 
Russian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur Escorts
Russian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur EscortsRussian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur Escorts
Russian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
Introduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxIntroduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxupamatechverse
 
Extrusion Processes and Their Limitations
Extrusion Processes and Their LimitationsExtrusion Processes and Their Limitations
Extrusion Processes and Their Limitations120cr0395
 
AKTU Computer Networks notes --- Unit 3.pdf
AKTU Computer Networks notes ---  Unit 3.pdfAKTU Computer Networks notes ---  Unit 3.pdf
AKTU Computer Networks notes --- Unit 3.pdfankushspencer015
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCall Girls in Nagpur High Profile
 
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdfONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdfKamal Acharya
 
Glass Ceramics: Processing and Properties
Glass Ceramics: Processing and PropertiesGlass Ceramics: Processing and Properties
Glass Ceramics: Processing and PropertiesPrabhanshu Chaturvedi
 
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...Call Girls in Nagpur High Profile
 
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINEMANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINESIVASHANKAR N
 
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...ranjana rawat
 
result management system report for college project
result management system report for college projectresult management system report for college project
result management system report for college projectTonystark477637
 
UNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular ConduitsUNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular Conduitsrknatarajan
 
UNIT-III FMM. DIMENSIONAL ANALYSIS
UNIT-III FMM.        DIMENSIONAL ANALYSISUNIT-III FMM.        DIMENSIONAL ANALYSIS
UNIT-III FMM. DIMENSIONAL ANALYSISrknatarajan
 

Último (20)

Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024
 
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
 
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSMANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
 
Russian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur Escorts
Russian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur EscortsRussian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur Escorts
Russian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur Escorts
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
 
Introduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxIntroduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptx
 
Extrusion Processes and Their Limitations
Extrusion Processes and Their LimitationsExtrusion Processes and Their Limitations
Extrusion Processes and Their Limitations
 
AKTU Computer Networks notes --- Unit 3.pdf
AKTU Computer Networks notes ---  Unit 3.pdfAKTU Computer Networks notes ---  Unit 3.pdf
AKTU Computer Networks notes --- Unit 3.pdf
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
 
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdfONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
 
Glass Ceramics: Processing and Properties
Glass Ceramics: Processing and PropertiesGlass Ceramics: Processing and Properties
Glass Ceramics: Processing and Properties
 
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
 
Roadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and RoutesRoadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and Routes
 
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINEMANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
 
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
 
result management system report for college project
result management system report for college projectresult management system report for college project
result management system report for college project
 
UNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular ConduitsUNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular Conduits
 
UNIT-III FMM. DIMENSIONAL ANALYSIS
UNIT-III FMM.        DIMENSIONAL ANALYSISUNIT-III FMM.        DIMENSIONAL ANALYSIS
UNIT-III FMM. DIMENSIONAL ANALYSIS
 

Energy Auditing of a Typical Residential Building in Ibadan Metropolis

  • 1. IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) e-ISSN: 2278-1676,p-ISSN: 2320-3331, Volume 6, Issue 5 (Jul. - Aug. 2013), PP 24-29 www.iosrjournals.org www.iosrjournals.org 24 | Page Energy Auditing of a Typical Residential Building in Ibadan Metropolis *Diji, C.J and **Ganiyu, H. * Ojoo Business Unit, Ibadan Electricity Distribution Company ** Department of Mechanical Engineering, University of Ibadan, Ibadan Abstract: An electricity audit of a building is the process whereby an energy manager survey and analyzes how energy is used in the building with the main objective of identifying opportunities for reducing the amount of energy used and ensuring that available energy is used efficiently. This study reports the outcome of an electricity audit on a typical residential building in a major location of Ibadan metropolis. The audited building is a four – flat apartment where all the customers in the building have different tariff plans. Two of the customers labeled Customer A and B are metered, while the other two Customers labeled C and D are not metered. The result of the audit showed that the metered customers were paying the actual estimated electricity bills, while the non – metered customers were over billed by over 30 and 80% respectively. The study concluded by recommending the metering of all residential apartments and the use of pre – paid meters as it not only stimulate demand but also is more effective in the electricity billing process Key Words: Electricity Audit, Residential Building, Ibadan I. Introduction Electricity is the main energy source used in most building. Indeed, electricity is required for the operation of numerous appliances in all residential building. Residential or domestic load consists of lights, fans, and appliances like radios, heaters, electric irons, refrigerators, coolers, electric water heaters, washing machines, amongst others. The small residential electricity consumers may generally use all the light points simultaneously given a demand factor of unity. For big houses, the demand factor may be only around 0.5. The demand for electricity continues to rise as population grows. Electrical energy demand refers to the maximum amount of electrical energy that is being consumed at a giving time. It is necessary, for system planning and operation, to know the total electrical energy requirements and the duration of various loads in residential apartments. This is necessary to give residential consumers and building owners a proper sense of how much energy different appliances and activities consumed, because most people consistently overestimate the impact of less energy consuming appliances and less effective conservation activities and under estimate the impact of energy of more energy consuming appliances and more effective conservation activities (Kempton et.al 1985). Understanding the way electricity is billed in residential apartments could sometimes seem very confusing, this is because unlike some other products, electrical energy cannot, in a practical sense, be stored. Rather, it needs to be generated and supplied as various equipments and home appliances require it. Day or night, the electricity utility provider must be able to meet the electricity requirements of its residential customers.The demand for electricity, and the flexibility needed to supply this electricity during peak times leads to “demand charges.” An energy survey and audit of buildings is the process by which a building is inspected and analyzed by an energy manager to determine how energy is used in it, with the goal of identifying opportunities for reducing the amount needed to operate the building while maintaining comfort level (Thumann and Young 2003). This study reports the outcome of an energy survey and audit of a typical residential apartment in a typical residential area in Ibadan metropolis. The residential apartment is located at Onikoro area, Shasa, Ibadan. It is made up of a four flat apartment with each flat consisting of three bedroom, sitting room, dinning, two toilets, two bathrooms, kitchen, store, passage and corridor. It takes its source of electricity from Shasa 1 500KVA substation on Shasa 11KVA feeder. The occupants of the apartment are on different electricity tariff plans. One of the occupants uses a single phase prepaid meter, another an analogue meter while the remaining two flats are on no meter. The study involves the interpretation and comparison of one of the monthly electricity bills of the different apartments in the building. The interpretation and comparison is done to make appropriate recommendations to the occupants of the building and the utility provider, the Power Holding Company of Nigeria (PHCN) on appropriate electricity consumption and billing for future electricity planning purposes.
  • 2. Energy Auditing of a Typical Residential Building in Ibadan Metropolis www.iosrjournals.org 25 | Page The study is divided into five sections. The first section includes the introduction; section two discusses extensively the concept of energy survey and auditing in buildings, while the third section elaborates the methodology used in conducting the study. Section four discusses the results of the study and section five concludes. II. ElectricityUse and Auditing in Buildings Electrical loads refer to the power consumed by a circuit and they are classified by tariff schedules into three major categories namely: industrial, commercial and residential loads. Industrial electricity customers usually engage in the manufacture of certain product or commodities and or convert given raw materials into partly processed or finished products basically different from the raw materials. The factories usually have a large number of motor, heaters, oven, presses air conditioning equipment and other electrical appliances. Assessing maximum electricity demands require a thorough knowledge of the industrial processes involved. Residential electricity consumers are typified by normal domestic utilization of electric energy for lighting, cooking, refrigeration and air conditioning, water heating, laundry and other miscellaneous applications. In assessing maximum demands of this category of loads, special attention should be paid to the air conditioning load and the standard of living of the occupier vis – a – vis the ability of the consumer to pay the electricity bills which may arise as a result of load and diversity factors assured in assessing the maximum demands and electricity requirements. Commercial electrical loads are all electrical loads that are neither residential nor industrial, usually involving small scale business outfits that are involved in providing various services. An electricity audit is simply an audit or calculation of how much electricity is being used in the home and of where that electricity is going. An electricity audit can help to identify waste so that the causes of additional electricity use can be eliminated thereby reducing the expenditure on electricity in the home and reducing damages to the environment. There are two different types of electricity audit. The first is simply a do – it – yourself audit; this involves the use of a calculator to find out how much energy each appliance and activity is using in order to identify where your money is going when you pay your electric bill. There are several online calculator tools that can be used for this purpose, thereby allowing the consumer to do is own electricity audit. The second type of energy audit involves hiring a professional energy auditor to come to your home to identify where and how energy is being wasted. These energy professionals usual work for home improvement or building companies, and usually assist the residential consumer in identifying leaks and other areas of inefficient use of electricity. The outcome of their work is expected to assist the consumer to improve in efficient utilization of electricity and reduction in electricity costs in the home. 2.1 Estimating Electricity Consumption and Cost of Domestic Appliances Electricity consumption is measured in kilowatt-hours (kWh), and one kWh equals 1,000 watts of electricity used during one hour. To determine the total electricity consumed in the home by an electrical appliance over a given period of time, it is first important to determine the amount of power (watts) of the appliance. Manufacturers typically indicate the wattage on the back of the appliance. If the wattage is not given, look for the amperage (amps) and voltage (volts) listed on the appliance. The multiplication of the amperage with the voltage of the appliance will give the power (Watts) rating of the appliance. To determine the electrical consumption of the appliance for a month, simply multiply the wattage times the number of hours the appliances is used and divide by 1000 to get the kWhs. For example if a 60 Watts bulb is used for a 5 hour period per day for a 30 days month; then the total electrical consumption will be 9 kWh. The power consumed by each appliance during the year depends on, amongst other factors: 1. The average watts per hour consumed by the appliance when in active use. For many appliances, this is not the same as the rated power consumption of the appliance since most do not normally operate continuously at their rated energy consumption. 2. The number of hours in active use of each appliance per year. 3. The power consumed by the appliance (standby power) when it is not in active use. 4. Year in which it was sold 5. The market mix of the appliances sold in that year (size, technology, supplier) 6. The mean energy efficiency of those appliances both in operation and standby. To calculate the cost of your electricity, whether for a particular appliance or other device, you need to know the rate of consumption and the price of the electricity. The former you can find either printed on the unit or in the manual. In addition to the rate of power usage, the duration of usage is part of the calculation. For the cost or the electric power, check your bill. The bill will show the price per power unit, the kilowatt-hour. That unit equals a consumption rate of 1,000 watts, in operation for one hour.
  • 3. Energy Auditing of a Typical Residential Building in Ibadan Metropolis www.iosrjournals.org 26 | Page 2.2 Electricity Metering and Billing An electric meter or energy meter is a device that measures the amount of electrical energy supplied to a residence or business. These are the customers of an electric utility. Utilities record the values measured by these meters to generate an invoice for the electricity consumed. The most common unit for measurement on the electricity meter is the kilowatt-hour which is equal to the amount of energy used by a load of one kilowatt over a period of one hour, or 3,600,000 joules. Electrical metering is important because the performance of utilities at various points is judged by the global metering at grid points. For efficiency, therefore, the metering should be cascaded to the individual customer’s premises. The accuracy of billing largely depends on the accuracy of metering and the number of metered premises. Thus there is the need to strive to provide meters to the customers not having meters and to repair or replace the faulty meters in the system. Modern electricity meters operate by continuously measuring the instantaneous voltage (volts) and current (amperes) and findings the product of these to give instantaneous electrical power (watts) which is then integrated against time to give energy used (joules, kilowatt-hours etc). The meters fall into two basic categories: These are electromechanical and electronic meters. Electricity billing is the process of converting the electric meter reading or estimation of the customer’s consumption (and demand) to a bill using appropriate tariff. An electric bill is expected to indicate the information provided in Table 1. Table 1: Information on an Electricity Bill S/N INFORMATION DETAILS 1. Customer Information Account Number Name Service Centre Type of Account Meter Status/dials Customer Type Average Daily consumption 2. Description of Charge Energy charge (Where Applicable) Fixed Charge Meter Maintenance Charge 3. Transaction information Previous Balance Payments Adjustments Current Charges Value Added Tax Total Amount Due For Payment 4. Other Required Information LAR (Last Actual Reading) Date Date of Last Payment/Amount Paid Reconnection Fee Charges Tariff Rate for Account Type Due Date Read Date Tariff Code Electricity bills are produced through three broad forms namely: meter reading, estimation and fixed consumption (direct) modes. Meter reading involves the subtraction of the previous reading from the present reading and the value obtained is used to bill the consumption of the customer, this mode of billing is the most convenient and appropriate form of billing. Estimation mode of billing is used when there is no access to the customer premises and in situations in which the previous reading is observed to be higher than the present reading. The Fixed consumption mode of billing is used in situations where the bills are produced on fixed consumption; this mode is applied in situations where there is delayed meter installation, faulty meter or where the meter has been stolen. III. Research Methodology The study involved the energy survey and auditing of the selected area of research, which is the four – flat apartment at the Onikoro area of Shasha area in Ibadan metropolis. The customers in the four flat as stated earlier have different tariff plans and their energy bills are estimated differently. Each of the flats consists of three bedroom, sitting room, dining room, two toilets, two bathrooms, kitchen, store, passage and corridor.
  • 4. Energy Auditing of a Typical Residential Building in Ibadan Metropolis www.iosrjournals.org 27 | Page The four customers have been designated as Customer A, B, C and D. Customer A uses a pre – paid meter; Customer B uses an analogue meter, while Customer C and D have no meters and their energy billing is currently done by fixed consumption mode. The complete energy audit of the apartment was conducted over a two week period and involved collection of all necessary electrical appliances in each apartment. This included the identification of the electrical devices used, their types, models, current ratings, voltage ratings, cautions on them, input and output powers, amongst others. The audit also took into cognizance factors that could affect the effective distribution of electricity in the apartment such as technical and commercial losses, as well as unforeseen emergencies of extra load. The general procedure used in the audit involved the following: 1. Facility and Utility Data Analysis 2. Walk through survey 3. Administration of questionnaires 4. Data processing and production of final report It must be noted that in performing the audit, several of the tasks under the procedures stated above have to repeated, reduced in scope or even eliminated based on the findings of other tasks. Hence, an audit is often not a linear process, but is rather an iterative one. 3.1 Facility and Utility Data Analysis In this step, the characteristics and patterns of electricity usein the building apartment was established. This involved the compilation and historical analysis of the utility bills of the apartment over a three months period i.e. from December 2011 to February, 2012. This was done to see if there is any seasonal and weather effects on the building electricity use. The monthly utility bills were obtained from the PHCN business unit in Ojoo and from established customer data for the same period. 3.2 Walk through Survey During the audit exercise, a walk through survey was conducted to estimate the electrical load for each of the apartments and to identify potential energy saving measures that will eliminate wasteful usage of electricity. The tasks carried out during the walk through survey included: I. Identifying the customer concerns and needs. II. Checking the current operating and maintenance procedures. III. Determining the existing operating conditions of major energy-use equipment (lighting, HVAC systems, etc.). IV. Estimate the occupancy, equipment, and lighting (energy-use density and hours of operation). 3.4 Field Questionnaires This was administered to each of the flats in the apartment to identify how electricity supply was received by each flat, the appliances used and the number of hours there was electricity availability during February 2012. 3.5 Data Processing and Production of Final Report The results of the walk through survey and the administered questionnaires were used to estimate the connected load, maximum demand and demand factors of each flat and a full comparative energy use analysis of the building was carried out with the identification of energy losses. 3.5.1 Connected load The connected load of a customer means the sum of the continuous rating of all the devices and outlet installed on all the distribution circuit. By calculating the Total Connected Load (TCL), it will be possible to estimate the TCL for a particular area and for determining the sizing of cables. The TCL also makes it possible to determine Maximum Demand (MD) for a customer or group of customers and provides the utility provider useful information for the purpose of meter deposit and utility bill. 3.5.2 Maximum Demand (MD) This is the maximum power that a circuit is likely to draw at a certain time. Thus the maximum demand of a customer is always less than the connected load of a customer.The reason for this is that the connected loads are used intermittently and usually does not operate at their full electrical ratings. Also the maximum load demand cannot be calculated simply by adding the maximum demands of individual loads since the individual maximum demands occur at deferent times The Maximum Demand is connected to the TCL by the Demand Factor (DF). The DF is the ratio of the MD of a system or part of a system, to the TCL on the system or part of the system under consideration. DF is always less than 1 (one).
  • 5. Energy Auditing of a Typical Residential Building in Ibadan Metropolis www.iosrjournals.org 28 | Page 𝐷𝑒𝑚𝑎𝑛𝑑𝐹𝑎𝑐𝑡𝑜𝑟 𝐷𝐹 = 𝑀𝑎𝑥𝑖𝑚𝑢𝑚𝐷𝑒𝑚𝑎𝑛𝑑 𝑇𝑜𝑡𝑎𝑙𝐶𝑜𝑛𝑛𝑒𝑐𝑡𝑒𝑑𝐿𝑜𝑎𝑑 IV. Results and Discussion Table 2 shows the preliminary results of the energy audit of the four apartments while Table 3 shows the estimated connected load for the residential apartment and Table 4 shows actual energy consumption and cost of electricity for the month of electricity and the electricity billing from the utility provider, the PHCN. From the aforementioned tables, it is obvious that customer A with the pre- paid meters paid actual electricity bills and paid over 4 times more than the other customers in the apartment. Customer B, who is analogue metered and with a maximum demand of 2.9kW was also properly billed as there is little or no disparity between the estimated cost of using electricity and the electricity billing from the utility company. In addition, customer B is obviously the most energy efficient occupant of the building. Customer C and D who pay a fixed monthly charge are overbilled by over 30% and 80% respectively, due to non – availability of meters. This shows that fixed monthly charges will not be beneficial in the long run to most residential electricity consumers. It is better for all residential customers to be metered. With regards to the Electricity Utility company. It is obvious that the use of pre – paid meters will stimulate consumption and bring more revenue to the company. The practice should be encouraged and sustained. Table 2: Preliminary Results of Electricity Audit S/N LOCATION Customer A Customer B Customer C Customer D 1 Master Room 1No 60w bulb 1No 65w Standing Fan 1No 64w TV 1No 60w Laptop 2Nos 25w Energy Bulb 1No 60w Bulb 1No 65w Fan 2Nos 25w Energy Bulb 1No 180w Portable Fridge 1No 100w Bulb 1No 55w Ceiling Fan 2Nos 25w Energy Bulb 1No 45w Standing Fan 1No 60w Bulb 1No 55w Ceiling Fan 2Nos 25w Energy Bulb 2 Master Toilet Ino 100w Bulb 32 4Ft Fluorescent tube 1No 40w 1No 60w Bulb 1No 100w Bulb 3 2nd Room 1No 100w Bulb 1No 55w Standing Fan 2Nos 25w Energy Bulb 1No 60w Bulb 1No 60w Laptop 1No 55w Ceiling Fan 2Nos 25w Energy Bulb 1No 60w Bulb 1No 65w Fan 2Nos 25w Energy Bulb 1No 60w Bulb 1No 55w Standing Fan 2Nos 25w Energy Bulb 4 3rd Room 1No 60w Bulb 1No 65w Fan 2Nos 25w Energy Bulb 1No 60w Bulb 1No 65w Fan 2Nos 25w Energy Bulb 1No 60w Bulb 1No 55w Ceiling Fan 2Nos 25w Energy Bulb 1No 60w Bulb 2Nos 25w Energy Bulb 5 2nd Toilet 1No 100w Bulb 1No 60w Bulb 1No 60w Bulb 1No 100w Bulb 6 Sitting Room 1No 100w T.V 1No 130w Standing Fan 1No 190w DVD Player 1No 25w DSTV Decoder 4Nos 25w Energy Bulb 1No 40w 32' 4Ft Fluorescent 1No 55w Ceiling Fan 1No 2Hp Airconditioning 1No 1000w Stabilizer 1No 159w Computer System (Monitor, System Unit, Stabilizer & UPS) 1No 35w Radio 1No 75w T.V 1No 55w Ceiling Fan 1No 25w DSTV Decoder 4No 25w Energy Bulb 1No 1000w Stabilizer 1No 25w Radio 1No 40w 32' 4Ft Fluorescent 1No 64w T.V 1No 55w Ceiling Fan 1No 190w DVD Player 1No 35w Radio 4Nos 25w Energy Bulb 1No 100w Bulb 1No 1200w Pressing Iron 1No 100w T.V 1No 130w Standing Fan 1No 25w DSTV Decoder 1No 40w 32' 4 Ft Fluorescent 1No 1000w Stabilizer 1No Laptop 80w 4Nos 25w Energy Bulb 7 Dining Room 2Nos 25w Energy Bulb 1No 60w Bulb 1No 55w Ceiling Fan 1No 150w Refrigerator 1No1000w Stabilizer 2No 25w Energy Bulb 1No 60w Bulb 1No 65w Standing Fan 2Nos 25w Energy Bulb 1No 60w Bulb 1No 45w Standing Fan 2No 25w Energy Bulb 1No 100w Bulb 1No 55w Ceiling Fan 8 Kitchen 1No 200w Freezer 1No 100w Bulb 1No 300w Fruit Extraction 1No 700w Toaster 1No 350w Blender 1No 500w Stabilizer 1No 180w Freezer 1No 100w Bulb 1No 1000w Stabilizer 1No 1600w Electric Kettle 1No 60w Bulb 1No 300w Blender 1No 1000w Hotplate 1No 1000w Boiling Ring 1No 1000w Hotplate 1No 100w Bulb 1No 150w Refrigerator 9 Passage 1No 100w Bulb 1No 1200w Pressing Iron 1No 40w 2' 4Ft Fluorescent tube 1No 1200w Pressing iron 1No 60w Bulb 1No 60w Bulb 1No 1000w Pressing Iron 10 Store 1No 100w Bulb 1No 60w Bulb 1No 100w Bulb 1No 100w Bulb 11 Surrounding 2Nos 100w Bulb 2Nos 100w Bulb 2Nos 100w Bulb 2Nos 100w Bulb
  • 6. Energy Auditing of a Typical Residential Building in Ibadan Metropolis www.iosrjournals.org 29 | Page Table 3: Estimated Connected Load for Each Apartment S/N LOCATION Customer A (Watts) Customer B (Watts) Customer C (Watts) Customer D (Watts) 1 Master Room 299 355 250 165 2 Master Toilet 100 40 60 100 3 2nd Room 205 225 175 165 4 3rd Room 175 175 165 110 5 2nd Toilet 100 60 60 100 6 Sitting Room 3299 1320 1744 1744 7 Dining Room 1315 175 155 155 8 Kitchen 2150 2880 2360 2360 9 Passage 2200 1240 60 1060 10 Store 100 60 60 60 11 Surrounding 200 200 200 200 TOTAL 10,143 6,730 5,289 4,680 Table 4: Actual Energy Consumed and Cost of Electricity Supplied S/N ITEM Customer A Customer B Customer C Customer D 1. Connected Load (kW) 10.14 6.73 5.29 4.68 2. Maximum demand (kW) 3.3 2.88 2.36 1.27 3. Demand Factor 0.33 0.43 0.45 0.36 3. Total Energy Consumed(kWh) 610.23 176.97 170 134.01 4. Cost of Energy consumed (N) 4,342 1,291.88 1,240.93 978.27 5. Energy Billing by PHCN for February, 2012 (N) 1,301.04 1,825 1,825 V. Conclusion The paper examined the outcome of an electricity audit on four customers on different tariff plans in a typical residential building in Ibadan metropolis. It is the conclusion of the study that the use of fixed charges for electricity billing is not favourable to residential consumers of electricity and the use of pre – paid meters will obviously stimulate electricity demand and consumption. References [1]. Electric Power Research Institute (1993) - Reduction cost by understanding your bill. [2]. Ezeruigbo E. N (2001) - AT&C Loss reduction India Experience [3]. Osideide, A. A. (2011) - Strategic electricity marketing Activities in distribution companies of Nigeria [4]. PHCN(2011) - Commercial instruction manuals [5]. Taylor Francis Group LLC, (2006) - Handbook of energy efficiency and renewable energy