Enhancement of the Performance of Vector Controlled Back-toBack VSC System under Grid Disturbances
G. Bhaskar Rao, Ch. Sreenu
Abstract
The increasing emergence of VSC-based transmission is the result of development in semiconductor devices,
power electronic circuits, control, and executive engineering, The most important limiting factor of power
semiconductors is their switching properties since they are usually optimized for the conduction intervals. This
concept specifically proposes a control structure to improve the performance of high-power vector-controlled
back-to-back VSC systems for wind generators and for transmission systems applications. The main
improvement is to suppress the possible dc-link voltage fluctuations under power line faults and unbalanced
conditions. The proposed controller structure is designed based on regulating the converter system’s states
locally in d-q synchronous reference frame without sequence components extraction or resonant notch
compensator. The mat lab results verify the validity of the proposed control architecture during normal and
unbalanced power system conditions.
Index terms: Vector controlled, VSC, Wind, Recovery transformer,Matlab

I.

Introduction

It is desirable to have high-power highvoltage converter based systems available
During power system faults when they may be needed
the most. Voltage-source converter (VSC)-based
transmission systems have attractive potential features
in terms of power flow control and stability of the
network. A voltage-source converter (VSC) is the
main building block for flexible ac transmission
systems (FACTS) devices and, as of today HVDC
technology up to several hundred megawatts.
Although relatively low switching frequency operation
of high-power converters (9–15 times the line
frequency) is desirable, it makes them sensitive to
power network imbalances when they may be needed
the most.
Today, the most promising market for HVDC
technology is interconnection of the networks where
the centers of the loads are located far from the points
of connection. The problem of ac systems arises as the
phase angle drifts and varies over a wide range with
daily load changes [3].
This phenomenon especially in a weak ac
network along with the power line faults exacerbates
the operation of HVDC systems. If the protection
measures trip the converter system, it can take several
fractions of an hour, depending on the size of the
converter, to discharge the dc link and check the
healthiness of the whole system. Hence, several
practical methods have been proposed and
implemented to keep a system operating under power
system faults and disturbances [1], [2]. However,
generally, less dependence on power semiconductor
characteristics amounts to having more supplier
possibilities for the VSC-based transmission.

www.ijera.com

The most important limiting factor of power
semiconductors is their switching properties since they
are usually optimized for the conduction intervals.
Hence, high-power electronic converters are desired to
operate with relatively low switching frequencies
(maximum 9–15 times the line frequency, and even
lower for multilevel converters). The low switching
frequency operation of VSC systems imposes control
limitations in case of power system faults and
disturbances when they may be needed the most. This
paper specifically proposes a control structure to
improve the performance of high-power vectorcontrolled back-to-back VSC systems for conventional
and emerging utility applications.
The main improvement is to suppress the
possible dc-link voltage fluctuations under power line
faults and unbalanced conditions. The increasing
emergence of VSC-based transmission is the result of
development in semiconductor devices, power
electronic circuits, control, and executive engineering,
[4]–[6]. Previously, the lack of these developments
had prohibited the VSC-based technology from being
the first choice. While each development is moving
forward individually, the result of each one influences
the design criteria and application requirements of the
overall system. To the best of the authors’ knowledge
with emerging high-power applications such as 10MW wind generation turbines or transportable
recovery transformers, the dynamic operation of the
VSC under power system disturbances must be
revisited.
This paper proposes an alternative control
framework to obtain robust dc-link voltage with
specific attention to design the VSC controller in the
back-to-back (BTB) configuration. The proposed
controller is implemented in the d-q (rotating)
1217 | P a g e
G. Bhaskar Rao et al Int. Journal of Engineering Research and Application
ISSN : 2248-9622, Vol. 3, Issue 5, Sep-Oct 2013, pp.1217-1221
synchronous reference frame without sequence
extraction system.
The proposed controller structure is designed
based on regulating the converter system’s states
locally in d-q synchronous reference frame without
sequence components extraction or resonant notch
compensator.

II.

www.ijera.com

model looks similar to the large-signal model. The
state-space representation of the VSC can be obtained
from (3), (4), and(7). State variable vector x(t) is the
state variable vector, u(t) is the input vector, and e(t) is
considered as the disturbance vector, (8)

Modeling of VSC

The modeling of VSC, the building block of
the BTB system, is based on the state-space average
modeling approach. This modeling is based on the
principal circuit analysis and voltage and current
equations for storage elements known as state
equations. the state equations of a VSC in the threephase stationary coordinates are as follows:

In order to benefit from all decoupling and constant
properties of a two-phase system instead of a threephase one, d-q transformation is considered to convert
all quantities in the abc stationary coordinate frame to
the synchronously rotating reference frame, i.e., de–qe

In (3) and (4), Vd and Vq are the converter output
voltages in the synchronous reference frame. The
modulation index can also be written in this frame as
(5) where k depends on the modulation technique. In
this study, we use the vector control method or type-I
control

In many literature works especially for dc/dc
converters, the modulation index is used as the control
input; therefore, (3) and (4) present the nonlinear
system. DC-link dynamics are also nonlinear by
introducing the definition for IDC as (6). However, by
considering Vd and Vq as the control inputs, (3) and
(4) can be treated as linear ones. Also, power balance
is used to derive the equation for the dc-link voltage
neglecting the interface losses as in (7). Ea (the PCC
phase A voltage) is aligned with the d-axis in the
synchronously rotating reference frame.
The result of dc-link dynamics shown in (7)
is linear as long as Ed and Eq are constant.
Consequently, no linearization around specific
operating points is needed and the small-signal VSC
www.ijera.com

In the vector-controlled BTB VSC systems regardless
of the topology, one converter typically controls the
dc-link voltage and supports its reactive power. This
converter can be operated as rectifier in HVDC
applications or as an inverter in direct driven wind
turbines. The other converter is operated in PQ or V/f
(voltage/frequency) mode controlling the active and
reactive powers. A simplified schematic of the BTB
VSC system with its control. To design a closed-loop
system, the eigen structure assignment or any linear
feedback design method can be used to place the poles
at the desired locations. Eigen structure assignment is
explained for STATCOM and we use it to develop
the general controller and as the baseline for the VSC
in the BTB configuration as presented . According to
the system equations, the mode associated with the qcomponent of the current (typically for reactive power
control) can be adjusted based on the ac-side interface
parameters and required response time.
On the other hand, dc-link voltage closedloop dynamics consist of the modes associated with
two eigen values. One of the system poles affects the
charging and discharging of the capacitor which is
called λc . This eigen value should be placed near to
the origin to avoid either high charging
or discharging current. The other pole can be placed at
the same location the reactive current control mode is,
which we call it λi . It should be noted that the poles
associated with the current mode can be placed as far
as the inherent delay of the converter modeling
allows; current regulators often present a fast first
order behavior. To achieve a non oscillatory output
response, it is sufficient to place the poles at the real
axis. Consequently, the dc-link voltage regulator can
be designed based on the system specifications and
requirements. The performance of the BTB system
under balanced conditions through the proposed
modeling and control .

III.

BTB VSC System for Drive (Wind)
Applications

This section is provided to address emerging
large capacity wind turbines (>10 MW). These
turbines are expected to use direct-drive technologies
1218 | P a g e
G. Bhaskar Rao et al Int. Journal of Engineering Research and Application
ISSN : 2248-9622, Vol. 3, Issue 5, Sep-Oct 2013, pp.1217-1221
shown in Fig.1 and the BTB VSC system as the
enabling interface. A robust dc-link voltage is
considered to be one of the key factors that affect the
turbine operation. In the following case studies, it is
assumed that the turbine-side converter (VSC 2)
operates at 30 Hz and supplies 0.8 p.u. active power
and absorbs 0.6 p.u. inductive reactive power, while
the grid-side converter (VSC 1) regulates the dclink
voltage and provides 0.2 p.u. capacitive reactive
power. The dynamic performance of the VSC BTB
system in the drive application under unbalanced
conditions in the inverter side or grid side (dc-link
voltage controller converter) is presented in Figs .1,2,
3, 4. In Fig. 1, the unbalance system is represented by
50% voltage drop in phase B of the inverter-side PCC.
In Fig.5,6,7,8, a more severe fault occurs which is
represented by a 50% voltage sag in phase B in
addition to a 30% voltage drop in phase C of the grid.
From the results obtained, it can be concluded that the
proposed control scheme is effective in maintaining a
robust dc-link voltage even under unbalanced grid
conditions. In other words, the drive side in this case
of high power wind generators with a BTB VSC
interface can operate independently from the grid
disturbances translating to higher availability of the
renewable resources.
4. BTB VSC System for Transmission Transformer
(Partial) Bypass
With increasing demands of power
electronics in the network, it is expected to have
hybrid systems. One example of a hybrid system
approach is known as the modular transformer
converter (MTC) in which a single or a group of BTB

www.ijera.com

VSC system(s) is connected across transmission-level
transformers. An MTC as the transmission controller
provides the flexibility of full or partial utilization for
the transmission lines and power transformers. This
flexibility effectively increases the system’s spare
capacity and operating margins, and also provides
back-up in case of substation transformer failure or
forced reduced rating operation scenarios by
continuous power flow control. A simplified
schematic of the MTC as the transmission controller
connected in parallel to a transmission transformer is
depicted in Fig.12. Introducing the MTC, as shown in
Fig. 9,10,11, brings remarkable effects on the
dynamics of the system. In particular, any imbalance
in the power system is seen by both converters, which
has been little appreciated in conventional
applications of BTB VSC systems.
The dynamic performance of the VSC BTB
system with the proposed control structure for hybrid
power system applications under balanced and
unbalanced conditions is presented in Fig.9,10,11. The
power flow in the BTB system remains as stated in the
previous case studies except that the two networks
have a 5◦ phase difference for the natural power flow
of the grid. The unbalanced system is represented by a
90% voltage drop in phase A of the PCC voltages. As
can be observed, the dc-link voltage remains
practically stiff, and harmonic measurement of the dclink voltage for the second and fourth harmonics
shows a satisfactory level of compensation under this
severe fault case. Therefore, an MTC with the
proposed control structure can be utilized even under
unbalanced conditions when it is needed the most.

Fig.1. Simulink model for the proposed cicuit(Wind application)

Fig.2. Output Voltages of Vsc1,Vsc2.
www.ijera.com

Fig.3.Output currents of Vsc1,Vsc2.
1219 | P a g e
G. Bhaskar Rao et al Int. Journal of Engineering Research and Application
ISSN : 2248-9622, Vol. 3, Issue 5, Sep-Oct 2013, pp.1217-1221

www.ijera.com

Fig.4.DC link voltage.

Fig.6.Output currents of Vsc1,Vsc2.

Fig.5. Output Voltages of Vsc1,Vsc2.

Fig.7.DC link voltage.

Fig.8.Simulink model of proposed circuit under faults at phase B,C .

Fig.9.Output voltages of Vsc1,Vsc2.
Fig.10.Output currents of Vsc1,Vsc2.
www.ijera.com

1220 | P a g e
G. Bhaskar Rao et al Int. Journal of Engineering Research and Application
ISSN : 2248-9622, Vol. 3, Issue 5, Sep-Oct 2013, pp.1217-1221

Fig.11. DC link voltage.

IV.

Conclusion

This paper has addressed the dc-link voltage
control issues for vector-controlled VSC-based
transmission systems under power system
disturbances. Having analyzed the current state-ofthe-art methods of mitigating the dc-link voltage
fluctuations under grid faults and disturbances, we
have proposed a control structure in the commonly
used d-q synchronous reference frame. The proposed

www.ijera.com

structure obviates the need for the sequence
extraction blocks or the resonant compensators.
Therefore, there is no diminishing bandwidth factor.
The scheme, however, utilizes the interaction of
the converters, the load, bus voltage, and their
derivatives to compensate for the phase delay in the
current regulator. The proposed scheme was
explained through a back stepping control method in
which its Lyapunov-based structure ensures the
stability of the system. The RTDS verification of the
controller attained less than 1% dc-link voltage
deviation under most common faults and
disturbances, demonstrating the applicability and
effectiveness of the proposed scheme for different
transmission applications denoted as HVDC, drive,
and
hybrid
power
systems.

Fig.12. Simulink model of proposed circuit for transformer applicatio

Referenes
[1]

[2]

[3]

[4]

[5]

A. Petersson and A. Edris, “Dynamic
performance of the Eagle Pass back-to back
HVDC light tie,” in Proc. IEEE 7th Int.
Conf. AD-DC Power Transmiss., Nov.
2001, pp. 220–225.
S. Teeuwsen, “Modeling the Trans Bay
Cable project as voltage-sourced converter
design,” in. IEEE Power Energy Soc. Annu.
Meeting, Jul. 2011, pp. 1–8.
3.N. G. Hingorani and L. Gyugyi,
Understanding FACTS, Piscataway, NJ:
IEEE Press, 1999.
M. Callavik, “ABB-HVDC grids for
integration of renewable power sources,” in
Proc. EPRI HVDC & FACTS Users
Meeting, 2010.
V. Hild and J. Vivian, “Siemens HVDC &
FACTS innovations and projects,” in Proc.
EPRI HVDC & FACTS Users Meeting,
2010.

Ch.Sreenu:

He received B.Tech degree from NIET
college, Affiliated to JNTUH, now he is pursuing his
M.Tech from Annamacharya Institute of Technology
and Sceinces ,Hyd.

About Authors
G.Bhaskar Rao
He received B.tech ,M.Tech degrees from JNTU
Anantapur in Electrical and Electronics Engineering.
Now he is working as Asso.prof, Head of dept of
EEE in Annamacharya Institute of Technology and
Sciences, hyd.
www.ijera.com

1221 | P a g e

Más contenido relacionado

La actualidad más candente

2018 2019 ieee power electronics and drives title and abstract
2018 2019 ieee power electronics and drives title and abstract2018 2019 ieee power electronics and drives title and abstract
2018 2019 ieee power electronics and drives title and abstractPower Integrated Solutions
 
IRJET- Improving Power Quality by using MC-UPQC
IRJET- Improving Power Quality by using MC-UPQCIRJET- Improving Power Quality by using MC-UPQC
IRJET- Improving Power Quality by using MC-UPQCIRJET Journal
 
Modeling Optimization Voltage Index Unified Power Flow Controller Equivalent ...
Modeling Optimization Voltage Index Unified Power Flow Controller Equivalent ...Modeling Optimization Voltage Index Unified Power Flow Controller Equivalent ...
Modeling Optimization Voltage Index Unified Power Flow Controller Equivalent ...IJMTST Journal
 
International Journal of Computational Engineering Research(IJCER)
 International Journal of Computational Engineering Research(IJCER)  International Journal of Computational Engineering Research(IJCER)
International Journal of Computational Engineering Research(IJCER) ijceronline
 
Universal Four Leg v4
Universal Four Leg v4Universal Four Leg v4
Universal Four Leg v4AxelDijksman
 
Enhancement of Reactive Power Compensation in PV Grid System To Increase The ...
Enhancement of Reactive Power Compensation in PV Grid System To Increase The ...Enhancement of Reactive Power Compensation in PV Grid System To Increase The ...
Enhancement of Reactive Power Compensation in PV Grid System To Increase The ...IJSRD
 
1.compensation of reactive power using d statcom in grid interfaced pv system
1.compensation of reactive power using d statcom in grid interfaced pv system1.compensation of reactive power using d statcom in grid interfaced pv system
1.compensation of reactive power using d statcom in grid interfaced pv systemEditorJST
 
Ieee 2015 2014 power electronics project titles
Ieee 2015 2014 power electronics project titlesIeee 2015 2014 power electronics project titles
Ieee 2015 2014 power electronics project titlespowerprojects
 
Mitigation of Voltage Fluctuations in Power System Using STATCOM
Mitigation of Voltage Fluctuations in Power System Using STATCOMMitigation of Voltage Fluctuations in Power System Using STATCOM
Mitigation of Voltage Fluctuations in Power System Using STATCOMIJERA Editor
 
A Review of Analysis and Modeling of Grid Connected Three Phase Multilevel Un...
A Review of Analysis and Modeling of Grid Connected Three Phase Multilevel Un...A Review of Analysis and Modeling of Grid Connected Three Phase Multilevel Un...
A Review of Analysis and Modeling of Grid Connected Three Phase Multilevel Un...IRJET Journal
 
Major Project, HVDC Thesis - Saurabh Saxena
Major Project, HVDC Thesis - Saurabh SaxenaMajor Project, HVDC Thesis - Saurabh Saxena
Major Project, HVDC Thesis - Saurabh SaxenaSaurabh Saxena
 
Enhancement of Power System Dynamics Using a Novel Series Compensation Scheme
Enhancement of Power System Dynamics Using a Novel Series Compensation SchemeEnhancement of Power System Dynamics Using a Novel Series Compensation Scheme
Enhancement of Power System Dynamics Using a Novel Series Compensation SchemeIJMER
 
P-Q Theory Based UPQC for Reactive Power Compensation with UCAP
P-Q Theory Based UPQC for Reactive Power Compensation with UCAPP-Q Theory Based UPQC for Reactive Power Compensation with UCAP
P-Q Theory Based UPQC for Reactive Power Compensation with UCAPIRJET Journal
 
Optimal Placement of TCSC and SVC Using PSO
Optimal Placement of TCSC and SVC Using PSOOptimal Placement of TCSC and SVC Using PSO
Optimal Placement of TCSC and SVC Using PSOIOSR Journals
 

La actualidad más candente (20)

2018 2019 ieee power electronics and drives title and abstract
2018 2019 ieee power electronics and drives title and abstract2018 2019 ieee power electronics and drives title and abstract
2018 2019 ieee power electronics and drives title and abstract
 
IRJET- Improving Power Quality by using MC-UPQC
IRJET- Improving Power Quality by using MC-UPQCIRJET- Improving Power Quality by using MC-UPQC
IRJET- Improving Power Quality by using MC-UPQC
 
Y04408126132
Y04408126132Y04408126132
Y04408126132
 
Modeling Optimization Voltage Index Unified Power Flow Controller Equivalent ...
Modeling Optimization Voltage Index Unified Power Flow Controller Equivalent ...Modeling Optimization Voltage Index Unified Power Flow Controller Equivalent ...
Modeling Optimization Voltage Index Unified Power Flow Controller Equivalent ...
 
International Journal of Computational Engineering Research(IJCER)
 International Journal of Computational Engineering Research(IJCER)  International Journal of Computational Engineering Research(IJCER)
International Journal of Computational Engineering Research(IJCER)
 
Universal Four Leg v4
Universal Four Leg v4Universal Four Leg v4
Universal Four Leg v4
 
Eo35798805
Eo35798805Eo35798805
Eo35798805
 
Enhancement of Reactive Power Compensation in PV Grid System To Increase The ...
Enhancement of Reactive Power Compensation in PV Grid System To Increase The ...Enhancement of Reactive Power Compensation in PV Grid System To Increase The ...
Enhancement of Reactive Power Compensation in PV Grid System To Increase The ...
 
1.compensation of reactive power using d statcom in grid interfaced pv system
1.compensation of reactive power using d statcom in grid interfaced pv system1.compensation of reactive power using d statcom in grid interfaced pv system
1.compensation of reactive power using d statcom in grid interfaced pv system
 
Ieee 2015 2014 power electronics project titles
Ieee 2015 2014 power electronics project titlesIeee 2015 2014 power electronics project titles
Ieee 2015 2014 power electronics project titles
 
Mitigation of Voltage Fluctuations in Power System Using STATCOM
Mitigation of Voltage Fluctuations in Power System Using STATCOMMitigation of Voltage Fluctuations in Power System Using STATCOM
Mitigation of Voltage Fluctuations in Power System Using STATCOM
 
Power Quality Problems and Solutions
Power Quality Problems and Solutions Power Quality Problems and Solutions
Power Quality Problems and Solutions
 
A Review of Analysis and Modeling of Grid Connected Three Phase Multilevel Un...
A Review of Analysis and Modeling of Grid Connected Three Phase Multilevel Un...A Review of Analysis and Modeling of Grid Connected Three Phase Multilevel Un...
A Review of Analysis and Modeling of Grid Connected Three Phase Multilevel Un...
 
A new switching look-up table for direct power control of grid connected 3L-N...
A new switching look-up table for direct power control of grid connected 3L-N...A new switching look-up table for direct power control of grid connected 3L-N...
A new switching look-up table for direct power control of grid connected 3L-N...
 
Major Project, HVDC Thesis - Saurabh Saxena
Major Project, HVDC Thesis - Saurabh SaxenaMajor Project, HVDC Thesis - Saurabh Saxena
Major Project, HVDC Thesis - Saurabh Saxena
 
Enhancement of Power System Dynamics Using a Novel Series Compensation Scheme
Enhancement of Power System Dynamics Using a Novel Series Compensation SchemeEnhancement of Power System Dynamics Using a Novel Series Compensation Scheme
Enhancement of Power System Dynamics Using a Novel Series Compensation Scheme
 
P-Q Theory Based UPQC for Reactive Power Compensation with UCAP
P-Q Theory Based UPQC for Reactive Power Compensation with UCAPP-Q Theory Based UPQC for Reactive Power Compensation with UCAP
P-Q Theory Based UPQC for Reactive Power Compensation with UCAP
 
Optimal Placement of TCSC and SVC Using PSO
Optimal Placement of TCSC and SVC Using PSOOptimal Placement of TCSC and SVC Using PSO
Optimal Placement of TCSC and SVC Using PSO
 
Segan
SeganSegan
Segan
 
Review ijaet
Review ijaetReview ijaet
Review ijaet
 

Destacado (20)

Gz3512221228
Gz3512221228Gz3512221228
Gz3512221228
 
Hf3512571274
Hf3512571274Hf3512571274
Hf3512571274
 
Hb3512341239
Hb3512341239Hb3512341239
Hb3512341239
 
Hn3513151319
Hn3513151319Hn3513151319
Hn3513151319
 
Gv3512031207
Gv3512031207Gv3512031207
Gv3512031207
 
Fv3510271037
Fv3510271037Fv3510271037
Fv3510271037
 
Gq3511781181
Gq3511781181Gq3511781181
Gq3511781181
 
Ha3512291233
Ha3512291233Ha3512291233
Ha3512291233
 
Gk3511271132
Gk3511271132Gk3511271132
Gk3511271132
 
Gl3511331144
Gl3511331144Gl3511331144
Gl3511331144
 
Hg3512751279
Hg3512751279Hg3512751279
Hg3512751279
 
Gw3512081212
Gw3512081212Gw3512081212
Gw3512081212
 
Gc3510651086
Gc3510651086Gc3510651086
Gc3510651086
 
Gh3511131117
Gh3511131117Gh3511131117
Gh3511131117
 
Gj3511231126
Gj3511231126Gj3511231126
Gj3511231126
 
Gg3511071112
Gg3511071112Gg3511071112
Gg3511071112
 
Fx3510401044
Fx3510401044Fx3510401044
Fx3510401044
 
Gt3511931198
Gt3511931198Gt3511931198
Gt3511931198
 
Ge3510911102
Ge3510911102Ge3510911102
Ge3510911102
 
Hc3512401245
Hc3512401245Hc3512401245
Hc3512401245
 

Similar a Gy3512171221

Implementation of DC voltage controllers on enhancing the stability of multi-...
Implementation of DC voltage controllers on enhancing the stability of multi-...Implementation of DC voltage controllers on enhancing the stability of multi-...
Implementation of DC voltage controllers on enhancing the stability of multi-...IJECEIAES
 
DG FED MULTILEVEL INVERTER BASED D-STATCOM FOR VARIOUS LOADING CONDITIONS
DG FED MULTILEVEL INVERTER BASED D-STATCOM FOR VARIOUS LOADING CONDITIONSDG FED MULTILEVEL INVERTER BASED D-STATCOM FOR VARIOUS LOADING CONDITIONS
DG FED MULTILEVEL INVERTER BASED D-STATCOM FOR VARIOUS LOADING CONDITIONSIJCI JOURNAL
 
The DC-fault Blocking Capability by a New Hybrid Multilevel Converter in HVDC...
The DC-fault Blocking Capability by a New Hybrid Multilevel Converter in HVDC...The DC-fault Blocking Capability by a New Hybrid Multilevel Converter in HVDC...
The DC-fault Blocking Capability by a New Hybrid Multilevel Converter in HVDC...Editor IJCATR
 
Impact of LCC–HVDC multiterminal on generator rotor angle stability
Impact of LCC–HVDC multiterminal on generator rotor  angle stability  Impact of LCC–HVDC multiterminal on generator rotor  angle stability
Impact of LCC–HVDC multiterminal on generator rotor angle stability IJECEIAES
 
Controllers For A VSC-HVDC Link Connected To A Weak AC System
Controllers For A VSC-HVDC Link Connected To A Weak AC SystemControllers For A VSC-HVDC Link Connected To A Weak AC System
Controllers For A VSC-HVDC Link Connected To A Weak AC SystemIOSR Journals
 
IRJET-Analysis and Rectification of Fault in Power System by Multilevel Modul...
IRJET-Analysis and Rectification of Fault in Power System by Multilevel Modul...IRJET-Analysis and Rectification of Fault in Power System by Multilevel Modul...
IRJET-Analysis and Rectification of Fault in Power System by Multilevel Modul...IRJET Journal
 
IRJET- Comparative Study of Common Methods of Frequency Response using MTDC G...
IRJET- Comparative Study of Common Methods of Frequency Response using MTDC G...IRJET- Comparative Study of Common Methods of Frequency Response using MTDC G...
IRJET- Comparative Study of Common Methods of Frequency Response using MTDC G...IRJET Journal
 
Steady State Fault Analysis of VSC- HVDC Transmission System
Steady State Fault Analysis of VSC- HVDC Transmission SystemSteady State Fault Analysis of VSC- HVDC Transmission System
Steady State Fault Analysis of VSC- HVDC Transmission SystemIRJET Journal
 
Improved Transient Compensation using PI-SRF Control Scheme Based UHVDC for O...
Improved Transient Compensation using PI-SRF Control Scheme Based UHVDC for O...Improved Transient Compensation using PI-SRF Control Scheme Based UHVDC for O...
Improved Transient Compensation using PI-SRF Control Scheme Based UHVDC for O...IRJET Journal
 
Real and Reactive Power Compensation by using Diode Clamped Multilevel Invert...
Real and Reactive Power Compensation by using Diode Clamped Multilevel Invert...Real and Reactive Power Compensation by using Diode Clamped Multilevel Invert...
Real and Reactive Power Compensation by using Diode Clamped Multilevel Invert...IRJET Journal
 
Design and Simulation of a Three Phase Power Converter Connected To a Distrib...
Design and Simulation of a Three Phase Power Converter Connected To a Distrib...Design and Simulation of a Three Phase Power Converter Connected To a Distrib...
Design and Simulation of a Three Phase Power Converter Connected To a Distrib...IJERA Editor
 
Shunt Compensation for Power Quality Improvement using a STATCOM Controller
Shunt Compensation for Power Quality Improvement using a STATCOM ControllerShunt Compensation for Power Quality Improvement using a STATCOM Controller
Shunt Compensation for Power Quality Improvement using a STATCOM ControllerIDES Editor
 
IRJET- Level of Service & Throughput Maximization at Operational Toll Plazas
IRJET- Level of Service & Throughput Maximization at Operational Toll PlazasIRJET- Level of Service & Throughput Maximization at Operational Toll Plazas
IRJET- Level of Service & Throughput Maximization at Operational Toll PlazasIRJET Journal
 
IRJET- Different Control Strategies for Power Control of Voltage Source Conve...
IRJET- Different Control Strategies for Power Control of Voltage Source Conve...IRJET- Different Control Strategies for Power Control of Voltage Source Conve...
IRJET- Different Control Strategies for Power Control of Voltage Source Conve...IRJET Journal
 
PERFORMANCE EXPLORATION OF SINGLE PHASE DAB DC-DC CONVERTER UNDER LOAD VARIATION
PERFORMANCE EXPLORATION OF SINGLE PHASE DAB DC-DC CONVERTER UNDER LOAD VARIATIONPERFORMANCE EXPLORATION OF SINGLE PHASE DAB DC-DC CONVERTER UNDER LOAD VARIATION
PERFORMANCE EXPLORATION OF SINGLE PHASE DAB DC-DC CONVERTER UNDER LOAD VARIATIONIRJET Journal
 

Similar a Gy3512171221 (20)

C05821529
C05821529C05821529
C05821529
 
Implementation of DC voltage controllers on enhancing the stability of multi-...
Implementation of DC voltage controllers on enhancing the stability of multi-...Implementation of DC voltage controllers on enhancing the stability of multi-...
Implementation of DC voltage controllers on enhancing the stability of multi-...
 
DG FED MULTILEVEL INVERTER BASED D-STATCOM FOR VARIOUS LOADING CONDITIONS
DG FED MULTILEVEL INVERTER BASED D-STATCOM FOR VARIOUS LOADING CONDITIONSDG FED MULTILEVEL INVERTER BASED D-STATCOM FOR VARIOUS LOADING CONDITIONS
DG FED MULTILEVEL INVERTER BASED D-STATCOM FOR VARIOUS LOADING CONDITIONS
 
The DC-fault Blocking Capability by a New Hybrid Multilevel Converter in HVDC...
The DC-fault Blocking Capability by a New Hybrid Multilevel Converter in HVDC...The DC-fault Blocking Capability by a New Hybrid Multilevel Converter in HVDC...
The DC-fault Blocking Capability by a New Hybrid Multilevel Converter in HVDC...
 
Impact of LCC–HVDC multiterminal on generator rotor angle stability
Impact of LCC–HVDC multiterminal on generator rotor  angle stability  Impact of LCC–HVDC multiterminal on generator rotor  angle stability
Impact of LCC–HVDC multiterminal on generator rotor angle stability
 
Controllers For A VSC-HVDC Link Connected To A Weak AC System
Controllers For A VSC-HVDC Link Connected To A Weak AC SystemControllers For A VSC-HVDC Link Connected To A Weak AC System
Controllers For A VSC-HVDC Link Connected To A Weak AC System
 
D010121832
D010121832D010121832
D010121832
 
IRJET-Analysis and Rectification of Fault in Power System by Multilevel Modul...
IRJET-Analysis and Rectification of Fault in Power System by Multilevel Modul...IRJET-Analysis and Rectification of Fault in Power System by Multilevel Modul...
IRJET-Analysis and Rectification of Fault in Power System by Multilevel Modul...
 
H04945260
H04945260H04945260
H04945260
 
www.ijerd.com
www.ijerd.comwww.ijerd.com
www.ijerd.com
 
IRJET- Comparative Study of Common Methods of Frequency Response using MTDC G...
IRJET- Comparative Study of Common Methods of Frequency Response using MTDC G...IRJET- Comparative Study of Common Methods of Frequency Response using MTDC G...
IRJET- Comparative Study of Common Methods of Frequency Response using MTDC G...
 
Steady State Fault Analysis of VSC- HVDC Transmission System
Steady State Fault Analysis of VSC- HVDC Transmission SystemSteady State Fault Analysis of VSC- HVDC Transmission System
Steady State Fault Analysis of VSC- HVDC Transmission System
 
An Analysis of Virtual Flux Direct Power Control of Three-Phase AC-DC Converter
An Analysis of Virtual Flux Direct Power Control of Three-Phase AC-DC ConverterAn Analysis of Virtual Flux Direct Power Control of Three-Phase AC-DC Converter
An Analysis of Virtual Flux Direct Power Control of Three-Phase AC-DC Converter
 
Improved Transient Compensation using PI-SRF Control Scheme Based UHVDC for O...
Improved Transient Compensation using PI-SRF Control Scheme Based UHVDC for O...Improved Transient Compensation using PI-SRF Control Scheme Based UHVDC for O...
Improved Transient Compensation using PI-SRF Control Scheme Based UHVDC for O...
 
Real and Reactive Power Compensation by using Diode Clamped Multilevel Invert...
Real and Reactive Power Compensation by using Diode Clamped Multilevel Invert...Real and Reactive Power Compensation by using Diode Clamped Multilevel Invert...
Real and Reactive Power Compensation by using Diode Clamped Multilevel Invert...
 
Design and Simulation of a Three Phase Power Converter Connected To a Distrib...
Design and Simulation of a Three Phase Power Converter Connected To a Distrib...Design and Simulation of a Three Phase Power Converter Connected To a Distrib...
Design and Simulation of a Three Phase Power Converter Connected To a Distrib...
 
Shunt Compensation for Power Quality Improvement using a STATCOM Controller
Shunt Compensation for Power Quality Improvement using a STATCOM ControllerShunt Compensation for Power Quality Improvement using a STATCOM Controller
Shunt Compensation for Power Quality Improvement using a STATCOM Controller
 
IRJET- Level of Service & Throughput Maximization at Operational Toll Plazas
IRJET- Level of Service & Throughput Maximization at Operational Toll PlazasIRJET- Level of Service & Throughput Maximization at Operational Toll Plazas
IRJET- Level of Service & Throughput Maximization at Operational Toll Plazas
 
IRJET- Different Control Strategies for Power Control of Voltage Source Conve...
IRJET- Different Control Strategies for Power Control of Voltage Source Conve...IRJET- Different Control Strategies for Power Control of Voltage Source Conve...
IRJET- Different Control Strategies for Power Control of Voltage Source Conve...
 
PERFORMANCE EXPLORATION OF SINGLE PHASE DAB DC-DC CONVERTER UNDER LOAD VARIATION
PERFORMANCE EXPLORATION OF SINGLE PHASE DAB DC-DC CONVERTER UNDER LOAD VARIATIONPERFORMANCE EXPLORATION OF SINGLE PHASE DAB DC-DC CONVERTER UNDER LOAD VARIATION
PERFORMANCE EXPLORATION OF SINGLE PHASE DAB DC-DC CONVERTER UNDER LOAD VARIATION
 

Último

GenCyber Cyber Security Day Presentation
GenCyber Cyber Security Day PresentationGenCyber Cyber Security Day Presentation
GenCyber Cyber Security Day PresentationMichael W. Hawkins
 
Scaling API-first – The story of a global engineering organization
Scaling API-first – The story of a global engineering organizationScaling API-first – The story of a global engineering organization
Scaling API-first – The story of a global engineering organizationRadu Cotescu
 
IAC 2024 - IA Fast Track to Search Focused AI Solutions
IAC 2024 - IA Fast Track to Search Focused AI SolutionsIAC 2024 - IA Fast Track to Search Focused AI Solutions
IAC 2024 - IA Fast Track to Search Focused AI SolutionsEnterprise Knowledge
 
Unblocking The Main Thread Solving ANRs and Frozen Frames
Unblocking The Main Thread Solving ANRs and Frozen FramesUnblocking The Main Thread Solving ANRs and Frozen Frames
Unblocking The Main Thread Solving ANRs and Frozen FramesSinan KOZAK
 
Breaking the Kubernetes Kill Chain: Host Path Mount
Breaking the Kubernetes Kill Chain: Host Path MountBreaking the Kubernetes Kill Chain: Host Path Mount
Breaking the Kubernetes Kill Chain: Host Path MountPuma Security, LLC
 
Factors to Consider When Choosing Accounts Payable Services Providers.pptx
Factors to Consider When Choosing Accounts Payable Services Providers.pptxFactors to Consider When Choosing Accounts Payable Services Providers.pptx
Factors to Consider When Choosing Accounts Payable Services Providers.pptxKatpro Technologies
 
Boost PC performance: How more available memory can improve productivity
Boost PC performance: How more available memory can improve productivityBoost PC performance: How more available memory can improve productivity
Boost PC performance: How more available memory can improve productivityPrincipled Technologies
 
🐬 The future of MySQL is Postgres 🐘
🐬  The future of MySQL is Postgres   🐘🐬  The future of MySQL is Postgres   🐘
🐬 The future of MySQL is Postgres 🐘RTylerCroy
 
The Codex of Business Writing Software for Real-World Solutions 2.pptx
The Codex of Business Writing Software for Real-World Solutions 2.pptxThe Codex of Business Writing Software for Real-World Solutions 2.pptx
The Codex of Business Writing Software for Real-World Solutions 2.pptxMalak Abu Hammad
 
Driving Behavioral Change for Information Management through Data-Driven Gree...
Driving Behavioral Change for Information Management through Data-Driven Gree...Driving Behavioral Change for Information Management through Data-Driven Gree...
Driving Behavioral Change for Information Management through Data-Driven Gree...Enterprise Knowledge
 
2024: Domino Containers - The Next Step. News from the Domino Container commu...
2024: Domino Containers - The Next Step. News from the Domino Container commu...2024: Domino Containers - The Next Step. News from the Domino Container commu...
2024: Domino Containers - The Next Step. News from the Domino Container commu...Martijn de Jong
 
08448380779 Call Girls In Greater Kailash - I Women Seeking Men
08448380779 Call Girls In Greater Kailash - I Women Seeking Men08448380779 Call Girls In Greater Kailash - I Women Seeking Men
08448380779 Call Girls In Greater Kailash - I Women Seeking MenDelhi Call girls
 
08448380779 Call Girls In Friends Colony Women Seeking Men
08448380779 Call Girls In Friends Colony Women Seeking Men08448380779 Call Girls In Friends Colony Women Seeking Men
08448380779 Call Girls In Friends Colony Women Seeking MenDelhi Call girls
 
Finology Group – Insurtech Innovation Award 2024
Finology Group – Insurtech Innovation Award 2024Finology Group – Insurtech Innovation Award 2024
Finology Group – Insurtech Innovation Award 2024The Digital Insurer
 
Exploring the Future Potential of AI-Enabled Smartphone Processors
Exploring the Future Potential of AI-Enabled Smartphone ProcessorsExploring the Future Potential of AI-Enabled Smartphone Processors
Exploring the Future Potential of AI-Enabled Smartphone Processorsdebabhi2
 
Apidays Singapore 2024 - Building Digital Trust in a Digital Economy by Veron...
Apidays Singapore 2024 - Building Digital Trust in a Digital Economy by Veron...Apidays Singapore 2024 - Building Digital Trust in a Digital Economy by Veron...
Apidays Singapore 2024 - Building Digital Trust in a Digital Economy by Veron...apidays
 
A Domino Admins Adventures (Engage 2024)
A Domino Admins Adventures (Engage 2024)A Domino Admins Adventures (Engage 2024)
A Domino Admins Adventures (Engage 2024)Gabriella Davis
 
Raspberry Pi 5: Challenges and Solutions in Bringing up an OpenGL/Vulkan Driv...
Raspberry Pi 5: Challenges and Solutions in Bringing up an OpenGL/Vulkan Driv...Raspberry Pi 5: Challenges and Solutions in Bringing up an OpenGL/Vulkan Driv...
Raspberry Pi 5: Challenges and Solutions in Bringing up an OpenGL/Vulkan Driv...Igalia
 
How to convert PDF to text with Nanonets
How to convert PDF to text with NanonetsHow to convert PDF to text with Nanonets
How to convert PDF to text with Nanonetsnaman860154
 
Data Cloud, More than a CDP by Matt Robison
Data Cloud, More than a CDP by Matt RobisonData Cloud, More than a CDP by Matt Robison
Data Cloud, More than a CDP by Matt RobisonAnna Loughnan Colquhoun
 

Último (20)

GenCyber Cyber Security Day Presentation
GenCyber Cyber Security Day PresentationGenCyber Cyber Security Day Presentation
GenCyber Cyber Security Day Presentation
 
Scaling API-first – The story of a global engineering organization
Scaling API-first – The story of a global engineering organizationScaling API-first – The story of a global engineering organization
Scaling API-first – The story of a global engineering organization
 
IAC 2024 - IA Fast Track to Search Focused AI Solutions
IAC 2024 - IA Fast Track to Search Focused AI SolutionsIAC 2024 - IA Fast Track to Search Focused AI Solutions
IAC 2024 - IA Fast Track to Search Focused AI Solutions
 
Unblocking The Main Thread Solving ANRs and Frozen Frames
Unblocking The Main Thread Solving ANRs and Frozen FramesUnblocking The Main Thread Solving ANRs and Frozen Frames
Unblocking The Main Thread Solving ANRs and Frozen Frames
 
Breaking the Kubernetes Kill Chain: Host Path Mount
Breaking the Kubernetes Kill Chain: Host Path MountBreaking the Kubernetes Kill Chain: Host Path Mount
Breaking the Kubernetes Kill Chain: Host Path Mount
 
Factors to Consider When Choosing Accounts Payable Services Providers.pptx
Factors to Consider When Choosing Accounts Payable Services Providers.pptxFactors to Consider When Choosing Accounts Payable Services Providers.pptx
Factors to Consider When Choosing Accounts Payable Services Providers.pptx
 
Boost PC performance: How more available memory can improve productivity
Boost PC performance: How more available memory can improve productivityBoost PC performance: How more available memory can improve productivity
Boost PC performance: How more available memory can improve productivity
 
🐬 The future of MySQL is Postgres 🐘
🐬  The future of MySQL is Postgres   🐘🐬  The future of MySQL is Postgres   🐘
🐬 The future of MySQL is Postgres 🐘
 
The Codex of Business Writing Software for Real-World Solutions 2.pptx
The Codex of Business Writing Software for Real-World Solutions 2.pptxThe Codex of Business Writing Software for Real-World Solutions 2.pptx
The Codex of Business Writing Software for Real-World Solutions 2.pptx
 
Driving Behavioral Change for Information Management through Data-Driven Gree...
Driving Behavioral Change for Information Management through Data-Driven Gree...Driving Behavioral Change for Information Management through Data-Driven Gree...
Driving Behavioral Change for Information Management through Data-Driven Gree...
 
2024: Domino Containers - The Next Step. News from the Domino Container commu...
2024: Domino Containers - The Next Step. News from the Domino Container commu...2024: Domino Containers - The Next Step. News from the Domino Container commu...
2024: Domino Containers - The Next Step. News from the Domino Container commu...
 
08448380779 Call Girls In Greater Kailash - I Women Seeking Men
08448380779 Call Girls In Greater Kailash - I Women Seeking Men08448380779 Call Girls In Greater Kailash - I Women Seeking Men
08448380779 Call Girls In Greater Kailash - I Women Seeking Men
 
08448380779 Call Girls In Friends Colony Women Seeking Men
08448380779 Call Girls In Friends Colony Women Seeking Men08448380779 Call Girls In Friends Colony Women Seeking Men
08448380779 Call Girls In Friends Colony Women Seeking Men
 
Finology Group – Insurtech Innovation Award 2024
Finology Group – Insurtech Innovation Award 2024Finology Group – Insurtech Innovation Award 2024
Finology Group – Insurtech Innovation Award 2024
 
Exploring the Future Potential of AI-Enabled Smartphone Processors
Exploring the Future Potential of AI-Enabled Smartphone ProcessorsExploring the Future Potential of AI-Enabled Smartphone Processors
Exploring the Future Potential of AI-Enabled Smartphone Processors
 
Apidays Singapore 2024 - Building Digital Trust in a Digital Economy by Veron...
Apidays Singapore 2024 - Building Digital Trust in a Digital Economy by Veron...Apidays Singapore 2024 - Building Digital Trust in a Digital Economy by Veron...
Apidays Singapore 2024 - Building Digital Trust in a Digital Economy by Veron...
 
A Domino Admins Adventures (Engage 2024)
A Domino Admins Adventures (Engage 2024)A Domino Admins Adventures (Engage 2024)
A Domino Admins Adventures (Engage 2024)
 
Raspberry Pi 5: Challenges and Solutions in Bringing up an OpenGL/Vulkan Driv...
Raspberry Pi 5: Challenges and Solutions in Bringing up an OpenGL/Vulkan Driv...Raspberry Pi 5: Challenges and Solutions in Bringing up an OpenGL/Vulkan Driv...
Raspberry Pi 5: Challenges and Solutions in Bringing up an OpenGL/Vulkan Driv...
 
How to convert PDF to text with Nanonets
How to convert PDF to text with NanonetsHow to convert PDF to text with Nanonets
How to convert PDF to text with Nanonets
 
Data Cloud, More than a CDP by Matt Robison
Data Cloud, More than a CDP by Matt RobisonData Cloud, More than a CDP by Matt Robison
Data Cloud, More than a CDP by Matt Robison
 

Gy3512171221

  • 1. G. Bhaskar Rao et al Int. Journal of Engineering Research and Application ISSN : 2248-9622, Vol. 3, Issue 5, Sep-Oct 2013, pp.1217-1221 RESEARCH ARTICLE www.ijera.com OPEN ACCESS Enhancement of the Performance of Vector Controlled Back-toBack VSC System under Grid Disturbances G. Bhaskar Rao, Ch. Sreenu Abstract The increasing emergence of VSC-based transmission is the result of development in semiconductor devices, power electronic circuits, control, and executive engineering, The most important limiting factor of power semiconductors is their switching properties since they are usually optimized for the conduction intervals. This concept specifically proposes a control structure to improve the performance of high-power vector-controlled back-to-back VSC systems for wind generators and for transmission systems applications. The main improvement is to suppress the possible dc-link voltage fluctuations under power line faults and unbalanced conditions. The proposed controller structure is designed based on regulating the converter system’s states locally in d-q synchronous reference frame without sequence components extraction or resonant notch compensator. The mat lab results verify the validity of the proposed control architecture during normal and unbalanced power system conditions. Index terms: Vector controlled, VSC, Wind, Recovery transformer,Matlab I. Introduction It is desirable to have high-power highvoltage converter based systems available During power system faults when they may be needed the most. Voltage-source converter (VSC)-based transmission systems have attractive potential features in terms of power flow control and stability of the network. A voltage-source converter (VSC) is the main building block for flexible ac transmission systems (FACTS) devices and, as of today HVDC technology up to several hundred megawatts. Although relatively low switching frequency operation of high-power converters (9–15 times the line frequency) is desirable, it makes them sensitive to power network imbalances when they may be needed the most. Today, the most promising market for HVDC technology is interconnection of the networks where the centers of the loads are located far from the points of connection. The problem of ac systems arises as the phase angle drifts and varies over a wide range with daily load changes [3]. This phenomenon especially in a weak ac network along with the power line faults exacerbates the operation of HVDC systems. If the protection measures trip the converter system, it can take several fractions of an hour, depending on the size of the converter, to discharge the dc link and check the healthiness of the whole system. Hence, several practical methods have been proposed and implemented to keep a system operating under power system faults and disturbances [1], [2]. However, generally, less dependence on power semiconductor characteristics amounts to having more supplier possibilities for the VSC-based transmission. www.ijera.com The most important limiting factor of power semiconductors is their switching properties since they are usually optimized for the conduction intervals. Hence, high-power electronic converters are desired to operate with relatively low switching frequencies (maximum 9–15 times the line frequency, and even lower for multilevel converters). The low switching frequency operation of VSC systems imposes control limitations in case of power system faults and disturbances when they may be needed the most. This paper specifically proposes a control structure to improve the performance of high-power vectorcontrolled back-to-back VSC systems for conventional and emerging utility applications. The main improvement is to suppress the possible dc-link voltage fluctuations under power line faults and unbalanced conditions. The increasing emergence of VSC-based transmission is the result of development in semiconductor devices, power electronic circuits, control, and executive engineering, [4]–[6]. Previously, the lack of these developments had prohibited the VSC-based technology from being the first choice. While each development is moving forward individually, the result of each one influences the design criteria and application requirements of the overall system. To the best of the authors’ knowledge with emerging high-power applications such as 10MW wind generation turbines or transportable recovery transformers, the dynamic operation of the VSC under power system disturbances must be revisited. This paper proposes an alternative control framework to obtain robust dc-link voltage with specific attention to design the VSC controller in the back-to-back (BTB) configuration. The proposed controller is implemented in the d-q (rotating) 1217 | P a g e
  • 2. G. Bhaskar Rao et al Int. Journal of Engineering Research and Application ISSN : 2248-9622, Vol. 3, Issue 5, Sep-Oct 2013, pp.1217-1221 synchronous reference frame without sequence extraction system. The proposed controller structure is designed based on regulating the converter system’s states locally in d-q synchronous reference frame without sequence components extraction or resonant notch compensator. II. www.ijera.com model looks similar to the large-signal model. The state-space representation of the VSC can be obtained from (3), (4), and(7). State variable vector x(t) is the state variable vector, u(t) is the input vector, and e(t) is considered as the disturbance vector, (8) Modeling of VSC The modeling of VSC, the building block of the BTB system, is based on the state-space average modeling approach. This modeling is based on the principal circuit analysis and voltage and current equations for storage elements known as state equations. the state equations of a VSC in the threephase stationary coordinates are as follows: In order to benefit from all decoupling and constant properties of a two-phase system instead of a threephase one, d-q transformation is considered to convert all quantities in the abc stationary coordinate frame to the synchronously rotating reference frame, i.e., de–qe In (3) and (4), Vd and Vq are the converter output voltages in the synchronous reference frame. The modulation index can also be written in this frame as (5) where k depends on the modulation technique. In this study, we use the vector control method or type-I control In many literature works especially for dc/dc converters, the modulation index is used as the control input; therefore, (3) and (4) present the nonlinear system. DC-link dynamics are also nonlinear by introducing the definition for IDC as (6). However, by considering Vd and Vq as the control inputs, (3) and (4) can be treated as linear ones. Also, power balance is used to derive the equation for the dc-link voltage neglecting the interface losses as in (7). Ea (the PCC phase A voltage) is aligned with the d-axis in the synchronously rotating reference frame. The result of dc-link dynamics shown in (7) is linear as long as Ed and Eq are constant. Consequently, no linearization around specific operating points is needed and the small-signal VSC www.ijera.com In the vector-controlled BTB VSC systems regardless of the topology, one converter typically controls the dc-link voltage and supports its reactive power. This converter can be operated as rectifier in HVDC applications or as an inverter in direct driven wind turbines. The other converter is operated in PQ or V/f (voltage/frequency) mode controlling the active and reactive powers. A simplified schematic of the BTB VSC system with its control. To design a closed-loop system, the eigen structure assignment or any linear feedback design method can be used to place the poles at the desired locations. Eigen structure assignment is explained for STATCOM and we use it to develop the general controller and as the baseline for the VSC in the BTB configuration as presented . According to the system equations, the mode associated with the qcomponent of the current (typically for reactive power control) can be adjusted based on the ac-side interface parameters and required response time. On the other hand, dc-link voltage closedloop dynamics consist of the modes associated with two eigen values. One of the system poles affects the charging and discharging of the capacitor which is called λc . This eigen value should be placed near to the origin to avoid either high charging or discharging current. The other pole can be placed at the same location the reactive current control mode is, which we call it λi . It should be noted that the poles associated with the current mode can be placed as far as the inherent delay of the converter modeling allows; current regulators often present a fast first order behavior. To achieve a non oscillatory output response, it is sufficient to place the poles at the real axis. Consequently, the dc-link voltage regulator can be designed based on the system specifications and requirements. The performance of the BTB system under balanced conditions through the proposed modeling and control . III. BTB VSC System for Drive (Wind) Applications This section is provided to address emerging large capacity wind turbines (>10 MW). These turbines are expected to use direct-drive technologies 1218 | P a g e
  • 3. G. Bhaskar Rao et al Int. Journal of Engineering Research and Application ISSN : 2248-9622, Vol. 3, Issue 5, Sep-Oct 2013, pp.1217-1221 shown in Fig.1 and the BTB VSC system as the enabling interface. A robust dc-link voltage is considered to be one of the key factors that affect the turbine operation. In the following case studies, it is assumed that the turbine-side converter (VSC 2) operates at 30 Hz and supplies 0.8 p.u. active power and absorbs 0.6 p.u. inductive reactive power, while the grid-side converter (VSC 1) regulates the dclink voltage and provides 0.2 p.u. capacitive reactive power. The dynamic performance of the VSC BTB system in the drive application under unbalanced conditions in the inverter side or grid side (dc-link voltage controller converter) is presented in Figs .1,2, 3, 4. In Fig. 1, the unbalance system is represented by 50% voltage drop in phase B of the inverter-side PCC. In Fig.5,6,7,8, a more severe fault occurs which is represented by a 50% voltage sag in phase B in addition to a 30% voltage drop in phase C of the grid. From the results obtained, it can be concluded that the proposed control scheme is effective in maintaining a robust dc-link voltage even under unbalanced grid conditions. In other words, the drive side in this case of high power wind generators with a BTB VSC interface can operate independently from the grid disturbances translating to higher availability of the renewable resources. 4. BTB VSC System for Transmission Transformer (Partial) Bypass With increasing demands of power electronics in the network, it is expected to have hybrid systems. One example of a hybrid system approach is known as the modular transformer converter (MTC) in which a single or a group of BTB www.ijera.com VSC system(s) is connected across transmission-level transformers. An MTC as the transmission controller provides the flexibility of full or partial utilization for the transmission lines and power transformers. This flexibility effectively increases the system’s spare capacity and operating margins, and also provides back-up in case of substation transformer failure or forced reduced rating operation scenarios by continuous power flow control. A simplified schematic of the MTC as the transmission controller connected in parallel to a transmission transformer is depicted in Fig.12. Introducing the MTC, as shown in Fig. 9,10,11, brings remarkable effects on the dynamics of the system. In particular, any imbalance in the power system is seen by both converters, which has been little appreciated in conventional applications of BTB VSC systems. The dynamic performance of the VSC BTB system with the proposed control structure for hybrid power system applications under balanced and unbalanced conditions is presented in Fig.9,10,11. The power flow in the BTB system remains as stated in the previous case studies except that the two networks have a 5◦ phase difference for the natural power flow of the grid. The unbalanced system is represented by a 90% voltage drop in phase A of the PCC voltages. As can be observed, the dc-link voltage remains practically stiff, and harmonic measurement of the dclink voltage for the second and fourth harmonics shows a satisfactory level of compensation under this severe fault case. Therefore, an MTC with the proposed control structure can be utilized even under unbalanced conditions when it is needed the most. Fig.1. Simulink model for the proposed cicuit(Wind application) Fig.2. Output Voltages of Vsc1,Vsc2. www.ijera.com Fig.3.Output currents of Vsc1,Vsc2. 1219 | P a g e
  • 4. G. Bhaskar Rao et al Int. Journal of Engineering Research and Application ISSN : 2248-9622, Vol. 3, Issue 5, Sep-Oct 2013, pp.1217-1221 www.ijera.com Fig.4.DC link voltage. Fig.6.Output currents of Vsc1,Vsc2. Fig.5. Output Voltages of Vsc1,Vsc2. Fig.7.DC link voltage. Fig.8.Simulink model of proposed circuit under faults at phase B,C . Fig.9.Output voltages of Vsc1,Vsc2. Fig.10.Output currents of Vsc1,Vsc2. www.ijera.com 1220 | P a g e
  • 5. G. Bhaskar Rao et al Int. Journal of Engineering Research and Application ISSN : 2248-9622, Vol. 3, Issue 5, Sep-Oct 2013, pp.1217-1221 Fig.11. DC link voltage. IV. Conclusion This paper has addressed the dc-link voltage control issues for vector-controlled VSC-based transmission systems under power system disturbances. Having analyzed the current state-ofthe-art methods of mitigating the dc-link voltage fluctuations under grid faults and disturbances, we have proposed a control structure in the commonly used d-q synchronous reference frame. The proposed www.ijera.com structure obviates the need for the sequence extraction blocks or the resonant compensators. Therefore, there is no diminishing bandwidth factor. The scheme, however, utilizes the interaction of the converters, the load, bus voltage, and their derivatives to compensate for the phase delay in the current regulator. The proposed scheme was explained through a back stepping control method in which its Lyapunov-based structure ensures the stability of the system. The RTDS verification of the controller attained less than 1% dc-link voltage deviation under most common faults and disturbances, demonstrating the applicability and effectiveness of the proposed scheme for different transmission applications denoted as HVDC, drive, and hybrid power systems. Fig.12. Simulink model of proposed circuit for transformer applicatio Referenes [1] [2] [3] [4] [5] A. Petersson and A. Edris, “Dynamic performance of the Eagle Pass back-to back HVDC light tie,” in Proc. IEEE 7th Int. Conf. AD-DC Power Transmiss., Nov. 2001, pp. 220–225. S. Teeuwsen, “Modeling the Trans Bay Cable project as voltage-sourced converter design,” in. IEEE Power Energy Soc. Annu. Meeting, Jul. 2011, pp. 1–8. 3.N. G. Hingorani and L. Gyugyi, Understanding FACTS, Piscataway, NJ: IEEE Press, 1999. M. Callavik, “ABB-HVDC grids for integration of renewable power sources,” in Proc. EPRI HVDC & FACTS Users Meeting, 2010. V. Hild and J. Vivian, “Siemens HVDC & FACTS innovations and projects,” in Proc. EPRI HVDC & FACTS Users Meeting, 2010. Ch.Sreenu: He received B.Tech degree from NIET college, Affiliated to JNTUH, now he is pursuing his M.Tech from Annamacharya Institute of Technology and Sceinces ,Hyd. About Authors G.Bhaskar Rao He received B.tech ,M.Tech degrees from JNTU Anantapur in Electrical and Electronics Engineering. Now he is working as Asso.prof, Head of dept of EEE in Annamacharya Institute of Technology and Sciences, hyd. www.ijera.com 1221 | P a g e