    ANALYSIS OF 3-D VIBRATIONS OF THE BASE ISOLATED SCHOOL BUILDING
       "PESTALOZZI" BY ANALYTICAL AND EXPERIMENTAL APPROACH


                            Mihail A GAREVSKI1, James M KELLY2 And Nikola V ZISI3


                                                            SUMMARY

The results obtained by experimental dynamic ambient and forced vibration tests, as well as from the 3-D finite
element analyses on a base-isolated structure are presented and discussed in this paper. Since the isolators of the
structure were placed 30 years ago, one of the goals of these investigations was to discover whether the isolators
have been affected by aging, i.e., whether there has been a change of the dynamic characteristics of the structure.

First of all, the school building is described and the characteristics of the bearings are given. Then, the results
obtained by means of the ambient and forced vibration technique are presented. Based on these tests, some of the
necessary characteristics of the isolators to be used for formulation of the 3-D mathematical model of the school
were obtained.

Described is the mathematical model that is used in the analyses for obtaining of the fundamental frequencies
and mode shapes (fixed and isolated model). The results from these analyses are also presented in this text.
Finally, the results obtained analytically and experimentally are analysed and discussed.



                                                        INTRODUCTION

The primary school "Pestalozzi" in Skopje, built in 1969, is the first building in the world for which natural
rubber isolators were used for its protection against strong earthquakes. [4,5,6] Since the isolators on which the
school is placed are more than 30 years old, a project is currently being carried out jointly by IZIIS (Institute of
Earthquake Engineering and Engineering Seismology, University "St. Cyril and Methodius", Skopje, Republic of
Macedonia) and EERC (Earthquake Engineering Research Center at the University of California at Berkeley) to
evaluate the state of the isolators after passing of so many years. [2]

The behaviour of the school building under the effect of strong earthquakes shall be analysed by using a 3-D
mathematical model that shall include all the present characteristics of the isolators. To accurately formulate this
model, it is necessary to consider the effect of aging of the isolators, i.e., define their present stiffness
characteristics and equivalent damping. For the purpose of defining the mentioned characteristics, experimental
laboratory tests of two isolators taken from the foundation of the school building "Pestalozzi" are planned to be
performed. [2] To define the dynamic characteristics, in-situ, ambient and forced vibration tests were performed
obtaining thus the fundamental and some of the higher frequencies and the corresponding mode shapes for the
three orthogonal directions of the school building. [3,4] Two torsional modes of vibration and equivalent
damping for all the measured mode shapes were also defined.

A 3-D mathematical model of the school building and the bearings was formulated in order to analytically define
the dynamic characteristics of the structure. The discretization of the structure was done by using shell finite
elements, while the bearings were modelled with spring elements. In addition to the fundamental shapes of
vibration, higher vibration modes were also obtained analytically. Comparison between the experimental and
analytical results was done.

1
     Institute of Earthquake Engineering and Engineering Seismology, University "St. Cyril & Methodius", Skopje, R. Macedonia
2
     Earthquake Engineering Research Center, University of California at Berkeley, California, U.S.A.
3
     Institute of Earthquake Engineering and Engineering Seismology, University "St. Cyril & Methodius", Skopje, R. Macedonia
The results from the ambient and forced vibration tests, as well as from the 3-D finite element analyses of the
school building "Pestalozzi", are given in the subsequent text.



                                      DESRIPTION OF THE BUILDING

The building which is subject of the investigations, i.e., the primary school "J.H. Pestalozzi" in Skopje was
donated to Skopje by the Swiss Government after the catastrophic earthquake of July 26, 1963. The school
building consists of several units of different number of stories and outline. The base isolation system has been
applied only for the main school building, while the other units are founded in the classical way.

The main school building consists of a ground floor and two stories. The proportions of the stricture at plan are
11.0 m / 61.5 m, while its height is 10.0 m. It represents a reinforced concrete box system. The bearing wall
system is composed of shear walls with a thickness of 0.18 m, while the floor slabs are 0.20 m thick. The
building has a strip foundation forming a beam grid, which is sufficiently rigid to sustain all the effects from the
upper structure without heavier deformations. Along the edges of the building, there is a seismic gap with a
width of 0.3 m. The gap is covered with reinforced concrete plates.

The structure is base isolated by its placement on special rubber bearings incorporated between the foundation
structure and the first floor slab. (Fig.1) [8] There are a total of 54 bearings made of natural rubber, with a square
shape, a side of 0.7 m and a height of 0.35 m. Each bearing transfers an axial force amounting to approximately
455 kN. The Swiss firm HUBER-SUHNER from Zurich produced the rubber bearings. The isolators do not
contain reinforcing steel plates. They are fabricated by gluing together several rubber layers. The vertical
stiffness of such bearings is therefore not much greater than the horizontal one. In addition to the negative effect
of the low vertical stiffness of the bearings on the possible rocking motion, there is another disadvantage of these
bearings, which is the occurrence of large lateral deformations of the rubber bearings due to dead load effects.
[1]




Figure 1. Rubber bearings placed between the strip foundation and the building



                DYNAMIC TESTING OF THE PRIMARY SCHOOL "J.H. PESTALOZZI"

Dynamic testing of the main (isolated) school building was performed by application of two independent testing
methods:


                                                          2                                                      1683
Ambient vibration method - This method was used for fast obtaining of preliminary results on the dynamic
characteristics - resonant frequencies and mode shapes of vibration of the tested structure. The vertical vibration
of the structure obtained by this method was used as a referent one since the vibrators used for the forced
vibration tests cannot induce vertical displacements.

Forced vibration method - This method was applied to define some characteristic vibrations of the structure in
both horizontal directions as well as the torsional one.

To define the damping coefficients, two methods were used: (1) half-power bandwidth (frequency-response)
method and (2) logarithmic decrement (time-response) method.

The dynamic characteristics of the building were obtained for the state of reinforced concrete plates being
removed from the seismic gap and free motion of the isolated building in all directions was enabled. [3,4]

Fig. 2 displays the plan of the second storey of the structure with marked measuring points and position of
vibration exciters by which it was excited during the forced vibration tests.




Figure 2. Plan of the second storey of the tested structure with presentation of measuring points and position of
the two vibration exciters



Results From the Tests Performed by Applying the Ambient Vibration Method

To define the resonant frequencies of the structure in both orthogonal directions - transverse (N-S) and
longitudinal (E-W), and the vertical one, four Range Seismometers, Model SS-1 produced by Kinemetrics from
USA were used as sensors. Seismometer was placed in the central part of the structure, at the level of the second
storey, at point "C" (Fig. 2). Seismometers were placed at the ends of the structure (measuring points 1 and 5)
and also at the level of the second storey to define the resonant frequencies of the torsional vibration. The
Fourier amplitude spectra corresponding to the torsional vibrations of the structure were obtained by combining
the signals from both seismometers.

Fig. 3 shows the Fourier amplitude spectra recorded on the structure in the corresponding directions of vibrations
from which the resonant frequencies were defined. For such defined resonant frequencies of the structure, the
corresponding mode shapes were obtained. However, these and the mode shapes obtained by other
measurements are not presented in this paper due to lack of space.




                                                         3                                                    1683
Figure 3. Fourier amplitude spectra on the isolated building recorded with the ambient vibration method



Results From Tests Performed by Using the Forced Vibration Method

In the process of testing, the resonant frequencies of the structure were first of all defined for both orthogonal
directions (N- S) and (E-W) and then for torsion. The structural response to the generated excitation, while
defining the resonant frequencies for the N-S and E-W directions, was recorded at several measuring points. The
recorded responses at the points located in the midst of the structure (point "C" or point "3") were considered
referent. The referent point for definition of the torsional resonant frequencies was point "5" on the east side of
the structure. Based on the recorded amplitudes of the response of the structure to the generated excitations, the
corresponding resonant frequency curves were established. (Fig. 4) Certain tests performed for definition of the
same frequency were carried out by different excitation forces for the purpose of evaluating the relation between
modification of the resonant frequency and the excitation intensity.




Figure 4. Resonant curves of the structural response obtained with the force excitation method


                                                        4                                                     1683
Due to the flexibility of the isolators, some of the mode shapes could quite well be excited and even visually
observed. Therefore, apart from using accelerometers, which is the usual practice in performing these tests,
displacement-meters (LVDT-s) were also used.

The frequency curves presented in Fig. 4 were established based on the recorded amplitudes of structural
response to the generated excitations.

For such defined resonant frequencies, the corresponding mode shapes of vibration were also recorded.



                                          3-D EIGENPAIR ANALYSIS

For both cases of support of the school building, the eigen values and the eigen vectors were computed. First, the
fundamental vibrations of the school fixed at its base were computed. Then, the fundamental frequencies and the
corresponding mode shapes of the school building placed on rubber bearings were obtained. The finite elements
mesh for both analyses was the same.



Description of the Finite Element Model

The analyses of the mathematical model of the "Pestalozzi" primary school building has been done by means of
the SAP2000 computer programme. [7] The structure itself has been modelled by a total number of 7189
"SHELL" elements. Due to the size of the model, the individual structural elements: floor slabs, bearing walls in
both orthogonal directions, staircase slabs, parapet walls and alike have been modelled separately. Then the
structure has been assembled as a whole by means of "welding" of the joints that share the same location. The
rubber bearings supporting the structure have been modelled by a total of 54 "NLLINK" elements. These have
been taken as one-joint grounded spring, and they are of the type of biaxial base isolators. During the analysis of
this model, it has been necessary to solve 43596 equilibrium equations.

Such a refined model (with a large number of finite elements) was used because the generation of the mesh was
not time consuming, as were also the analyses. Such a model is necessary for further analyses when the stress
state in the walls is to be analysed.



Analysis of the School Building Model Fixed at its Base

This analysis was necessary to be performed because of two reasons: (1) the fundamental frequencies of the
fixed structure had to prove whether the base isolation of the structure is justified; (2) this analysis had to prove
whether rigid-structure approximation is possible for the performance of a simpler analysis.

Table 1 shows the eigen frequencies of the first fundamental modes of vibration obtained by this analysis.



Analysis of the School Building Model on Rubber Isolators

Precise determination of stiffness characteristics in lateral and vertical direction was not possible at present since
force-displacement hysteretic loops of the installed rubber isolators were not available. Therefore, the
approximate values of stiffness characteristics of isolators were obtained via the measured values of fundamental
frequencies by using the following basic formula:

           54

          ∑k
          i =1
                 Bi   = ω B M total
                          2




where: k_Bi - stiffness of i-th base isolator, ω_B - measured circular frequency of the base isolated building, and
M_total - total mass of building structure and base isolators.

                                                          5                                                      1683
It is assumed that: (1) the structure is rigid (the fixed-base analysis (f_N-S = 12.97 Hz; f_E-W = 8.32 Hz did
confirm this assumption), and (2) the mass is known (it can be computed from the given geometry and the bulk
density of the concrete). However, it should be noted that the computation of the lateral stiffness in this way is
partially compromised since the fundamental modes of vibration in both orthogonal directions are not purely
translational, but there is also a rocking motion due to the low vertical stiffness of the isolators.

Table 1 shows the eigen frequencies of the first fundamental modes of vibration, while the characteristics mode
shapes are presented in Fig 5.




a) Mode: 1, Period: 1.408 s, Frequency: 0.710 Hz, Dominant direction: N-S (transversal)




b) Mode: 2, Period: 1.167 s, Frequency: 0.857 Hz, Dominant direction: E-W (longitudinal)




c) Mode: 3, Period: 1.133 s, Frequency: 0.882 Hz, Dominant direction: torsional

Fig 5 Characteristics mode shapes of the base isolated building model


                                                        6                                                    1683
DISCUSSION OF THE RESULTS OBTAINED THROUGH THE EXPERIMENTAL
                     MEASUREMENTS AND ANALYTICAL PROCEDURES

Based on the data obtained from the performed testing of the structure, the following is concluded:

The values of the frequencies of the fundamental vibration modes in certain directions when the plates covering
the seismic gap are removed are: for transverse direction (N-S): f_1f = 0.76 Hz (forced vibration tests) and
f_1a = 0.96 Hz (ambient vibration tests); for torsion: f_2f = 0.84 Hz (forced vibration tests) and f_2a = 1.04 Hz
(ambient vibration tests); for the longitudinal direction (E-W): f_3f = 0.88 Hz (forced vibration tests) and
f_3a = 1.28 Hz (ambient vibration tests) and for vertical direction: f_5a = 2.56 Hz (ambient vibration tests).

Apart from the fundamental vibration modes, some of the higher modes were recorded. The frequency of
f_4f = 2.08 Hz represents the second natural frequency of the structure in the (N-S) direction, while f_6f= 3.20
Hz represents the second natural frequency at torsional excitation. The second natural frequency of the structure
in the E-W direction is very close (almost equal) to the corresponding frequency at torsional excitation
amounting to f = 3.20 Hz, i.e., f_7f= 3.28 Hz.

 The recorded higher frequencies of f_8f = 3.44 Hz, f_9f= 5.28 Hz, f_12f = 5.92 Hz in the transverse direction
and f_10f = 5.28 Hz in the longitudinal direction, i.e., f_11f = 5.52 Hz at torsional vibrations are associated with
some of the higher mode shapes of vibration of the structure.

The frequencies and the corresponding damping measured by applying both methods are presented in Table 1.


Table 1
          Mode                    Experimental Testing                             Analytical
          No.      Direction      Ambient Forced vibration                         Fix Base Isolated
                                  f           f              Damping   Damping     f           f
                                  [Hz]        [Hz]           [%] hp*   [%] ld**    [Hz]        [Hz]
          1        first (N-S)    0.96        0.76           3.8       3.5         12.97       0.71
          2        first (E-W)    1.28        0.88           7.3       6.3         8.32        0.86
          3        torsion        1.04        0.84           5.4       3.0         -           0.88
          4        vertical       2.56        -              -         -           -           1.87
*Half-power bandwidth method          **Logarithmic decrement method

Analysing the recorded mode shapes, it can be said that the translatory components dominate over the first two
modes of vibration of the school building (f_1f = 0.76 Hz, f_2f = 0.88 Hz).

Characteristic for the second vibration modes in E-W direction (f_4f = 2.08 Hz) and N-S direction (f_7f = 3.28
Hz) is the rocking motion which is more pronounced for the mode with a frequency of f_4f = 2.08 Hz.

The experimentally measured mode shapes and those obtained analytically clearly point to the fact that the
modes, in addition to the translation component, contain also the component of a rocking motion.

The complex motions of the mode shapes result from the low vertical stiffness of the rubber bearings.

Since the fundamental modes for the two horizontal directions are not purely translatory (there are rotation
components), their frequencies are not identical. There occurs a difference of 15.8% in the values of their
frequencies.

The obtained results on damping presented in Table 1 point to similar damping obtained by both methods. The
damping values lead to the conclusion that the internal damping of the bearing is small since the coefficients of
viscous damping for the fundamental vibration modes are 3.5%, 3% and 6.3% of the critical one in the N-S and
E-W directions as well as torsion respectively.

The fundamental frequencies of the fixed base model do justify the performed isolation of the building.
However, the first modes of vibration for both orthogonal directions f_N-S = 0.76 Hz; f_E-W = 0.88 Hz


                                                         7                                                     1683
obtained experimentally are far above the minimum frequency of f = 0.5 Hz which is necessary for the isolators
in order that they be efficient.

The mathematical discretization and analysis of the isolated structure has successfully been done since there is a
good correlation between the analytical and experimental values of the fundamental frequencies and their mode
shapes. However, evaluation of the efficiency of the base isolation could be made in the final phase of this
project when two isolators shall be taken off and the hysteresis curves obtained in laboratory conditions. The
final analyses shall be performed by use of these curves and shall lead to obtaining of the base shear and the
maximum displacements. From the laboratory testing on the taken off bearings and the analyses, one could
further conclude whether the old bearings are necessary to be replaced by new ones or whether it is only
necessary to add dampers for dissipation of the input energy from the earthquake.



                                           ACKNOWLEDGMENT

This paper is based on the investigations sponsored by the Macedonian – US Joint Fund in cooperation with the
Macedonian Ministry of Science and US - NIST under project number 056/600. The authors are indebted to
these two institutions for the correct evaluation of the necessity for these investigations.



                                                REFERENCES

1.       Bridgestone corporation, 1991. Rubber technology for seismic isolation. Proc., 11th international conf.
on struc. mech. in reactor technology: 45-56, Tokyo, Japan.

2.      Garevski, M. & Kelly, M. J., 1996. Evaluation of the proper functioning of the rubber isolators of the
primary school Pestalozzi in Skopje under strong earthquake. U.S.- Macedonian science and technology
program-project proposal.

3.        Garevski, M., Kelly, M. J. & Bojadziev, M.,1998. Evaluation of the proper functioning of the rubber
isolators of the primary school Pestalozzi in Skopje under strong earthquake: part I- Full-scale dynamic testing
of the first rubber base-isolated building in the world. Report IZIIS.

4.       Garevski, M., Kelly, J. M. & Bojadziev, M., 1998. Experimental dynamic tests on the first structure in
the world isolated with rubber bearings. 11th European Conference on Earthquake Engineering, Paris, France

5.      Izumi, M., 1988. Base isolation and passive seismic response control. Proc., 9th world conference on
earthquake engineering, vol. VII: 386-396,Tokyo-Kyoto, Japan,.

6.     Kelly, J.M., 1981. The Development of base isolation for the seismic protection of structures. Report
No. UCB/EERC-81/01, Earthquake Engineering Research Center, University of California, Berkeley, California.

7.     SAP2000 Integrated Finite Element Analysis and Design of Structures; Analysis Reference, Vol. 1 &
2; Computers and Structures, Inc; Berkeley, California, USA

8.       Staudacher, K., 1982. The Swiss full base isolation system (3D) for extreme earthquake safety of
structures. Proc. of the 1982 convention of the structural engineering association of California, Sacramento,
California.




                                                        8                                                    1683

Más contenido relacionado

La actualidad más candente

Numerical modeling of reinforced soil segmental wall under surcharge loading
Numerical modeling of reinforced soil segmental wall under surcharge loadingNumerical modeling of reinforced soil segmental wall under surcharge loading
Numerical modeling of reinforced soil segmental wall under surcharge loadingIAEME Publication
 
Acta 59 (2011) E C C I Fe Mn C
Acta 59 (2011)  E C C I  Fe  Mn  CActa 59 (2011)  E C C I  Fe  Mn  C
Acta 59 (2011) E C C I Fe Mn CDierk Raabe
 
Cundall 2008 rock mass workshop
Cundall 2008 rock mass workshopCundall 2008 rock mass workshop
Cundall 2008 rock mass workshopNicolas Giraldo
 
IRJET - Effect of Seismic Pounding between Adjacent Irregular Buildings a...
IRJET -  	  Effect of Seismic Pounding between Adjacent Irregular Buildings a...IRJET -  	  Effect of Seismic Pounding between Adjacent Irregular Buildings a...
IRJET - Effect of Seismic Pounding between Adjacent Irregular Buildings a...IRJET Journal
 
Numerical Study of Star Anchor Plate Embedded in Cohesive Soil
Numerical Study of Star Anchor Plate Embedded in Cohesive SoilNumerical Study of Star Anchor Plate Embedded in Cohesive Soil
Numerical Study of Star Anchor Plate Embedded in Cohesive SoilIJERA Editor
 
Investigation of the Behaviour for Reinforced Concrete Beam Using Non Linear...
Investigation of the Behaviour for Reinforced Concrete Beam  Using Non Linear...Investigation of the Behaviour for Reinforced Concrete Beam  Using Non Linear...
Investigation of the Behaviour for Reinforced Concrete Beam Using Non Linear...IJMER
 
seismic response of multi storey building equipped with steel bracing
 seismic response of multi storey building equipped with steel bracing seismic response of multi storey building equipped with steel bracing
seismic response of multi storey building equipped with steel bracingINFOGAIN PUBLICATION
 
Motion detection applied to
Motion detection applied toMotion detection applied to
Motion detection applied toijcsa
 
Programmable assembly of bi walled nonuniform beams concept, modeling and app...
Programmable assembly of bi walled nonuniform beams concept, modeling and app...Programmable assembly of bi walled nonuniform beams concept, modeling and app...
Programmable assembly of bi walled nonuniform beams concept, modeling and app...TalalSalem5
 
Seismic pounding of multistoreyed buildings
Seismic pounding of multistoreyed buildingsSeismic pounding of multistoreyed buildings
Seismic pounding of multistoreyed buildingseSAT Publishing House
 
Seismic Vulnerability Assessment of Steel Moment Resisting Frame due to Infil...
Seismic Vulnerability Assessment of Steel Moment Resisting Frame due to Infil...Seismic Vulnerability Assessment of Steel Moment Resisting Frame due to Infil...
Seismic Vulnerability Assessment of Steel Moment Resisting Frame due to Infil...IDES Editor
 

La actualidad más candente (16)

14 05 01-0432
14 05 01-043214 05 01-0432
14 05 01-0432
 
Numerical modeling of reinforced soil segmental wall under surcharge loading
Numerical modeling of reinforced soil segmental wall under surcharge loadingNumerical modeling of reinforced soil segmental wall under surcharge loading
Numerical modeling of reinforced soil segmental wall under surcharge loading
 
Acta 59 (2011) E C C I Fe Mn C
Acta 59 (2011)  E C C I  Fe  Mn  CActa 59 (2011)  E C C I  Fe  Mn  C
Acta 59 (2011) E C C I Fe Mn C
 
Cundall 2008 rock mass workshop
Cundall 2008 rock mass workshopCundall 2008 rock mass workshop
Cundall 2008 rock mass workshop
 
IRJET - Effect of Seismic Pounding between Adjacent Irregular Buildings a...
IRJET -  	  Effect of Seismic Pounding between Adjacent Irregular Buildings a...IRJET -  	  Effect of Seismic Pounding between Adjacent Irregular Buildings a...
IRJET - Effect of Seismic Pounding between Adjacent Irregular Buildings a...
 
A05710107
A05710107A05710107
A05710107
 
Numerical Study of Star Anchor Plate Embedded in Cohesive Soil
Numerical Study of Star Anchor Plate Embedded in Cohesive SoilNumerical Study of Star Anchor Plate Embedded in Cohesive Soil
Numerical Study of Star Anchor Plate Embedded in Cohesive Soil
 
Investigation of the Behaviour for Reinforced Concrete Beam Using Non Linear...
Investigation of the Behaviour for Reinforced Concrete Beam  Using Non Linear...Investigation of the Behaviour for Reinforced Concrete Beam  Using Non Linear...
Investigation of the Behaviour for Reinforced Concrete Beam Using Non Linear...
 
seismic response of multi storey building equipped with steel bracing
 seismic response of multi storey building equipped with steel bracing seismic response of multi storey building equipped with steel bracing
seismic response of multi storey building equipped with steel bracing
 
Motion detection applied to
Motion detection applied toMotion detection applied to
Motion detection applied to
 
J013166067
J013166067J013166067
J013166067
 
Programmable assembly of bi walled nonuniform beams concept, modeling and app...
Programmable assembly of bi walled nonuniform beams concept, modeling and app...Programmable assembly of bi walled nonuniform beams concept, modeling and app...
Programmable assembly of bi walled nonuniform beams concept, modeling and app...
 
Wcee2012 2054
Wcee2012 2054Wcee2012 2054
Wcee2012 2054
 
Seismic pounding of multistoreyed buildings
Seismic pounding of multistoreyed buildingsSeismic pounding of multistoreyed buildings
Seismic pounding of multistoreyed buildings
 
Seismic Vulnerability Assessment of Steel Moment Resisting Frame due to Infil...
Seismic Vulnerability Assessment of Steel Moment Resisting Frame due to Infil...Seismic Vulnerability Assessment of Steel Moment Resisting Frame due to Infil...
Seismic Vulnerability Assessment of Steel Moment Resisting Frame due to Infil...
 
infilled frame
infilled frame infilled frame
infilled frame
 

Destacado

Maahanmuuttajanuorten Helsinki -hankkeen esittely 22.3. Ympäristö ministeriö
Maahanmuuttajanuorten Helsinki -hankkeen esittely 22.3.  Ympäristö ministeriöMaahanmuuttajanuorten Helsinki -hankkeen esittely 22.3.  Ympäristö ministeriö
Maahanmuuttajanuorten Helsinki -hankkeen esittely 22.3. Ympäristö ministeriöIikka Lovio
 
Monikulttuurisen nuorisotyön suunta
Monikulttuurisen nuorisotyön suunta Monikulttuurisen nuorisotyön suunta
Monikulttuurisen nuorisotyön suunta Iikka Lovio
 
Maahanmuuttajanuorten helsinki
Maahanmuuttajanuorten helsinki  Maahanmuuttajanuorten helsinki
Maahanmuuttajanuorten helsinki Iikka Lovio
 
Idade media
Idade mediaIdade media
Idade mediaTuli Cm
 
Jaettu asuminen_Iikka Lovio_26.11.11
Jaettu asuminen_Iikka Lovio_26.11.11Jaettu asuminen_Iikka Lovio_26.11.11
Jaettu asuminen_Iikka Lovio_26.11.11Iikka Lovio
 
Cушилки для рук NEOCLIMA
Cушилки для рук NEOCLIMACушилки для рук NEOCLIMA
Cушилки для рук NEOCLIMAsibiko
 
подготовка к новому учебному году
подготовка к новому учебному годуподготовка к новому учебному году
подготовка к новому учебному годуMrgut
 
A szilvafa és rokonai
A szilvafa és rokonaiA szilvafa és rokonai
A szilvafa és rokonaisztalker
 
Pisave, karolinška minuskula
Pisave, karolinška minuskulaPisave, karolinška minuskula
Pisave, karolinška minuskulaTamara Rifelj
 
BIOLOGICAL SCIENCE~photosynthesis and cellular respiration
BIOLOGICAL SCIENCE~photosynthesis and cellular respirationBIOLOGICAL SCIENCE~photosynthesis and cellular respiration
BIOLOGICAL SCIENCE~photosynthesis and cellular respirationEligardi Enterprises Inc.
 
Types of Claims
Types of ClaimsTypes of Claims
Types of Claimseveldys
 

Destacado (18)

Maahanmuuttajanuorten Helsinki -hankkeen esittely 22.3. Ympäristö ministeriö
Maahanmuuttajanuorten Helsinki -hankkeen esittely 22.3.  Ympäristö ministeriöMaahanmuuttajanuorten Helsinki -hankkeen esittely 22.3.  Ympäristö ministeriö
Maahanmuuttajanuorten Helsinki -hankkeen esittely 22.3. Ympäristö ministeriö
 
Diagnostico individual completo
Diagnostico individual completoDiagnostico individual completo
Diagnostico individual completo
 
Monikulttuurisen nuorisotyön suunta
Monikulttuurisen nuorisotyön suunta Monikulttuurisen nuorisotyön suunta
Monikulttuurisen nuorisotyön suunta
 
Maahanmuuttajanuorten helsinki
Maahanmuuttajanuorten helsinki  Maahanmuuttajanuorten helsinki
Maahanmuuttajanuorten helsinki
 
Idade media
Idade mediaIdade media
Idade media
 
Jaettu asuminen_Iikka Lovio_26.11.11
Jaettu asuminen_Iikka Lovio_26.11.11Jaettu asuminen_Iikka Lovio_26.11.11
Jaettu asuminen_Iikka Lovio_26.11.11
 
Cушилки для рук NEOCLIMA
Cушилки для рук NEOCLIMACушилки для рук NEOCLIMA
Cушилки для рук NEOCLIMA
 
Computer 4color
Computer 4colorComputer 4color
Computer 4color
 
подготовка к новому учебному году
подготовка к новому учебному годуподготовка к новому учебному году
подготовка к новому учебному году
 
Migrator.net
Migrator.net Migrator.net
Migrator.net
 
Hiv dan konseling
Hiv dan konselingHiv dan konseling
Hiv dan konseling
 
Chagall y van gogh
Chagall y van goghChagall y van gogh
Chagall y van gogh
 
A szilvafa és rokonai
A szilvafa és rokonaiA szilvafa és rokonai
A szilvafa és rokonai
 
Pisave, karolinška minuskula
Pisave, karolinška minuskulaPisave, karolinška minuskula
Pisave, karolinška minuskula
 
Gg zat, alkohol & rokok
Gg zat, alkohol & rokokGg zat, alkohol & rokok
Gg zat, alkohol & rokok
 
Kw spm jiwa napza
Kw spm jiwa   napzaKw spm jiwa   napza
Kw spm jiwa napza
 
BIOLOGICAL SCIENCE~photosynthesis and cellular respiration
BIOLOGICAL SCIENCE~photosynthesis and cellular respirationBIOLOGICAL SCIENCE~photosynthesis and cellular respiration
BIOLOGICAL SCIENCE~photosynthesis and cellular respiration
 
Types of Claims
Types of ClaimsTypes of Claims
Types of Claims
 

Similar a 1683

Stress ribbon bridges stiffened by arches or cables
Stress ribbon bridges stiffened by arches or cablesStress ribbon bridges stiffened by arches or cables
Stress ribbon bridges stiffened by arches or cablesMasum Majid
 
Effect of structural uncertainties on seismic performance of rc frames.
Effect of structural uncertainties on seismic performance of rc frames.Effect of structural uncertainties on seismic performance of rc frames.
Effect of structural uncertainties on seismic performance of rc frames.Saniul Mahi
 
seismic analysis of structures presentation
seismic analysis of structures presentationseismic analysis of structures presentation
seismic analysis of structures presentationDrAhmedNabil2
 
SEISMIC ISOLATION OF EARTH RETAINING WALLS USING EPS
SEISMIC ISOLATION OF EARTH RETAINING WALLS USING EPSSEISMIC ISOLATION OF EARTH RETAINING WALLS USING EPS
SEISMIC ISOLATION OF EARTH RETAINING WALLS USING EPSPantelis Pateniotis
 
Earthquake response of modified folded cantilever shear structurewith fix
Earthquake response of modified folded cantilever shear structurewith fixEarthquake response of modified folded cantilever shear structurewith fix
Earthquake response of modified folded cantilever shear structurewith fixIAEME Publication
 
Seismic Response of Non-Structural Element Placed on Single Story Two-Way Asy...
Seismic Response of Non-Structural Element Placed on Single Story Two-Way Asy...Seismic Response of Non-Structural Element Placed on Single Story Two-Way Asy...
Seismic Response of Non-Structural Element Placed on Single Story Two-Way Asy...IJERA Editor
 
APPLICATION OF TAGUCHI METHOD FOR PARAMETRIC STUDIES OF A FUNNEL SHAPED STRUC...
APPLICATION OF TAGUCHI METHOD FOR PARAMETRIC STUDIES OF A FUNNEL SHAPED STRUC...APPLICATION OF TAGUCHI METHOD FOR PARAMETRIC STUDIES OF A FUNNEL SHAPED STRUC...
APPLICATION OF TAGUCHI METHOD FOR PARAMETRIC STUDIES OF A FUNNEL SHAPED STRUC...ijmech
 
SMiRT-23_EPGB Paper-495
SMiRT-23_EPGB Paper-495SMiRT-23_EPGB Paper-495
SMiRT-23_EPGB Paper-495Tobias Richter
 
Modelling Visco-elastic material for Building structure
Modelling Visco-elastic material for Building structureModelling Visco-elastic material for Building structure
Modelling Visco-elastic material for Building structureDigvijay Gaikwad
 
2013 siryabe - holes effects in plane periodic multilayered viscoelastic media
2013   siryabe - holes effects in plane periodic multilayered viscoelastic media2013   siryabe - holes effects in plane periodic multilayered viscoelastic media
2013 siryabe - holes effects in plane periodic multilayered viscoelastic mediaPierre Maréchal
 
Experimental in Structural Dynamics Base Isolation System Modelling
Experimental in Structural Dynamics Base Isolation System ModellingExperimental in Structural Dynamics Base Isolation System Modelling
Experimental in Structural Dynamics Base Isolation System Modellingijtsrd
 
SEISMIC MITIGATION OF TWIN TOWER STRUCTURES USING AN ISOLATED CORRIDOR
SEISMIC MITIGATION OF TWIN TOWER STRUCTURES USING AN ISOLATED CORRIDORSEISMIC MITIGATION OF TWIN TOWER STRUCTURES USING AN ISOLATED CORRIDOR
SEISMIC MITIGATION OF TWIN TOWER STRUCTURES USING AN ISOLATED CORRIDORharshilshah546931
 
Development of-new-control-techniques-for-vibration-isolation-of-structures-u...
Development of-new-control-techniques-for-vibration-isolation-of-structures-u...Development of-new-control-techniques-for-vibration-isolation-of-structures-u...
Development of-new-control-techniques-for-vibration-isolation-of-structures-u...Cemal Ardil
 
Rutherford Backscattering Spectrometry: A Laboratory Didactic Path About the ...
Rutherford Backscattering Spectrometry: A Laboratory Didactic Path About the ...Rutherford Backscattering Spectrometry: A Laboratory Didactic Path About the ...
Rutherford Backscattering Spectrometry: A Laboratory Didactic Path About the ...SEENET-MTP
 
Fracture Toughness Characterization
Fracture Toughness CharacterizationFracture Toughness Characterization
Fracture Toughness CharacterizationIJERA Editor
 
5.structural engineering
5.structural engineering5.structural engineering
5.structural engineeringhlksd
 
Inelastic Period of Multi Degree of Freedom System Estimation using Wavelet T...
Inelastic Period of Multi Degree of Freedom System Estimation using Wavelet T...Inelastic Period of Multi Degree of Freedom System Estimation using Wavelet T...
Inelastic Period of Multi Degree of Freedom System Estimation using Wavelet T...Harshana Prabhath
 

Similar a 1683 (20)

Arch. maria rosaria_marsico
Arch. maria rosaria_marsicoArch. maria rosaria_marsico
Arch. maria rosaria_marsico
 
Stress ribbon bridges stiffened by arches or cables
Stress ribbon bridges stiffened by arches or cablesStress ribbon bridges stiffened by arches or cables
Stress ribbon bridges stiffened by arches or cables
 
Effect of structural uncertainties on seismic performance of rc frames.
Effect of structural uncertainties on seismic performance of rc frames.Effect of structural uncertainties on seismic performance of rc frames.
Effect of structural uncertainties on seismic performance of rc frames.
 
seismic analysis of structures presentation
seismic analysis of structures presentationseismic analysis of structures presentation
seismic analysis of structures presentation
 
14WCEE Paper S12-001
14WCEE Paper S12-00114WCEE Paper S12-001
14WCEE Paper S12-001
 
SEISMIC ISOLATION OF EARTH RETAINING WALLS USING EPS
SEISMIC ISOLATION OF EARTH RETAINING WALLS USING EPSSEISMIC ISOLATION OF EARTH RETAINING WALLS USING EPS
SEISMIC ISOLATION OF EARTH RETAINING WALLS USING EPS
 
Earthquake response of modified folded cantilever shear structurewith fix
Earthquake response of modified folded cantilever shear structurewith fixEarthquake response of modified folded cantilever shear structurewith fix
Earthquake response of modified folded cantilever shear structurewith fix
 
Seismic Response of Non-Structural Element Placed on Single Story Two-Way Asy...
Seismic Response of Non-Structural Element Placed on Single Story Two-Way Asy...Seismic Response of Non-Structural Element Placed on Single Story Two-Way Asy...
Seismic Response of Non-Structural Element Placed on Single Story Two-Way Asy...
 
APPLICATION OF TAGUCHI METHOD FOR PARAMETRIC STUDIES OF A FUNNEL SHAPED STRUC...
APPLICATION OF TAGUCHI METHOD FOR PARAMETRIC STUDIES OF A FUNNEL SHAPED STRUC...APPLICATION OF TAGUCHI METHOD FOR PARAMETRIC STUDIES OF A FUNNEL SHAPED STRUC...
APPLICATION OF TAGUCHI METHOD FOR PARAMETRIC STUDIES OF A FUNNEL SHAPED STRUC...
 
SMiRT-23_EPGB Paper-495
SMiRT-23_EPGB Paper-495SMiRT-23_EPGB Paper-495
SMiRT-23_EPGB Paper-495
 
Modelling Visco-elastic material for Building structure
Modelling Visco-elastic material for Building structureModelling Visco-elastic material for Building structure
Modelling Visco-elastic material for Building structure
 
2013 siryabe - holes effects in plane periodic multilayered viscoelastic media
2013   siryabe - holes effects in plane periodic multilayered viscoelastic media2013   siryabe - holes effects in plane periodic multilayered viscoelastic media
2013 siryabe - holes effects in plane periodic multilayered viscoelastic media
 
Experimental in Structural Dynamics Base Isolation System Modelling
Experimental in Structural Dynamics Base Isolation System ModellingExperimental in Structural Dynamics Base Isolation System Modelling
Experimental in Structural Dynamics Base Isolation System Modelling
 
SEISMIC MITIGATION OF TWIN TOWER STRUCTURES USING AN ISOLATED CORRIDOR
SEISMIC MITIGATION OF TWIN TOWER STRUCTURES USING AN ISOLATED CORRIDORSEISMIC MITIGATION OF TWIN TOWER STRUCTURES USING AN ISOLATED CORRIDOR
SEISMIC MITIGATION OF TWIN TOWER STRUCTURES USING AN ISOLATED CORRIDOR
 
Development of-new-control-techniques-for-vibration-isolation-of-structures-u...
Development of-new-control-techniques-for-vibration-isolation-of-structures-u...Development of-new-control-techniques-for-vibration-isolation-of-structures-u...
Development of-new-control-techniques-for-vibration-isolation-of-structures-u...
 
B05
B05B05
B05
 
Rutherford Backscattering Spectrometry: A Laboratory Didactic Path About the ...
Rutherford Backscattering Spectrometry: A Laboratory Didactic Path About the ...Rutherford Backscattering Spectrometry: A Laboratory Didactic Path About the ...
Rutherford Backscattering Spectrometry: A Laboratory Didactic Path About the ...
 
Fracture Toughness Characterization
Fracture Toughness CharacterizationFracture Toughness Characterization
Fracture Toughness Characterization
 
5.structural engineering
5.structural engineering5.structural engineering
5.structural engineering
 
Inelastic Period of Multi Degree of Freedom System Estimation using Wavelet T...
Inelastic Period of Multi Degree of Freedom System Estimation using Wavelet T...Inelastic Period of Multi Degree of Freedom System Estimation using Wavelet T...
Inelastic Period of Multi Degree of Freedom System Estimation using Wavelet T...
 

1683

  • 1. 1683 ANALYSIS OF 3-D VIBRATIONS OF THE BASE ISOLATED SCHOOL BUILDING "PESTALOZZI" BY ANALYTICAL AND EXPERIMENTAL APPROACH Mihail A GAREVSKI1, James M KELLY2 And Nikola V ZISI3 SUMMARY The results obtained by experimental dynamic ambient and forced vibration tests, as well as from the 3-D finite element analyses on a base-isolated structure are presented and discussed in this paper. Since the isolators of the structure were placed 30 years ago, one of the goals of these investigations was to discover whether the isolators have been affected by aging, i.e., whether there has been a change of the dynamic characteristics of the structure. First of all, the school building is described and the characteristics of the bearings are given. Then, the results obtained by means of the ambient and forced vibration technique are presented. Based on these tests, some of the necessary characteristics of the isolators to be used for formulation of the 3-D mathematical model of the school were obtained. Described is the mathematical model that is used in the analyses for obtaining of the fundamental frequencies and mode shapes (fixed and isolated model). The results from these analyses are also presented in this text. Finally, the results obtained analytically and experimentally are analysed and discussed. INTRODUCTION The primary school "Pestalozzi" in Skopje, built in 1969, is the first building in the world for which natural rubber isolators were used for its protection against strong earthquakes. [4,5,6] Since the isolators on which the school is placed are more than 30 years old, a project is currently being carried out jointly by IZIIS (Institute of Earthquake Engineering and Engineering Seismology, University "St. Cyril and Methodius", Skopje, Republic of Macedonia) and EERC (Earthquake Engineering Research Center at the University of California at Berkeley) to evaluate the state of the isolators after passing of so many years. [2] The behaviour of the school building under the effect of strong earthquakes shall be analysed by using a 3-D mathematical model that shall include all the present characteristics of the isolators. To accurately formulate this model, it is necessary to consider the effect of aging of the isolators, i.e., define their present stiffness characteristics and equivalent damping. For the purpose of defining the mentioned characteristics, experimental laboratory tests of two isolators taken from the foundation of the school building "Pestalozzi" are planned to be performed. [2] To define the dynamic characteristics, in-situ, ambient and forced vibration tests were performed obtaining thus the fundamental and some of the higher frequencies and the corresponding mode shapes for the three orthogonal directions of the school building. [3,4] Two torsional modes of vibration and equivalent damping for all the measured mode shapes were also defined. A 3-D mathematical model of the school building and the bearings was formulated in order to analytically define the dynamic characteristics of the structure. The discretization of the structure was done by using shell finite elements, while the bearings were modelled with spring elements. In addition to the fundamental shapes of vibration, higher vibration modes were also obtained analytically. Comparison between the experimental and analytical results was done. 1 Institute of Earthquake Engineering and Engineering Seismology, University "St. Cyril & Methodius", Skopje, R. Macedonia 2 Earthquake Engineering Research Center, University of California at Berkeley, California, U.S.A. 3 Institute of Earthquake Engineering and Engineering Seismology, University "St. Cyril & Methodius", Skopje, R. Macedonia
  • 2. The results from the ambient and forced vibration tests, as well as from the 3-D finite element analyses of the school building "Pestalozzi", are given in the subsequent text. DESRIPTION OF THE BUILDING The building which is subject of the investigations, i.e., the primary school "J.H. Pestalozzi" in Skopje was donated to Skopje by the Swiss Government after the catastrophic earthquake of July 26, 1963. The school building consists of several units of different number of stories and outline. The base isolation system has been applied only for the main school building, while the other units are founded in the classical way. The main school building consists of a ground floor and two stories. The proportions of the stricture at plan are 11.0 m / 61.5 m, while its height is 10.0 m. It represents a reinforced concrete box system. The bearing wall system is composed of shear walls with a thickness of 0.18 m, while the floor slabs are 0.20 m thick. The building has a strip foundation forming a beam grid, which is sufficiently rigid to sustain all the effects from the upper structure without heavier deformations. Along the edges of the building, there is a seismic gap with a width of 0.3 m. The gap is covered with reinforced concrete plates. The structure is base isolated by its placement on special rubber bearings incorporated between the foundation structure and the first floor slab. (Fig.1) [8] There are a total of 54 bearings made of natural rubber, with a square shape, a side of 0.7 m and a height of 0.35 m. Each bearing transfers an axial force amounting to approximately 455 kN. The Swiss firm HUBER-SUHNER from Zurich produced the rubber bearings. The isolators do not contain reinforcing steel plates. They are fabricated by gluing together several rubber layers. The vertical stiffness of such bearings is therefore not much greater than the horizontal one. In addition to the negative effect of the low vertical stiffness of the bearings on the possible rocking motion, there is another disadvantage of these bearings, which is the occurrence of large lateral deformations of the rubber bearings due to dead load effects. [1] Figure 1. Rubber bearings placed between the strip foundation and the building DYNAMIC TESTING OF THE PRIMARY SCHOOL "J.H. PESTALOZZI" Dynamic testing of the main (isolated) school building was performed by application of two independent testing methods: 2 1683
  • 3. Ambient vibration method - This method was used for fast obtaining of preliminary results on the dynamic characteristics - resonant frequencies and mode shapes of vibration of the tested structure. The vertical vibration of the structure obtained by this method was used as a referent one since the vibrators used for the forced vibration tests cannot induce vertical displacements. Forced vibration method - This method was applied to define some characteristic vibrations of the structure in both horizontal directions as well as the torsional one. To define the damping coefficients, two methods were used: (1) half-power bandwidth (frequency-response) method and (2) logarithmic decrement (time-response) method. The dynamic characteristics of the building were obtained for the state of reinforced concrete plates being removed from the seismic gap and free motion of the isolated building in all directions was enabled. [3,4] Fig. 2 displays the plan of the second storey of the structure with marked measuring points and position of vibration exciters by which it was excited during the forced vibration tests. Figure 2. Plan of the second storey of the tested structure with presentation of measuring points and position of the two vibration exciters Results From the Tests Performed by Applying the Ambient Vibration Method To define the resonant frequencies of the structure in both orthogonal directions - transverse (N-S) and longitudinal (E-W), and the vertical one, four Range Seismometers, Model SS-1 produced by Kinemetrics from USA were used as sensors. Seismometer was placed in the central part of the structure, at the level of the second storey, at point "C" (Fig. 2). Seismometers were placed at the ends of the structure (measuring points 1 and 5) and also at the level of the second storey to define the resonant frequencies of the torsional vibration. The Fourier amplitude spectra corresponding to the torsional vibrations of the structure were obtained by combining the signals from both seismometers. Fig. 3 shows the Fourier amplitude spectra recorded on the structure in the corresponding directions of vibrations from which the resonant frequencies were defined. For such defined resonant frequencies of the structure, the corresponding mode shapes were obtained. However, these and the mode shapes obtained by other measurements are not presented in this paper due to lack of space. 3 1683
  • 4. Figure 3. Fourier amplitude spectra on the isolated building recorded with the ambient vibration method Results From Tests Performed by Using the Forced Vibration Method In the process of testing, the resonant frequencies of the structure were first of all defined for both orthogonal directions (N- S) and (E-W) and then for torsion. The structural response to the generated excitation, while defining the resonant frequencies for the N-S and E-W directions, was recorded at several measuring points. The recorded responses at the points located in the midst of the structure (point "C" or point "3") were considered referent. The referent point for definition of the torsional resonant frequencies was point "5" on the east side of the structure. Based on the recorded amplitudes of the response of the structure to the generated excitations, the corresponding resonant frequency curves were established. (Fig. 4) Certain tests performed for definition of the same frequency were carried out by different excitation forces for the purpose of evaluating the relation between modification of the resonant frequency and the excitation intensity. Figure 4. Resonant curves of the structural response obtained with the force excitation method 4 1683
  • 5. Due to the flexibility of the isolators, some of the mode shapes could quite well be excited and even visually observed. Therefore, apart from using accelerometers, which is the usual practice in performing these tests, displacement-meters (LVDT-s) were also used. The frequency curves presented in Fig. 4 were established based on the recorded amplitudes of structural response to the generated excitations. For such defined resonant frequencies, the corresponding mode shapes of vibration were also recorded. 3-D EIGENPAIR ANALYSIS For both cases of support of the school building, the eigen values and the eigen vectors were computed. First, the fundamental vibrations of the school fixed at its base were computed. Then, the fundamental frequencies and the corresponding mode shapes of the school building placed on rubber bearings were obtained. The finite elements mesh for both analyses was the same. Description of the Finite Element Model The analyses of the mathematical model of the "Pestalozzi" primary school building has been done by means of the SAP2000 computer programme. [7] The structure itself has been modelled by a total number of 7189 "SHELL" elements. Due to the size of the model, the individual structural elements: floor slabs, bearing walls in both orthogonal directions, staircase slabs, parapet walls and alike have been modelled separately. Then the structure has been assembled as a whole by means of "welding" of the joints that share the same location. The rubber bearings supporting the structure have been modelled by a total of 54 "NLLINK" elements. These have been taken as one-joint grounded spring, and they are of the type of biaxial base isolators. During the analysis of this model, it has been necessary to solve 43596 equilibrium equations. Such a refined model (with a large number of finite elements) was used because the generation of the mesh was not time consuming, as were also the analyses. Such a model is necessary for further analyses when the stress state in the walls is to be analysed. Analysis of the School Building Model Fixed at its Base This analysis was necessary to be performed because of two reasons: (1) the fundamental frequencies of the fixed structure had to prove whether the base isolation of the structure is justified; (2) this analysis had to prove whether rigid-structure approximation is possible for the performance of a simpler analysis. Table 1 shows the eigen frequencies of the first fundamental modes of vibration obtained by this analysis. Analysis of the School Building Model on Rubber Isolators Precise determination of stiffness characteristics in lateral and vertical direction was not possible at present since force-displacement hysteretic loops of the installed rubber isolators were not available. Therefore, the approximate values of stiffness characteristics of isolators were obtained via the measured values of fundamental frequencies by using the following basic formula: 54 ∑k i =1 Bi = ω B M total 2 where: k_Bi - stiffness of i-th base isolator, ω_B - measured circular frequency of the base isolated building, and M_total - total mass of building structure and base isolators. 5 1683
  • 6. It is assumed that: (1) the structure is rigid (the fixed-base analysis (f_N-S = 12.97 Hz; f_E-W = 8.32 Hz did confirm this assumption), and (2) the mass is known (it can be computed from the given geometry and the bulk density of the concrete). However, it should be noted that the computation of the lateral stiffness in this way is partially compromised since the fundamental modes of vibration in both orthogonal directions are not purely translational, but there is also a rocking motion due to the low vertical stiffness of the isolators. Table 1 shows the eigen frequencies of the first fundamental modes of vibration, while the characteristics mode shapes are presented in Fig 5. a) Mode: 1, Period: 1.408 s, Frequency: 0.710 Hz, Dominant direction: N-S (transversal) b) Mode: 2, Period: 1.167 s, Frequency: 0.857 Hz, Dominant direction: E-W (longitudinal) c) Mode: 3, Period: 1.133 s, Frequency: 0.882 Hz, Dominant direction: torsional Fig 5 Characteristics mode shapes of the base isolated building model 6 1683
  • 7. DISCUSSION OF THE RESULTS OBTAINED THROUGH THE EXPERIMENTAL MEASUREMENTS AND ANALYTICAL PROCEDURES Based on the data obtained from the performed testing of the structure, the following is concluded: The values of the frequencies of the fundamental vibration modes in certain directions when the plates covering the seismic gap are removed are: for transverse direction (N-S): f_1f = 0.76 Hz (forced vibration tests) and f_1a = 0.96 Hz (ambient vibration tests); for torsion: f_2f = 0.84 Hz (forced vibration tests) and f_2a = 1.04 Hz (ambient vibration tests); for the longitudinal direction (E-W): f_3f = 0.88 Hz (forced vibration tests) and f_3a = 1.28 Hz (ambient vibration tests) and for vertical direction: f_5a = 2.56 Hz (ambient vibration tests). Apart from the fundamental vibration modes, some of the higher modes were recorded. The frequency of f_4f = 2.08 Hz represents the second natural frequency of the structure in the (N-S) direction, while f_6f= 3.20 Hz represents the second natural frequency at torsional excitation. The second natural frequency of the structure in the E-W direction is very close (almost equal) to the corresponding frequency at torsional excitation amounting to f = 3.20 Hz, i.e., f_7f= 3.28 Hz. The recorded higher frequencies of f_8f = 3.44 Hz, f_9f= 5.28 Hz, f_12f = 5.92 Hz in the transverse direction and f_10f = 5.28 Hz in the longitudinal direction, i.e., f_11f = 5.52 Hz at torsional vibrations are associated with some of the higher mode shapes of vibration of the structure. The frequencies and the corresponding damping measured by applying both methods are presented in Table 1. Table 1 Mode Experimental Testing Analytical No. Direction Ambient Forced vibration Fix Base Isolated f f Damping Damping f f [Hz] [Hz] [%] hp* [%] ld** [Hz] [Hz] 1 first (N-S) 0.96 0.76 3.8 3.5 12.97 0.71 2 first (E-W) 1.28 0.88 7.3 6.3 8.32 0.86 3 torsion 1.04 0.84 5.4 3.0 - 0.88 4 vertical 2.56 - - - - 1.87 *Half-power bandwidth method **Logarithmic decrement method Analysing the recorded mode shapes, it can be said that the translatory components dominate over the first two modes of vibration of the school building (f_1f = 0.76 Hz, f_2f = 0.88 Hz). Characteristic for the second vibration modes in E-W direction (f_4f = 2.08 Hz) and N-S direction (f_7f = 3.28 Hz) is the rocking motion which is more pronounced for the mode with a frequency of f_4f = 2.08 Hz. The experimentally measured mode shapes and those obtained analytically clearly point to the fact that the modes, in addition to the translation component, contain also the component of a rocking motion. The complex motions of the mode shapes result from the low vertical stiffness of the rubber bearings. Since the fundamental modes for the two horizontal directions are not purely translatory (there are rotation components), their frequencies are not identical. There occurs a difference of 15.8% in the values of their frequencies. The obtained results on damping presented in Table 1 point to similar damping obtained by both methods. The damping values lead to the conclusion that the internal damping of the bearing is small since the coefficients of viscous damping for the fundamental vibration modes are 3.5%, 3% and 6.3% of the critical one in the N-S and E-W directions as well as torsion respectively. The fundamental frequencies of the fixed base model do justify the performed isolation of the building. However, the first modes of vibration for both orthogonal directions f_N-S = 0.76 Hz; f_E-W = 0.88 Hz 7 1683
  • 8. obtained experimentally are far above the minimum frequency of f = 0.5 Hz which is necessary for the isolators in order that they be efficient. The mathematical discretization and analysis of the isolated structure has successfully been done since there is a good correlation between the analytical and experimental values of the fundamental frequencies and their mode shapes. However, evaluation of the efficiency of the base isolation could be made in the final phase of this project when two isolators shall be taken off and the hysteresis curves obtained in laboratory conditions. The final analyses shall be performed by use of these curves and shall lead to obtaining of the base shear and the maximum displacements. From the laboratory testing on the taken off bearings and the analyses, one could further conclude whether the old bearings are necessary to be replaced by new ones or whether it is only necessary to add dampers for dissipation of the input energy from the earthquake. ACKNOWLEDGMENT This paper is based on the investigations sponsored by the Macedonian – US Joint Fund in cooperation with the Macedonian Ministry of Science and US - NIST under project number 056/600. The authors are indebted to these two institutions for the correct evaluation of the necessity for these investigations. REFERENCES 1. Bridgestone corporation, 1991. Rubber technology for seismic isolation. Proc., 11th international conf. on struc. mech. in reactor technology: 45-56, Tokyo, Japan. 2. Garevski, M. & Kelly, M. J., 1996. Evaluation of the proper functioning of the rubber isolators of the primary school Pestalozzi in Skopje under strong earthquake. U.S.- Macedonian science and technology program-project proposal. 3. Garevski, M., Kelly, M. J. & Bojadziev, M.,1998. Evaluation of the proper functioning of the rubber isolators of the primary school Pestalozzi in Skopje under strong earthquake: part I- Full-scale dynamic testing of the first rubber base-isolated building in the world. Report IZIIS. 4. Garevski, M., Kelly, J. M. & Bojadziev, M., 1998. Experimental dynamic tests on the first structure in the world isolated with rubber bearings. 11th European Conference on Earthquake Engineering, Paris, France 5. Izumi, M., 1988. Base isolation and passive seismic response control. Proc., 9th world conference on earthquake engineering, vol. VII: 386-396,Tokyo-Kyoto, Japan,. 6. Kelly, J.M., 1981. The Development of base isolation for the seismic protection of structures. Report No. UCB/EERC-81/01, Earthquake Engineering Research Center, University of California, Berkeley, California. 7. SAP2000 Integrated Finite Element Analysis and Design of Structures; Analysis Reference, Vol. 1 & 2; Computers and Structures, Inc; Berkeley, California, USA 8. Staudacher, K., 1982. The Swiss full base isolation system (3D) for extreme earthquake safety of structures. Proc. of the 1982 convention of the structural engineering association of California, Sacramento, California. 8 1683