Mohammed Asim Khan Int. Journal of Engineering Research and Applications www.ijera.com 
ISSN : 2248-9622, Vol. 4, Issue 9( Version 4), September 2014, pp.87-91 
www.ijera.com 87 | P a g e 
Nonlinear Static Analysis Of 3-D RC Framed Asymmetric Building With Lead Rubber Isolator Using Sap2000v15 Mohammed Asim Khan*, Prof. Shaik Abdulla** *(P.G Student of Structural Engineering, Department of Civil Engineering, Khaja Banda Nawaz College of Engineering, Gulbarga, Karnataka, India -585104 ** Associate Prof. Shaikh Abdulla, Department of Civil Engineering, Khaja Banda Nawaz College of Engineering, Gulbarga, Karnataka, India -585104 ABSTRACT Many buildings in the present scenario have irregular configurations both in plan and elevation. This in future may be subjected to devastating earthquakes. So it is also necessary to enhance the seismic performance of asymmetric buildings by using seismic control techniques. In the present study a total of 9 models, asymmetrical in plan (L-shape) are taken for analysis to cover the broader spectrum of low, medium & high rise buildings for the seismic control of the structures using pushover analysis, two different techniques were considered such as lead rubber bearing isolator and masonry infill walls, the analysis has been carried out using SAP2000V15. The results of bare frame and other building models have been compared, the presence of lead rubber base isolator, top story drift get reduced as compared with masonry infill wall. The trend was found to be reversed for high rise buildings especially with the application of isolation systems due to the massive increase in the story displacements suggesting the ineffectiveness of the base isolators for high rise buildings successively the plastic hinge pattern formed after carrying out the pushover analysis was also studied which indicated that structural performance was considerably improved. 
Keywords – bare frame, lead rubber bearing isolator, masonry infill 
I. INTRODUCTION 
The buildings with regular geometry and uniformly distributed mass and stiffness in plan as well as in elevation suffer much less damage compared to irregular configurations. The promise of nonlinear static analysis that is pushover analysis is to produce structures with predictable seismic performance. Seismic isolation is relatively recent and evolving technology. The main feature of the base isolation technology is that it introduces flexibility in the structures. Advantages of lead rubber isolator with RC framed buildings properly designed and detailed buildings with lead rubber base isolator shown good response in past earthquakes. Although infill panels considerably enrich both the strength and stiffness of the frame, because of lack of knowledge of the multiple behavior of the frame and infill, their influence is not taken into account. Hence the structural action of infill walls cannot be neglected. Therefore, masonry infill panel should be considered as structural element. The main aim of the present study is to illustrate the effect of base isolation and masonry infill wall as shell element on the response of low, medium and high rise L-shape asymmetric buildings. 
II. DESCRIPTION OF STRUCTURAL MODELS 
In this study, a total number of 9 different models of 5, 10 and 15 story R.C framed buildings are considered for analysis, the building has seven bays in X direction and five bays in Y direction with the plan dimension 28 m x 20 m and a story height of 3.5 m each in all the floors. The building is kept asymmetric in plan. The alignment and size of column is kept same throughout the height of the structure. The building is considered to be located in zone IV. The building is founded on medium strength soil through isolated footing under the columns. Elastic moduli of concrete and masonry are taken as 25000 MPa and 3500 MPa respectively and their poisons ratio as 0.20 and 0.17 respectively. The unit weights of concrete and masonry are taken as 25.0 KN/m3 and 20.0 KN/m3 respectively the floor finish on the floors is 1.0 KN/m2. The live load on floor is taken as 3.5 KN/m2. In seismic weight calculations, 50% of the floor live loads considered. Thickness of slab and masonry infill wall as 0.120 m and 0.23 m respectively. The base isolation used in this study is New Zealand rubber bearing system [6]. Nonlinear static analysis is used on both of fixed base and base isolated buildings. In fixed base condition, all of structures are considered in elastic stage and in base- isolated condition, the superstructure of the building 
RESEARCH ARTICLE OPEN ACCESS
Mohammed Asim Khan Int. Journal of Engineering Research and Applications www.ijera.com 
ISSN : 2248-9622, Vol. 4, Issue 9( Version 4), September 2014, pp.87-91 
www.ijera.com 88 | P a g e 
is considered in elastic stage and base isolator is considered in inelastic stage. 
III. ANALYTICAL MODELS CONSIDERED FOR ANALYSIS 
Model 5A: Five story bare frame with fixed base. However masses of the walls (230mm thick) are included on all stories. Model 5B: Five story bare frame with Lead Rubber Isolator. However masses of the walls (230mm thick) are included on all stories. Model 5C: Five story building with fixed base has masonry infill wall as shell element in all the stories. Model 10A: Ten story bare frame with fixed base. However masses of the walls (230mm thick) are included on all stories. Model 10B: Ten story bare frame with Lead Rubber Isolator. However masses of the walls (230mm thick) are included on all stories. Model 10C: Ten story building with fixed base has masonry infill wall as shell element in all the stories. Model 15A: Fifteen story bare frame with fixed base. However masses of the walls (230mm thick) are included on all stories. Model 15B: Fifteen story bare frame with Lead Rubber Isolator. However masses of the walls (230mm thick) are included on all stories. 
Model 15C: Fifteen story building with fixed base has masonry infill wall as shell element in all the stories. 
Fig1: plan 
Fig 2: Elevations of model 5A, 5B and 5C 
Fig 4: Elevations of model 15A, 15B and 15C 
IV. RESULTS AND DISCUSSION 
In this paper the results of the selected building models studies are presented. Analysis were carried out using SAP2000V15 and different parameters studied such as Fundamental natural time period, Base shear, torsional moment, story displacement and story drifts, the tables and figures are shown below. Table 1: Fundamental Natural Time Period FUNDAMENTAL NATURAL TIME PERIOD 
Model No. 
T in sec 
5A 0.71886 
5B 3.62464 
5C 0.19853 
10A 1.62007 
10B 3.56055 
10C 0.47643 
15A 2.5934 
15B 4.5859 
15C 0.85854 
Fig 5: Model Vs Time period for different building model It can be observed that the % increase of fundamental natural time period of model 5B, 10B and 15B are 80.16%, 54.5% and 43.44% compared to as model 5A, 10A and 15A. Also the % reduction of fundamental natural time period of model 5C, 10C and 15C are 72.38%, 70.6% and 67.09% as compared to model 5A, 10A and 15A.
Mohammed Asim Khan Int. Journal of Engineering Research and Applications www.ijera.com 
ISSN : 2248-9622, Vol. 4, Issue 9( Version 4), September 2014, pp.87-91 
www.ijera.com 89 | P a g e 
Table 2: Base Shear BASE SHEAR (KN) 
MODEL NO. 
PUSH Y dir. 
PUSH X dir. 
5A 
4096.05 
4379.94 
5B 656.432 
744.759 
5C 41175.8 
43306 
10A 2646.65 
3148.85 
10B 1995 2139.98 
10C 24513.6 28136.4 
15A 2093.36 
2441.24 
15B 1705.71 1838.96 
15C 19830.4 27367.6 
From table 2, it is observed that % reduction of base shear is 84%, 24.6% and 18.51% for model 5B, 10B and 15B compared to model 5A, 10A and 15A. The % increase of base shear is 90.05%, 89.20% and 89.44% for model 5C, 10C and 15C compared to model 5A, 10A and 15A along transverse direction. From table 2, it is observed that % reduction of base shear is 83%, 32.04% and 24.67% for model 5B, 10B and 15B compared to model 5A, 10A and 15A. The % increase of base shear is 89.88%, 88.8% and 91.07% for model 5C, 10C and 15C compared to model 5A, 10A and15A along longitudinal direction. 
Fig 6: Base Shear of all different building models along longitudinal direction 
Table 3:Torsional Moments 
From table3, it is observed that % reduction of torsional moment is 93.202%, 37.03% and 28.76% for model 5B,10B and 15B compared to model 5A,10A and 15A.and the % increase of torsional moment is 91.6%, 90.81% and 90.86% for model 5C,10C and 15C compared to model 5A,10A and 15A. From table3, it is observed that % reduction of torsional moment is 76.51%, 29.58% and 26.07% for model 5B,10B and 15B compared to model 5A,10A and 15A.and the % increase of torsional moment is 90.5%, 84.82% and 80.87% for model 5C,10C and 15C compared to model 5A,10A and 15A. 
Fig 7: Torsional moments of all different building models along longitudinal direction TORSIONAL MOMENTS KNm 
Model No. 
Push 1 
Push2 
5A 53547 55266 
5B 3639.712 12982.172 
5C 644398.8 581481.84 
10A 36077.34 39891.105 
10B 22718.07 28090.396 
10C 392561.4 262899.88 
15A 29587.45 30715.217 
15B 21077.03 22707.117 
15C 323894.6 160599.51
Mohammed Asim Khan Int. Journal of Engineering Research and Applications www.ijera.com 
ISSN : 2248-9622, Vol. 4, Issue 9( Version 4), September 2014, pp.87-91 
www.ijera.com 90 | P a g e 
Fig 8: Displacement Vs Story level for different building models along transverse direction From figure 5.12 it is observed that the maximum % increase of Lateral displacements is 93%, 94% and 91.58% for model 5B, 10B and 15B as compare to model 5A, 10A and 15A. Whereas for the lateral displacements are reduced to a maximum of 82.14%, 83.23% and 84.93% for model 5C, 10C and 15C as compare to model 5A, 10A and 15A. Fig 9: Ductility ratio for different building models along longitudinal direction 
Table 4: Ductility ratio and Response reduction factor along longitudinal direction 
Fig 10: Response reduction factor for different building models along longitudinal direction From table 4. It can be observed that the ductility ratio for model 5B is greater than the other models in both transverse and longitudinal direction. It can also be observed that the response reduction factor for model 5B is greater than the all other models in both transverse and longitudinal direction. Hence it can be concluded that the model 5B is more flexible than the other models. 
V. CONCLUSION 
1. Fundamental natural time period increases with the use of Lead Rubber Isolation, and decreases when masonry infill wall is considered. 
2. Increased flexibility of the system led to increase of the total displacements due to the elasticity of the existing isolation. 
3. The presence of masonry infill influences the overall behavior of structures when subjected to lateral forces. Story displacements are considerably reduced while contribution of masonry infill wall is taken into account. 
4. Ductility ratio is maximum for Lead Rubber Isolation structure i-e model-5B and for full infill building i-e model 5C, 10C and 15C it get reduced. It indicates that these structures will show adequate warning before collapse. 
5. Lead Rubber Isolation structures are having highest response reduction factor as compared to infill frame structures. It indicates that Lead Rubber Isolation structures are capable of resisting the forces still after first hinge. 
6. From the above study we conclude that model- 5B i-e five story asymmetric R C framed building with Lead Rubber Isolation shows better performance among the others for the given seismic parameters. 
7. Model 5B shows a maximum reduction in terms of torsional moment as compare to other models. 
REFERENCES 
[1] Helmut Krawinkler and G.D.P.K. Seneviratna (1998) “Pros & Cons of Pushover Analysis of Seismic Performance Evaluation”,
Mohammed Asim Khan Int. Journal of Engineering Research and Applications www.ijera.com 
ISSN : 2248-9622, Vol. 4, Issue 9( Version 4), September 2014, pp.87-91 
www.ijera.com 91 | P a g e 
Engineering Structures, Vol. 20, Nos 4-6, pp. 452-464, 1998. 
[2] M A M Akberuddin (2013) “Pushover Analysis of Medium Rise Multi-Story RCC Frame With and Without Vertical Irregularity”, International Journal of Engineering Research and Application Vol. 3, Issue 5, Sep-Oct 2013, pp.540-546 
[3] S.M. Kalantari, H.Naderpour and S.R.Hoseini Vaez " Investigation Of Base-Isolator Type Selection On Seismic Behavior Of Structures Including Story Drifts And Plastic Hinge Formation." The 14th World Conference on Earthquake Engineering October 12-17, 2008, Beijing, China. 
[4] Dakshes J. Pambhar (2012) “Performance Based Pushover Analysis of R.C.C. Frames”International Journal of Advanced Engineering Research and Studies IJAERS/Vol. I/ Issue III/April-June, 2012/329-333. 
[5] Ashraf Habibullah, Stephen Pyle“Practical three-dimensional non-linear static pushover analysis” Structure Magazine, winter, 1998. 
[6] T.K. Datta “Seismic Analysis of Structures “Indian Institute of Technology Delhi, India. 
[7] CSI computer and structure. Inc.SAP 2000, linear & non-linear static and dynamic analysis of 3D-structure. 
[8] IS 1893(part 1):2002Criteria for earthquake resistant design of structures, Part-I General Provision and Buildings (Fifth Revision). Bureau of Indian Standards, New Delhi. 
[9] IS 456-2000 “Indian Standard Code of Practice for plain and reinforced concrete”, Bureau of Indian Standards, New Delhi.

Más contenido relacionado

La actualidad más candente

La actualidad más candente (20)

B250917
B250917B250917
B250917
 
IRJET- Retrofitting of Reinforced Concrete Frames using different X Braci...
IRJET-  	  Retrofitting of Reinforced Concrete Frames using different X Braci...IRJET-  	  Retrofitting of Reinforced Concrete Frames using different X Braci...
IRJET- Retrofitting of Reinforced Concrete Frames using different X Braci...
 
IRJET- Study & Improvement of Design and Construction Methodology of Precast ...
IRJET- Study & Improvement of Design and Construction Methodology of Precast ...IRJET- Study & Improvement of Design and Construction Methodology of Precast ...
IRJET- Study & Improvement of Design and Construction Methodology of Precast ...
 
Optimization of Pre Engineered Buildings
Optimization of Pre Engineered BuildingsOptimization of Pre Engineered Buildings
Optimization of Pre Engineered Buildings
 
Performance Based Evaluation of Conventional RC Framed Structure Compared wit...
Performance Based Evaluation of Conventional RC Framed Structure Compared wit...Performance Based Evaluation of Conventional RC Framed Structure Compared wit...
Performance Based Evaluation of Conventional RC Framed Structure Compared wit...
 
IRJET- https://www.irjet.net/archives/V6/i7/IRJET-V6I7339.pdf
IRJET- https://www.irjet.net/archives/V6/i7/IRJET-V6I7339.pdfIRJET- https://www.irjet.net/archives/V6/i7/IRJET-V6I7339.pdf
IRJET- https://www.irjet.net/archives/V6/i7/IRJET-V6I7339.pdf
 
Lateral Load Analysis of Shear Wall and Concrete Braced Multi-Storeyed R.C Fr...
Lateral Load Analysis of Shear Wall and Concrete Braced Multi-Storeyed R.C Fr...Lateral Load Analysis of Shear Wall and Concrete Braced Multi-Storeyed R.C Fr...
Lateral Load Analysis of Shear Wall and Concrete Braced Multi-Storeyed R.C Fr...
 
Effective Use of Shelves in Cantilever Retaining Walls
Effective Use of Shelves in Cantilever Retaining WallsEffective Use of Shelves in Cantilever Retaining Walls
Effective Use of Shelves in Cantilever Retaining Walls
 
IRJET- Significance of Shear Wall in Multistory Building with Seismic Ana...
IRJET-  	  Significance of Shear Wall in Multistory Building with Seismic Ana...IRJET-  	  Significance of Shear Wall in Multistory Building with Seismic Ana...
IRJET- Significance of Shear Wall in Multistory Building with Seismic Ana...
 
Seismic Analysis of Multistorey RC Building with Mass Irregularity using ETABS
Seismic Analysis of Multistorey RC Building with Mass Irregularity using ETABSSeismic Analysis of Multistorey RC Building with Mass Irregularity using ETABS
Seismic Analysis of Multistorey RC Building with Mass Irregularity using ETABS
 
1 st ppt presentation to final ppt presentation
1 st ppt presentation to final ppt presentation1 st ppt presentation to final ppt presentation
1 st ppt presentation to final ppt presentation
 
Economic Concrete Frame Elements to Eurocode 2
Economic Concrete Frame Elements to Eurocode 2Economic Concrete Frame Elements to Eurocode 2
Economic Concrete Frame Elements to Eurocode 2
 
Comparative Study on Non-Linear Analysis of Infilled Frames for Vertically Ir...
Comparative Study on Non-Linear Analysis of Infilled Frames for Vertically Ir...Comparative Study on Non-Linear Analysis of Infilled Frames for Vertically Ir...
Comparative Study on Non-Linear Analysis of Infilled Frames for Vertically Ir...
 
IRJET - Analysis of Flat Slab Structural System in Different Earthquake Zones...
IRJET - Analysis of Flat Slab Structural System in Different Earthquake Zones...IRJET - Analysis of Flat Slab Structural System in Different Earthquake Zones...
IRJET - Analysis of Flat Slab Structural System in Different Earthquake Zones...
 
Computation of Loads on Buildings of Different Typologies
Computation of Loads on Buildings of Different Typologies Computation of Loads on Buildings of Different Typologies
Computation of Loads on Buildings of Different Typologies
 
IRJET- A Study on RCC Frames under Sloping Ground with Different Shear Wall C...
IRJET- A Study on RCC Frames under Sloping Ground with Different Shear Wall C...IRJET- A Study on RCC Frames under Sloping Ground with Different Shear Wall C...
IRJET- A Study on RCC Frames under Sloping Ground with Different Shear Wall C...
 
IRJET- Seismic Behaviour of Steel Structures with Bracings Having Seismic Irr...
IRJET- Seismic Behaviour of Steel Structures with Bracings Having Seismic Irr...IRJET- Seismic Behaviour of Steel Structures with Bracings Having Seismic Irr...
IRJET- Seismic Behaviour of Steel Structures with Bracings Having Seismic Irr...
 
IRJET- Analysis of Overhead Water Tank with Different Staging Height and Base...
IRJET- Analysis of Overhead Water Tank with Different Staging Height and Base...IRJET- Analysis of Overhead Water Tank with Different Staging Height and Base...
IRJET- Analysis of Overhead Water Tank with Different Staging Height and Base...
 
Comparative study on behaviour of RCC and steel – concrete composite multisto...
Comparative study on behaviour of RCC and steel – concrete composite multisto...Comparative study on behaviour of RCC and steel – concrete composite multisto...
Comparative study on behaviour of RCC and steel – concrete composite multisto...
 
Analysis of warehouse in staad pro.
Analysis of warehouse in staad pro. Analysis of warehouse in staad pro.
Analysis of warehouse in staad pro.
 

Destacado (20)

Arquitectura de Computadores 3 (EFA, 9º ano)
Arquitectura de Computadores 3 (EFA, 9º ano)Arquitectura de Computadores 3 (EFA, 9º ano)
Arquitectura de Computadores 3 (EFA, 9º ano)
 
Conterecothist
ConterecothistConterecothist
Conterecothist
 
Still Lifes Art Photos Igor Kolosov
Still Lifes Art Photos Igor KolosovStill Lifes Art Photos Igor Kolosov
Still Lifes Art Photos Igor Kolosov
 
Organización
OrganizaciónOrganización
Organización
 
25
2525
25
 
Reunió De Pares
Reunió De ParesReunió De Pares
Reunió De Pares
 
Miniaturk Istanbul
Miniaturk  IstanbulMiniaturk  Istanbul
Miniaturk Istanbul
 
Apostila adobe photo shop
Apostila adobe photo shopApostila adobe photo shop
Apostila adobe photo shop
 
Superb Photos
Superb PhotosSuperb Photos
Superb Photos
 
Cuerpo y mente una polémica contemporánea en la cibercultura
Cuerpo y mente una polémica contemporánea en la ciberculturaCuerpo y mente una polémica contemporánea en la cibercultura
Cuerpo y mente una polémica contemporánea en la cibercultura
 
Photos Aerienne 1203183126494583 4
Photos Aerienne 1203183126494583 4Photos Aerienne 1203183126494583 4
Photos Aerienne 1203183126494583 4
 
Theroutedanube
TheroutedanubeTheroutedanube
Theroutedanube
 
2
22
2
 
2
22
2
 
Moderate
ModerateModerate
Moderate
 
Ice
IceIce
Ice
 
TCC Marcus Winicius e Rayner Max - Analise de Desempenho de um Servidor Proxy...
TCC Marcus Winicius e Rayner Max - Analise de Desempenho de um Servidor Proxy...TCC Marcus Winicius e Rayner Max - Analise de Desempenho de um Servidor Proxy...
TCC Marcus Winicius e Rayner Max - Analise de Desempenho de um Servidor Proxy...
 
Como montar um computador
Como montar um computadorComo montar um computador
Como montar um computador
 
Instrumentos slide share
Instrumentos slide shareInstrumentos slide share
Instrumentos slide share
 
1
11
1
 

Similar a Nonlinear Static Analysis Of 3-D RC Framed Asymmetric Building With Lead Rubber Isolator Using Sap2000v15

Similar a Nonlinear Static Analysis Of 3-D RC Framed Asymmetric Building With Lead Rubber Isolator Using Sap2000v15 (20)

Elastic and Inelastic Responses of Multi-Storey Buildings Symmetric and Asymm...
Elastic and Inelastic Responses of Multi-Storey Buildings Symmetric and Asymm...Elastic and Inelastic Responses of Multi-Storey Buildings Symmetric and Asymm...
Elastic and Inelastic Responses of Multi-Storey Buildings Symmetric and Asymm...
 
Seismic optimization of horizontally irregular buildings with floating column...
Seismic optimization of horizontally irregular buildings with floating column...Seismic optimization of horizontally irregular buildings with floating column...
Seismic optimization of horizontally irregular buildings with floating column...
 
Lateral Load Analysis of Shear Wall and Concrete Braced Multi-Storeyed R.C Fr...
Lateral Load Analysis of Shear Wall and Concrete Braced Multi-Storeyed R.C Fr...Lateral Load Analysis of Shear Wall and Concrete Braced Multi-Storeyed R.C Fr...
Lateral Load Analysis of Shear Wall and Concrete Braced Multi-Storeyed R.C Fr...
 
STUDIES OF ANALYSIS AND DESIGN FOR MULTI-STORIES STRUCTURES WITH TRANSFER PLA...
STUDIES OF ANALYSIS AND DESIGN FOR MULTI-STORIES STRUCTURES WITH TRANSFER PLA...STUDIES OF ANALYSIS AND DESIGN FOR MULTI-STORIES STRUCTURES WITH TRANSFER PLA...
STUDIES OF ANALYSIS AND DESIGN FOR MULTI-STORIES STRUCTURES WITH TRANSFER PLA...
 
Seismic Performance and Shear Wall Position Assessment of the Buildings Resti...
Seismic Performance and Shear Wall Position Assessment of the Buildings Resti...Seismic Performance and Shear Wall Position Assessment of the Buildings Resti...
Seismic Performance and Shear Wall Position Assessment of the Buildings Resti...
 
Seismic Performance Study of RC Framed Building with Diaphragm Discontinuity
Seismic Performance Study of RC Framed Building with Diaphragm DiscontinuitySeismic Performance Study of RC Framed Building with Diaphragm Discontinuity
Seismic Performance Study of RC Framed Building with Diaphragm Discontinuity
 
ANALYSIS OF REINFORCED CONCRETE FRAMED STRUCTURE(G+15) WITH STEEL BRACING SYS...
ANALYSIS OF REINFORCED CONCRETE FRAMED STRUCTURE(G+15) WITH STEEL BRACING SYS...ANALYSIS OF REINFORCED CONCRETE FRAMED STRUCTURE(G+15) WITH STEEL BRACING SYS...
ANALYSIS OF REINFORCED CONCRETE FRAMED STRUCTURE(G+15) WITH STEEL BRACING SYS...
 
IRJET- Response of Adjacent Building for Seismic Pounding Effect on Bare Fram...
IRJET- Response of Adjacent Building for Seismic Pounding Effect on Bare Fram...IRJET- Response of Adjacent Building for Seismic Pounding Effect on Bare Fram...
IRJET- Response of Adjacent Building for Seismic Pounding Effect on Bare Fram...
 
Dynamic Analysis of Soft Storey Frame with Isolators
Dynamic Analysis of Soft Storey Frame with IsolatorsDynamic Analysis of Soft Storey Frame with Isolators
Dynamic Analysis of Soft Storey Frame with Isolators
 
Study on Concentric Steel Bracing at Soft Storey During Earthquake
Study on Concentric Steel Bracing at Soft Storey During EarthquakeStudy on Concentric Steel Bracing at Soft Storey During Earthquake
Study on Concentric Steel Bracing at Soft Storey During Earthquake
 
IRJET- A Parametric Study on the Siesmic Performance of Flat Slab Multi-S...
IRJET-  	  A Parametric Study on the Siesmic Performance of Flat Slab Multi-S...IRJET-  	  A Parametric Study on the Siesmic Performance of Flat Slab Multi-S...
IRJET- A Parametric Study on the Siesmic Performance of Flat Slab Multi-S...
 
Behavioural Study of RC Flat Plate Multi-Storey Building Persuaded By Stiffne...
Behavioural Study of RC Flat Plate Multi-Storey Building Persuaded By Stiffne...Behavioural Study of RC Flat Plate Multi-Storey Building Persuaded By Stiffne...
Behavioural Study of RC Flat Plate Multi-Storey Building Persuaded By Stiffne...
 
Effect of Oblique Column and Viscous Damper on Podium Structure Using Etabs
Effect of Oblique Column and Viscous Damper on Podium Structure Using EtabsEffect of Oblique Column and Viscous Damper on Podium Structure Using Etabs
Effect of Oblique Column and Viscous Damper on Podium Structure Using Etabs
 
Analysis of flat slab building with and without shear wall
Analysis of flat slab building with and without shear wall Analysis of flat slab building with and without shear wall
Analysis of flat slab building with and without shear wall
 
IRJET- Comparative Seismic Evaluation of Response of RC Building with Shear W...
IRJET- Comparative Seismic Evaluation of Response of RC Building with Shear W...IRJET- Comparative Seismic Evaluation of Response of RC Building with Shear W...
IRJET- Comparative Seismic Evaluation of Response of RC Building with Shear W...
 
IRJET- Progressive Collapse Resistance of Flat Slab Building
IRJET- Progressive Collapse Resistance of Flat Slab BuildingIRJET- Progressive Collapse Resistance of Flat Slab Building
IRJET- Progressive Collapse Resistance of Flat Slab Building
 
Comparative Analysis of RCC and Composite Building Subjected to Lateral Load
Comparative Analysis of RCC and Composite Building Subjected to Lateral LoadComparative Analysis of RCC and Composite Building Subjected to Lateral Load
Comparative Analysis of RCC and Composite Building Subjected to Lateral Load
 
Analysis of 3d RC Frame on Sloping Ground
Analysis of 3d RC Frame on Sloping GroundAnalysis of 3d RC Frame on Sloping Ground
Analysis of 3d RC Frame on Sloping Ground
 
IRJET- Effect of Steel Ratio and Mineral Admixtures on Short Columns
IRJET- Effect of Steel Ratio and Mineral Admixtures on Short ColumnsIRJET- Effect of Steel Ratio and Mineral Admixtures on Short Columns
IRJET- Effect of Steel Ratio and Mineral Admixtures on Short Columns
 
Analysis For Retrofitting Of An Existing Failed RC Column Using FEM Software’s
Analysis For Retrofitting Of An Existing Failed RC Column Using FEM Software’sAnalysis For Retrofitting Of An Existing Failed RC Column Using FEM Software’s
Analysis For Retrofitting Of An Existing Failed RC Column Using FEM Software’s
 

Último

UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and workingUNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
rknatarajan
 
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Dr.Costas Sachpazis
 
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Christo Ananth
 
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
dollysharma2066
 

Último (20)

(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7
(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7
(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7
 
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and workingUNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
 
Roadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and RoutesRoadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and Routes
 
Thermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.pptThermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.ppt
 
Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024
 
Unit 1 - Soil Classification and Compaction.pdf
Unit 1 - Soil Classification and Compaction.pdfUnit 1 - Soil Classification and Compaction.pdf
Unit 1 - Soil Classification and Compaction.pdf
 
UNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its PerformanceUNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its Performance
 
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
 
Thermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - VThermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - V
 
Glass Ceramics: Processing and Properties
Glass Ceramics: Processing and PropertiesGlass Ceramics: Processing and Properties
Glass Ceramics: Processing and Properties
 
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
 
Thermal Engineering Unit - I & II . ppt
Thermal Engineering  Unit - I & II . pptThermal Engineering  Unit - I & II . ppt
Thermal Engineering Unit - I & II . ppt
 
UNIT-IFLUID PROPERTIES & FLOW CHARACTERISTICS
UNIT-IFLUID PROPERTIES & FLOW CHARACTERISTICSUNIT-IFLUID PROPERTIES & FLOW CHARACTERISTICS
UNIT-IFLUID PROPERTIES & FLOW CHARACTERISTICS
 
Extrusion Processes and Their Limitations
Extrusion Processes and Their LimitationsExtrusion Processes and Their Limitations
Extrusion Processes and Their Limitations
 
chapter 5.pptx: drainage and irrigation engineering
chapter 5.pptx: drainage and irrigation engineeringchapter 5.pptx: drainage and irrigation engineering
chapter 5.pptx: drainage and irrigation engineering
 
PVC VS. FIBERGLASS (FRP) GRAVITY SEWER - UNI BELL
PVC VS. FIBERGLASS (FRP) GRAVITY SEWER - UNI BELLPVC VS. FIBERGLASS (FRP) GRAVITY SEWER - UNI BELL
PVC VS. FIBERGLASS (FRP) GRAVITY SEWER - UNI BELL
 
Call Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance BookingCall Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance Booking
 
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
 
(INDIRA) Call Girl Bhosari Call Now 8617697112 Bhosari Escorts 24x7
(INDIRA) Call Girl Bhosari Call Now 8617697112 Bhosari Escorts 24x7(INDIRA) Call Girl Bhosari Call Now 8617697112 Bhosari Escorts 24x7
(INDIRA) Call Girl Bhosari Call Now 8617697112 Bhosari Escorts 24x7
 
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
 

Nonlinear Static Analysis Of 3-D RC Framed Asymmetric Building With Lead Rubber Isolator Using Sap2000v15

  • 1. Mohammed Asim Khan Int. Journal of Engineering Research and Applications www.ijera.com ISSN : 2248-9622, Vol. 4, Issue 9( Version 4), September 2014, pp.87-91 www.ijera.com 87 | P a g e Nonlinear Static Analysis Of 3-D RC Framed Asymmetric Building With Lead Rubber Isolator Using Sap2000v15 Mohammed Asim Khan*, Prof. Shaik Abdulla** *(P.G Student of Structural Engineering, Department of Civil Engineering, Khaja Banda Nawaz College of Engineering, Gulbarga, Karnataka, India -585104 ** Associate Prof. Shaikh Abdulla, Department of Civil Engineering, Khaja Banda Nawaz College of Engineering, Gulbarga, Karnataka, India -585104 ABSTRACT Many buildings in the present scenario have irregular configurations both in plan and elevation. This in future may be subjected to devastating earthquakes. So it is also necessary to enhance the seismic performance of asymmetric buildings by using seismic control techniques. In the present study a total of 9 models, asymmetrical in plan (L-shape) are taken for analysis to cover the broader spectrum of low, medium & high rise buildings for the seismic control of the structures using pushover analysis, two different techniques were considered such as lead rubber bearing isolator and masonry infill walls, the analysis has been carried out using SAP2000V15. The results of bare frame and other building models have been compared, the presence of lead rubber base isolator, top story drift get reduced as compared with masonry infill wall. The trend was found to be reversed for high rise buildings especially with the application of isolation systems due to the massive increase in the story displacements suggesting the ineffectiveness of the base isolators for high rise buildings successively the plastic hinge pattern formed after carrying out the pushover analysis was also studied which indicated that structural performance was considerably improved. Keywords – bare frame, lead rubber bearing isolator, masonry infill I. INTRODUCTION The buildings with regular geometry and uniformly distributed mass and stiffness in plan as well as in elevation suffer much less damage compared to irregular configurations. The promise of nonlinear static analysis that is pushover analysis is to produce structures with predictable seismic performance. Seismic isolation is relatively recent and evolving technology. The main feature of the base isolation technology is that it introduces flexibility in the structures. Advantages of lead rubber isolator with RC framed buildings properly designed and detailed buildings with lead rubber base isolator shown good response in past earthquakes. Although infill panels considerably enrich both the strength and stiffness of the frame, because of lack of knowledge of the multiple behavior of the frame and infill, their influence is not taken into account. Hence the structural action of infill walls cannot be neglected. Therefore, masonry infill panel should be considered as structural element. The main aim of the present study is to illustrate the effect of base isolation and masonry infill wall as shell element on the response of low, medium and high rise L-shape asymmetric buildings. II. DESCRIPTION OF STRUCTURAL MODELS In this study, a total number of 9 different models of 5, 10 and 15 story R.C framed buildings are considered for analysis, the building has seven bays in X direction and five bays in Y direction with the plan dimension 28 m x 20 m and a story height of 3.5 m each in all the floors. The building is kept asymmetric in plan. The alignment and size of column is kept same throughout the height of the structure. The building is considered to be located in zone IV. The building is founded on medium strength soil through isolated footing under the columns. Elastic moduli of concrete and masonry are taken as 25000 MPa and 3500 MPa respectively and their poisons ratio as 0.20 and 0.17 respectively. The unit weights of concrete and masonry are taken as 25.0 KN/m3 and 20.0 KN/m3 respectively the floor finish on the floors is 1.0 KN/m2. The live load on floor is taken as 3.5 KN/m2. In seismic weight calculations, 50% of the floor live loads considered. Thickness of slab and masonry infill wall as 0.120 m and 0.23 m respectively. The base isolation used in this study is New Zealand rubber bearing system [6]. Nonlinear static analysis is used on both of fixed base and base isolated buildings. In fixed base condition, all of structures are considered in elastic stage and in base- isolated condition, the superstructure of the building RESEARCH ARTICLE OPEN ACCESS
  • 2. Mohammed Asim Khan Int. Journal of Engineering Research and Applications www.ijera.com ISSN : 2248-9622, Vol. 4, Issue 9( Version 4), September 2014, pp.87-91 www.ijera.com 88 | P a g e is considered in elastic stage and base isolator is considered in inelastic stage. III. ANALYTICAL MODELS CONSIDERED FOR ANALYSIS Model 5A: Five story bare frame with fixed base. However masses of the walls (230mm thick) are included on all stories. Model 5B: Five story bare frame with Lead Rubber Isolator. However masses of the walls (230mm thick) are included on all stories. Model 5C: Five story building with fixed base has masonry infill wall as shell element in all the stories. Model 10A: Ten story bare frame with fixed base. However masses of the walls (230mm thick) are included on all stories. Model 10B: Ten story bare frame with Lead Rubber Isolator. However masses of the walls (230mm thick) are included on all stories. Model 10C: Ten story building with fixed base has masonry infill wall as shell element in all the stories. Model 15A: Fifteen story bare frame with fixed base. However masses of the walls (230mm thick) are included on all stories. Model 15B: Fifteen story bare frame with Lead Rubber Isolator. However masses of the walls (230mm thick) are included on all stories. Model 15C: Fifteen story building with fixed base has masonry infill wall as shell element in all the stories. Fig1: plan Fig 2: Elevations of model 5A, 5B and 5C Fig 4: Elevations of model 15A, 15B and 15C IV. RESULTS AND DISCUSSION In this paper the results of the selected building models studies are presented. Analysis were carried out using SAP2000V15 and different parameters studied such as Fundamental natural time period, Base shear, torsional moment, story displacement and story drifts, the tables and figures are shown below. Table 1: Fundamental Natural Time Period FUNDAMENTAL NATURAL TIME PERIOD Model No. T in sec 5A 0.71886 5B 3.62464 5C 0.19853 10A 1.62007 10B 3.56055 10C 0.47643 15A 2.5934 15B 4.5859 15C 0.85854 Fig 5: Model Vs Time period for different building model It can be observed that the % increase of fundamental natural time period of model 5B, 10B and 15B are 80.16%, 54.5% and 43.44% compared to as model 5A, 10A and 15A. Also the % reduction of fundamental natural time period of model 5C, 10C and 15C are 72.38%, 70.6% and 67.09% as compared to model 5A, 10A and 15A.
  • 3. Mohammed Asim Khan Int. Journal of Engineering Research and Applications www.ijera.com ISSN : 2248-9622, Vol. 4, Issue 9( Version 4), September 2014, pp.87-91 www.ijera.com 89 | P a g e Table 2: Base Shear BASE SHEAR (KN) MODEL NO. PUSH Y dir. PUSH X dir. 5A 4096.05 4379.94 5B 656.432 744.759 5C 41175.8 43306 10A 2646.65 3148.85 10B 1995 2139.98 10C 24513.6 28136.4 15A 2093.36 2441.24 15B 1705.71 1838.96 15C 19830.4 27367.6 From table 2, it is observed that % reduction of base shear is 84%, 24.6% and 18.51% for model 5B, 10B and 15B compared to model 5A, 10A and 15A. The % increase of base shear is 90.05%, 89.20% and 89.44% for model 5C, 10C and 15C compared to model 5A, 10A and 15A along transverse direction. From table 2, it is observed that % reduction of base shear is 83%, 32.04% and 24.67% for model 5B, 10B and 15B compared to model 5A, 10A and 15A. The % increase of base shear is 89.88%, 88.8% and 91.07% for model 5C, 10C and 15C compared to model 5A, 10A and15A along longitudinal direction. Fig 6: Base Shear of all different building models along longitudinal direction Table 3:Torsional Moments From table3, it is observed that % reduction of torsional moment is 93.202%, 37.03% and 28.76% for model 5B,10B and 15B compared to model 5A,10A and 15A.and the % increase of torsional moment is 91.6%, 90.81% and 90.86% for model 5C,10C and 15C compared to model 5A,10A and 15A. From table3, it is observed that % reduction of torsional moment is 76.51%, 29.58% and 26.07% for model 5B,10B and 15B compared to model 5A,10A and 15A.and the % increase of torsional moment is 90.5%, 84.82% and 80.87% for model 5C,10C and 15C compared to model 5A,10A and 15A. Fig 7: Torsional moments of all different building models along longitudinal direction TORSIONAL MOMENTS KNm Model No. Push 1 Push2 5A 53547 55266 5B 3639.712 12982.172 5C 644398.8 581481.84 10A 36077.34 39891.105 10B 22718.07 28090.396 10C 392561.4 262899.88 15A 29587.45 30715.217 15B 21077.03 22707.117 15C 323894.6 160599.51
  • 4. Mohammed Asim Khan Int. Journal of Engineering Research and Applications www.ijera.com ISSN : 2248-9622, Vol. 4, Issue 9( Version 4), September 2014, pp.87-91 www.ijera.com 90 | P a g e Fig 8: Displacement Vs Story level for different building models along transverse direction From figure 5.12 it is observed that the maximum % increase of Lateral displacements is 93%, 94% and 91.58% for model 5B, 10B and 15B as compare to model 5A, 10A and 15A. Whereas for the lateral displacements are reduced to a maximum of 82.14%, 83.23% and 84.93% for model 5C, 10C and 15C as compare to model 5A, 10A and 15A. Fig 9: Ductility ratio for different building models along longitudinal direction Table 4: Ductility ratio and Response reduction factor along longitudinal direction Fig 10: Response reduction factor for different building models along longitudinal direction From table 4. It can be observed that the ductility ratio for model 5B is greater than the other models in both transverse and longitudinal direction. It can also be observed that the response reduction factor for model 5B is greater than the all other models in both transverse and longitudinal direction. Hence it can be concluded that the model 5B is more flexible than the other models. V. CONCLUSION 1. Fundamental natural time period increases with the use of Lead Rubber Isolation, and decreases when masonry infill wall is considered. 2. Increased flexibility of the system led to increase of the total displacements due to the elasticity of the existing isolation. 3. The presence of masonry infill influences the overall behavior of structures when subjected to lateral forces. Story displacements are considerably reduced while contribution of masonry infill wall is taken into account. 4. Ductility ratio is maximum for Lead Rubber Isolation structure i-e model-5B and for full infill building i-e model 5C, 10C and 15C it get reduced. It indicates that these structures will show adequate warning before collapse. 5. Lead Rubber Isolation structures are having highest response reduction factor as compared to infill frame structures. It indicates that Lead Rubber Isolation structures are capable of resisting the forces still after first hinge. 6. From the above study we conclude that model- 5B i-e five story asymmetric R C framed building with Lead Rubber Isolation shows better performance among the others for the given seismic parameters. 7. Model 5B shows a maximum reduction in terms of torsional moment as compare to other models. REFERENCES [1] Helmut Krawinkler and G.D.P.K. Seneviratna (1998) “Pros & Cons of Pushover Analysis of Seismic Performance Evaluation”,
  • 5. Mohammed Asim Khan Int. Journal of Engineering Research and Applications www.ijera.com ISSN : 2248-9622, Vol. 4, Issue 9( Version 4), September 2014, pp.87-91 www.ijera.com 91 | P a g e Engineering Structures, Vol. 20, Nos 4-6, pp. 452-464, 1998. [2] M A M Akberuddin (2013) “Pushover Analysis of Medium Rise Multi-Story RCC Frame With and Without Vertical Irregularity”, International Journal of Engineering Research and Application Vol. 3, Issue 5, Sep-Oct 2013, pp.540-546 [3] S.M. Kalantari, H.Naderpour and S.R.Hoseini Vaez " Investigation Of Base-Isolator Type Selection On Seismic Behavior Of Structures Including Story Drifts And Plastic Hinge Formation." The 14th World Conference on Earthquake Engineering October 12-17, 2008, Beijing, China. [4] Dakshes J. Pambhar (2012) “Performance Based Pushover Analysis of R.C.C. Frames”International Journal of Advanced Engineering Research and Studies IJAERS/Vol. I/ Issue III/April-June, 2012/329-333. [5] Ashraf Habibullah, Stephen Pyle“Practical three-dimensional non-linear static pushover analysis” Structure Magazine, winter, 1998. [6] T.K. Datta “Seismic Analysis of Structures “Indian Institute of Technology Delhi, India. [7] CSI computer and structure. Inc.SAP 2000, linear & non-linear static and dynamic analysis of 3D-structure. [8] IS 1893(part 1):2002Criteria for earthquake resistant design of structures, Part-I General Provision and Buildings (Fifth Revision). Bureau of Indian Standards, New Delhi. [9] IS 456-2000 “Indian Standard Code of Practice for plain and reinforced concrete”, Bureau of Indian Standards, New Delhi.