FIRE AND SMOKE
RESISTANT ASSEMBLIES
BARRIERS, ASSEMBLIES AND PARTITIONS
 Three basic types of rated assemblies:
 Fire barriers
 Fire partitions
 Horizontal assemblies
 Fire barriers are walls that a fire resistant rating
and in most cases must be continuous and extend
vertically from the bottom to the top of the
floor/ceiling assembly
 Additional fire blocking is required at the intersection
with other rated elements
 Openings are limited
 Opening assemblies need to be rated
 Floor/ceiling assemblies are horizontal assemblies
 Limited openings
 Openings and penetrations must be rated as well
 Fire partitions are similar to fire barriers but less
restrictive
 Separate exit access corridors, tenant spaces in malls,
dwellings and /or sleeping units
 Allowed to stop at the rated ceiling system
 Not required to be a full enclosure
 Rating of at least one hour
 Ratings depends on purpose, occupancy
classification and if space has sprinklers
 Openings required to be protected but not limited
 Fire enclosures separates occupancy types
 Not required between similar hazardous
occupancies
 Multiple tenants of different occupancies in the
same building
 Single user with multiple occupancies or uses within
the same structure
 Tenant separations in malls required to be rated
 Dwelling and sleeping units in residential
occupancies to be separated by fire partitions
 Some incidental accessory occupancies to be
separated
 Required for vertical shaft enclosures as elevators,
dumbwaiters, mechanical chases, etc.
 Smoke barriers provide protection form movement
and passage of smoke and fire gases
 Barriers are usually rated
 Partitions are not required to have fire resistance
rating
 Complete opening assemblies in rated barriers are
required to be also rated
 Although ratings of opening assemblies – doors,
windows, and other penetrations – is lower than the
assembly – the quantity and dimensions are limited
 Opening assemblies include the door, the frame, and
other required hardware.
 All rated doors are required to have a self closing
device that will close the door after each use. Not
necessary for it to be automatic (usually electrically
activated)
 Glazing products in rated assemblies must:
 Stay in place during a fire
 Resist thermal shock – by a hose stream
 Strength from human contact
 Resist heat transfer to unexposed side
 Codes allow the use of glass in some rated
partitions – type, size, and quantity is limited
 Wired glass – wire mesh sandwiched between two
layers of glass
 Safety resists impact
 Nonsafety does not resist impact
 Only type of glass addressed by codes for use in
rated opening protectives
 Specialty tempered glass – treated for fire
resistance
 Some can be used in 1 hr rated walls
 Cannot be used near sprinklers since it does not pass
the hose stream test
 Glass block
 Can be used in some 1 hr rated partitions – glass rated
to 45 minutes
 Clear ceramics
 High resistance
to heat
 Resists thermal
shock
 20mins to 2hr.
 Up to 23s.f. can
be used
 Sometimes has
more distortion
and tint
 Laminated glass
 Firestops and smokestops
 F-rated and T-rated
 T is stricter than F as it
includes a maximum
temperature resistance
 Fireblocks and Draftstops
 Restrict the spread of smoke and
fire through concealed spaces
 Fireblocks – small spaces
 Draftstops – large spaces
 Damper systems
 Interrupts air flow through ducts
going through rated assemblies
QUESTIONS
 An active fire-protection system is sometimes referred to
as a prevention system.
A. True
B. False
 The fire-resistance rating of a floor/ceiling assembly is
controlled only by the construction type of the building.
A. True
B. False
 All fire-protected doors must have an automatic dosing
device.
A. True
B. False
 The fire rating of a through-penetration is typically
lower than the fire rating of the construction assembly it
is penetrating.
A. True
B. False
 A fire-protected door can also be used as a
smokestop door.
A. True
B. False
 Fire barriers are typically used to create
compartments within a building.
A. True
B. False
 Occupancy separation walls and demising walls are
the same thing.
A. True
B. False
 Doors with fire-protection ratings are not allowed to
have glass lites as part of the door.
A. True
B. False
 __________Walls are used to create a continuous
vertical separation within a building or between two
different buildings.
 Fire/Party
 A door assembly typically consists of a door, frame,
and _____________.
 hardware
 What is the typical fire-resistance rating of a tenant
separation wall?
A. 2 hour
B. 1 1/2 hour
C. 1 hour
D. No rating is required.
 Which of the following statements is true about
firestops?
A. They are required at through penetrations in fire
barriers.
B. They are a means of restricting the passage of smoke,
heat, and flames in concealed spaces.
C. They can have two different ratings: a T-rating and a
stricter F-rating.
D. a and c only
E. All of the above
 A wall assembly with a 2-hour fire-resistance rating
is typically required for which means of egress
component?
A. Exit access
B. Public way
C. Exit discharge
D. Exit
 Which of the following devices is used to prevent
the movement of air, smoke, gases, and flame
through large, concealed spaces?
A. Firestops
B. Draftstops
C. Fireblocking
D. Dampers
 Which of the following types of glass is typically
considered to have a fire-protection rating?
A. Wired glass
B. Tempered glass
C. Glass block
D. a and c only
E. All of the above
 Which of the following statements about fire-protected
doors is correct?
A. The quantity of hinges is regulated but the type of
hinge is not.
B. Sills used at fire-rated doors do not typically need to
meet accessibility requirements.
C. Fire-rated doors are available as flush doors and
panel doors.
D. A variety of rated glazing can be used as lites in fire
rated doors as long as they are within a certain size
range.
 Which of the following is typically considered a fire
partition by the International Building Code?
A. A wall between two guest rooms in a hotel.
B. A wall between an office space and an exit access
corridor.
C. A wall between two tenants in a shopping mall.
D. a and c only
E. All of the above
 Which of the following can be used to help control
smoke during a fire?
A. Smoke barriers
B. Pressurized exits
C. Sprinklers
D. a and b
E. A and c
 Which type of through-penetration is required in a
duct that extends through a rated floor assembly?
A. Draftstop
B. Fire damper
C. Ceiling damper
D. None of the above
 Which of the following statements about smoke
dampers is NOT correct?
A. Smoke dampers are typically used in ducts that
penetrate smoke barriers.
B. Smoke dampers are usually installed with a smoke
detector.
C. Smoke dampers are typically installed adjacent to a
duct.
D. Smoke dampers can be classified in one of four
classes.
E. All of the above are correct.
 Which of the following would compromise the rating
of a 1 hour fire-resistant wall assembly?
A. Using a building material differently than
specified by the manufacturer
B. Not using rated caulk at the seams and joints
C. Installing an electrical box in the wall cavity for a
switch
D. a and b only
E. All of the above

Más contenido relacionado

La actualidad más candente

Ch 04 Building and Fire Codes
Ch 04 Building and Fire CodesCh 04 Building and Fire Codes
Ch 04 Building and Fire Codes
snoshoesam
 

La actualidad más candente (19)

Unit iii (3.1)
Unit iii (3.1)Unit iii (3.1)
Unit iii (3.1)
 
Chapter 09
Chapter 09Chapter 09
Chapter 09
 
Chapter 12 special treatments
Chapter 12 special treatmentsChapter 12 special treatments
Chapter 12 special treatments
 
Materials and Usage of Treatment for Thermal Insulation
Materials and Usage of Treatment for Thermal Insulation Materials and Usage of Treatment for Thermal Insulation
Materials and Usage of Treatment for Thermal Insulation
 
Building insulation
Building insulationBuilding insulation
Building insulation
 
What is passive fireproofing
What is passive fireproofing What is passive fireproofing
What is passive fireproofing
 
Ch 04 Building and Fire Codes
Ch 04 Building and Fire CodesCh 04 Building and Fire Codes
Ch 04 Building and Fire Codes
 
Thermal insulation of buildings
Thermal insulation of buildingsThermal insulation of buildings
Thermal insulation of buildings
 
Fire protection buildings
Fire protection buildingsFire protection buildings
Fire protection buildings
 
Thermal Insulation in UAE
Thermal Insulation in UAEThermal Insulation in UAE
Thermal Insulation in UAE
 
Thermal insulating material
Thermal insulating materialThermal insulating material
Thermal insulating material
 
Ch12 ppt
Ch12 pptCh12 ppt
Ch12 ppt
 
Building with Timber in Bushfire-prone Areas - Lunch & Learn
Building with Timber in Bushfire-prone Areas - Lunch & LearnBuilding with Timber in Bushfire-prone Areas - Lunch & Learn
Building with Timber in Bushfire-prone Areas - Lunch & Learn
 
Insulating material
Insulating materialInsulating material
Insulating material
 
Insulation materials
Insulation materialsInsulation materials
Insulation materials
 
Ch3 Building Construction Jeopardy
Ch3 Building Construction JeopardyCh3 Building Construction Jeopardy
Ch3 Building Construction Jeopardy
 
Building construction
Building constructionBuilding construction
Building construction
 
Heat & sound insulation
Heat & sound insulationHeat & sound insulation
Heat & sound insulation
 
Thermal treatments on construction - Building materials
Thermal treatments on construction - Building materialsThermal treatments on construction - Building materials
Thermal treatments on construction - Building materials
 

Similar a fire resistant assemblies

Similar a fire resistant assemblies (20)

2120 Ch 5 PowerPoint.pptx
2120 Ch 5 PowerPoint.pptx2120 Ch 5 PowerPoint.pptx
2120 Ch 5 PowerPoint.pptx
 
Fire Safety and Performance of Wood
Fire Safety and Performance of WoodFire Safety and Performance of Wood
Fire Safety and Performance of Wood
 
Understanding Fire-Rated Assemblies
Understanding Fire-Rated AssembliesUnderstanding Fire-Rated Assemblies
Understanding Fire-Rated Assemblies
 
Fire Protection Notes PPT.pdf
Fire Protection Notes PPT.pdfFire Protection Notes PPT.pdf
Fire Protection Notes PPT.pdf
 
Fire safety as per National Building Code-2016
Fire safety as per National Building Code-2016Fire safety as per National Building Code-2016
Fire safety as per National Building Code-2016
 
Fire Protection
Fire ProtectionFire Protection
Fire Protection
 
Fire Safety and Building Materials
Fire Safety and Building MaterialsFire Safety and Building Materials
Fire Safety and Building Materials
 
Air Curtains for revolving doors Catalogue
Air Curtains for revolving doors CatalogueAir Curtains for revolving doors Catalogue
Air Curtains for revolving doors Catalogue
 
Fire pro
Fire proFire pro
Fire pro
 
Fire pro
Fire proFire pro
Fire pro
 
Fire pro
Fire proFire pro
Fire pro
 
DARK ROOM.ppt
DARK ROOM.pptDARK ROOM.ppt
DARK ROOM.ppt
 
Fire safety
Fire safety Fire safety
Fire safety
 
Energy efficient for part 9 buildings and city bylaws
Energy efficient for part 9 buildings and city bylawsEnergy efficient for part 9 buildings and city bylaws
Energy efficient for part 9 buildings and city bylaws
 
B.service
B.serviceB.service
B.service
 
Building services
Building servicesBuilding services
Building services
 
BCT - Module 5 special treatment part 3
BCT - Module 5 special treatment part 3BCT - Module 5 special treatment part 3
BCT - Module 5 special treatment part 3
 
Concept of Fire damper by Md Yusuf
Concept of Fire damper by Md Yusuf Concept of Fire damper by Md Yusuf
Concept of Fire damper by Md Yusuf
 
Fire and Flat Roofs #SPRAConference2019
Fire and Flat Roofs #SPRAConference2019Fire and Flat Roofs #SPRAConference2019
Fire and Flat Roofs #SPRAConference2019
 
Fire system.pdf
Fire system.pdfFire system.pdf
Fire system.pdf
 

Más de Tala Jazzy (20)

Work samples TALA JAZZY
Work samples TALA JAZZYWork samples TALA JAZZY
Work samples TALA JAZZY
 
Tala Jazzy Portfolio
Tala Jazzy PortfolioTala Jazzy Portfolio
Tala Jazzy Portfolio
 
165 CHARLES ST,NY,NY
165 CHARLES ST,NY,NY165 CHARLES ST,NY,NY
165 CHARLES ST,NY,NY
 
Hagia sophia
Hagia sophiaHagia sophia
Hagia sophia
 
Falling water by frank lloyd
Falling water  by frank lloydFalling water  by frank lloyd
Falling water by frank lloyd
 
Architectural history
Architectural history Architectural history
Architectural history
 
The rotunda
The rotundaThe rotunda
The rotunda
 
Le castel béranger
Le castel bérangerLe castel béranger
Le castel béranger
 
Architectural History
Architectural History Architectural History
Architectural History
 
fire resistant assemblies
 fire resistant assemblies fire resistant assemblies
fire resistant assemblies
 
Means of egress
Means of egressMeans of egress
Means of egress
 
Occupancy Load
Occupancy Load Occupancy Load
Occupancy Load
 
Sustainable design
Sustainable designSustainable design
Sustainable design
 
Ada
AdaAda
Ada
 
Victorian House
Victorian House Victorian House
Victorian House
 
roof systems
 roof systems  roof systems
roof systems
 
foundations
foundations foundations
foundations
 
Doors and windows
Doors and windowsDoors and windows
Doors and windows
 
Building site and zoning
Building site and zoning Building site and zoning
Building site and zoning
 
Building loads and floor systems
Building loads and floor systemsBuilding loads and floor systems
Building loads and floor systems
 

Último

Vip Mumbai Call Girls Bandra West Call On 9920725232 With Body to body massag...
Vip Mumbai Call Girls Bandra West Call On 9920725232 With Body to body massag...Vip Mumbai Call Girls Bandra West Call On 9920725232 With Body to body massag...
Vip Mumbai Call Girls Bandra West Call On 9920725232 With Body to body massag...
amitlee9823
 
How to Build a Simple Shopify Website
How to Build a Simple Shopify WebsiteHow to Build a Simple Shopify Website
How to Build a Simple Shopify Website
mark11275
 
Call Girls In Jp Nagar ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Jp Nagar ☎ 7737669865 🥵 Book Your One night StandCall Girls In Jp Nagar ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Jp Nagar ☎ 7737669865 🥵 Book Your One night Stand
amitlee9823
 
Verified Trusted Call Girls Adugodi💘 9352852248 Good Looking standard Profil...
Verified Trusted Call Girls Adugodi💘 9352852248  Good Looking standard Profil...Verified Trusted Call Girls Adugodi💘 9352852248  Good Looking standard Profil...
Verified Trusted Call Girls Adugodi💘 9352852248 Good Looking standard Profil...
kumaririma588
 
Escorts Service Nagavara ☎ 7737669865☎ Book Your One night Stand (Bangalore)
Escorts Service Nagavara ☎ 7737669865☎ Book Your One night Stand (Bangalore)Escorts Service Nagavara ☎ 7737669865☎ Book Your One night Stand (Bangalore)
Escorts Service Nagavara ☎ 7737669865☎ Book Your One night Stand (Bangalore)
amitlee9823
 
➥🔝 7737669865 🔝▻ jhansi Call-girls in Women Seeking Men 🔝jhansi🔝 Escorts S...
➥🔝 7737669865 🔝▻ jhansi Call-girls in Women Seeking Men  🔝jhansi🔝   Escorts S...➥🔝 7737669865 🔝▻ jhansi Call-girls in Women Seeking Men  🔝jhansi🔝   Escorts S...
➥🔝 7737669865 🔝▻ jhansi Call-girls in Women Seeking Men 🔝jhansi🔝 Escorts S...
amitlee9823
 
Anamika Escorts Service Darbhanga ❣️ 7014168258 ❣️ High Cost Unlimited Hard ...
Anamika Escorts Service Darbhanga ❣️ 7014168258 ❣️ High Cost Unlimited Hard  ...Anamika Escorts Service Darbhanga ❣️ 7014168258 ❣️ High Cost Unlimited Hard  ...
Anamika Escorts Service Darbhanga ❣️ 7014168258 ❣️ High Cost Unlimited Hard ...
nirzagarg
 
Call Girls Basavanagudi Just Call 👗 7737669865 👗 Top Class Call Girl Service ...
Call Girls Basavanagudi Just Call 👗 7737669865 👗 Top Class Call Girl Service ...Call Girls Basavanagudi Just Call 👗 7737669865 👗 Top Class Call Girl Service ...
Call Girls Basavanagudi Just Call 👗 7737669865 👗 Top Class Call Girl Service ...
amitlee9823
 
call girls in Dakshinpuri (DELHI) 🔝 >༒9953056974 🔝 genuine Escort Service 🔝✔️✔️
call girls in Dakshinpuri  (DELHI) 🔝 >༒9953056974 🔝 genuine Escort Service 🔝✔️✔️call girls in Dakshinpuri  (DELHI) 🔝 >༒9953056974 🔝 genuine Escort Service 🔝✔️✔️
call girls in Dakshinpuri (DELHI) 🔝 >༒9953056974 🔝 genuine Escort Service 🔝✔️✔️
9953056974 Low Rate Call Girls In Saket, Delhi NCR
 
RT Nagar Call Girls Service: 🍓 7737669865 🍓 High Profile Model Escorts | Bang...
RT Nagar Call Girls Service: 🍓 7737669865 🍓 High Profile Model Escorts | Bang...RT Nagar Call Girls Service: 🍓 7737669865 🍓 High Profile Model Escorts | Bang...
RT Nagar Call Girls Service: 🍓 7737669865 🍓 High Profile Model Escorts | Bang...
amitlee9823
 
Escorts Service Basapura ☎ 7737669865☎ Book Your One night Stand (Bangalore)
Escorts Service Basapura ☎ 7737669865☎ Book Your One night Stand (Bangalore)Escorts Service Basapura ☎ 7737669865☎ Book Your One night Stand (Bangalore)
Escorts Service Basapura ☎ 7737669865☎ Book Your One night Stand (Bangalore)
amitlee9823
 
怎样办理伯明翰大学学院毕业证(Birmingham毕业证书)成绩单留信认证
怎样办理伯明翰大学学院毕业证(Birmingham毕业证书)成绩单留信认证怎样办理伯明翰大学学院毕业证(Birmingham毕业证书)成绩单留信认证
怎样办理伯明翰大学学院毕业证(Birmingham毕业证书)成绩单留信认证
eeanqy
 
Abortion Pills in Oman (+918133066128) Cytotec clinic buy Oman Muscat
Abortion Pills in Oman (+918133066128) Cytotec clinic buy Oman MuscatAbortion Pills in Oman (+918133066128) Cytotec clinic buy Oman Muscat
Abortion Pills in Oman (+918133066128) Cytotec clinic buy Oman Muscat
Abortion pills in Kuwait Cytotec pills in Kuwait
 

Último (20)

Vip Mumbai Call Girls Bandra West Call On 9920725232 With Body to body massag...
Vip Mumbai Call Girls Bandra West Call On 9920725232 With Body to body massag...Vip Mumbai Call Girls Bandra West Call On 9920725232 With Body to body massag...
Vip Mumbai Call Girls Bandra West Call On 9920725232 With Body to body massag...
 
VIP Model Call Girls Kalyani Nagar ( Pune ) Call ON 8005736733 Starting From ...
VIP Model Call Girls Kalyani Nagar ( Pune ) Call ON 8005736733 Starting From ...VIP Model Call Girls Kalyani Nagar ( Pune ) Call ON 8005736733 Starting From ...
VIP Model Call Girls Kalyani Nagar ( Pune ) Call ON 8005736733 Starting From ...
 
Book Paid In Vashi In 8976425520 Navi Mumbai Call Girls
Book Paid In Vashi In 8976425520 Navi Mumbai Call GirlsBook Paid In Vashi In 8976425520 Navi Mumbai Call Girls
Book Paid In Vashi In 8976425520 Navi Mumbai Call Girls
 
How to Build a Simple Shopify Website
How to Build a Simple Shopify WebsiteHow to Build a Simple Shopify Website
How to Build a Simple Shopify Website
 
Call Girls In Jp Nagar ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Jp Nagar ☎ 7737669865 🥵 Book Your One night StandCall Girls In Jp Nagar ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Jp Nagar ☎ 7737669865 🥵 Book Your One night Stand
 
Verified Trusted Call Girls Adugodi💘 9352852248 Good Looking standard Profil...
Verified Trusted Call Girls Adugodi💘 9352852248  Good Looking standard Profil...Verified Trusted Call Girls Adugodi💘 9352852248  Good Looking standard Profil...
Verified Trusted Call Girls Adugodi💘 9352852248 Good Looking standard Profil...
 
Escorts Service Nagavara ☎ 7737669865☎ Book Your One night Stand (Bangalore)
Escorts Service Nagavara ☎ 7737669865☎ Book Your One night Stand (Bangalore)Escorts Service Nagavara ☎ 7737669865☎ Book Your One night Stand (Bangalore)
Escorts Service Nagavara ☎ 7737669865☎ Book Your One night Stand (Bangalore)
 
➥🔝 7737669865 🔝▻ jhansi Call-girls in Women Seeking Men 🔝jhansi🔝 Escorts S...
➥🔝 7737669865 🔝▻ jhansi Call-girls in Women Seeking Men  🔝jhansi🔝   Escorts S...➥🔝 7737669865 🔝▻ jhansi Call-girls in Women Seeking Men  🔝jhansi🔝   Escorts S...
➥🔝 7737669865 🔝▻ jhansi Call-girls in Women Seeking Men 🔝jhansi🔝 Escorts S...
 
Anamika Escorts Service Darbhanga ❣️ 7014168258 ❣️ High Cost Unlimited Hard ...
Anamika Escorts Service Darbhanga ❣️ 7014168258 ❣️ High Cost Unlimited Hard  ...Anamika Escorts Service Darbhanga ❣️ 7014168258 ❣️ High Cost Unlimited Hard  ...
Anamika Escorts Service Darbhanga ❣️ 7014168258 ❣️ High Cost Unlimited Hard ...
 
Call Girls Basavanagudi Just Call 👗 7737669865 👗 Top Class Call Girl Service ...
Call Girls Basavanagudi Just Call 👗 7737669865 👗 Top Class Call Girl Service ...Call Girls Basavanagudi Just Call 👗 7737669865 👗 Top Class Call Girl Service ...
Call Girls Basavanagudi Just Call 👗 7737669865 👗 Top Class Call Girl Service ...
 
Top Rated Pune Call Girls Koregaon Park ⟟ 6297143586 ⟟ Call Me For Genuine S...
Top Rated  Pune Call Girls Koregaon Park ⟟ 6297143586 ⟟ Call Me For Genuine S...Top Rated  Pune Call Girls Koregaon Park ⟟ 6297143586 ⟟ Call Me For Genuine S...
Top Rated Pune Call Girls Koregaon Park ⟟ 6297143586 ⟟ Call Me For Genuine S...
 
call girls in Dakshinpuri (DELHI) 🔝 >༒9953056974 🔝 genuine Escort Service 🔝✔️✔️
call girls in Dakshinpuri  (DELHI) 🔝 >༒9953056974 🔝 genuine Escort Service 🔝✔️✔️call girls in Dakshinpuri  (DELHI) 🔝 >༒9953056974 🔝 genuine Escort Service 🔝✔️✔️
call girls in Dakshinpuri (DELHI) 🔝 >༒9953056974 🔝 genuine Escort Service 🔝✔️✔️
 
💫✅jodhpur 24×7 BEST GENUINE PERSON LOW PRICE CALL GIRL SERVICE FULL SATISFACT...
💫✅jodhpur 24×7 BEST GENUINE PERSON LOW PRICE CALL GIRL SERVICE FULL SATISFACT...💫✅jodhpur 24×7 BEST GENUINE PERSON LOW PRICE CALL GIRL SERVICE FULL SATISFACT...
💫✅jodhpur 24×7 BEST GENUINE PERSON LOW PRICE CALL GIRL SERVICE FULL SATISFACT...
 
WhatsApp Chat: 📞 8617697112 Call Girl Baran is experienced
WhatsApp Chat: 📞 8617697112 Call Girl Baran is experiencedWhatsApp Chat: 📞 8617697112 Call Girl Baran is experienced
WhatsApp Chat: 📞 8617697112 Call Girl Baran is experienced
 
RT Nagar Call Girls Service: 🍓 7737669865 🍓 High Profile Model Escorts | Bang...
RT Nagar Call Girls Service: 🍓 7737669865 🍓 High Profile Model Escorts | Bang...RT Nagar Call Girls Service: 🍓 7737669865 🍓 High Profile Model Escorts | Bang...
RT Nagar Call Girls Service: 🍓 7737669865 🍓 High Profile Model Escorts | Bang...
 
❤Personal Whatsapp Number 8617697112 Samba Call Girls 💦✅.
❤Personal Whatsapp Number 8617697112 Samba Call Girls 💦✅.❤Personal Whatsapp Number 8617697112 Samba Call Girls 💦✅.
❤Personal Whatsapp Number 8617697112 Samba Call Girls 💦✅.
 
Escorts Service Basapura ☎ 7737669865☎ Book Your One night Stand (Bangalore)
Escorts Service Basapura ☎ 7737669865☎ Book Your One night Stand (Bangalore)Escorts Service Basapura ☎ 7737669865☎ Book Your One night Stand (Bangalore)
Escorts Service Basapura ☎ 7737669865☎ Book Your One night Stand (Bangalore)
 
怎样办理伯明翰大学学院毕业证(Birmingham毕业证书)成绩单留信认证
怎样办理伯明翰大学学院毕业证(Birmingham毕业证书)成绩单留信认证怎样办理伯明翰大学学院毕业证(Birmingham毕业证书)成绩单留信认证
怎样办理伯明翰大学学院毕业证(Birmingham毕业证书)成绩单留信认证
 
call girls in Kaushambi (Ghaziabad) 🔝 >༒8448380779 🔝 genuine Escort Service 🔝...
call girls in Kaushambi (Ghaziabad) 🔝 >༒8448380779 🔝 genuine Escort Service 🔝...call girls in Kaushambi (Ghaziabad) 🔝 >༒8448380779 🔝 genuine Escort Service 🔝...
call girls in Kaushambi (Ghaziabad) 🔝 >༒8448380779 🔝 genuine Escort Service 🔝...
 
Abortion Pills in Oman (+918133066128) Cytotec clinic buy Oman Muscat
Abortion Pills in Oman (+918133066128) Cytotec clinic buy Oman MuscatAbortion Pills in Oman (+918133066128) Cytotec clinic buy Oman Muscat
Abortion Pills in Oman (+918133066128) Cytotec clinic buy Oman Muscat
 

fire resistant assemblies

  • 1. FIRE AND SMOKE RESISTANT ASSEMBLIES BARRIERS, ASSEMBLIES AND PARTITIONS
  • 2.  Three basic types of rated assemblies:  Fire barriers  Fire partitions  Horizontal assemblies
  • 3.  Fire barriers are walls that a fire resistant rating and in most cases must be continuous and extend vertically from the bottom to the top of the floor/ceiling assembly  Additional fire blocking is required at the intersection with other rated elements  Openings are limited  Opening assemblies need to be rated
  • 4.  Floor/ceiling assemblies are horizontal assemblies  Limited openings  Openings and penetrations must be rated as well
  • 5.
  • 6.  Fire partitions are similar to fire barriers but less restrictive  Separate exit access corridors, tenant spaces in malls, dwellings and /or sleeping units  Allowed to stop at the rated ceiling system  Not required to be a full enclosure  Rating of at least one hour
  • 7.  Ratings depends on purpose, occupancy classification and if space has sprinklers  Openings required to be protected but not limited
  • 8.
  • 9.  Fire enclosures separates occupancy types  Not required between similar hazardous occupancies
  • 10.  Multiple tenants of different occupancies in the same building  Single user with multiple occupancies or uses within the same structure
  • 11.
  • 12.
  • 13.
  • 14.  Tenant separations in malls required to be rated  Dwelling and sleeping units in residential occupancies to be separated by fire partitions  Some incidental accessory occupancies to be separated
  • 15.  Required for vertical shaft enclosures as elevators, dumbwaiters, mechanical chases, etc.  Smoke barriers provide protection form movement and passage of smoke and fire gases  Barriers are usually rated  Partitions are not required to have fire resistance rating
  • 16.  Complete opening assemblies in rated barriers are required to be also rated  Although ratings of opening assemblies – doors, windows, and other penetrations – is lower than the assembly – the quantity and dimensions are limited  Opening assemblies include the door, the frame, and other required hardware.  All rated doors are required to have a self closing device that will close the door after each use. Not necessary for it to be automatic (usually electrically activated)
  • 17.
  • 18.  Glazing products in rated assemblies must:  Stay in place during a fire  Resist thermal shock – by a hose stream  Strength from human contact  Resist heat transfer to unexposed side
  • 19.  Codes allow the use of glass in some rated partitions – type, size, and quantity is limited  Wired glass – wire mesh sandwiched between two layers of glass  Safety resists impact  Nonsafety does not resist impact  Only type of glass addressed by codes for use in rated opening protectives
  • 20.  Specialty tempered glass – treated for fire resistance  Some can be used in 1 hr rated walls  Cannot be used near sprinklers since it does not pass the hose stream test  Glass block  Can be used in some 1 hr rated partitions – glass rated to 45 minutes
  • 21.  Clear ceramics  High resistance to heat  Resists thermal shock  20mins to 2hr.  Up to 23s.f. can be used  Sometimes has more distortion and tint
  • 23.  Firestops and smokestops  F-rated and T-rated  T is stricter than F as it includes a maximum temperature resistance
  • 24.  Fireblocks and Draftstops  Restrict the spread of smoke and fire through concealed spaces  Fireblocks – small spaces  Draftstops – large spaces  Damper systems  Interrupts air flow through ducts going through rated assemblies
  • 26.  An active fire-protection system is sometimes referred to as a prevention system. A. True B. False  The fire-resistance rating of a floor/ceiling assembly is controlled only by the construction type of the building. A. True B. False
  • 27.  All fire-protected doors must have an automatic dosing device. A. True B. False  The fire rating of a through-penetration is typically lower than the fire rating of the construction assembly it is penetrating. A. True B. False
  • 28.  A fire-protected door can also be used as a smokestop door. A. True B. False  Fire barriers are typically used to create compartments within a building. A. True B. False
  • 29.  Occupancy separation walls and demising walls are the same thing. A. True B. False  Doors with fire-protection ratings are not allowed to have glass lites as part of the door. A. True B. False
  • 30.  __________Walls are used to create a continuous vertical separation within a building or between two different buildings.  Fire/Party  A door assembly typically consists of a door, frame, and _____________.  hardware
  • 31.  What is the typical fire-resistance rating of a tenant separation wall? A. 2 hour B. 1 1/2 hour C. 1 hour D. No rating is required.
  • 32.  Which of the following statements is true about firestops? A. They are required at through penetrations in fire barriers. B. They are a means of restricting the passage of smoke, heat, and flames in concealed spaces. C. They can have two different ratings: a T-rating and a stricter F-rating. D. a and c only E. All of the above
  • 33.  A wall assembly with a 2-hour fire-resistance rating is typically required for which means of egress component? A. Exit access B. Public way C. Exit discharge D. Exit
  • 34.  Which of the following devices is used to prevent the movement of air, smoke, gases, and flame through large, concealed spaces? A. Firestops B. Draftstops C. Fireblocking D. Dampers
  • 35.  Which of the following types of glass is typically considered to have a fire-protection rating? A. Wired glass B. Tempered glass C. Glass block D. a and c only E. All of the above
  • 36.  Which of the following statements about fire-protected doors is correct? A. The quantity of hinges is regulated but the type of hinge is not. B. Sills used at fire-rated doors do not typically need to meet accessibility requirements. C. Fire-rated doors are available as flush doors and panel doors. D. A variety of rated glazing can be used as lites in fire rated doors as long as they are within a certain size range.
  • 37.  Which of the following is typically considered a fire partition by the International Building Code? A. A wall between two guest rooms in a hotel. B. A wall between an office space and an exit access corridor. C. A wall between two tenants in a shopping mall. D. a and c only E. All of the above
  • 38.  Which of the following can be used to help control smoke during a fire? A. Smoke barriers B. Pressurized exits C. Sprinklers D. a and b E. A and c
  • 39.  Which type of through-penetration is required in a duct that extends through a rated floor assembly? A. Draftstop B. Fire damper C. Ceiling damper D. None of the above
  • 40.  Which of the following statements about smoke dampers is NOT correct? A. Smoke dampers are typically used in ducts that penetrate smoke barriers. B. Smoke dampers are usually installed with a smoke detector. C. Smoke dampers are typically installed adjacent to a duct. D. Smoke dampers can be classified in one of four classes. E. All of the above are correct.
  • 41.  Which of the following would compromise the rating of a 1 hour fire-resistant wall assembly? A. Using a building material differently than specified by the manufacturer B. Not using rated caulk at the seams and joints C. Installing an electrical box in the wall cavity for a switch D. a and b only E. All of the above