International Journal of Computational Engineering Research||Vol, 03||Issue, 6||
www.ijceronline.com ||June ||2013|| Page 53
Harmonic Analysis and Power Factor Correction For Food
Processing Industry
Rupali Shinde1
, Amit Pathak2 ,
Bhakti Chaughule3
1,2,3,
M.Tech Pursuer (Power System), Bharati Vidyapeeth University’s college of engg, Pune.
I. INTRODUCTION
It is the objective of the electric utility to supply its customers with a sinusoidal voltage of fairly
constant magnitude and frequency. To ensure compliance with the Grid Code [2] voltage and current distortion
levels must satisfy limits set out by IEC 61000-3-6 [5]. In any industry, the three top operating expenses are
often found to be on energy, labor and materials. If one were to find out the potential cost savings in each of the
components, energy would invariably emerge at the top, and thus energy management function constitutes a
strategic area for cost reduction. . Industries use a large amount of electrical energy, and that is why it is
important to ensure a loss-free and energy-efficient system in industries [3]. In developing countries like India,
where electrical energy resources are scarce and production of electricity is very costly, energy conservation
studies are of great importance. Energy audit is the translation of conservation ideas into realities by blending
technically feasible solutions with economic and other organizational considerations within a specified time
frame [4]. An energy audit is a study of a plant or facility to determine how and where energy is used and to
identify methods for energy savings. An energy audit was carried out under four major heads: (i) process section
audit, (ii) Refrigeration section audit, (iii) power load audit (motors, compressor, etc.), and (iv) harmonic
analysis. Readings were taken under these heads and analyzed to find the scope of energy conservation
opportunities in the selected test case industrial unit.
II. AUDITING PROCEDURE
Energy audit cannot be successfully carried out without the commitment from the top management.
Management must be firstly convinced of the necessity of implementing energy management and hence energy
audit [7] . Energy audit consists of several tasks, which can be carried out depending on the type of the audit and
the size and the function of the audited facility [8] . Therefore, an energy audit is not a linear process and is
rather iterative. The audit described in this paper has been carried out based on the following functional
activities:
 Walk-through survey
 Motor load survey used in various processes
 Harmonic analysis
ABSTRACT
Harmonic analysis of the distribution system is essential to study the behavior of equipments
connected in the non-sinusoidal system environment for designing and optimal location of filters.
Harmonic distortion can have a significant impact on industrial customers such as additional losses and
heating of certain network equipment, faulty operation of control equipment and interference in
neighboring telecommunication system. In this case study harmonic analysis of food processing
industry has done using harmonic analyzer ‘YOKOGAVA’. The aim of the study was to improve the
power factor, maintain harmonic distortion within acceptable levels and reduce possible resonance
problem at the plant. Analysis of voltage and current harmonics is performed at distribution side point
of common coupling before and after connecting APFC panel.
KEY WORDS: APFC Panel, Energy Audit, Harmonics, Nonlinear load, Total Harmonic Distortion,
Under loaded motors, Yokogava.
Harmonic Analysis And Power…
www.ijceronline.com ||June ||2013|| Page 54
III. FIELD VISITS AND MEASUREMENT WORK
Katraj Dairy is one of the oldest milk processing industry in Pune, Maharashtra. Readings for harmonic
distortion and and for power factor improvement are taken with the help of YOKOGAWA(Harmonic Analyser)
before and after connecting APFC Pannal.
3.1 Plant Electrical Energy Consumption
The energy consumption of the industry was identified in terms of the equipments and functional area
wise. The results were obtained after measurements during the factory visits. Power analyzers, Harmonic
Analyzer, clamp meters, etc. were used to measure the electrical energy consumption of the industry. The total
load of the unit is approximately 1326.3 kW .
TABLE.1 Total load of Katraj Dairy
1
2
3
4
5
6
7
8
Fig.1Load division chart of Katraj Dairy
Sr.no Sections Connected load in HP
1 Air compressor section 182
2 Process section 349.5
3 Refrigeration section 882
4 Boiler section 120
5 E.T.P. section 180
6 Raw water sector 30
7 Ice cream plant 10
8 Illumination 15
Total load in HP 1768.5
Total load in KW 1326.3
Harmonic Analysis And Power…
www.ijceronline.com ||June ||2013|| Page 55
The following points can be observed from this survey:
 The major load in the plant is that of refrigeration, which constitutes approximately 66 % of the total load.
 Motor load constitutes approximately 38% of the total load.
 Total number of units consumed per month is 188380 after taking the average of 12 months.
3.3 Motor Survey
For most of the applications, three-phase, 4-pole, 1470- rpm induction motors of Kirloskar make have
been used for various production processes in the plant. During survey and measurement process, it was
observed that some of the motors are underloaded. And most of the motors used are energy efficient motors.
Load on compressor where 45 KW,1460 rpm, 415V,80 amp,3ph,50 Hz motor is used is continuously varying
between 40amp to 80 amp. Other motors have almost constant load on them.
3.4 Problems with Underloaded Motor
 An underloaded motor always runs at a low lagging power factor. If the motor is loaded around 50% of
the rated load, power factor can be as low as 0.5 lagging. This means industry is utilizing only 50% of the
power from the supply mains and paying for 100% if the billing is kVA based.
 Extra expenditure on installation of power factor improvement equipment to maintain the power factor
within permissible limits set by the state electricity board needs to be done. Otherwise, penalty has to be
paid.
 Efficiency of a standard induction motor is about 87-90% at the rated load and it reduces drastically at
half of the rated load depending upon the size of the motor and loading (about 70-75% for 60 hp
motor). This means motor will draw more current for the same mechanical output
IV. ENERGY-EFFICIENT MOTORS
More and more industries are switching to energy-efficient motors (EEMs) because EEMs lower the
production costs. Just a small increase in motor efficiency can significantly lower the production costs. A motor
can cost thousands of rupees a year to operate, so savings of even a few percent add up quickly. An EEM
generates savings whenever it is running and as long as it lasts, which may be 20 years or more. EEMs cost
more than the standard motors, but purchase price can be paled in comparison to a motor's operating costs. Since
the annual operating cost of a motor is often 5-10 times its initial cost, the typical 3-5% higher efficiency of an
EEM can more than offset its 15-20% higher initial cost over its life. In addition to costing less to operate,
EEMs generally last longer, require less maintenance, and reduce system amperage draw. The efficiency curves
of two EEMs are shown
Figure 2: Efficiency of EEMs as per IS-12615 (Eff1 = 2-pole motor, Eff2 = 4-pole motor)
EEMs also offer other advantages, such as longer insulation life, longer lubrication interval, greater inertial
acceleration, and higher service factors. In addition, they may be better equipped to handle heavy starting loads,
large sustained loads, phase imbalances, voltage excursions, high ambient temperatures, and impaired
ventilation. EEMs also do not add as much to air-conditioning loads as standard motors, since they do not give
off as much heat.
Harmonic Analysis And Power…
www.ijceronline.com ||June ||2013|| Page 56
4.1 Energy-efficient Motor's Performance
The efficiency of a motor is the ratio of the mechanical power output to the electrical power input.
Design changes, better materials, and manufacturing improvements reduce motor losses, making premium or
EEMs more efficient than the standard motors [Figure 2]. Reduced losses mean that an EEM produces a given
amount of work with less energy input than a standard motor. In 1989, the National Electrical Manufacturers
Association (NEMA) developed a standard definition for EEMs [10]
. The definition was designed to help users
identify and compare electric motor efficiencies on an equal basis.
Figure 3: Losses comparison among standard and high efficiency motors [14]
V. Harmonic Analysis
Harmonics are one of the major concerns in a power system. Harmonics cause distortion in current and
voltage waveforms resulting into deterioration of the power system. The first step for harmonic analysis is the
harmonics from non-linear loads. The results of such analysis are complex. Over many years, much importance
is given to the methods of analysis and control of harmonics. Harmonics present in power system also has non-
integer multiples of the fundamental frequency and have aperiodic waveform. The harmonics are generated in a
power system from two distinct types of loads.
First category of loads are described as linear loads. The linear time-invariant loads are
characterized such that application of sinusoidal voltage results in sinusoidal flow of current. A constant steady-
impedance is displayed from these loads during the applied sinusoidal voltage. As the voltage and current are
directly proportional to each other, if voltage is increased it will also result into increase in the current. An
example of such a load is incandescent lighting. Even if the flux wave in air gap of rotating machine is not
sinusoidal, under normal loading conditions transformers and rotation machines pretty much meet this
definition. Also, in a transformer the current contains odd and even harmonics including a dc component. More
and more use of magnetic circuits over a period of time may get saturated and result into generation of
harmonics. In power systems, synchronous generators produce sinusoidal voltages and the loads draw
sinusoidal currents. In this case, the harmonic distortion is produced because of the linear load types for
sinusoidal voltage is small.
Non-linear loads are considered as the second category of loads. The application of sinusoidal voltage
does not result in a sinusoidal flow applied sinusoidal voltage for a non-linear devices. The non-linear loads
draw a current that may be discontinuous. Harmonic current is isolated by using harmonic filters in order to
protect the electrical equipment from getting damaged due to harmonic voltage distortion. They can also be
used to improve the power factor. The harmful and damaging effects of harmonic distortion can be evident in
many different ways such as electronics miss-timings, increased heating effect in electrical equipments,
capacitor overloads, etc. There can be two types of filters that are used in order to reduce the harmonic
distortion i.e. the active filters and the passive filters. Active harmonic filters are electronic devices that
eliminate the undesirable harmonics on the network by inserting negative harmonics into the network. The goal
of harmonic studies is to quantify the distortion in voltage and current waveforms in the power system of
industrial units. The results are useful for evaluating corrective measures and troubleshooting harmonic related
problems.
Harmonic Analysis And Power…
www.ijceronline.com ||June ||2013|| Page 57
5.1 Effects of Harmonics on Networks [10]
 Overloading of neutral conductor
 Reduced efficiency of motors
 Malfunctioning of control equipment
 Poor power factor of the total system due to introduction of distortion power factor
 Overloading of power factor capacitors
 Increase in kVA demand of the plant due to increase in rms current drawn
VI. RESULTS:
Following results are obtained before after connecting APFC panel.
Total consumption for FEB- 2013 is 139300.
KVA demand is 419. MSEB charges 190Rs. Per KVA for industrial load.
Total electricity bill including (TOD tariff, Electricity Duty and other charges) is 10,36,033.06 Rs.
They are getting power factor incentive 67,848.40Rs.
Total current bill is 9,68,184.66 Rs.
Figure (4) Without APFC panel connected THD = 9.1 %
Figure (5) With APFC panel with the system THD = 2.3 %
Harmonic Analysis And Power…
www.ijceronline.com ||June ||2013|| Page 58
VII. CONCLUSION
On the basis of Harmonic analysis study & electrical energy audit conducted, the following
recommendations have been suggested to the consumer:
 In due course of time, if any motor gets damaged or some new motor is to be purchased, EEMs should be
purchased.
 Harmonic components at PCC are greater than the permissible limits. Therefore, the consumer must install
harmonic filter to improve the power quality and save the penalty on harmonic emission.
 Harmonic component across individual loads is much higher where variable frequency drives are used,
which reflects at the PCC, so a more in-depth analysis is required and a harmonic filter can be designed.
 It is also shown in this paper that the proposed PFC capacitor banks can be tuned to act as harmonic filters
and operate to reduce the harmonic distortion to acceptable levels. It is recommended that the PFC
capacitor banks be tuned to act as harmonic filters and also that upon completion of the plant expansion
harmonic measurement are taken to meet the grid code requirement. Proper size of motor should be used, as
per the rated load. If possible, motor should be replaced with a proper size motor in a phased manner.
REFERENCE
[1] Modeling And Harmonic Analysis Of Domestic/Industrial Loads Purushothama Rao Nasini, Narender Reddy Narra and Santosh
AEirgrid Grid Code, V.3.1
[2] P. Z. Yaacoh, and A. A. Mohd. Zin, "Electical energy management in small and medium size industries", IEEE TENCON,
Beijing, 1993.
[3] Thumann, and W. J. Yonger, "Hand Book of Energy Audits", 7 th
ed, Lilburn: Fairmont Press Inc.; 2007.
[4] IEC 61000-3-6 - Electromagnetic compatibility (EMC) -Part 3-6: Limits - Assessment of harmonic emission limits for the
connection of distorting installations to MV, HV and EHV power systems.
[5] Huyck, and J. Cappelle, "Electrical energy management for low-voltage clients", International Conference on Clean Electrical
Power, IEEE, 2007.
[6] X. W. Chen, "Energy Audit of Building: A Case Study of A Commercial Building in Shanghai", Power and Energy Engineering
Conference, Asia-Pacific, 2010.
[7] Tyagi, "Hand Book of Energy Audit & Management" India: TERI Press; 2000.
[8] Catalouge Surelink Technologies" Shenzhen, China, 2008
[9] "IEEE recommended practice for electric power systems in commercial buildings", Recognized as an American National
Standard (ANSI) IEEE Standard, pp. 241, 1990.
Rupali shinde-M.Tech Electrical Power System (Pursuing), Department of Electrical
Engineering, Bharati Vidhyapeeth University’s College of Engineering, Pune, India.
Amit pathak - M.Tech Electrical Power System (Pursuing), Department of Electrical
Engineering, Bharati Vidhyapeeth University’s College of Engineering, Pune, India.
Bhakti Chaughule- M.Tech Electrical Power System (Pursuing), Department of
Electrical Engineering, Bharati Vidhyapeeth University’s College of Engineering, Pune,
India.

Más contenido relacionado

La actualidad más candente

Protection schemes
Protection schemesProtection schemes
Protection schemesv Kalairajan
 
Load on power system
Load on power systemLoad on power system
Load on power systemv Kalairajan
 
Lead acid battery management system for electrical vehicles
Lead acid battery management system for electrical vehiclesLead acid battery management system for electrical vehicles
Lead acid battery management system for electrical vehiclesIAEME Publication
 
ASYNCHRONOUS DRIVE CONTROL OF A TRACTION VEHICLE USING TCMS SYSTEM
ASYNCHRONOUS DRIVE CONTROL OF A TRACTION VEHICLE USING TCMS SYSTEMASYNCHRONOUS DRIVE CONTROL OF A TRACTION VEHICLE USING TCMS SYSTEM
ASYNCHRONOUS DRIVE CONTROL OF A TRACTION VEHICLE USING TCMS SYSTEMIAEME Publication
 
Speed Control of Three Phase Induction Motor Using PLC under Open and Closed ...
Speed Control of Three Phase Induction Motor Using PLC under Open and Closed ...Speed Control of Three Phase Induction Motor Using PLC under Open and Closed ...
Speed Control of Three Phase Induction Motor Using PLC under Open and Closed ...IJERA Editor
 
A NEW APPROACH TO DTC METHOD FOR BLDC MOTOR ADJUSTABLE SPEED DRIVES
A NEW APPROACH TO DTC METHOD FOR BLDC MOTOR ADJUSTABLE SPEED DRIVESA NEW APPROACH TO DTC METHOD FOR BLDC MOTOR ADJUSTABLE SPEED DRIVES
A NEW APPROACH TO DTC METHOD FOR BLDC MOTOR ADJUSTABLE SPEED DRIVEScscpconf
 
DATA DRIVEN ANALYSIS OF ENERGY MANAGEMENT IN ELECTRIC VEHICLES
DATA DRIVEN ANALYSIS OF ENERGY MANAGEMENT IN ELECTRIC VEHICLESDATA DRIVEN ANALYSIS OF ENERGY MANAGEMENT IN ELECTRIC VEHICLES
DATA DRIVEN ANALYSIS OF ENERGY MANAGEMENT IN ELECTRIC VEHICLESvivatechijri
 
Comprehensive Motor Testing Technique
Comprehensive Motor Testing TechniqueComprehensive Motor Testing Technique
Comprehensive Motor Testing TechniqueAvinash Sista
 
Smfir technology based transportation system and applicability of mppt
Smfir technology based transportation system and applicability of mpptSmfir technology based transportation system and applicability of mppt
Smfir technology based transportation system and applicability of mppteSAT Publishing House
 
Efficient speed governor for blower motor
Efficient speed governor for blower motorEfficient speed governor for blower motor
Efficient speed governor for blower motoreSAT Publishing House
 
A Novel Technique for Tuning PI-controller in Switched Reluctance Motor Drive...
A Novel Technique for Tuning PI-controller in Switched Reluctance Motor Drive...A Novel Technique for Tuning PI-controller in Switched Reluctance Motor Drive...
A Novel Technique for Tuning PI-controller in Switched Reluctance Motor Drive...IJECEIAES
 
Battery Energy Management
Battery Energy ManagementBattery Energy Management
Battery Energy ManagementGlen Carvalho
 
Test platform for electronic control units of high-performance safety-critica...
Test platform for electronic control units of high-performance safety-critica...Test platform for electronic control units of high-performance safety-critica...
Test platform for electronic control units of high-performance safety-critica...IJECEIAES
 
Analysis of vehicle power supply systems using system simulation
Analysis of vehicle power supply systems using system simulationAnalysis of vehicle power supply systems using system simulation
Analysis of vehicle power supply systems using system simulationIsabelle Cantuel
 
Maxon presentation sizing drive systems with low power dc motors 02-2014
Maxon presentation   sizing drive systems with low power dc motors 02-2014Maxon presentation   sizing drive systems with low power dc motors 02-2014
Maxon presentation sizing drive systems with low power dc motors 02-2014Electromate
 

La actualidad más candente (20)

Protection schemes
Protection schemesProtection schemes
Protection schemes
 
Load on power system
Load on power systemLoad on power system
Load on power system
 
Lead acid battery management system for electrical vehicles
Lead acid battery management system for electrical vehiclesLead acid battery management system for electrical vehicles
Lead acid battery management system for electrical vehicles
 
ASYNCHRONOUS DRIVE CONTROL OF A TRACTION VEHICLE USING TCMS SYSTEM
ASYNCHRONOUS DRIVE CONTROL OF A TRACTION VEHICLE USING TCMS SYSTEMASYNCHRONOUS DRIVE CONTROL OF A TRACTION VEHICLE USING TCMS SYSTEM
ASYNCHRONOUS DRIVE CONTROL OF A TRACTION VEHICLE USING TCMS SYSTEM
 
Speed Control of Three Phase Induction Motor Using PLC under Open and Closed ...
Speed Control of Three Phase Induction Motor Using PLC under Open and Closed ...Speed Control of Three Phase Induction Motor Using PLC under Open and Closed ...
Speed Control of Three Phase Induction Motor Using PLC under Open and Closed ...
 
A NEW APPROACH TO DTC METHOD FOR BLDC MOTOR ADJUSTABLE SPEED DRIVES
A NEW APPROACH TO DTC METHOD FOR BLDC MOTOR ADJUSTABLE SPEED DRIVESA NEW APPROACH TO DTC METHOD FOR BLDC MOTOR ADJUSTABLE SPEED DRIVES
A NEW APPROACH TO DTC METHOD FOR BLDC MOTOR ADJUSTABLE SPEED DRIVES
 
DATA DRIVEN ANALYSIS OF ENERGY MANAGEMENT IN ELECTRIC VEHICLES
DATA DRIVEN ANALYSIS OF ENERGY MANAGEMENT IN ELECTRIC VEHICLESDATA DRIVEN ANALYSIS OF ENERGY MANAGEMENT IN ELECTRIC VEHICLES
DATA DRIVEN ANALYSIS OF ENERGY MANAGEMENT IN ELECTRIC VEHICLES
 
Applied measurement of the motor speed controller for washing machine with ra...
Applied measurement of the motor speed controller for washing machine with ra...Applied measurement of the motor speed controller for washing machine with ra...
Applied measurement of the motor speed controller for washing machine with ra...
 
H045045059
H045045059H045045059
H045045059
 
New DTC strategy of multi-machines single-inverter systems for electric vehic...
New DTC strategy of multi-machines single-inverter systems for electric vehic...New DTC strategy of multi-machines single-inverter systems for electric vehic...
New DTC strategy of multi-machines single-inverter systems for electric vehic...
 
Ijeet 06 08_009
Ijeet 06 08_009Ijeet 06 08_009
Ijeet 06 08_009
 
Comprehensive Motor Testing Technique
Comprehensive Motor Testing TechniqueComprehensive Motor Testing Technique
Comprehensive Motor Testing Technique
 
Smfir technology based transportation system and applicability of mppt
Smfir technology based transportation system and applicability of mpptSmfir technology based transportation system and applicability of mppt
Smfir technology based transportation system and applicability of mppt
 
Efficient speed governor for blower motor
Efficient speed governor for blower motorEfficient speed governor for blower motor
Efficient speed governor for blower motor
 
Experimental Comparison between Four and Six Switch Inverters Fed FLC Based S...
Experimental Comparison between Four and Six Switch Inverters Fed FLC Based S...Experimental Comparison between Four and Six Switch Inverters Fed FLC Based S...
Experimental Comparison between Four and Six Switch Inverters Fed FLC Based S...
 
A Novel Technique for Tuning PI-controller in Switched Reluctance Motor Drive...
A Novel Technique for Tuning PI-controller in Switched Reluctance Motor Drive...A Novel Technique for Tuning PI-controller in Switched Reluctance Motor Drive...
A Novel Technique for Tuning PI-controller in Switched Reluctance Motor Drive...
 
Battery Energy Management
Battery Energy ManagementBattery Energy Management
Battery Energy Management
 
Test platform for electronic control units of high-performance safety-critica...
Test platform for electronic control units of high-performance safety-critica...Test platform for electronic control units of high-performance safety-critica...
Test platform for electronic control units of high-performance safety-critica...
 
Analysis of vehicle power supply systems using system simulation
Analysis of vehicle power supply systems using system simulationAnalysis of vehicle power supply systems using system simulation
Analysis of vehicle power supply systems using system simulation
 
Maxon presentation sizing drive systems with low power dc motors 02-2014
Maxon presentation   sizing drive systems with low power dc motors 02-2014Maxon presentation   sizing drive systems with low power dc motors 02-2014
Maxon presentation sizing drive systems with low power dc motors 02-2014
 

Destacado

Sociales presentacion
Sociales presentacionSociales presentacion
Sociales presentacionemma-r-s
 
우리들만의 리그 사업계획서
우리들만의 리그 사업계획서우리들만의 리그 사업계획서
우리들만의 리그 사업계획서Sang-hoon Choi
 
Solar energy and its applcations
Solar energy and its applcationsSolar energy and its applcations
Solar energy and its applcationssaiganesh seku
 
.Organizational Strategy and Information Systems
.Organizational Strategy and Information Systems.Organizational Strategy and Information Systems
.Organizational Strategy and Information SystemsLauren Riley
 

Destacado (8)

Sociales presentacion
Sociales presentacionSociales presentacion
Sociales presentacion
 
우리들만의 리그 사업계획서
우리들만의 리그 사업계획서우리들만의 리그 사업계획서
우리들만의 리그 사업계획서
 
Ebola br
Ebola   brEbola   br
Ebola br
 
H0361039052
H0361039052H0361039052
H0361039052
 
Solar energy and its applcations
Solar energy and its applcationsSolar energy and its applcations
Solar energy and its applcations
 
.Organizational Strategy and Information Systems
.Organizational Strategy and Information Systems.Organizational Strategy and Information Systems
.Organizational Strategy and Information Systems
 
qbrownresume
qbrownresumeqbrownresume
qbrownresume
 
Movimiento
MovimientoMovimiento
Movimiento
 

Similar a I0361053058

A Review on Energy Consumption Monitoring and Analysis System
A Review on Energy Consumption Monitoring and Analysis SystemA Review on Energy Consumption Monitoring and Analysis System
A Review on Energy Consumption Monitoring and Analysis SystemIRJET Journal
 
Consideration of reactive energy in the tariff structure
Consideration of reactive energy in the tariff structureConsideration of reactive energy in the tariff structure
Consideration of reactive energy in the tariff structureIAEME Publication
 
IRJET- Analysis of Load Frequency Control for a Distributed Grid System Invol...
IRJET- Analysis of Load Frequency Control for a Distributed Grid System Invol...IRJET- Analysis of Load Frequency Control for a Distributed Grid System Invol...
IRJET- Analysis of Load Frequency Control for a Distributed Grid System Invol...IRJET Journal
 
A Comparative Study of GA tuned and PSO tuned PI Controller Based Speed Contr...
A Comparative Study of GA tuned and PSO tuned PI Controller Based Speed Contr...A Comparative Study of GA tuned and PSO tuned PI Controller Based Speed Contr...
A Comparative Study of GA tuned and PSO tuned PI Controller Based Speed Contr...paperpublications3
 
IRJET- Regenerative System and it’s Application
IRJET- Regenerative System and it’s ApplicationIRJET- Regenerative System and it’s Application
IRJET- Regenerative System and it’s ApplicationIRJET Journal
 
IRJET- STATCOM based Control Scheme for Power Quality Improvement in Grid-Con...
IRJET- STATCOM based Control Scheme for Power Quality Improvement in Grid-Con...IRJET- STATCOM based Control Scheme for Power Quality Improvement in Grid-Con...
IRJET- STATCOM based Control Scheme for Power Quality Improvement in Grid-Con...IRJET Journal
 
Development of Battery Management System for Maximizing Battery Performance i...
Development of Battery Management System for Maximizing Battery Performance i...Development of Battery Management System for Maximizing Battery Performance i...
Development of Battery Management System for Maximizing Battery Performance i...IRJET Journal
 
Power Factor Control at ABA Control 33/11kV Injection Substation Using Auto T...
Power Factor Control at ABA Control 33/11kV Injection Substation Using Auto T...Power Factor Control at ABA Control 33/11kV Injection Substation Using Auto T...
Power Factor Control at ABA Control 33/11kV Injection Substation Using Auto T...IRJET Journal
 
Energy Audit of a Food Industry
Energy Audit of a Food IndustryEnergy Audit of a Food Industry
Energy Audit of a Food IndustryIJMER
 
A Review on Electric Vehicle Powertrain System Components and the Challenges ...
A Review on Electric Vehicle Powertrain System Components and the Challenges ...A Review on Electric Vehicle Powertrain System Components and the Challenges ...
A Review on Electric Vehicle Powertrain System Components and the Challenges ...IRJET Journal
 
IRJET- Optimal Performance of Mechanical Load Factor for the Solar Photovolta...
IRJET- Optimal Performance of Mechanical Load Factor for the Solar Photovolta...IRJET- Optimal Performance of Mechanical Load Factor for the Solar Photovolta...
IRJET- Optimal Performance of Mechanical Load Factor for the Solar Photovolta...IRJET Journal
 
Enhancement of reactive power capability of doubly fed induction generator 2-3
Enhancement of reactive power capability of doubly fed induction generator 2-3Enhancement of reactive power capability of doubly fed induction generator 2-3
Enhancement of reactive power capability of doubly fed induction generator 2-3IAEME Publication
 
IRJET- Design, Implementation & Analysis of Three Phase Asynchronous Indu...
IRJET-  	  Design, Implementation & Analysis of Three Phase Asynchronous Indu...IRJET-  	  Design, Implementation & Analysis of Three Phase Asynchronous Indu...
IRJET- Design, Implementation & Analysis of Three Phase Asynchronous Indu...IRJET Journal
 
Harmonic Distortion Evaluation Generated by PWM Motor Drives in Electrical In...
Harmonic Distortion Evaluation Generated by PWM Motor Drives in Electrical In...Harmonic Distortion Evaluation Generated by PWM Motor Drives in Electrical In...
Harmonic Distortion Evaluation Generated by PWM Motor Drives in Electrical In...IJECEIAES
 

Similar a I0361053058 (20)

Presentation tahir
Presentation tahirPresentation tahir
Presentation tahir
 
Bg4201393395
Bg4201393395Bg4201393395
Bg4201393395
 
Loss minimization DTC electric motor drive system based on adaptive ANN strategy
Loss minimization DTC electric motor drive system based on adaptive ANN strategyLoss minimization DTC electric motor drive system based on adaptive ANN strategy
Loss minimization DTC electric motor drive system based on adaptive ANN strategy
 
Big Presentation
Big PresentationBig Presentation
Big Presentation
 
A Review on Energy Consumption Monitoring and Analysis System
A Review on Energy Consumption Monitoring and Analysis SystemA Review on Energy Consumption Monitoring and Analysis System
A Review on Energy Consumption Monitoring and Analysis System
 
Consideration of reactive energy in the tariff structure
Consideration of reactive energy in the tariff structureConsideration of reactive energy in the tariff structure
Consideration of reactive energy in the tariff structure
 
IRJET- Analysis of Load Frequency Control for a Distributed Grid System Invol...
IRJET- Analysis of Load Frequency Control for a Distributed Grid System Invol...IRJET- Analysis of Load Frequency Control for a Distributed Grid System Invol...
IRJET- Analysis of Load Frequency Control for a Distributed Grid System Invol...
 
A Comparative Study of GA tuned and PSO tuned PI Controller Based Speed Contr...
A Comparative Study of GA tuned and PSO tuned PI Controller Based Speed Contr...A Comparative Study of GA tuned and PSO tuned PI Controller Based Speed Contr...
A Comparative Study of GA tuned and PSO tuned PI Controller Based Speed Contr...
 
IRJET- Regenerative System and it’s Application
IRJET- Regenerative System and it’s ApplicationIRJET- Regenerative System and it’s Application
IRJET- Regenerative System and it’s Application
 
IRJET- STATCOM based Control Scheme for Power Quality Improvement in Grid-Con...
IRJET- STATCOM based Control Scheme for Power Quality Improvement in Grid-Con...IRJET- STATCOM based Control Scheme for Power Quality Improvement in Grid-Con...
IRJET- STATCOM based Control Scheme for Power Quality Improvement in Grid-Con...
 
mehtodalgy.docx
mehtodalgy.docxmehtodalgy.docx
mehtodalgy.docx
 
Development of Battery Management System for Maximizing Battery Performance i...
Development of Battery Management System for Maximizing Battery Performance i...Development of Battery Management System for Maximizing Battery Performance i...
Development of Battery Management System for Maximizing Battery Performance i...
 
Power Factor Control at ABA Control 33/11kV Injection Substation Using Auto T...
Power Factor Control at ABA Control 33/11kV Injection Substation Using Auto T...Power Factor Control at ABA Control 33/11kV Injection Substation Using Auto T...
Power Factor Control at ABA Control 33/11kV Injection Substation Using Auto T...
 
Energy Audit of a Food Industry
Energy Audit of a Food IndustryEnergy Audit of a Food Industry
Energy Audit of a Food Industry
 
A Review on Electric Vehicle Powertrain System Components and the Challenges ...
A Review on Electric Vehicle Powertrain System Components and the Challenges ...A Review on Electric Vehicle Powertrain System Components and the Challenges ...
A Review on Electric Vehicle Powertrain System Components and the Challenges ...
 
IRJET- Optimal Performance of Mechanical Load Factor for the Solar Photovolta...
IRJET- Optimal Performance of Mechanical Load Factor for the Solar Photovolta...IRJET- Optimal Performance of Mechanical Load Factor for the Solar Photovolta...
IRJET- Optimal Performance of Mechanical Load Factor for the Solar Photovolta...
 
Enhancement of reactive power capability of doubly fed induction generator 2-3
Enhancement of reactive power capability of doubly fed induction generator 2-3Enhancement of reactive power capability of doubly fed induction generator 2-3
Enhancement of reactive power capability of doubly fed induction generator 2-3
 
IRJET- Design, Implementation & Analysis of Three Phase Asynchronous Indu...
IRJET-  	  Design, Implementation & Analysis of Three Phase Asynchronous Indu...IRJET-  	  Design, Implementation & Analysis of Three Phase Asynchronous Indu...
IRJET- Design, Implementation & Analysis of Three Phase Asynchronous Indu...
 
UNIT-1-PPT.pptx
UNIT-1-PPT.pptxUNIT-1-PPT.pptx
UNIT-1-PPT.pptx
 
Harmonic Distortion Evaluation Generated by PWM Motor Drives in Electrical In...
Harmonic Distortion Evaluation Generated by PWM Motor Drives in Electrical In...Harmonic Distortion Evaluation Generated by PWM Motor Drives in Electrical In...
Harmonic Distortion Evaluation Generated by PWM Motor Drives in Electrical In...
 

Último

Lucknow 💋 Escorts in Lucknow - 450+ Call Girl Cash Payment 8923113531 Neha Th...
Lucknow 💋 Escorts in Lucknow - 450+ Call Girl Cash Payment 8923113531 Neha Th...Lucknow 💋 Escorts in Lucknow - 450+ Call Girl Cash Payment 8923113531 Neha Th...
Lucknow 💋 Escorts in Lucknow - 450+ Call Girl Cash Payment 8923113531 Neha Th...anilsa9823
 
Insurers' journeys to build a mastery in the IoT usage
Insurers' journeys to build a mastery in the IoT usageInsurers' journeys to build a mastery in the IoT usage
Insurers' journeys to build a mastery in the IoT usageMatteo Carbone
 
FULL ENJOY Call Girls In Majnu Ka Tilla, Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Majnu Ka Tilla, Delhi Contact Us 8377877756FULL ENJOY Call Girls In Majnu Ka Tilla, Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Majnu Ka Tilla, Delhi Contact Us 8377877756dollysharma2066
 
Call Girls in Gomti Nagar - 7388211116 - With room Service
Call Girls in Gomti Nagar - 7388211116  - With room ServiceCall Girls in Gomti Nagar - 7388211116  - With room Service
Call Girls in Gomti Nagar - 7388211116 - With room Servicediscovermytutordmt
 
KYC-Verified Accounts: Helping Companies Handle Challenging Regulatory Enviro...
KYC-Verified Accounts: Helping Companies Handle Challenging Regulatory Enviro...KYC-Verified Accounts: Helping Companies Handle Challenging Regulatory Enviro...
KYC-Verified Accounts: Helping Companies Handle Challenging Regulatory Enviro...Any kyc Account
 
It will be International Nurses' Day on 12 May
It will be International Nurses' Day on 12 MayIt will be International Nurses' Day on 12 May
It will be International Nurses' Day on 12 MayNZSG
 
Mondelez State of Snacking and Future Trends 2023
Mondelez State of Snacking and Future Trends 2023Mondelez State of Snacking and Future Trends 2023
Mondelez State of Snacking and Future Trends 2023Neil Kimberley
 
Yaroslav Rozhankivskyy: Три складові і три передумови максимальної продуктивн...
Yaroslav Rozhankivskyy: Три складові і три передумови максимальної продуктивн...Yaroslav Rozhankivskyy: Три складові і три передумови максимальної продуктивн...
Yaroslav Rozhankivskyy: Три складові і три передумови максимальної продуктивн...Lviv Startup Club
 
Call Girls Navi Mumbai Just Call 9907093804 Top Class Call Girl Service Avail...
Call Girls Navi Mumbai Just Call 9907093804 Top Class Call Girl Service Avail...Call Girls Navi Mumbai Just Call 9907093804 Top Class Call Girl Service Avail...
Call Girls Navi Mumbai Just Call 9907093804 Top Class Call Girl Service Avail...Dipal Arora
 
A DAY IN THE LIFE OF A SALESMAN / WOMAN
A DAY IN THE LIFE OF A  SALESMAN / WOMANA DAY IN THE LIFE OF A  SALESMAN / WOMAN
A DAY IN THE LIFE OF A SALESMAN / WOMANIlamathiKannappan
 
Enhancing and Restoring Safety & Quality Cultures - Dave Litwiller - May 2024...
Enhancing and Restoring Safety & Quality Cultures - Dave Litwiller - May 2024...Enhancing and Restoring Safety & Quality Cultures - Dave Litwiller - May 2024...
Enhancing and Restoring Safety & Quality Cultures - Dave Litwiller - May 2024...Dave Litwiller
 
Monthly Social Media Update April 2024 pptx.pptx
Monthly Social Media Update April 2024 pptx.pptxMonthly Social Media Update April 2024 pptx.pptx
Monthly Social Media Update April 2024 pptx.pptxAndy Lambert
 
Best VIP Call Girls Noida Sector 40 Call Me: 8448380779
Best VIP Call Girls Noida Sector 40 Call Me: 8448380779Best VIP Call Girls Noida Sector 40 Call Me: 8448380779
Best VIP Call Girls Noida Sector 40 Call Me: 8448380779Delhi Call girls
 
7.pdf This presentation captures many uses and the significance of the number...
7.pdf This presentation captures many uses and the significance of the number...7.pdf This presentation captures many uses and the significance of the number...
7.pdf This presentation captures many uses and the significance of the number...Paul Menig
 
Call Girls Hebbal Just Call 👗 7737669865 👗 Top Class Call Girl Service Bangalore
Call Girls Hebbal Just Call 👗 7737669865 👗 Top Class Call Girl Service BangaloreCall Girls Hebbal Just Call 👗 7737669865 👗 Top Class Call Girl Service Bangalore
Call Girls Hebbal Just Call 👗 7737669865 👗 Top Class Call Girl Service Bangaloreamitlee9823
 
Russian Call Girls In Gurgaon ❤️8448577510 ⊹Best Escorts Service In 24/7 Delh...
Russian Call Girls In Gurgaon ❤️8448577510 ⊹Best Escorts Service In 24/7 Delh...Russian Call Girls In Gurgaon ❤️8448577510 ⊹Best Escorts Service In 24/7 Delh...
Russian Call Girls In Gurgaon ❤️8448577510 ⊹Best Escorts Service In 24/7 Delh...lizamodels9
 
0183760ssssssssssssssssssssssssssss00101011 (27).pdf
0183760ssssssssssssssssssssssssssss00101011 (27).pdf0183760ssssssssssssssssssssssssssss00101011 (27).pdf
0183760ssssssssssssssssssssssssssss00101011 (27).pdfRenandantas16
 

Último (20)

Lucknow 💋 Escorts in Lucknow - 450+ Call Girl Cash Payment 8923113531 Neha Th...
Lucknow 💋 Escorts in Lucknow - 450+ Call Girl Cash Payment 8923113531 Neha Th...Lucknow 💋 Escorts in Lucknow - 450+ Call Girl Cash Payment 8923113531 Neha Th...
Lucknow 💋 Escorts in Lucknow - 450+ Call Girl Cash Payment 8923113531 Neha Th...
 
Insurers' journeys to build a mastery in the IoT usage
Insurers' journeys to build a mastery in the IoT usageInsurers' journeys to build a mastery in the IoT usage
Insurers' journeys to build a mastery in the IoT usage
 
FULL ENJOY Call Girls In Majnu Ka Tilla, Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Majnu Ka Tilla, Delhi Contact Us 8377877756FULL ENJOY Call Girls In Majnu Ka Tilla, Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Majnu Ka Tilla, Delhi Contact Us 8377877756
 
Call Girls in Gomti Nagar - 7388211116 - With room Service
Call Girls in Gomti Nagar - 7388211116  - With room ServiceCall Girls in Gomti Nagar - 7388211116  - With room Service
Call Girls in Gomti Nagar - 7388211116 - With room Service
 
KYC-Verified Accounts: Helping Companies Handle Challenging Regulatory Enviro...
KYC-Verified Accounts: Helping Companies Handle Challenging Regulatory Enviro...KYC-Verified Accounts: Helping Companies Handle Challenging Regulatory Enviro...
KYC-Verified Accounts: Helping Companies Handle Challenging Regulatory Enviro...
 
It will be International Nurses' Day on 12 May
It will be International Nurses' Day on 12 MayIt will be International Nurses' Day on 12 May
It will be International Nurses' Day on 12 May
 
VVVIP Call Girls In Greater Kailash ➡️ Delhi ➡️ 9999965857 🚀 No Advance 24HRS...
VVVIP Call Girls In Greater Kailash ➡️ Delhi ➡️ 9999965857 🚀 No Advance 24HRS...VVVIP Call Girls In Greater Kailash ➡️ Delhi ➡️ 9999965857 🚀 No Advance 24HRS...
VVVIP Call Girls In Greater Kailash ➡️ Delhi ➡️ 9999965857 🚀 No Advance 24HRS...
 
Mondelez State of Snacking and Future Trends 2023
Mondelez State of Snacking and Future Trends 2023Mondelez State of Snacking and Future Trends 2023
Mondelez State of Snacking and Future Trends 2023
 
Yaroslav Rozhankivskyy: Три складові і три передумови максимальної продуктивн...
Yaroslav Rozhankivskyy: Три складові і три передумови максимальної продуктивн...Yaroslav Rozhankivskyy: Три складові і три передумови максимальної продуктивн...
Yaroslav Rozhankivskyy: Три складові і три передумови максимальної продуктивн...
 
unwanted pregnancy Kit [+918133066128] Abortion Pills IN Dubai UAE Abudhabi
unwanted pregnancy Kit [+918133066128] Abortion Pills IN Dubai UAE Abudhabiunwanted pregnancy Kit [+918133066128] Abortion Pills IN Dubai UAE Abudhabi
unwanted pregnancy Kit [+918133066128] Abortion Pills IN Dubai UAE Abudhabi
 
Call Girls Navi Mumbai Just Call 9907093804 Top Class Call Girl Service Avail...
Call Girls Navi Mumbai Just Call 9907093804 Top Class Call Girl Service Avail...Call Girls Navi Mumbai Just Call 9907093804 Top Class Call Girl Service Avail...
Call Girls Navi Mumbai Just Call 9907093804 Top Class Call Girl Service Avail...
 
A DAY IN THE LIFE OF A SALESMAN / WOMAN
A DAY IN THE LIFE OF A  SALESMAN / WOMANA DAY IN THE LIFE OF A  SALESMAN / WOMAN
A DAY IN THE LIFE OF A SALESMAN / WOMAN
 
Mifty kit IN Salmiya (+918133066128) Abortion pills IN Salmiyah Cytotec pills
Mifty kit IN Salmiya (+918133066128) Abortion pills IN Salmiyah Cytotec pillsMifty kit IN Salmiya (+918133066128) Abortion pills IN Salmiyah Cytotec pills
Mifty kit IN Salmiya (+918133066128) Abortion pills IN Salmiyah Cytotec pills
 
Enhancing and Restoring Safety & Quality Cultures - Dave Litwiller - May 2024...
Enhancing and Restoring Safety & Quality Cultures - Dave Litwiller - May 2024...Enhancing and Restoring Safety & Quality Cultures - Dave Litwiller - May 2024...
Enhancing and Restoring Safety & Quality Cultures - Dave Litwiller - May 2024...
 
Monthly Social Media Update April 2024 pptx.pptx
Monthly Social Media Update April 2024 pptx.pptxMonthly Social Media Update April 2024 pptx.pptx
Monthly Social Media Update April 2024 pptx.pptx
 
Best VIP Call Girls Noida Sector 40 Call Me: 8448380779
Best VIP Call Girls Noida Sector 40 Call Me: 8448380779Best VIP Call Girls Noida Sector 40 Call Me: 8448380779
Best VIP Call Girls Noida Sector 40 Call Me: 8448380779
 
7.pdf This presentation captures many uses and the significance of the number...
7.pdf This presentation captures many uses and the significance of the number...7.pdf This presentation captures many uses and the significance of the number...
7.pdf This presentation captures many uses and the significance of the number...
 
Call Girls Hebbal Just Call 👗 7737669865 👗 Top Class Call Girl Service Bangalore
Call Girls Hebbal Just Call 👗 7737669865 👗 Top Class Call Girl Service BangaloreCall Girls Hebbal Just Call 👗 7737669865 👗 Top Class Call Girl Service Bangalore
Call Girls Hebbal Just Call 👗 7737669865 👗 Top Class Call Girl Service Bangalore
 
Russian Call Girls In Gurgaon ❤️8448577510 ⊹Best Escorts Service In 24/7 Delh...
Russian Call Girls In Gurgaon ❤️8448577510 ⊹Best Escorts Service In 24/7 Delh...Russian Call Girls In Gurgaon ❤️8448577510 ⊹Best Escorts Service In 24/7 Delh...
Russian Call Girls In Gurgaon ❤️8448577510 ⊹Best Escorts Service In 24/7 Delh...
 
0183760ssssssssssssssssssssssssssss00101011 (27).pdf
0183760ssssssssssssssssssssssssssss00101011 (27).pdf0183760ssssssssssssssssssssssssssss00101011 (27).pdf
0183760ssssssssssssssssssssssssssss00101011 (27).pdf
 

I0361053058

  • 1. International Journal of Computational Engineering Research||Vol, 03||Issue, 6|| www.ijceronline.com ||June ||2013|| Page 53 Harmonic Analysis and Power Factor Correction For Food Processing Industry Rupali Shinde1 , Amit Pathak2 , Bhakti Chaughule3 1,2,3, M.Tech Pursuer (Power System), Bharati Vidyapeeth University’s college of engg, Pune. I. INTRODUCTION It is the objective of the electric utility to supply its customers with a sinusoidal voltage of fairly constant magnitude and frequency. To ensure compliance with the Grid Code [2] voltage and current distortion levels must satisfy limits set out by IEC 61000-3-6 [5]. In any industry, the three top operating expenses are often found to be on energy, labor and materials. If one were to find out the potential cost savings in each of the components, energy would invariably emerge at the top, and thus energy management function constitutes a strategic area for cost reduction. . Industries use a large amount of electrical energy, and that is why it is important to ensure a loss-free and energy-efficient system in industries [3]. In developing countries like India, where electrical energy resources are scarce and production of electricity is very costly, energy conservation studies are of great importance. Energy audit is the translation of conservation ideas into realities by blending technically feasible solutions with economic and other organizational considerations within a specified time frame [4]. An energy audit is a study of a plant or facility to determine how and where energy is used and to identify methods for energy savings. An energy audit was carried out under four major heads: (i) process section audit, (ii) Refrigeration section audit, (iii) power load audit (motors, compressor, etc.), and (iv) harmonic analysis. Readings were taken under these heads and analyzed to find the scope of energy conservation opportunities in the selected test case industrial unit. II. AUDITING PROCEDURE Energy audit cannot be successfully carried out without the commitment from the top management. Management must be firstly convinced of the necessity of implementing energy management and hence energy audit [7] . Energy audit consists of several tasks, which can be carried out depending on the type of the audit and the size and the function of the audited facility [8] . Therefore, an energy audit is not a linear process and is rather iterative. The audit described in this paper has been carried out based on the following functional activities:  Walk-through survey  Motor load survey used in various processes  Harmonic analysis ABSTRACT Harmonic analysis of the distribution system is essential to study the behavior of equipments connected in the non-sinusoidal system environment for designing and optimal location of filters. Harmonic distortion can have a significant impact on industrial customers such as additional losses and heating of certain network equipment, faulty operation of control equipment and interference in neighboring telecommunication system. In this case study harmonic analysis of food processing industry has done using harmonic analyzer ‘YOKOGAVA’. The aim of the study was to improve the power factor, maintain harmonic distortion within acceptable levels and reduce possible resonance problem at the plant. Analysis of voltage and current harmonics is performed at distribution side point of common coupling before and after connecting APFC panel. KEY WORDS: APFC Panel, Energy Audit, Harmonics, Nonlinear load, Total Harmonic Distortion, Under loaded motors, Yokogava.
  • 2. Harmonic Analysis And Power… www.ijceronline.com ||June ||2013|| Page 54 III. FIELD VISITS AND MEASUREMENT WORK Katraj Dairy is one of the oldest milk processing industry in Pune, Maharashtra. Readings for harmonic distortion and and for power factor improvement are taken with the help of YOKOGAWA(Harmonic Analyser) before and after connecting APFC Pannal. 3.1 Plant Electrical Energy Consumption The energy consumption of the industry was identified in terms of the equipments and functional area wise. The results were obtained after measurements during the factory visits. Power analyzers, Harmonic Analyzer, clamp meters, etc. were used to measure the electrical energy consumption of the industry. The total load of the unit is approximately 1326.3 kW . TABLE.1 Total load of Katraj Dairy 1 2 3 4 5 6 7 8 Fig.1Load division chart of Katraj Dairy Sr.no Sections Connected load in HP 1 Air compressor section 182 2 Process section 349.5 3 Refrigeration section 882 4 Boiler section 120 5 E.T.P. section 180 6 Raw water sector 30 7 Ice cream plant 10 8 Illumination 15 Total load in HP 1768.5 Total load in KW 1326.3
  • 3. Harmonic Analysis And Power… www.ijceronline.com ||June ||2013|| Page 55 The following points can be observed from this survey:  The major load in the plant is that of refrigeration, which constitutes approximately 66 % of the total load.  Motor load constitutes approximately 38% of the total load.  Total number of units consumed per month is 188380 after taking the average of 12 months. 3.3 Motor Survey For most of the applications, three-phase, 4-pole, 1470- rpm induction motors of Kirloskar make have been used for various production processes in the plant. During survey and measurement process, it was observed that some of the motors are underloaded. And most of the motors used are energy efficient motors. Load on compressor where 45 KW,1460 rpm, 415V,80 amp,3ph,50 Hz motor is used is continuously varying between 40amp to 80 amp. Other motors have almost constant load on them. 3.4 Problems with Underloaded Motor  An underloaded motor always runs at a low lagging power factor. If the motor is loaded around 50% of the rated load, power factor can be as low as 0.5 lagging. This means industry is utilizing only 50% of the power from the supply mains and paying for 100% if the billing is kVA based.  Extra expenditure on installation of power factor improvement equipment to maintain the power factor within permissible limits set by the state electricity board needs to be done. Otherwise, penalty has to be paid.  Efficiency of a standard induction motor is about 87-90% at the rated load and it reduces drastically at half of the rated load depending upon the size of the motor and loading (about 70-75% for 60 hp motor). This means motor will draw more current for the same mechanical output IV. ENERGY-EFFICIENT MOTORS More and more industries are switching to energy-efficient motors (EEMs) because EEMs lower the production costs. Just a small increase in motor efficiency can significantly lower the production costs. A motor can cost thousands of rupees a year to operate, so savings of even a few percent add up quickly. An EEM generates savings whenever it is running and as long as it lasts, which may be 20 years or more. EEMs cost more than the standard motors, but purchase price can be paled in comparison to a motor's operating costs. Since the annual operating cost of a motor is often 5-10 times its initial cost, the typical 3-5% higher efficiency of an EEM can more than offset its 15-20% higher initial cost over its life. In addition to costing less to operate, EEMs generally last longer, require less maintenance, and reduce system amperage draw. The efficiency curves of two EEMs are shown Figure 2: Efficiency of EEMs as per IS-12615 (Eff1 = 2-pole motor, Eff2 = 4-pole motor) EEMs also offer other advantages, such as longer insulation life, longer lubrication interval, greater inertial acceleration, and higher service factors. In addition, they may be better equipped to handle heavy starting loads, large sustained loads, phase imbalances, voltage excursions, high ambient temperatures, and impaired ventilation. EEMs also do not add as much to air-conditioning loads as standard motors, since they do not give off as much heat.
  • 4. Harmonic Analysis And Power… www.ijceronline.com ||June ||2013|| Page 56 4.1 Energy-efficient Motor's Performance The efficiency of a motor is the ratio of the mechanical power output to the electrical power input. Design changes, better materials, and manufacturing improvements reduce motor losses, making premium or EEMs more efficient than the standard motors [Figure 2]. Reduced losses mean that an EEM produces a given amount of work with less energy input than a standard motor. In 1989, the National Electrical Manufacturers Association (NEMA) developed a standard definition for EEMs [10] . The definition was designed to help users identify and compare electric motor efficiencies on an equal basis. Figure 3: Losses comparison among standard and high efficiency motors [14] V. Harmonic Analysis Harmonics are one of the major concerns in a power system. Harmonics cause distortion in current and voltage waveforms resulting into deterioration of the power system. The first step for harmonic analysis is the harmonics from non-linear loads. The results of such analysis are complex. Over many years, much importance is given to the methods of analysis and control of harmonics. Harmonics present in power system also has non- integer multiples of the fundamental frequency and have aperiodic waveform. The harmonics are generated in a power system from two distinct types of loads. First category of loads are described as linear loads. The linear time-invariant loads are characterized such that application of sinusoidal voltage results in sinusoidal flow of current. A constant steady- impedance is displayed from these loads during the applied sinusoidal voltage. As the voltage and current are directly proportional to each other, if voltage is increased it will also result into increase in the current. An example of such a load is incandescent lighting. Even if the flux wave in air gap of rotating machine is not sinusoidal, under normal loading conditions transformers and rotation machines pretty much meet this definition. Also, in a transformer the current contains odd and even harmonics including a dc component. More and more use of magnetic circuits over a period of time may get saturated and result into generation of harmonics. In power systems, synchronous generators produce sinusoidal voltages and the loads draw sinusoidal currents. In this case, the harmonic distortion is produced because of the linear load types for sinusoidal voltage is small. Non-linear loads are considered as the second category of loads. The application of sinusoidal voltage does not result in a sinusoidal flow applied sinusoidal voltage for a non-linear devices. The non-linear loads draw a current that may be discontinuous. Harmonic current is isolated by using harmonic filters in order to protect the electrical equipment from getting damaged due to harmonic voltage distortion. They can also be used to improve the power factor. The harmful and damaging effects of harmonic distortion can be evident in many different ways such as electronics miss-timings, increased heating effect in electrical equipments, capacitor overloads, etc. There can be two types of filters that are used in order to reduce the harmonic distortion i.e. the active filters and the passive filters. Active harmonic filters are electronic devices that eliminate the undesirable harmonics on the network by inserting negative harmonics into the network. The goal of harmonic studies is to quantify the distortion in voltage and current waveforms in the power system of industrial units. The results are useful for evaluating corrective measures and troubleshooting harmonic related problems.
  • 5. Harmonic Analysis And Power… www.ijceronline.com ||June ||2013|| Page 57 5.1 Effects of Harmonics on Networks [10]  Overloading of neutral conductor  Reduced efficiency of motors  Malfunctioning of control equipment  Poor power factor of the total system due to introduction of distortion power factor  Overloading of power factor capacitors  Increase in kVA demand of the plant due to increase in rms current drawn VI. RESULTS: Following results are obtained before after connecting APFC panel. Total consumption for FEB- 2013 is 139300. KVA demand is 419. MSEB charges 190Rs. Per KVA for industrial load. Total electricity bill including (TOD tariff, Electricity Duty and other charges) is 10,36,033.06 Rs. They are getting power factor incentive 67,848.40Rs. Total current bill is 9,68,184.66 Rs. Figure (4) Without APFC panel connected THD = 9.1 % Figure (5) With APFC panel with the system THD = 2.3 %
  • 6. Harmonic Analysis And Power… www.ijceronline.com ||June ||2013|| Page 58 VII. CONCLUSION On the basis of Harmonic analysis study & electrical energy audit conducted, the following recommendations have been suggested to the consumer:  In due course of time, if any motor gets damaged or some new motor is to be purchased, EEMs should be purchased.  Harmonic components at PCC are greater than the permissible limits. Therefore, the consumer must install harmonic filter to improve the power quality and save the penalty on harmonic emission.  Harmonic component across individual loads is much higher where variable frequency drives are used, which reflects at the PCC, so a more in-depth analysis is required and a harmonic filter can be designed.  It is also shown in this paper that the proposed PFC capacitor banks can be tuned to act as harmonic filters and operate to reduce the harmonic distortion to acceptable levels. It is recommended that the PFC capacitor banks be tuned to act as harmonic filters and also that upon completion of the plant expansion harmonic measurement are taken to meet the grid code requirement. Proper size of motor should be used, as per the rated load. If possible, motor should be replaced with a proper size motor in a phased manner. REFERENCE [1] Modeling And Harmonic Analysis Of Domestic/Industrial Loads Purushothama Rao Nasini, Narender Reddy Narra and Santosh AEirgrid Grid Code, V.3.1 [2] P. Z. Yaacoh, and A. A. Mohd. Zin, "Electical energy management in small and medium size industries", IEEE TENCON, Beijing, 1993. [3] Thumann, and W. J. Yonger, "Hand Book of Energy Audits", 7 th ed, Lilburn: Fairmont Press Inc.; 2007. [4] IEC 61000-3-6 - Electromagnetic compatibility (EMC) -Part 3-6: Limits - Assessment of harmonic emission limits for the connection of distorting installations to MV, HV and EHV power systems. [5] Huyck, and J. Cappelle, "Electrical energy management for low-voltage clients", International Conference on Clean Electrical Power, IEEE, 2007. [6] X. W. Chen, "Energy Audit of Building: A Case Study of A Commercial Building in Shanghai", Power and Energy Engineering Conference, Asia-Pacific, 2010. [7] Tyagi, "Hand Book of Energy Audit & Management" India: TERI Press; 2000. [8] Catalouge Surelink Technologies" Shenzhen, China, 2008 [9] "IEEE recommended practice for electric power systems in commercial buildings", Recognized as an American National Standard (ANSI) IEEE Standard, pp. 241, 1990. Rupali shinde-M.Tech Electrical Power System (Pursuing), Department of Electrical Engineering, Bharati Vidhyapeeth University’s College of Engineering, Pune, India. Amit pathak - M.Tech Electrical Power System (Pursuing), Department of Electrical Engineering, Bharati Vidhyapeeth University’s College of Engineering, Pune, India. Bhakti Chaughule- M.Tech Electrical Power System (Pursuing), Department of Electrical Engineering, Bharati Vidhyapeeth University’s College of Engineering, Pune, India.