SlideShare una empresa de Scribd logo
1 de 6
Descargar para leer sin conexión
COLD-AISLE CONTAINMENT IN DATA CENTRES
             the smart concept for optimal energy use



                                                                                                 www.knuerr.com




                                          Application Report
                               Cold-Aisle Containment in Data Centres
                                       The smart concept for optimal energy use



 Cooling requirements in data centres are continually rising, causing conventional climate control systems to be
 overloaded.

 Switching to water cooling systems is an option, but structurally and financially this is not always possible.

 During 2007, Knürr, in cooperation with one of the largest data centre operators in Switzerland, installed and
 monitored over several months, a highly efficient cooling solution for both new and existing data centres.

 The results demonstrated that the energy costs for the output of the circulating air cooling unit (CACU) can
 be reduced by up to 90 %!

 Within one to three months, depending on original purchase, initial expenditure will be recovered through
 savings generated by increased energy efficiency.




                                                                                                                   1
COLD-AISLE CONTAINMENT IN DATA CENTRES
             the smart concept for optimal energy use



                                                                                                 www.knuerr.com



 Description of application
 Initial situation
 The data centre under review has experienced a constant rise in demand for server capacity in recent years. The
 Data Centre room is 300m², 3.2m high, with a raised floor of 0.4m and has a capacity for 350 additional production
 servers.

 The operator has provided the following information about the data centre.

   •      Cooling capacity of 1000 to 1500 W/m²
   •      Energy consumption of 1000 W/m²
   •      All IT-systems are installed with 100% dual power feed
   •      Additionally, the room has to accommodate15 freestanding systems (Disk), LAN/SAN communication to
          be implemented in 14 racks.

 Test conditions
 The raised floor provided greater energy efficiency by directing cool air through perforated plates in the cold aisle
 and by sealing the cable entry in to the racks.

 Knürr isolated the cold and hot zones within the server racks using infill panels. Both cold aisles were then
 enclosed via cold aisle containment. This process involved covering the cold aisle with transparent top covers,
 using double doors fitted with an automatic closer to seal the aisle.

 The 282 KW power loss was simulated via fan heaters, generating 30 x 9kW, and through an addition 3 racks
 populated with servers generating 12kW. This information is very important when considering the energy savings
 which can be achieved.

 The electricity supply was designed for 1500W/m² and has a 100% redundancy. It is therefore possible to obtain
 420kW of power. The supply was guaranteed using two independent UPS - systems.

 To provide n+1 cooling, six circulating air cooling units (CACU) were installed for every 60kW.
 All CACUs in operation were controlled by a specific temperature sensor within the cold zone. This guaranteed a
 consistent supply of air into the cold zones.

 To minimise the loss of circulation caused by air resistance under the raised floor, Knürr laid all cabling (power and
 network cabling) along the airflow. All holes for cables through the floor were sealed to prevent hot air shortcuts.




                                                                                                                         2
COLD-AISLE CONTAINMENT IN DATA CENTRES
             the smart concept for optimal energy use



                                                                                                  www.knuerr.com

 Test areas
  In reality many data centres are not fully populated, therefore knürr tested with a part load (ca. 180kW) and with a
  full load (ca. 280kW).

  Phase 1: The initial situation (with no energy efficiency measures)

  Phase 2: The raised floor was sealed allowing air to circulate through perforated plates in the cold aisle only and
           cable entries in the racking were also sealed.

  Phase 3: The raised floor was sealed allowing air to circulate through perforated plates in the cold aisle only and
           cable entries in the racking were also sealed; cold and hot areas within the racking were isolated using
           infill panels.

  Phase 4: The raised floor was sealed allowing air to circulate through perforated plates in the cold aisle only and
           cable entries in the racking were sealed; cold and hot areas within the racking were isolated using infill
           panels and cold aisle containment constructed.

  Phase 5: As phase 4, but with special software, allowing the fan air circulation cooling units to drive at speeds of
           30 %.

 During the entire test the temperature was 24°C in the cold aisle. This was checked and controlled via temperature
 probes, which where placed in the cold aisle.

 Results / Conclusions
 In full collaboration with the data centre operator, Knürr successfully demonstrated that cooling efficiency is
 considerably increased if the air flow in the cool and warm zones is regulated. The efficiency of the cooling process
 is greatly increased where there is a significant difference in air temperature entering and exiting the circulating air
 cooling units (CACU). This is achieved through cold aisle containment as the warm and cold zones are physically
 and constantly separated, preventing air flow short cuts.




 These tests demonstrate that energy costs for powering the circulating air cooling units(CACU) could be reduced
 from 45.600 SFr to 1.900 SFr per annum(ca. 95,8 % reduction). It is important to note that during this pilot project,
 fan heaters were used to demonstrate the cooling capacity. Fan heaters will only simulate the heat generated by
 servers, as they have a lower flow volume across the server. However when used in a fully operational data centre
 Knürr calculated that energy efficiency could still be increased by up to 70%.
                                                                                                                         3
COLD-AISLE CONTAINMENT IN DATA CENTRES
             the smart concept for optimal energy use



                                                                                                 www.knuerr.com


 These results also reveal that CACU redundancy can now be considered 2n instead of n + 1. The purchase of
 additional circulating air cooling units can be recovered within a short time period, depending on initial expenditure,
 as the air circulation cooling units can run on a lower speed, increasing energy efficiency.




 In the pilot project between Knürr and customer, the design was to reduce energy costs and increase energy
 efficiency. The secondary focus was to demonstrate that further power savings could be built into the racks, saving
 up to 10 kW per rack



                                                                                                                       4
COLD-AISLE CONTAINMENT IN DATA CENTRES
             the smart concept for optimal energy use



                                                        www.knuerr.com


 Pictures of test site




                                                                         5
COLD-AISLE CONTAINMENT IN DATA CENTRES
             the smart concept for optimal energy use



                                                                                              www.knuerr.com


 Services provided
 Using trained service personnel, Knürr is able to provide the following services:

  •   Consulting, calculation, and simulation of a solution.
  •   Simple installation into existing racks (dependent of make of rack).
  •   Integration and installation without the need for down time.
  •   Data Centres Thermal Assessment
      - Review of thermal and air flow within the data centre
      - Thermal imaging of the computing centre, several aisles and/or racks
      - Consideration of cost effective measures
      - Complete report with achievable improvements
  •   “Cold Aisle Containment” implementation of the solution
      - Oversize locally(inclusive demarcation of project specific items, especially competitor racks)
      - Creation of project plan
      - Detailed pricing offer


 Consider

 Knürr AG
 Mariakirchener Straße 38
 94424 Arnstorf
 Telefon +49 (0) 87 23-27-0
 Telefax +49 (0) 87 23-27-154
 E-Mail: info@knuerr.com
 www.knuerr.com




                                                                                                               6

Más contenido relacionado

Destacado

üBerblick maastricht
üBerblick maastrichtüBerblick maastricht
üBerblick maastrichtaim4asi
 
Bruneck preliminary pgr_131205
Bruneck preliminary pgr_131205Bruneck preliminary pgr_131205
Bruneck preliminary pgr_131205Lutz Hartmann
 
10 Ways to use OAUG Knowledge Factory
10 Ways to use OAUG Knowledge Factory10 Ways to use OAUG Knowledge Factory
10 Ways to use OAUG Knowledge FactoryMohan Dutt
 
Lehendakariaren hitzalida - Faes Farma enpresara bisita
Lehendakariaren hitzalida - Faes Farma enpresara bisitaLehendakariaren hitzalida - Faes Farma enpresara bisita
Lehendakariaren hitzalida - Faes Farma enpresara bisitaIrekia - EJGV
 
Experiencias con plantas medicinales andinas junio 2013
Experiencias con plantas medicinales andinas junio 2013Experiencias con plantas medicinales andinas junio 2013
Experiencias con plantas medicinales andinas junio 2013subcomitedemedicinatradicional
 
Improve your american english accent
Improve your american english accentImprove your american english accent
Improve your american english accentNguyễn Ánh
 
Leverage Project 2010 w/ SP2010 for PM Success @ SharePointFest Denver
Leverage Project 2010 w/ SP2010 for PM Success @ SharePointFest DenverLeverage Project 2010 w/ SP2010 for PM Success @ SharePointFest Denver
Leverage Project 2010 w/ SP2010 for PM Success @ SharePointFest DenverDux Raymond Sy
 
Las claves del alto rendimiento directivo (del deporte a la empresa)
Las claves del alto rendimiento directivo (del deporte a la empresa) Las claves del alto rendimiento directivo (del deporte a la empresa)
Las claves del alto rendimiento directivo (del deporte a la empresa) Jordi Diaz
 
ENSAYO INVESTIGACIÓN INFORMATICA
ENSAYO INVESTIGACIÓN INFORMATICAENSAYO INVESTIGACIÓN INFORMATICA
ENSAYO INVESTIGACIÓN INFORMATICAUNIANDES
 
What to expect at your disability hearing
What to expect at your disability hearingWhat to expect at your disability hearing
What to expect at your disability hearingJames Publishing
 
9 Things I've Learned About Content While Running A Content Agency
9 Things I've Learned About Content While Running A Content Agency9 Things I've Learned About Content While Running A Content Agency
9 Things I've Learned About Content While Running A Content AgencyThe Story Lab
 

Destacado (20)

üBerblick maastricht
üBerblick maastrichtüBerblick maastricht
üBerblick maastricht
 
Bruneck preliminary pgr_131205
Bruneck preliminary pgr_131205Bruneck preliminary pgr_131205
Bruneck preliminary pgr_131205
 
Propuesta evento macizo tierra de agua
Propuesta evento macizo tierra de aguaPropuesta evento macizo tierra de agua
Propuesta evento macizo tierra de agua
 
10 Ways to use OAUG Knowledge Factory
10 Ways to use OAUG Knowledge Factory10 Ways to use OAUG Knowledge Factory
10 Ways to use OAUG Knowledge Factory
 
Lehendakariaren hitzalida - Faes Farma enpresara bisita
Lehendakariaren hitzalida - Faes Farma enpresara bisitaLehendakariaren hitzalida - Faes Farma enpresara bisita
Lehendakariaren hitzalida - Faes Farma enpresara bisita
 
El plano secuencia
El plano secuenciaEl plano secuencia
El plano secuencia
 
Ficha Técnica 4Life - Sleep AMJ
Ficha Técnica 4Life - Sleep AMJFicha Técnica 4Life - Sleep AMJ
Ficha Técnica 4Life - Sleep AMJ
 
01 wikipedia areas descanso
01 wikipedia areas descanso01 wikipedia areas descanso
01 wikipedia areas descanso
 
Creating a Post-Secondary Vision
Creating a Post-Secondary VisionCreating a Post-Secondary Vision
Creating a Post-Secondary Vision
 
Marketing industrial transportes barreto
Marketing industrial  transportes barretoMarketing industrial  transportes barreto
Marketing industrial transportes barreto
 
Experiencias con plantas medicinales andinas junio 2013
Experiencias con plantas medicinales andinas junio 2013Experiencias con plantas medicinales andinas junio 2013
Experiencias con plantas medicinales andinas junio 2013
 
La noche de los lapices
La noche de los lapicesLa noche de los lapices
La noche de los lapices
 
Improve your american english accent
Improve your american english accentImprove your american english accent
Improve your american english accent
 
Leverage Project 2010 w/ SP2010 for PM Success @ SharePointFest Denver
Leverage Project 2010 w/ SP2010 for PM Success @ SharePointFest DenverLeverage Project 2010 w/ SP2010 for PM Success @ SharePointFest Denver
Leverage Project 2010 w/ SP2010 for PM Success @ SharePointFest Denver
 
Europ Assistance and Care Services
Europ Assistance and Care ServicesEurop Assistance and Care Services
Europ Assistance and Care Services
 
Las claves del alto rendimiento directivo (del deporte a la empresa)
Las claves del alto rendimiento directivo (del deporte a la empresa) Las claves del alto rendimiento directivo (del deporte a la empresa)
Las claves del alto rendimiento directivo (del deporte a la empresa)
 
Inventario libros
Inventario librosInventario libros
Inventario libros
 
ENSAYO INVESTIGACIÓN INFORMATICA
ENSAYO INVESTIGACIÓN INFORMATICAENSAYO INVESTIGACIÓN INFORMATICA
ENSAYO INVESTIGACIÓN INFORMATICA
 
What to expect at your disability hearing
What to expect at your disability hearingWhat to expect at your disability hearing
What to expect at your disability hearing
 
9 Things I've Learned About Content While Running A Content Agency
9 Things I've Learned About Content While Running A Content Agency9 Things I've Learned About Content While Running A Content Agency
9 Things I've Learned About Content While Running A Content Agency
 

Último

Mastering MySQL Database Architecture: Deep Dive into MySQL Shell and MySQL R...
Mastering MySQL Database Architecture: Deep Dive into MySQL Shell and MySQL R...Mastering MySQL Database Architecture: Deep Dive into MySQL Shell and MySQL R...
Mastering MySQL Database Architecture: Deep Dive into MySQL Shell and MySQL R...Miguel Araújo
 
08448380779 Call Girls In Civil Lines Women Seeking Men
08448380779 Call Girls In Civil Lines Women Seeking Men08448380779 Call Girls In Civil Lines Women Seeking Men
08448380779 Call Girls In Civil Lines Women Seeking MenDelhi Call girls
 
[2024]Digital Global Overview Report 2024 Meltwater.pdf
[2024]Digital Global Overview Report 2024 Meltwater.pdf[2024]Digital Global Overview Report 2024 Meltwater.pdf
[2024]Digital Global Overview Report 2024 Meltwater.pdfhans926745
 
Maximizing Board Effectiveness 2024 Webinar.pptx
Maximizing Board Effectiveness 2024 Webinar.pptxMaximizing Board Effectiveness 2024 Webinar.pptx
Maximizing Board Effectiveness 2024 Webinar.pptxOnBoard
 
Breaking the Kubernetes Kill Chain: Host Path Mount
Breaking the Kubernetes Kill Chain: Host Path MountBreaking the Kubernetes Kill Chain: Host Path Mount
Breaking the Kubernetes Kill Chain: Host Path MountPuma Security, LLC
 
🐬 The future of MySQL is Postgres 🐘
🐬  The future of MySQL is Postgres   🐘🐬  The future of MySQL is Postgres   🐘
🐬 The future of MySQL is Postgres 🐘RTylerCroy
 
Transcript: #StandardsGoals for 2024: What’s new for BISAC - Tech Forum 2024
Transcript: #StandardsGoals for 2024: What’s new for BISAC - Tech Forum 2024Transcript: #StandardsGoals for 2024: What’s new for BISAC - Tech Forum 2024
Transcript: #StandardsGoals for 2024: What’s new for BISAC - Tech Forum 2024BookNet Canada
 
Neo4j - How KGs are shaping the future of Generative AI at AWS Summit London ...
Neo4j - How KGs are shaping the future of Generative AI at AWS Summit London ...Neo4j - How KGs are shaping the future of Generative AI at AWS Summit London ...
Neo4j - How KGs are shaping the future of Generative AI at AWS Summit London ...Neo4j
 
Understanding the Laravel MVC Architecture
Understanding the Laravel MVC ArchitectureUnderstanding the Laravel MVC Architecture
Understanding the Laravel MVC ArchitecturePixlogix Infotech
 
The 7 Things I Know About Cyber Security After 25 Years | April 2024
The 7 Things I Know About Cyber Security After 25 Years | April 2024The 7 Things I Know About Cyber Security After 25 Years | April 2024
The 7 Things I Know About Cyber Security After 25 Years | April 2024Rafal Los
 
Finology Group – Insurtech Innovation Award 2024
Finology Group – Insurtech Innovation Award 2024Finology Group – Insurtech Innovation Award 2024
Finology Group – Insurtech Innovation Award 2024The Digital Insurer
 
FULL ENJOY 🔝 8264348440 🔝 Call Girls in Diplomatic Enclave | Delhi
FULL ENJOY 🔝 8264348440 🔝 Call Girls in Diplomatic Enclave | DelhiFULL ENJOY 🔝 8264348440 🔝 Call Girls in Diplomatic Enclave | Delhi
FULL ENJOY 🔝 8264348440 🔝 Call Girls in Diplomatic Enclave | Delhisoniya singh
 
The Role of Taxonomy and Ontology in Semantic Layers - Heather Hedden.pdf
The Role of Taxonomy and Ontology in Semantic Layers - Heather Hedden.pdfThe Role of Taxonomy and Ontology in Semantic Layers - Heather Hedden.pdf
The Role of Taxonomy and Ontology in Semantic Layers - Heather Hedden.pdfEnterprise Knowledge
 
Swan(sea) Song – personal research during my six years at Swansea ... and bey...
Swan(sea) Song – personal research during my six years at Swansea ... and bey...Swan(sea) Song – personal research during my six years at Swansea ... and bey...
Swan(sea) Song – personal research during my six years at Swansea ... and bey...Alan Dix
 
Injustice - Developers Among Us (SciFiDevCon 2024)
Injustice - Developers Among Us (SciFiDevCon 2024)Injustice - Developers Among Us (SciFiDevCon 2024)
Injustice - Developers Among Us (SciFiDevCon 2024)Allon Mureinik
 
08448380779 Call Girls In Diplomatic Enclave Women Seeking Men
08448380779 Call Girls In Diplomatic Enclave Women Seeking Men08448380779 Call Girls In Diplomatic Enclave Women Seeking Men
08448380779 Call Girls In Diplomatic Enclave Women Seeking MenDelhi Call girls
 
Handwritten Text Recognition for manuscripts and early printed texts
Handwritten Text Recognition for manuscripts and early printed textsHandwritten Text Recognition for manuscripts and early printed texts
Handwritten Text Recognition for manuscripts and early printed textsMaria Levchenko
 
Raspberry Pi 5: Challenges and Solutions in Bringing up an OpenGL/Vulkan Driv...
Raspberry Pi 5: Challenges and Solutions in Bringing up an OpenGL/Vulkan Driv...Raspberry Pi 5: Challenges and Solutions in Bringing up an OpenGL/Vulkan Driv...
Raspberry Pi 5: Challenges and Solutions in Bringing up an OpenGL/Vulkan Driv...Igalia
 
A Call to Action for Generative AI in 2024
A Call to Action for Generative AI in 2024A Call to Action for Generative AI in 2024
A Call to Action for Generative AI in 2024Results
 
04-2024-HHUG-Sales-and-Marketing-Alignment.pptx
04-2024-HHUG-Sales-and-Marketing-Alignment.pptx04-2024-HHUG-Sales-and-Marketing-Alignment.pptx
04-2024-HHUG-Sales-and-Marketing-Alignment.pptxHampshireHUG
 

Último (20)

Mastering MySQL Database Architecture: Deep Dive into MySQL Shell and MySQL R...
Mastering MySQL Database Architecture: Deep Dive into MySQL Shell and MySQL R...Mastering MySQL Database Architecture: Deep Dive into MySQL Shell and MySQL R...
Mastering MySQL Database Architecture: Deep Dive into MySQL Shell and MySQL R...
 
08448380779 Call Girls In Civil Lines Women Seeking Men
08448380779 Call Girls In Civil Lines Women Seeking Men08448380779 Call Girls In Civil Lines Women Seeking Men
08448380779 Call Girls In Civil Lines Women Seeking Men
 
[2024]Digital Global Overview Report 2024 Meltwater.pdf
[2024]Digital Global Overview Report 2024 Meltwater.pdf[2024]Digital Global Overview Report 2024 Meltwater.pdf
[2024]Digital Global Overview Report 2024 Meltwater.pdf
 
Maximizing Board Effectiveness 2024 Webinar.pptx
Maximizing Board Effectiveness 2024 Webinar.pptxMaximizing Board Effectiveness 2024 Webinar.pptx
Maximizing Board Effectiveness 2024 Webinar.pptx
 
Breaking the Kubernetes Kill Chain: Host Path Mount
Breaking the Kubernetes Kill Chain: Host Path MountBreaking the Kubernetes Kill Chain: Host Path Mount
Breaking the Kubernetes Kill Chain: Host Path Mount
 
🐬 The future of MySQL is Postgres 🐘
🐬  The future of MySQL is Postgres   🐘🐬  The future of MySQL is Postgres   🐘
🐬 The future of MySQL is Postgres 🐘
 
Transcript: #StandardsGoals for 2024: What’s new for BISAC - Tech Forum 2024
Transcript: #StandardsGoals for 2024: What’s new for BISAC - Tech Forum 2024Transcript: #StandardsGoals for 2024: What’s new for BISAC - Tech Forum 2024
Transcript: #StandardsGoals for 2024: What’s new for BISAC - Tech Forum 2024
 
Neo4j - How KGs are shaping the future of Generative AI at AWS Summit London ...
Neo4j - How KGs are shaping the future of Generative AI at AWS Summit London ...Neo4j - How KGs are shaping the future of Generative AI at AWS Summit London ...
Neo4j - How KGs are shaping the future of Generative AI at AWS Summit London ...
 
Understanding the Laravel MVC Architecture
Understanding the Laravel MVC ArchitectureUnderstanding the Laravel MVC Architecture
Understanding the Laravel MVC Architecture
 
The 7 Things I Know About Cyber Security After 25 Years | April 2024
The 7 Things I Know About Cyber Security After 25 Years | April 2024The 7 Things I Know About Cyber Security After 25 Years | April 2024
The 7 Things I Know About Cyber Security After 25 Years | April 2024
 
Finology Group – Insurtech Innovation Award 2024
Finology Group – Insurtech Innovation Award 2024Finology Group – Insurtech Innovation Award 2024
Finology Group – Insurtech Innovation Award 2024
 
FULL ENJOY 🔝 8264348440 🔝 Call Girls in Diplomatic Enclave | Delhi
FULL ENJOY 🔝 8264348440 🔝 Call Girls in Diplomatic Enclave | DelhiFULL ENJOY 🔝 8264348440 🔝 Call Girls in Diplomatic Enclave | Delhi
FULL ENJOY 🔝 8264348440 🔝 Call Girls in Diplomatic Enclave | Delhi
 
The Role of Taxonomy and Ontology in Semantic Layers - Heather Hedden.pdf
The Role of Taxonomy and Ontology in Semantic Layers - Heather Hedden.pdfThe Role of Taxonomy and Ontology in Semantic Layers - Heather Hedden.pdf
The Role of Taxonomy and Ontology in Semantic Layers - Heather Hedden.pdf
 
Swan(sea) Song – personal research during my six years at Swansea ... and bey...
Swan(sea) Song – personal research during my six years at Swansea ... and bey...Swan(sea) Song – personal research during my six years at Swansea ... and bey...
Swan(sea) Song – personal research during my six years at Swansea ... and bey...
 
Injustice - Developers Among Us (SciFiDevCon 2024)
Injustice - Developers Among Us (SciFiDevCon 2024)Injustice - Developers Among Us (SciFiDevCon 2024)
Injustice - Developers Among Us (SciFiDevCon 2024)
 
08448380779 Call Girls In Diplomatic Enclave Women Seeking Men
08448380779 Call Girls In Diplomatic Enclave Women Seeking Men08448380779 Call Girls In Diplomatic Enclave Women Seeking Men
08448380779 Call Girls In Diplomatic Enclave Women Seeking Men
 
Handwritten Text Recognition for manuscripts and early printed texts
Handwritten Text Recognition for manuscripts and early printed textsHandwritten Text Recognition for manuscripts and early printed texts
Handwritten Text Recognition for manuscripts and early printed texts
 
Raspberry Pi 5: Challenges and Solutions in Bringing up an OpenGL/Vulkan Driv...
Raspberry Pi 5: Challenges and Solutions in Bringing up an OpenGL/Vulkan Driv...Raspberry Pi 5: Challenges and Solutions in Bringing up an OpenGL/Vulkan Driv...
Raspberry Pi 5: Challenges and Solutions in Bringing up an OpenGL/Vulkan Driv...
 
A Call to Action for Generative AI in 2024
A Call to Action for Generative AI in 2024A Call to Action for Generative AI in 2024
A Call to Action for Generative AI in 2024
 
04-2024-HHUG-Sales-and-Marketing-Alignment.pptx
04-2024-HHUG-Sales-and-Marketing-Alignment.pptx04-2024-HHUG-Sales-and-Marketing-Alignment.pptx
04-2024-HHUG-Sales-and-Marketing-Alignment.pptx
 

Cold Aisle Containment – How To Save Energy In The Data Center

  • 1. COLD-AISLE CONTAINMENT IN DATA CENTRES the smart concept for optimal energy use www.knuerr.com Application Report Cold-Aisle Containment in Data Centres The smart concept for optimal energy use Cooling requirements in data centres are continually rising, causing conventional climate control systems to be overloaded. Switching to water cooling systems is an option, but structurally and financially this is not always possible. During 2007, Knürr, in cooperation with one of the largest data centre operators in Switzerland, installed and monitored over several months, a highly efficient cooling solution for both new and existing data centres. The results demonstrated that the energy costs for the output of the circulating air cooling unit (CACU) can be reduced by up to 90 %! Within one to three months, depending on original purchase, initial expenditure will be recovered through savings generated by increased energy efficiency. 1
  • 2. COLD-AISLE CONTAINMENT IN DATA CENTRES the smart concept for optimal energy use www.knuerr.com Description of application Initial situation The data centre under review has experienced a constant rise in demand for server capacity in recent years. The Data Centre room is 300m², 3.2m high, with a raised floor of 0.4m and has a capacity for 350 additional production servers. The operator has provided the following information about the data centre. • Cooling capacity of 1000 to 1500 W/m² • Energy consumption of 1000 W/m² • All IT-systems are installed with 100% dual power feed • Additionally, the room has to accommodate15 freestanding systems (Disk), LAN/SAN communication to be implemented in 14 racks. Test conditions The raised floor provided greater energy efficiency by directing cool air through perforated plates in the cold aisle and by sealing the cable entry in to the racks. Knürr isolated the cold and hot zones within the server racks using infill panels. Both cold aisles were then enclosed via cold aisle containment. This process involved covering the cold aisle with transparent top covers, using double doors fitted with an automatic closer to seal the aisle. The 282 KW power loss was simulated via fan heaters, generating 30 x 9kW, and through an addition 3 racks populated with servers generating 12kW. This information is very important when considering the energy savings which can be achieved. The electricity supply was designed for 1500W/m² and has a 100% redundancy. It is therefore possible to obtain 420kW of power. The supply was guaranteed using two independent UPS - systems. To provide n+1 cooling, six circulating air cooling units (CACU) were installed for every 60kW. All CACUs in operation were controlled by a specific temperature sensor within the cold zone. This guaranteed a consistent supply of air into the cold zones. To minimise the loss of circulation caused by air resistance under the raised floor, Knürr laid all cabling (power and network cabling) along the airflow. All holes for cables through the floor were sealed to prevent hot air shortcuts. 2
  • 3. COLD-AISLE CONTAINMENT IN DATA CENTRES the smart concept for optimal energy use www.knuerr.com Test areas In reality many data centres are not fully populated, therefore knürr tested with a part load (ca. 180kW) and with a full load (ca. 280kW). Phase 1: The initial situation (with no energy efficiency measures) Phase 2: The raised floor was sealed allowing air to circulate through perforated plates in the cold aisle only and cable entries in the racking were also sealed. Phase 3: The raised floor was sealed allowing air to circulate through perforated plates in the cold aisle only and cable entries in the racking were also sealed; cold and hot areas within the racking were isolated using infill panels. Phase 4: The raised floor was sealed allowing air to circulate through perforated plates in the cold aisle only and cable entries in the racking were sealed; cold and hot areas within the racking were isolated using infill panels and cold aisle containment constructed. Phase 5: As phase 4, but with special software, allowing the fan air circulation cooling units to drive at speeds of 30 %. During the entire test the temperature was 24°C in the cold aisle. This was checked and controlled via temperature probes, which where placed in the cold aisle. Results / Conclusions In full collaboration with the data centre operator, Knürr successfully demonstrated that cooling efficiency is considerably increased if the air flow in the cool and warm zones is regulated. The efficiency of the cooling process is greatly increased where there is a significant difference in air temperature entering and exiting the circulating air cooling units (CACU). This is achieved through cold aisle containment as the warm and cold zones are physically and constantly separated, preventing air flow short cuts. These tests demonstrate that energy costs for powering the circulating air cooling units(CACU) could be reduced from 45.600 SFr to 1.900 SFr per annum(ca. 95,8 % reduction). It is important to note that during this pilot project, fan heaters were used to demonstrate the cooling capacity. Fan heaters will only simulate the heat generated by servers, as they have a lower flow volume across the server. However when used in a fully operational data centre Knürr calculated that energy efficiency could still be increased by up to 70%. 3
  • 4. COLD-AISLE CONTAINMENT IN DATA CENTRES the smart concept for optimal energy use www.knuerr.com These results also reveal that CACU redundancy can now be considered 2n instead of n + 1. The purchase of additional circulating air cooling units can be recovered within a short time period, depending on initial expenditure, as the air circulation cooling units can run on a lower speed, increasing energy efficiency. In the pilot project between Knürr and customer, the design was to reduce energy costs and increase energy efficiency. The secondary focus was to demonstrate that further power savings could be built into the racks, saving up to 10 kW per rack 4
  • 5. COLD-AISLE CONTAINMENT IN DATA CENTRES the smart concept for optimal energy use www.knuerr.com Pictures of test site 5
  • 6. COLD-AISLE CONTAINMENT IN DATA CENTRES the smart concept for optimal energy use www.knuerr.com Services provided Using trained service personnel, Knürr is able to provide the following services: • Consulting, calculation, and simulation of a solution. • Simple installation into existing racks (dependent of make of rack). • Integration and installation without the need for down time. • Data Centres Thermal Assessment - Review of thermal and air flow within the data centre - Thermal imaging of the computing centre, several aisles and/or racks - Consideration of cost effective measures - Complete report with achievable improvements • “Cold Aisle Containment” implementation of the solution - Oversize locally(inclusive demarcation of project specific items, especially competitor racks) - Creation of project plan - Detailed pricing offer Consider Knürr AG Mariakirchener Straße 38 94424 Arnstorf Telefon +49 (0) 87 23-27-0 Telefax +49 (0) 87 23-27-154 E-Mail: info@knuerr.com www.knuerr.com 6