SlideShare una empresa de Scribd logo
1 de 65
12DE 
1004 Saiesh 
1005 Brembley 
1006 Russell 
1007 Mukesh
THE FIRE TRIANGLE 
Three components 
required for combustion 
Fuel – to vaporize and burn 
Oxygen – to combine with fuel vapour 
Heat – to raise the temperature of the fuel 
vapour to its ignition temperature.
 Two important factors to remember in 
preventing and extinguishing a fire: 
i) If any of the three components are missing, then a fire 
cannot start. 
ii) If any of the three components are removed, then the 
fire will go out.
THE FIRE TETRAHEDRON 
 solid figure with four triangular faces 
 shows the chain reaction and each face touches the 
other three faces. 
 The basic difference - illustrates how flaming combustion 
is supported and sustained through the chain reaction of 
the oxidation process.
VARIOUS SYSTEMS USED ONBOARD FOR 
FIGHTING FIRE 
 HIGH EXPANSION FOAM SYSTEM 
 CO2 SYSTEM 
 SPRINKLER & SPRAYER SYSTEM 
 HALON SYSTEM
WHAT IS FOAM ? 
 combination of three materials: 
• Water 
• Air 
• Foam making agent 
 formed by mixing the foam-making agent with water to 
create a foam solution. 
 foam bubbles created by introducing air into the foam 
solution through aerating devices. 
 Two most common concentrations are 3% and 6% 
foams.
HOWIS FOAM GENERATED ? 
 A constant amount of foam concentrate is added to water 
by means of a proportioner. 
 The resulting mixture of water/foam concentrate is 
expanded with air in the foam generator.
AIR IN 
FAN SPRAY NOZZLE 
SEA WATER EDUCTOR 
FOAM CONCENTRATOR 
NYLON MESH 
TO ENGINE ROOM
THE INDUCTION RATE 
 specifies the percentage ratio of foam concentrate added 
to water. 
 
 At 3% induction rate, for example, 3 parts of foam 
concentrate are mixed with 97 parts of water.
FILM FORMATION 
Aqueous film 
(AFFF effect) 
 The foam produces a very thin aqueous film on non polar 
liquids 
 This film floats ahead of the foam and provides for its 
excellent flowing, extinguishing and re-ignition inhibiting 
properties.
Polymer film 
• produced by the polymer film formers contained in the 
foam when extinguishing polar hydrocarbons (e.g 
alcohols, ketones, ester). 
• The film floats as an insulating protective layer between 
the foam destroying alcohol and the foam cover above.
HOWFOAM EXTINGUISHES FIRE ? 
o Separating effect 
The closed foam cover separates the combustion zone 
from the ambient air. 
o Cooling effect 
The flammable material is cooled down by the water/ 
foam solution discharged by the foam.
o Cover effect 
The closed foam cover stops any further gas evaporation 
from burning materials, i.e. flammable gases 
foam forms a blanket on the surface of flaming liquids 
o Repression effect 
Flooding spaces, channels, plant parts, etc. with high or 
medium expansion foam represses the atmospheric oxygen 
and flammable gases necessary for the combustion 
process. 
o Insulation effect 
foam insulates flammable material which has not yet caught 
fire
FOAM CHARACTERISTICS 
 Knockdown Speed and Flow- ability to spread across a 
fuel surface or around obstacles 
 
 Heat Resistance-able to resist the destructive effects of 
heat radiated from any remaining fire 
 Vapour Suppression. capable of suppressing the 
flammable vapours to break the fire triangle.
Alcohol Resistance-foam blankets that are not 
alcohol-resistant will be destroyed if used on 
alcohol-based cargoes. 
cohesive properties- to stick together 
sufficiently to establish and maintain a vapour 
tight blanket 
light enough-to float on flammable liquids, yet 
heavy enough to resist winds
TYPES OF FOAMS 
Chemical foam 
• formed by mixing together a solution of an alkali, an acid, 
water and a stabilizer. 
• forms a foam or froth of bubbles filled with carbon dioxide 
gas. 
• 7 to 16 volumes of foam are produced for each volume of 
water. 
• Needs a device called a foam hopper or separate tanks
 Mechanical (Air) Foam 
• produced by mixing a foam concentrate 
with water to produce a foam solution. 
• The bubbles are formed by the turbulent 
mixing of air and the foam solution.
TYPES OF MECHANICAL FOAMS 
 Protein Foam 
produced by the hydrolysis of waste protein material, such as 
protein-rich animal waste and vegetable waste that is 
hydrolyzed 
 Fluoroprotein Foam (FP). 
formed by the addition of special fluorochemical surfactants 
with protein foam 
 Film Forming Fluoroprotein Foam (FFFP) 
combination of fluorochemical surfactants with protein foam 
release a film on the surface of the hydrocarbon.
 Aqueous Film Forming Foam (AFFF) 
• combination of fluorochemical surfactants and synthetic foaming 
agents 
• film spreads rapidly causing dramatic fire knockdown. 
 Alcohol Resistant-Aqueous Film Forming Foam (AR-AFFF) 
• combination of synthetic stabilizers, foaming agents, fluorochemicals 
and alcohol resistant additives 
• offers good burnback resistance, knockdown and high fuel tolerance 
on both hydrocarbon and alcohol fuel fires. 
 Synthetic Foam 
• made up of alkyl sulfonates. 
• It foams more readily than the proteins and requires less water 
important where the water supply is limited
CATEGORIES OF FOAM SYTEMS 
 Low Expansion Foams 
• expansion ratio of 12:1 when mixed with air 
• effective in controlling and extinguishing most flammable liquid 
(Class “B”) fires 
• typically used on tanker deck foam systems 
 Mid Expansion Foams 
• expansion ratio of between about 20:1 to 100:1 
• truly three dimensional; it is measured in length, width, height, and 
cubic feet 
 High-expansion foam 
• designed for fires in confined spaces 
• Heavier than air but lighter than oil or water
LIMITATIONS ON THE USE OF FOAM 
 Because they are aqueous (water) solutions, foams are 
electrically conductive 
 Like water, foams should not be used on combustible-metal 
fires. 
 not suitable for fires involving gases and extremely low 
temperature liquids. 
 If placed on burning liquids whose temperatures exceed 
100°C (212°F), the water content of the foam may cause 
frothing, spattering or slopover. 
 Sufficient foam must be available.
ADVANTAGES OF FOAM 
 effective smothering agent and provides cooling effect. 
 sets up a vapor barrier that prevents flammable vapors 
from rising 
 Can be used on Class “A” fires because of its water 
content. 
 effective in blanketing oil spills 
 uses water economically
 most effective extinguishing agent for fires involving large 
tanks of flammable liquids. 
 can be made with fresh water or seawater, and hard or 
soft water 
 does not break down readily and extinguishes fire 
progressively 
 Foam stays in place, covers and absorbs heat from 
materials that could cause re-ignition 
 Foam concentrates are not heavy, and foam systems do 
not take up much space.
PRACTICAL ISSUES 
 Water Temperature and Contaminants 
more stable when generated with lower temperature 
water. 
temperature range 1.7°C to 26.7°C 
 Combustible Products in Air 
It is desirable to take clean air into the foam nozzle at all 
times 
 Water Pressures 
Nozzle pressures should be held between 3.4 bar and 
13.8 bar (50 and 200 psi)
 Non-ignited Spills 
Where flammable liquids have spilled, fires can be 
prevented by prompt coverage of the spill with a foam 
blanket 
 Electrical Fires 
not generally recommended for use on electrical fires 
 Vaporized Liquids 
not recommended for use on materials that react with 
water, such as magnesium, titanium, potassium etc.
HIGH EXPANSION FOAM SYSTEM AND EQUIPMENT
FOAM GENERATOR 
 Delivers large quantity of expanded foam by blowing air 
through a screen 
 Because of high expansion ratio requires little water
FOAM GENERATOR
FOAM GENERATOR SCREEN
FOAM GENERATOR SCREEN
FOAM GENERATOR SCREEN
1) Proportioning Devices 
 Eductor 
 most common form of proportioning equipment works on 
the Venturi principle. 
 extremely reliable and simple pieces of equipment
Around-the-Pump Systems 
 an eductor is installed on the discharge side of the water 
pump 
 water flow causes a vacuum that picks up and introduces 
the foam concentrate into the water
 Balanced Pressure Foam Proportioners 
 extremely versatile and accurate 
 The principle of operation based on the use of a 
modified venturi proportioner commonly called a 
ratio controller.
2) FOAM NOZZLES 
 designed to air aspirate (expand) the foam 
solution and form finished foam. 
 High expansion foam nozzles expands foam in 
excess of 100:1, when high expansion foam 
concentrates are used.
3) FOAM MONITORS 
 are permanently-installed foam discharge units 
 capable of being aimed and projecting large 
quantities of foam substantial distances. 
 normally mounted on a rotating base (360- 
degree circle)
4) VALVES AND PIPING 
must be adequately designed to match the flow 
rates of the equipment, and a thorough 
understanding of the system 
 control valves is critical for quick and effective 
operation of the system 
 Color coding of the valves
4) VALVES AND PIPING
5) FOAM CONCENTRATE STORAGE 
 stored in tanks ready to supply the proportioning 
system 
 The concentrate tank should be kept filled with 
liquid halfway 
 The tank should be kept closed to the atmosphere
SOLAS REQUIREMENTS 
 FOAM CONCENTRATE 
 Foam concentrates to be of the type approved by 
administration 
 Capable of rapidly discharging foam @ at least 1 m 
in depth per minute 
 Volume of foam = 5 x volume of largest space 
 Expansion ratio not to exceed 1000:1
 INSTALLATION REQUIREMENTS 
• System should provide effective foam production and 
distribution 
• Foam generator delivery ducting to be protected 
against fire risk, withstand 925 deg C. 
• Foam delivery ducts to be constructed of steel 
having thickness > 5 mm 
• Dampers to be automatically operated by remote 
control 
• All system equipment to be readily accessible and 
simple to operate
ABS REQUIREMENTS FOR FOAM EXTINGUISHING SYSTEMS 
 Design and Certification of Piping Components 
• All valves, fittings and piping to comply with the 
applicable requirements 
• be suitable for the intended pressures 
 Pipe and Pipe Joints 
the wall thickness, type and design of the pipe joints to 
comply with the requirements
 Materials 
• materials used in the system should not to be 
rendered ineffective by heat. 
• material to have a melting temperature higher 
than the test temperature specified in an 
acceptable fire test. 
Pumps 
• should be tested in the presence of a Surveyor
 Pressure Vessels 
 the tank is to be considered a pressure vessel and is to 
comply with the requirements as applicable. 
System Component Certification 
 fixed fire-extinguishing system components are to be 
certified. 
 Accordingly, components such as foam system eductors, 
proportioners, monitors, nozzles, etc., are to comply with 
the certification requirements
STARTING PROCEDURE 
 AUTOMATIC START 
 Stop the supply fan and exhaust fan in the E/R. 
 Break the Destruct plate and push the system standby 
switch. 
 Alarm sound for evacuation in the E/R. 
 Start the Emergency fire pump manually. 
 After evacuation is confirmed push the foam discharge 
switch. 
 TO STOP; 
 Push the system stop switch. 
 Stop the Emergency fire pump.
 MANUALLY START AT LOCAL SIDE. 
 Check all Valves. 
 Start the Emergency fire pump. 
 Check pressure gauge, indicate 4 bar. 
 Open valve and start foam liquid pump. 
 TO STOP: 
 Stop the Emergency fire pump. 
 Close the valves.
EXAMPLE CALCULATION OF THE CAPACITY OF 
FOAM SYSTEM FOR OIL CARRIER SHIP 
14.5 m 9m 
PARTICULARS 
• BEAM = 14.5 M 
• LENGTH = 56 56m 
OF CARGO AREA M 
• LENGTH OF LARGEST CARGO TANK = 9 M 
• CARGO DECK AREA = 14.5 M ×56 M = 812 M2 
• HORIZONTAL SECTIONAL AREA OF SINGLE LARGEST 
TANK = 14.5 M ×9 M = 130.5 M2 
• PROPOSED MONITOR SPACING = 9 M 
AREA PROTECTED BY LARGEST MONITOR = 9 M × 14.5 M = 130.5 M2
A CASE STUDY
LESSONS LEARNT 
 Proper maintenance should be done including putting 
back the cover 
 Blowing/purging the line after hydraulic pressure testing 
 Inspection of the foam nozzle after test 
 Foam line on board to be pressure tested regularly 
 Draining the line to prevent accumulation of water
WHERE IS HIGH EXPANSION FOAM SYSTEM 
USED ? 
 ENGINE ROOM 
 PURIFIER ROOM 
 INCINERATOR ROOM 
 PUMP ROOM
PACKING OF FOAM 
CONCENTRATES 
20 litres Plastic Can 
Size (ca. cm) 38 x 38 x 18 
Tara ca. kg 1,4 
Suitability Synthetic, Protein 
Net weight approx Synthetic 20 Kg, Protein 23 Kg 
Stackable 2 high, to 40°C, shrink-wrapped onto a 
pallet
20 litres Plastic Can 
Blue 
Size (ca. cm) 29 x 26 x 39 
Tara ca. kg 1,2 
Suitability Synthetic, Protein 
Net weight approx 25 – 30 Kg 
Stackable 2 high, to 40°C, shrink-wrapped onto a 
pallet
200 litresValenthene 
Barrel 
Size (ca. cm) 60 x 90 
Tara ca. kg 21 
Suitability Synthetic, Protein 
Net weight approx 200 – 225 Kg 
Stackable 2 high
1000 litres Palett 
Container 
Size (ca. cm) 100 x 120 x 116 
Tara ca. kg 80 
Suitability Synthetic, Protein 
Net weight approx Synthetic 1040 Kg, Protein 1150 Kg 
Stackable 2 high
TYPES OF HIGH EXPANSION FOAM SYSTEMS 
TOTAL FLOODING SYSTEM
MAINTENANCE AND INSPECTION OF SYSTEM AND 
APPLIANCES. 
 Operational readiness 
• To be in good order and readily available for immediate 
use while the ship is in service. 
 Maintenance and Testing 
• should be carried out in accordance with the ship's 
maintenance plan. 
• Inspections should be carried out by the crew in 
accordance with manufacturer's maintenance and 
inspection guidelines
 MONTHLY TESTING AND INSPECTIONS 
• Verify all control and section valves are in the 
proper open or closed position, and all pressure 
gauges are in the proper range.
 QUARTERLY TESTING AND INSPECTIONS 
• Verify the proper quantity of foam 
concentrate is provided in the foam 
system
ANNUAL TESTING AND INSPECTIONS. 
o visually inspect all accessible components 
o functionally test all fixed system audible alarms 
o flow test all water supply and foam pumps for 
proper pressure and capacity 
o Ensure all piping is thoroughly flushed with fresh 
water after service
o test all system cross connections to other sources of 
water supply for proper operation; 
o verify all pump relief valves, if provided, are properly set 
o examine all filters/strainers to verify they are free of 
debris and contamination 
o verify all control/section valves are in the correct 
position
 blow dry compressed air or nitrogen through the 
discharge piping 
 confirm the pipework and nozzles of high expansion foam 
systems are clear of any obstructions, debris and 
contamination 
 take samples from all foam concentrates carried on 
board and subject them to the periodical control tests 
 test all fuel shut-off controls connected to fire-protection 
systems for proper operation.
 FIVE-YEAR SERVICE 
 perform internal inspection of all control valves 
 flush piping with fresh water, drain and purge with air 
 check all nozzles to prove they are clear of debris 
 test all foam proportioners to confirm that the mixing 
ratio tolerance is within +30 to -10% of the nominal 
mixing ratio
TESTING OF FOAM SAMPLES 
No Type of foam concentrate Minimum frequency 
1 All Fixed systems except protein based non-alcoholic 
Within 3 years from the date 
of manufacture and every 
year thereafter. 
2 All Fixed systems of protein based non-alcoholic 
Annually. 
3 All factory-sealed portable containers excluding 
protein based 
Ten yearly. 
4 All factory-sealed portable containers of protein 
based concentrates 
Five yearly. 
5 All non-sealed portable containers Within 3 years from the date 
of manufacture and every 
year thereafter
High Expansion Foam System

Más contenido relacionado

La actualidad más candente

Work Permit System
Work Permit SystemWork Permit System
Work Permit SystemGagan Tanwar
 
V 1 presentation on safety aspects of lpg handling and storage
V 1 presentation on safety aspects of lpg handling  and storageV 1 presentation on safety aspects of lpg handling  and storage
V 1 presentation on safety aspects of lpg handling and storageImran Bokhari
 
Job Safety Analysis For Lifting Activity By Crane | JSA | Gaurav Singh Rajput
Job Safety Analysis For Lifting Activity By Crane | JSA | Gaurav Singh RajputJob Safety Analysis For Lifting Activity By Crane | JSA | Gaurav Singh Rajput
Job Safety Analysis For Lifting Activity By Crane | JSA | Gaurav Singh RajputGaurav Singh Rajput
 
chpter 9 FOAM & FOAM MAKING EQUIPMENTS.pptx
chpter 9 FOAM & FOAM MAKING EQUIPMENTS.pptxchpter 9 FOAM & FOAM MAKING EQUIPMENTS.pptx
chpter 9 FOAM & FOAM MAKING EQUIPMENTS.pptxshyleshkumar15
 
Classification of hazardous area for lighting
Classification of hazardous area   for lightingClassification of hazardous area   for lighting
Classification of hazardous area for lightingHarendra Vishwakarma
 
Risk Assessment At Tank- Truck Unloading Section Of LPG Bottling Plant I Gaur...
Risk Assessment At Tank- Truck Unloading Section Of LPG Bottling Plant I Gaur...Risk Assessment At Tank- Truck Unloading Section Of LPG Bottling Plant I Gaur...
Risk Assessment At Tank- Truck Unloading Section Of LPG Bottling Plant I Gaur...Gaurav Singh Rajput
 
Safety awareness training program
Safety awareness training programSafety awareness training program
Safety awareness training programNoel Tan
 
Storage tanks basic training (rev 2)
Storage tanks basic training (rev 2)Storage tanks basic training (rev 2)
Storage tanks basic training (rev 2)ledzung
 
Basic Fire Fighting Training
Basic Fire Fighting TrainingBasic Fire Fighting Training
Basic Fire Fighting TrainingChristian Escaler
 
Fire Fighting Training Manual 2003
Fire Fighting Training Manual 2003 Fire Fighting Training Manual 2003
Fire Fighting Training Manual 2003 Ajit Gautam
 
Lifting plan for bypass stack installation
Lifting plan for bypass stack installationLifting plan for bypass stack installation
Lifting plan for bypass stack installationShah Jalal
 
Safety guidelines for (lpg) cylinders.
Safety guidelines for (lpg) cylinders.Safety guidelines for (lpg) cylinders.
Safety guidelines for (lpg) cylinders.Francis K. Antwi
 

La actualidad más candente (20)

Work Permit System
Work Permit SystemWork Permit System
Work Permit System
 
V 1 presentation on safety aspects of lpg handling and storage
V 1 presentation on safety aspects of lpg handling  and storageV 1 presentation on safety aspects of lpg handling  and storage
V 1 presentation on safety aspects of lpg handling and storage
 
Job Safety Analysis For Lifting Activity By Crane | JSA | Gaurav Singh Rajput
Job Safety Analysis For Lifting Activity By Crane | JSA | Gaurav Singh RajputJob Safety Analysis For Lifting Activity By Crane | JSA | Gaurav Singh Rajput
Job Safety Analysis For Lifting Activity By Crane | JSA | Gaurav Singh Rajput
 
NFPA 11 - 2006.pdf
NFPA 11 - 2006.pdfNFPA 11 - 2006.pdf
NFPA 11 - 2006.pdf
 
chpter 9 FOAM & FOAM MAKING EQUIPMENTS.pptx
chpter 9 FOAM & FOAM MAKING EQUIPMENTS.pptxchpter 9 FOAM & FOAM MAKING EQUIPMENTS.pptx
chpter 9 FOAM & FOAM MAKING EQUIPMENTS.pptx
 
Storage Tank Safety
Storage Tank SafetyStorage Tank Safety
Storage Tank Safety
 
Classification of hazardous area for lighting
Classification of hazardous area   for lightingClassification of hazardous area   for lighting
Classification of hazardous area for lighting
 
Risk Assessment At Tank- Truck Unloading Section Of LPG Bottling Plant I Gaur...
Risk Assessment At Tank- Truck Unloading Section Of LPG Bottling Plant I Gaur...Risk Assessment At Tank- Truck Unloading Section Of LPG Bottling Plant I Gaur...
Risk Assessment At Tank- Truck Unloading Section Of LPG Bottling Plant I Gaur...
 
Fire Fighting and SOLAS Requirements
Fire Fighting and SOLAS RequirementsFire Fighting and SOLAS Requirements
Fire Fighting and SOLAS Requirements
 
Fire fighting course
Fire fighting courseFire fighting course
Fire fighting course
 
A fire training hindi
A fire training   hindiA fire training   hindi
A fire training hindi
 
Safety awareness training program
Safety awareness training programSafety awareness training program
Safety awareness training program
 
OSHA Emergency Response Plan by EPA
OSHA Emergency Response Plan by EPAOSHA Emergency Response Plan by EPA
OSHA Emergency Response Plan by EPA
 
Storage tanks basic training (rev 2)
Storage tanks basic training (rev 2)Storage tanks basic training (rev 2)
Storage tanks basic training (rev 2)
 
Basic Fire Fighting Training
Basic Fire Fighting TrainingBasic Fire Fighting Training
Basic Fire Fighting Training
 
Nfpa 557
Nfpa 557Nfpa 557
Nfpa 557
 
Fire Fighting Training Manual 2003
Fire Fighting Training Manual 2003 Fire Fighting Training Manual 2003
Fire Fighting Training Manual 2003
 
Lifting plan for bypass stack installation
Lifting plan for bypass stack installationLifting plan for bypass stack installation
Lifting plan for bypass stack installation
 
Fire Fighting Theory
Fire Fighting TheoryFire Fighting Theory
Fire Fighting Theory
 
Safety guidelines for (lpg) cylinders.
Safety guidelines for (lpg) cylinders.Safety guidelines for (lpg) cylinders.
Safety guidelines for (lpg) cylinders.
 

Similar a High Expansion Foam System

Design and installation of fixed foam fire extinguishing system
Design and installation of fixed foam fire extinguishing systemDesign and installation of fixed foam fire extinguishing system
Design and installation of fixed foam fire extinguishing systemSalim Solanki
 
Gas Flare Stack Process
Gas Flare Stack ProcessGas Flare Stack Process
Gas Flare Stack ProcessShad Ibrahim
 
System fire safety
System fire safetySystem fire safety
System fire safetyDamia Atieka
 
Foam fire suppression system
Foam fire suppression systemFoam fire suppression system
Foam fire suppression systemGlenn Johnson
 
FOAM MAT DRYING TECHNIQUE.pptx
FOAM MAT DRYING TECHNIQUE.pptxFOAM MAT DRYING TECHNIQUE.pptx
FOAM MAT DRYING TECHNIQUE.pptxMariahSadaf1
 
Evaporation: fundamentals and its design
Evaporation: fundamentals and its designEvaporation: fundamentals and its design
Evaporation: fundamentals and its designKulwinder Verma
 
Evaporation.pptx
Evaporation.pptxEvaporation.pptx
Evaporation.pptxRaageswariR
 
Apv Evaporator Handbook
Apv Evaporator HandbookApv Evaporator Handbook
Apv Evaporator Handbookceshesol71
 
Selecting the Evaporators Based On Processing Requirements
Selecting the Evaporators Based On Processing RequirementsSelecting the Evaporators Based On Processing Requirements
Selecting the Evaporators Based On Processing RequirementsAlaquainc
 
Drying and dehumidification
Drying and dehumidification Drying and dehumidification
Drying and dehumidification SURAJKUMAR1229
 
Instrument air package
Instrument air packageInstrument air package
Instrument air packageDipankar Maity
 

Similar a High Expansion Foam System (20)

Design and installation of fixed foam fire extinguishing system
Design and installation of fixed foam fire extinguishing systemDesign and installation of fixed foam fire extinguishing system
Design and installation of fixed foam fire extinguishing system
 
Foam Use Class PP
Foam Use Class PPFoam Use Class PP
Foam Use Class PP
 
evaporators
evaporatorsevaporators
evaporators
 
Fire protection
Fire protectionFire protection
Fire protection
 
Gas Flare Stack Process
Gas Flare Stack ProcessGas Flare Stack Process
Gas Flare Stack Process
 
Evaporators
EvaporatorsEvaporators
Evaporators
 
Foam Extinguisher
Foam ExtinguisherFoam Extinguisher
Foam Extinguisher
 
System fire safety
System fire safetySystem fire safety
System fire safety
 
Chapter 06
Chapter 06Chapter 06
Chapter 06
 
Foam fire suppression system
Foam fire suppression systemFoam fire suppression system
Foam fire suppression system
 
FOAM MAT DRYING TECHNIQUE.pptx
FOAM MAT DRYING TECHNIQUE.pptxFOAM MAT DRYING TECHNIQUE.pptx
FOAM MAT DRYING TECHNIQUE.pptx
 
aerosol
aerosolaerosol
aerosol
 
Evaporation: fundamentals and its design
Evaporation: fundamentals and its designEvaporation: fundamentals and its design
Evaporation: fundamentals and its design
 
Fixed or semi fixed-d10 d03192
Fixed or semi fixed-d10 d03192Fixed or semi fixed-d10 d03192
Fixed or semi fixed-d10 d03192
 
Evaporation.pptx
Evaporation.pptxEvaporation.pptx
Evaporation.pptx
 
Apv Evaporator Handbook
Apv Evaporator HandbookApv Evaporator Handbook
Apv Evaporator Handbook
 
Selecting the Evaporators Based On Processing Requirements
Selecting the Evaporators Based On Processing RequirementsSelecting the Evaporators Based On Processing Requirements
Selecting the Evaporators Based On Processing Requirements
 
Drying and dehumidification
Drying and dehumidification Drying and dehumidification
Drying and dehumidification
 
Instrument air package
Instrument air packageInstrument air package
Instrument air package
 
Drying of food
Drying of foodDrying of food
Drying of food
 

Último

Digital collaboration with Microsoft 365 as extension of Drupal
Digital collaboration with Microsoft 365 as extension of DrupalDigital collaboration with Microsoft 365 as extension of Drupal
Digital collaboration with Microsoft 365 as extension of DrupalFabian de Rijk
 
Zone Chairperson Role and Responsibilities New updated.pptx
Zone Chairperson Role and Responsibilities New updated.pptxZone Chairperson Role and Responsibilities New updated.pptx
Zone Chairperson Role and Responsibilities New updated.pptxlionnarsimharajumjf
 
My Presentation "In Your Hands" by Halle Bailey
My Presentation "In Your Hands" by Halle BaileyMy Presentation "In Your Hands" by Halle Bailey
My Presentation "In Your Hands" by Halle Baileyhlharris
 
lONG QUESTION ANSWER PAKISTAN STUDIES10.
lONG QUESTION ANSWER PAKISTAN STUDIES10.lONG QUESTION ANSWER PAKISTAN STUDIES10.
lONG QUESTION ANSWER PAKISTAN STUDIES10.lodhisaajjda
 
SOLID WASTE MANAGEMENT SYSTEM OF FENI PAURASHAVA, BANGLADESH.pdf
SOLID WASTE MANAGEMENT SYSTEM OF FENI PAURASHAVA, BANGLADESH.pdfSOLID WASTE MANAGEMENT SYSTEM OF FENI PAURASHAVA, BANGLADESH.pdf
SOLID WASTE MANAGEMENT SYSTEM OF FENI PAURASHAVA, BANGLADESH.pdfMahamudul Hasan
 
Dreaming Music Video Treatment _ Project & Portfolio III
Dreaming Music Video Treatment _ Project & Portfolio IIIDreaming Music Video Treatment _ Project & Portfolio III
Dreaming Music Video Treatment _ Project & Portfolio IIINhPhngng3
 
Introduction to Artificial intelligence.
Introduction to Artificial intelligence.Introduction to Artificial intelligence.
Introduction to Artificial intelligence.thamaeteboho94
 
Jual obat aborsi Jakarta 085657271886 Cytote pil telat bulan penggugur kandun...
Jual obat aborsi Jakarta 085657271886 Cytote pil telat bulan penggugur kandun...Jual obat aborsi Jakarta 085657271886 Cytote pil telat bulan penggugur kandun...
Jual obat aborsi Jakarta 085657271886 Cytote pil telat bulan penggugur kandun...ZurliaSoop
 
Report Writing Webinar Training
Report Writing Webinar TrainingReport Writing Webinar Training
Report Writing Webinar TrainingKylaCullinane
 
Unlocking Exploration: Self-Motivated Agents Thrive on Memory-Driven Curiosity
Unlocking Exploration: Self-Motivated Agents Thrive on Memory-Driven CuriosityUnlocking Exploration: Self-Motivated Agents Thrive on Memory-Driven Curiosity
Unlocking Exploration: Self-Motivated Agents Thrive on Memory-Driven CuriosityHung Le
 
Bring back lost lover in USA, Canada ,Uk ,Australia ,London Lost Love Spell C...
Bring back lost lover in USA, Canada ,Uk ,Australia ,London Lost Love Spell C...Bring back lost lover in USA, Canada ,Uk ,Australia ,London Lost Love Spell C...
Bring back lost lover in USA, Canada ,Uk ,Australia ,London Lost Love Spell C...amilabibi1
 
AWS Data Engineer Associate (DEA-C01) Exam Dumps 2024.pdf
AWS Data Engineer Associate (DEA-C01) Exam Dumps 2024.pdfAWS Data Engineer Associate (DEA-C01) Exam Dumps 2024.pdf
AWS Data Engineer Associate (DEA-C01) Exam Dumps 2024.pdfSkillCertProExams
 
Uncommon Grace The Autobiography of Isaac Folorunso
Uncommon Grace The Autobiography of Isaac FolorunsoUncommon Grace The Autobiography of Isaac Folorunso
Uncommon Grace The Autobiography of Isaac FolorunsoKayode Fayemi
 
Dreaming Marissa Sánchez Music Video Treatment
Dreaming Marissa Sánchez Music Video TreatmentDreaming Marissa Sánchez Music Video Treatment
Dreaming Marissa Sánchez Music Video Treatmentnswingard
 
Proofreading- Basics to Artificial Intelligence Integration - Presentation:Sl...
Proofreading- Basics to Artificial Intelligence Integration - Presentation:Sl...Proofreading- Basics to Artificial Intelligence Integration - Presentation:Sl...
Proofreading- Basics to Artificial Intelligence Integration - Presentation:Sl...David Celestin
 

Último (17)

Digital collaboration with Microsoft 365 as extension of Drupal
Digital collaboration with Microsoft 365 as extension of DrupalDigital collaboration with Microsoft 365 as extension of Drupal
Digital collaboration with Microsoft 365 as extension of Drupal
 
Zone Chairperson Role and Responsibilities New updated.pptx
Zone Chairperson Role and Responsibilities New updated.pptxZone Chairperson Role and Responsibilities New updated.pptx
Zone Chairperson Role and Responsibilities New updated.pptx
 
ICT role in 21st century education and it's challenges.pdf
ICT role in 21st century education and it's challenges.pdfICT role in 21st century education and it's challenges.pdf
ICT role in 21st century education and it's challenges.pdf
 
My Presentation "In Your Hands" by Halle Bailey
My Presentation "In Your Hands" by Halle BaileyMy Presentation "In Your Hands" by Halle Bailey
My Presentation "In Your Hands" by Halle Bailey
 
lONG QUESTION ANSWER PAKISTAN STUDIES10.
lONG QUESTION ANSWER PAKISTAN STUDIES10.lONG QUESTION ANSWER PAKISTAN STUDIES10.
lONG QUESTION ANSWER PAKISTAN STUDIES10.
 
SOLID WASTE MANAGEMENT SYSTEM OF FENI PAURASHAVA, BANGLADESH.pdf
SOLID WASTE MANAGEMENT SYSTEM OF FENI PAURASHAVA, BANGLADESH.pdfSOLID WASTE MANAGEMENT SYSTEM OF FENI PAURASHAVA, BANGLADESH.pdf
SOLID WASTE MANAGEMENT SYSTEM OF FENI PAURASHAVA, BANGLADESH.pdf
 
Dreaming Music Video Treatment _ Project & Portfolio III
Dreaming Music Video Treatment _ Project & Portfolio IIIDreaming Music Video Treatment _ Project & Portfolio III
Dreaming Music Video Treatment _ Project & Portfolio III
 
Introduction to Artificial intelligence.
Introduction to Artificial intelligence.Introduction to Artificial intelligence.
Introduction to Artificial intelligence.
 
Jual obat aborsi Jakarta 085657271886 Cytote pil telat bulan penggugur kandun...
Jual obat aborsi Jakarta 085657271886 Cytote pil telat bulan penggugur kandun...Jual obat aborsi Jakarta 085657271886 Cytote pil telat bulan penggugur kandun...
Jual obat aborsi Jakarta 085657271886 Cytote pil telat bulan penggugur kandun...
 
Report Writing Webinar Training
Report Writing Webinar TrainingReport Writing Webinar Training
Report Writing Webinar Training
 
Unlocking Exploration: Self-Motivated Agents Thrive on Memory-Driven Curiosity
Unlocking Exploration: Self-Motivated Agents Thrive on Memory-Driven CuriosityUnlocking Exploration: Self-Motivated Agents Thrive on Memory-Driven Curiosity
Unlocking Exploration: Self-Motivated Agents Thrive on Memory-Driven Curiosity
 
Bring back lost lover in USA, Canada ,Uk ,Australia ,London Lost Love Spell C...
Bring back lost lover in USA, Canada ,Uk ,Australia ,London Lost Love Spell C...Bring back lost lover in USA, Canada ,Uk ,Australia ,London Lost Love Spell C...
Bring back lost lover in USA, Canada ,Uk ,Australia ,London Lost Love Spell C...
 
in kuwait௹+918133066128....) @abortion pills for sale in Kuwait City
in kuwait௹+918133066128....) @abortion pills for sale in Kuwait Cityin kuwait௹+918133066128....) @abortion pills for sale in Kuwait City
in kuwait௹+918133066128....) @abortion pills for sale in Kuwait City
 
AWS Data Engineer Associate (DEA-C01) Exam Dumps 2024.pdf
AWS Data Engineer Associate (DEA-C01) Exam Dumps 2024.pdfAWS Data Engineer Associate (DEA-C01) Exam Dumps 2024.pdf
AWS Data Engineer Associate (DEA-C01) Exam Dumps 2024.pdf
 
Uncommon Grace The Autobiography of Isaac Folorunso
Uncommon Grace The Autobiography of Isaac FolorunsoUncommon Grace The Autobiography of Isaac Folorunso
Uncommon Grace The Autobiography of Isaac Folorunso
 
Dreaming Marissa Sánchez Music Video Treatment
Dreaming Marissa Sánchez Music Video TreatmentDreaming Marissa Sánchez Music Video Treatment
Dreaming Marissa Sánchez Music Video Treatment
 
Proofreading- Basics to Artificial Intelligence Integration - Presentation:Sl...
Proofreading- Basics to Artificial Intelligence Integration - Presentation:Sl...Proofreading- Basics to Artificial Intelligence Integration - Presentation:Sl...
Proofreading- Basics to Artificial Intelligence Integration - Presentation:Sl...
 

High Expansion Foam System

  • 1. 12DE 1004 Saiesh 1005 Brembley 1006 Russell 1007 Mukesh
  • 2. THE FIRE TRIANGLE Three components required for combustion Fuel – to vaporize and burn Oxygen – to combine with fuel vapour Heat – to raise the temperature of the fuel vapour to its ignition temperature.
  • 3.  Two important factors to remember in preventing and extinguishing a fire: i) If any of the three components are missing, then a fire cannot start. ii) If any of the three components are removed, then the fire will go out.
  • 4. THE FIRE TETRAHEDRON  solid figure with four triangular faces  shows the chain reaction and each face touches the other three faces.  The basic difference - illustrates how flaming combustion is supported and sustained through the chain reaction of the oxidation process.
  • 5. VARIOUS SYSTEMS USED ONBOARD FOR FIGHTING FIRE  HIGH EXPANSION FOAM SYSTEM  CO2 SYSTEM  SPRINKLER & SPRAYER SYSTEM  HALON SYSTEM
  • 6. WHAT IS FOAM ?  combination of three materials: • Water • Air • Foam making agent  formed by mixing the foam-making agent with water to create a foam solution.  foam bubbles created by introducing air into the foam solution through aerating devices.  Two most common concentrations are 3% and 6% foams.
  • 7. HOWIS FOAM GENERATED ?  A constant amount of foam concentrate is added to water by means of a proportioner.  The resulting mixture of water/foam concentrate is expanded with air in the foam generator.
  • 8. AIR IN FAN SPRAY NOZZLE SEA WATER EDUCTOR FOAM CONCENTRATOR NYLON MESH TO ENGINE ROOM
  • 9. THE INDUCTION RATE  specifies the percentage ratio of foam concentrate added to water.   At 3% induction rate, for example, 3 parts of foam concentrate are mixed with 97 parts of water.
  • 10. FILM FORMATION Aqueous film (AFFF effect)  The foam produces a very thin aqueous film on non polar liquids  This film floats ahead of the foam and provides for its excellent flowing, extinguishing and re-ignition inhibiting properties.
  • 11. Polymer film • produced by the polymer film formers contained in the foam when extinguishing polar hydrocarbons (e.g alcohols, ketones, ester). • The film floats as an insulating protective layer between the foam destroying alcohol and the foam cover above.
  • 12. HOWFOAM EXTINGUISHES FIRE ? o Separating effect The closed foam cover separates the combustion zone from the ambient air. o Cooling effect The flammable material is cooled down by the water/ foam solution discharged by the foam.
  • 13. o Cover effect The closed foam cover stops any further gas evaporation from burning materials, i.e. flammable gases foam forms a blanket on the surface of flaming liquids o Repression effect Flooding spaces, channels, plant parts, etc. with high or medium expansion foam represses the atmospheric oxygen and flammable gases necessary for the combustion process. o Insulation effect foam insulates flammable material which has not yet caught fire
  • 14. FOAM CHARACTERISTICS  Knockdown Speed and Flow- ability to spread across a fuel surface or around obstacles   Heat Resistance-able to resist the destructive effects of heat radiated from any remaining fire  Vapour Suppression. capable of suppressing the flammable vapours to break the fire triangle.
  • 15. Alcohol Resistance-foam blankets that are not alcohol-resistant will be destroyed if used on alcohol-based cargoes. cohesive properties- to stick together sufficiently to establish and maintain a vapour tight blanket light enough-to float on flammable liquids, yet heavy enough to resist winds
  • 16. TYPES OF FOAMS Chemical foam • formed by mixing together a solution of an alkali, an acid, water and a stabilizer. • forms a foam or froth of bubbles filled with carbon dioxide gas. • 7 to 16 volumes of foam are produced for each volume of water. • Needs a device called a foam hopper or separate tanks
  • 17.  Mechanical (Air) Foam • produced by mixing a foam concentrate with water to produce a foam solution. • The bubbles are formed by the turbulent mixing of air and the foam solution.
  • 18. TYPES OF MECHANICAL FOAMS  Protein Foam produced by the hydrolysis of waste protein material, such as protein-rich animal waste and vegetable waste that is hydrolyzed  Fluoroprotein Foam (FP). formed by the addition of special fluorochemical surfactants with protein foam  Film Forming Fluoroprotein Foam (FFFP) combination of fluorochemical surfactants with protein foam release a film on the surface of the hydrocarbon.
  • 19.  Aqueous Film Forming Foam (AFFF) • combination of fluorochemical surfactants and synthetic foaming agents • film spreads rapidly causing dramatic fire knockdown.  Alcohol Resistant-Aqueous Film Forming Foam (AR-AFFF) • combination of synthetic stabilizers, foaming agents, fluorochemicals and alcohol resistant additives • offers good burnback resistance, knockdown and high fuel tolerance on both hydrocarbon and alcohol fuel fires.  Synthetic Foam • made up of alkyl sulfonates. • It foams more readily than the proteins and requires less water important where the water supply is limited
  • 20. CATEGORIES OF FOAM SYTEMS  Low Expansion Foams • expansion ratio of 12:1 when mixed with air • effective in controlling and extinguishing most flammable liquid (Class “B”) fires • typically used on tanker deck foam systems  Mid Expansion Foams • expansion ratio of between about 20:1 to 100:1 • truly three dimensional; it is measured in length, width, height, and cubic feet  High-expansion foam • designed for fires in confined spaces • Heavier than air but lighter than oil or water
  • 21. LIMITATIONS ON THE USE OF FOAM  Because they are aqueous (water) solutions, foams are electrically conductive  Like water, foams should not be used on combustible-metal fires.  not suitable for fires involving gases and extremely low temperature liquids.  If placed on burning liquids whose temperatures exceed 100°C (212°F), the water content of the foam may cause frothing, spattering or slopover.  Sufficient foam must be available.
  • 22. ADVANTAGES OF FOAM  effective smothering agent and provides cooling effect.  sets up a vapor barrier that prevents flammable vapors from rising  Can be used on Class “A” fires because of its water content.  effective in blanketing oil spills  uses water economically
  • 23.  most effective extinguishing agent for fires involving large tanks of flammable liquids.  can be made with fresh water or seawater, and hard or soft water  does not break down readily and extinguishes fire progressively  Foam stays in place, covers and absorbs heat from materials that could cause re-ignition  Foam concentrates are not heavy, and foam systems do not take up much space.
  • 24. PRACTICAL ISSUES  Water Temperature and Contaminants more stable when generated with lower temperature water. temperature range 1.7°C to 26.7°C  Combustible Products in Air It is desirable to take clean air into the foam nozzle at all times  Water Pressures Nozzle pressures should be held between 3.4 bar and 13.8 bar (50 and 200 psi)
  • 25.  Non-ignited Spills Where flammable liquids have spilled, fires can be prevented by prompt coverage of the spill with a foam blanket  Electrical Fires not generally recommended for use on electrical fires  Vaporized Liquids not recommended for use on materials that react with water, such as magnesium, titanium, potassium etc.
  • 26. HIGH EXPANSION FOAM SYSTEM AND EQUIPMENT
  • 27. FOAM GENERATOR  Delivers large quantity of expanded foam by blowing air through a screen  Because of high expansion ratio requires little water
  • 29.
  • 33. 1) Proportioning Devices  Eductor  most common form of proportioning equipment works on the Venturi principle.  extremely reliable and simple pieces of equipment
  • 34. Around-the-Pump Systems  an eductor is installed on the discharge side of the water pump  water flow causes a vacuum that picks up and introduces the foam concentrate into the water
  • 35.  Balanced Pressure Foam Proportioners  extremely versatile and accurate  The principle of operation based on the use of a modified venturi proportioner commonly called a ratio controller.
  • 36. 2) FOAM NOZZLES  designed to air aspirate (expand) the foam solution and form finished foam.  High expansion foam nozzles expands foam in excess of 100:1, when high expansion foam concentrates are used.
  • 37. 3) FOAM MONITORS  are permanently-installed foam discharge units  capable of being aimed and projecting large quantities of foam substantial distances.  normally mounted on a rotating base (360- degree circle)
  • 38. 4) VALVES AND PIPING must be adequately designed to match the flow rates of the equipment, and a thorough understanding of the system  control valves is critical for quick and effective operation of the system  Color coding of the valves
  • 39. 4) VALVES AND PIPING
  • 40. 5) FOAM CONCENTRATE STORAGE  stored in tanks ready to supply the proportioning system  The concentrate tank should be kept filled with liquid halfway  The tank should be kept closed to the atmosphere
  • 41. SOLAS REQUIREMENTS  FOAM CONCENTRATE  Foam concentrates to be of the type approved by administration  Capable of rapidly discharging foam @ at least 1 m in depth per minute  Volume of foam = 5 x volume of largest space  Expansion ratio not to exceed 1000:1
  • 42.  INSTALLATION REQUIREMENTS • System should provide effective foam production and distribution • Foam generator delivery ducting to be protected against fire risk, withstand 925 deg C. • Foam delivery ducts to be constructed of steel having thickness > 5 mm • Dampers to be automatically operated by remote control • All system equipment to be readily accessible and simple to operate
  • 43. ABS REQUIREMENTS FOR FOAM EXTINGUISHING SYSTEMS  Design and Certification of Piping Components • All valves, fittings and piping to comply with the applicable requirements • be suitable for the intended pressures  Pipe and Pipe Joints the wall thickness, type and design of the pipe joints to comply with the requirements
  • 44.  Materials • materials used in the system should not to be rendered ineffective by heat. • material to have a melting temperature higher than the test temperature specified in an acceptable fire test. Pumps • should be tested in the presence of a Surveyor
  • 45.  Pressure Vessels  the tank is to be considered a pressure vessel and is to comply with the requirements as applicable. System Component Certification  fixed fire-extinguishing system components are to be certified.  Accordingly, components such as foam system eductors, proportioners, monitors, nozzles, etc., are to comply with the certification requirements
  • 46. STARTING PROCEDURE  AUTOMATIC START  Stop the supply fan and exhaust fan in the E/R.  Break the Destruct plate and push the system standby switch.  Alarm sound for evacuation in the E/R.  Start the Emergency fire pump manually.  After evacuation is confirmed push the foam discharge switch.  TO STOP;  Push the system stop switch.  Stop the Emergency fire pump.
  • 47.  MANUALLY START AT LOCAL SIDE.  Check all Valves.  Start the Emergency fire pump.  Check pressure gauge, indicate 4 bar.  Open valve and start foam liquid pump.  TO STOP:  Stop the Emergency fire pump.  Close the valves.
  • 48. EXAMPLE CALCULATION OF THE CAPACITY OF FOAM SYSTEM FOR OIL CARRIER SHIP 14.5 m 9m PARTICULARS • BEAM = 14.5 M • LENGTH = 56 56m OF CARGO AREA M • LENGTH OF LARGEST CARGO TANK = 9 M • CARGO DECK AREA = 14.5 M ×56 M = 812 M2 • HORIZONTAL SECTIONAL AREA OF SINGLE LARGEST TANK = 14.5 M ×9 M = 130.5 M2 • PROPOSED MONITOR SPACING = 9 M AREA PROTECTED BY LARGEST MONITOR = 9 M × 14.5 M = 130.5 M2
  • 50. LESSONS LEARNT  Proper maintenance should be done including putting back the cover  Blowing/purging the line after hydraulic pressure testing  Inspection of the foam nozzle after test  Foam line on board to be pressure tested regularly  Draining the line to prevent accumulation of water
  • 51. WHERE IS HIGH EXPANSION FOAM SYSTEM USED ?  ENGINE ROOM  PURIFIER ROOM  INCINERATOR ROOM  PUMP ROOM
  • 52. PACKING OF FOAM CONCENTRATES 20 litres Plastic Can Size (ca. cm) 38 x 38 x 18 Tara ca. kg 1,4 Suitability Synthetic, Protein Net weight approx Synthetic 20 Kg, Protein 23 Kg Stackable 2 high, to 40°C, shrink-wrapped onto a pallet
  • 53. 20 litres Plastic Can Blue Size (ca. cm) 29 x 26 x 39 Tara ca. kg 1,2 Suitability Synthetic, Protein Net weight approx 25 – 30 Kg Stackable 2 high, to 40°C, shrink-wrapped onto a pallet
  • 54. 200 litresValenthene Barrel Size (ca. cm) 60 x 90 Tara ca. kg 21 Suitability Synthetic, Protein Net weight approx 200 – 225 Kg Stackable 2 high
  • 55. 1000 litres Palett Container Size (ca. cm) 100 x 120 x 116 Tara ca. kg 80 Suitability Synthetic, Protein Net weight approx Synthetic 1040 Kg, Protein 1150 Kg Stackable 2 high
  • 56. TYPES OF HIGH EXPANSION FOAM SYSTEMS TOTAL FLOODING SYSTEM
  • 57. MAINTENANCE AND INSPECTION OF SYSTEM AND APPLIANCES.  Operational readiness • To be in good order and readily available for immediate use while the ship is in service.  Maintenance and Testing • should be carried out in accordance with the ship's maintenance plan. • Inspections should be carried out by the crew in accordance with manufacturer's maintenance and inspection guidelines
  • 58.  MONTHLY TESTING AND INSPECTIONS • Verify all control and section valves are in the proper open or closed position, and all pressure gauges are in the proper range.
  • 59.  QUARTERLY TESTING AND INSPECTIONS • Verify the proper quantity of foam concentrate is provided in the foam system
  • 60. ANNUAL TESTING AND INSPECTIONS. o visually inspect all accessible components o functionally test all fixed system audible alarms o flow test all water supply and foam pumps for proper pressure and capacity o Ensure all piping is thoroughly flushed with fresh water after service
  • 61. o test all system cross connections to other sources of water supply for proper operation; o verify all pump relief valves, if provided, are properly set o examine all filters/strainers to verify they are free of debris and contamination o verify all control/section valves are in the correct position
  • 62.  blow dry compressed air or nitrogen through the discharge piping  confirm the pipework and nozzles of high expansion foam systems are clear of any obstructions, debris and contamination  take samples from all foam concentrates carried on board and subject them to the periodical control tests  test all fuel shut-off controls connected to fire-protection systems for proper operation.
  • 63.  FIVE-YEAR SERVICE  perform internal inspection of all control valves  flush piping with fresh water, drain and purge with air  check all nozzles to prove they are clear of debris  test all foam proportioners to confirm that the mixing ratio tolerance is within +30 to -10% of the nominal mixing ratio
  • 64. TESTING OF FOAM SAMPLES No Type of foam concentrate Minimum frequency 1 All Fixed systems except protein based non-alcoholic Within 3 years from the date of manufacture and every year thereafter. 2 All Fixed systems of protein based non-alcoholic Annually. 3 All factory-sealed portable containers excluding protein based Ten yearly. 4 All factory-sealed portable containers of protein based concentrates Five yearly. 5 All non-sealed portable containers Within 3 years from the date of manufacture and every year thereafter