Machine Response During System Disturbances
(By Sarath Chandrasiri)
1. System Disturbances: A system disturbance can be defined as any event that
causes the frequency and/or voltage of the system to deviate from the normal range of
operation. These are caused by incidents such as occurrence of short circuits,
generator trips, feeder trips, sudden increase of power output of a generator due to a
defect in its control system.
The responses of the healthy machines for such events should be so as to return the
system to the normal status as quickly as possible and with as little manual
intervention as possible. Therefore, the response of machines is of utmost importance
from the point of view of system security and reliability.
Machine response to system disturbances: The response of machines should be
considered from two main aspects.
1. Load- frequency response (Governor response)
2. MVAR – Voltage response (AVR response)
Only the first will be considered below.
2. Load- frequency response (Governor response)
The frequency and load response of a machine that remains connected to the system
during the event is shown below:
fdev_dyn= Dynamic frequency deviation
Δf = Quasi steady state frequency deviation
Machine
Load
t
Page 1
f1
fdev_dyn
0 t1 t2 t3 t4
Δf
t
f
B
A
Fig 1 – Frequency variation of a machine after disturbance
The response can be considered to be in 4 stages.
i. Initial response
ii. Primary response
iii. Secondary response
iv. Final stage due to manual action or automatic action through a power system
controller.
These will now be considered in detail.
3. Initial Response (period from t=0 to t=t1 sec)
The initial response of the machine lasts between 0.5 to a few seconds depending on
the speed of response of the machine governors and the system involved. In the case
of the Bahrain system the initial response time duration is between 0.5 and 1 sec.
This period occurs immediately after the incident and the response comes due to the
kinetic energy of the GT rotor (GT + generator). The governor has not started
responding yet. Since any governor, however fast, has a mechanical device (fuel
control valve) as the final element, the response will be delayed due to the inertia of
the mechanical parts.
If the incident is due to a generation loss then the rest of the machines in the system
make a contribution to compensate for the short fall. As given before, the governor
has no time to respond and the opening of the fuel control valve remains unchanged
during this period. Then from where does the energy required for the increased output
of the generators come? It comes from the kinetic energy stored in the generator
rotors. A contribution also comes from the rotating loads such as induction motors
which is produced as a result a decrease in the KE stored in their rotors.
The frequency of the system falls linearly during the period as the stored kinetic
energy is converted to electrical energy.
Telec
=
Opposing
Torque of
Generator
Mover
Tmech
=
Mechanical
Torque of
Prime
Mover
Mover
SHAFT of
Moment of
Inertia I
Page 2
FIG-2
To analyze the situation consider Fig-2, which gives the torques acting on the
Machine shaft.
Tnett =Tmech – Telec = I dω/dt
where ωis the shaft angular speed in radians/sec.
Under normal system conditions, Tnett = 0 as Tmech = Telec. Therefore, ω
remains constant and consequently, the kinetic energy of the rotor remains constant.
Before analyzing the behavior of the generator after the disturbance, occurs it is useful
to consider some basic ideas.
For ease of analysis, it is useful to consider the process to be consisting of 2 different
periods:
1. Pre fault period (t<0)
2. Post fault period (t>0)
The disturbance is considered to occur at the instant t = 0.
Certain physical quantities remain constant as the pre-fault stage ends and the post
fault stage begins while other quantities undergo an abrupt change (step change) at
t=0.
Physical quantities that do not undergo any step change at t=0: These are
associated with energy. It is a physical principle that the energy of a system cannot be
changed abruptly as this would mean that dE/dt (Power) is infinite.
Thus the following quantities do not undergo step changes at t=0.
a) Kinetic energy of the rotor
b) Speed (and hence system frequency)
c) The nett magnetic flux in the direct axis of the generator
d) Mechanical torque produced by the GT.
Physical quantities that undergo a step change at t=0: Some of these are as
follows:
a) Electrical power output of the generator
b) Reverse torque generated by the generator.
c) Generator terminal voltage and current
Page 3
During this period Tnett < 0 as Tmech < Telec. Thus ω decreases linearly as
shown below.
is negative but constant.
Tnett = I dω/dt
dω/dt = Tnett/I (a constant)
The shaft decelerates from a speed corresponding to the rated frequency of f Hz to
one corresponding to f1 Hz.
Storage of Kinetic Energy in the Rotor
Due to its moment of inertia the rotor stores kinetic energy.
KE energy stored in the rotor (EKE) = ½ I ω2
X 10-6
(MJ)
The power available from the shaft can be obtained by differentiating the above.
Rotor Power (EKE) = I ω . dω/dt X 10-6
MW
As shown in the diagram below this power can flow both ways.
• When the speed is decreasing the KE is converted to Electrical Power.
• When the speed is increasing the Mechanical Power is converted to KE.
When the system is considered as a whole the recovery process depends on the
Kinetic energy of the Generating sets and the Motors connected as loads.
Page 4
FIG-3
4. The H-Constant
It is useful to define a quantity called H which is directly proportional to the Moment
of Inertia I of the rotor.
If the f0 is the rated frequency in Hz (50 Hz)
Pn the Rated Load in MW
KE0 the Kinetic Energy of the rotor in MWs
Then H=( KE0 / Pn)
The advantage of using the H constant is that it is essentially independent of the
generator size. Typical values of H lie in the range 2 to 8 sec.
Initial rate of decrease of frequency = (df/dt)0 = ΔPf0/2H
Thus the rate of drop of frequency will increase with decreasing H and increasing ΔP
(pu).
Therefore, it is advantageous to have a high H.
5. Primary Response (period from t= t1 to t=t3 sec)
At the beginning of this period the fuel control valve starts to move, increasing its
opening in response to the output signal from the governor (PRIMARY
CONTROLLER), which increases in response to the drop in frequency.
With the increased flow of fuel, the Mechanical Torque of the GT (Tmech) starts to
increase and at point B on the graph in Fig -1 it Tmech becomes equal to Telec .
Therefore at this point deceleration of the shaft ceases.
The controller continues to increase its output signal and the shaft accelerates back to
a speed corresponding to a freq of f2 Hz. However, the controller cannot bring the
frequency back to f due to the droop of the control system, which is explained in the
next section.
During this period the primary controllers alter the power delivered by the generators
until a balance is re-established between the load power and the generated power. The
period is characterized by oscillatory phenomena due to the dynamic response of the
controllers and the process.
Dynamic Frequency Deviation (fdev_dyn): The magnitude of this (See Fig-1) depends
on the following:
• The magnitude of the disturbance
Page 5
• KE of rotating machines in the system
• The primary controller reserve of all generators
• Dynamic characteristics of the machines (including controllers)
• Dynamic characteristics of the loads, particularly the self regulating effect
loads.
Quasi Steady State Frequency Deviation (Δf): The magnitude of this (See Fig-1)
depends on the following:
The magnitude of the disturbance
Power – frequency characteristic of the system
6. Secondary Response (period from to t=t3 to t4 sec)
During this period, the generator operates at a steady frequency of f2 Hz, which is less
than the rated frequency Δf = (f-f2) H z. The magnitude of Δf depends on the Speed
Droop of the governor.
Speed Droop: The steady state Load vs. frequency characteristic of the governor
system has a drooping characteristic, which is built in to achieve stable operation of
the generators ting in parallel.
FIG-4
The interpretation of the above speed droops is as follows:
Page 6
If the machine is operating initially at 50% load and a frequency of 50 Hz and a
disturbance occurs, which causes a steady state drop of frequency by 0.5 % (0.25
Hz), then the steady state load rise would be,
• 10% if the droop was 5% and
• 25% if the droop was 2%.
In general the droop SG of a generator is defined as follows:
Under steady state (secondary response) conditions,
Δ PG = The change in load due to Primary Control action
PGn = Rated Load
Δf = The change in frequency that is necessary for the Primary Controller to
produce the above load change
f0= Rated frequency
Then, SG = (-Δf / f0) / (Δ PG / PGn) in %
The – sign takes care of the fact that a negative Δf produces a positive Δ PG and vice
versa, provided the Primary Control Reserve has not been completely used up (see
below).
FIG-5
The contribution of a generator to a system disturbance depends mainly upon
• The Droop
• The Primary Control Reserve
Referring to FIG-5, in case of a minor disturbance (frequency offset < ΔfB ) the
contribution of generator a (which has the controller with a smaller droop) will be
greater than that of generator b which has the controller with the smaller droop.
Page 7
fA
fB
fN
PMAX
fN = Rated Freq
In case of a major disturbance (frequency offset > ΔfB ), the contributions of both
generators to PRIMARY CONTROL under quasi – steady-state conditions will be
equal.
The operation of the system though stable in terms of frequency and voltage is not
acceptable for an extended period as the above parameters would be out of their
normal range.
It is also undesirable from the point of view of power flow in the tie lines (if there are
any) as the actual active and reactive power flows are different from the specified
levels.
Furthermore, since the system frequency and voltage are lower than rated there is a
possibility that those of the system stability will be lost if another disturbance occurs.
Due to these reasons it is necessary to restore the frequency and voltage to rated levels
as soon as possible. This can be done manually or through a power system controller.
In the secondary response period the governor load set points are adjusted by the
operators to bring the system frequency back to normal.
Final Response:
7. Dead Band: Usually there is a provision in the governor control system to
introduce a dead band. The dead band makes the controller insensitive to small band
of frequency changes (Ex 0.1 Hz) around the rated frequency.
The dead band serves the following purposes:
• Immunity to power system noise: If the GT is is only to play a stabilizing
role when large frequency deviations occur, the dead band can be switched on
to obtain some insensitivity to frequency. The governor would not react to
frequency deviations adjustable over a range of ±0.5 Hz from the set point
frequency. The dead band functions only when the machine is on load.
• In interconnected systems, where a stable system frequency with very narrow
tolerances (± 0.05 Hz) and closely defined cross border tie line power between
subsystems are required the dead band merely suppresses the power system
noise.
• Lower thermal loading of the turbine blades: Turbine blades are highly
susceptible to temperature gradients. Therefore, the dead band provides a way
of suppressing constant changes of turbine inlet temperature to some extent.
This prolongs the life of the blades.
• Compressor surges: The dead band also has the effect of keeping the
operating point away from the point at which the compressor surge protection
starts to operate.
Page 8
Prepared by K. A. Chandrasiri
Senior General Engineer
Office of the Director of Electricity Production
Page 9
References:
Electrical Energy Systems Theory by Olle L. Elgerd
Transient Processes in Electrical Systems by V. Venikov
Page 10

Más contenido relacionado

La actualidad más candente

Advanced control techniques for the brushless permanent magnet ac motor by po...
Advanced control techniques for the brushless permanent magnet ac motor by po...Advanced control techniques for the brushless permanent magnet ac motor by po...
Advanced control techniques for the brushless permanent magnet ac motor by po...
IIT Roorkee
 

La actualidad más candente (19)

FREQUENCY STABILITY
FREQUENCY STABILITYFREQUENCY STABILITY
FREQUENCY STABILITY
 
Control of Direct Current Machine by the Change of Resistance in Armature Cir...
Control of Direct Current Machine by the Change of Resistance in Armature Cir...Control of Direct Current Machine by the Change of Resistance in Armature Cir...
Control of Direct Current Machine by the Change of Resistance in Armature Cir...
 
Maintopik3
Maintopik3Maintopik3
Maintopik3
 
Unit 1 Power System Stability
Unit 1 Power System Stability Unit 1 Power System Stability
Unit 1 Power System Stability
 
Indirect Vector Control of Induction Motor Using Pi Speed Controller and Neur...
Indirect Vector Control of Induction Motor Using Pi Speed Controller and Neur...Indirect Vector Control of Induction Motor Using Pi Speed Controller and Neur...
Indirect Vector Control of Induction Motor Using Pi Speed Controller and Neur...
 
Classification Of Power System Stability
Classification Of Power System StabilityClassification Of Power System Stability
Classification Of Power System Stability
 
Introduction to control system
Introduction to control systemIntroduction to control system
Introduction to control system
 
Power System Control
Power System ControlPower System Control
Power System Control
 
POINT ON WAVE SWITCHING
POINT ON WAVE SWITCHINGPOINT ON WAVE SWITCHING
POINT ON WAVE SWITCHING
 
Power system stability
Power system stabilityPower system stability
Power system stability
 
Eet3082 binod kumar sahu lecturer_17
Eet3082 binod kumar sahu lecturer_17Eet3082 binod kumar sahu lecturer_17
Eet3082 binod kumar sahu lecturer_17
 
P1111146023
P1111146023P1111146023
P1111146023
 
Different methods of pwm for inverter control
Different methods of pwm for inverter controlDifferent methods of pwm for inverter control
Different methods of pwm for inverter control
 
Advanced control techniques for the brushless permanent magnet ac motor by po...
Advanced control techniques for the brushless permanent magnet ac motor by po...Advanced control techniques for the brushless permanent magnet ac motor by po...
Advanced control techniques for the brushless permanent magnet ac motor by po...
 
2015 12-02-optiwind-inertial response-u_gent
2015 12-02-optiwind-inertial response-u_gent2015 12-02-optiwind-inertial response-u_gent
2015 12-02-optiwind-inertial response-u_gent
 
Speed control of dc motor
Speed control of dc motorSpeed control of dc motor
Speed control of dc motor
 
Anees ppt on hcc
Anees ppt on hccAnees ppt on hcc
Anees ppt on hcc
 
International Refereed Journal of Engineering and Science (IRJES)
International Refereed Journal of Engineering and Science (IRJES)International Refereed Journal of Engineering and Science (IRJES)
International Refereed Journal of Engineering and Science (IRJES)
 
1.general block diagram
1.general block diagram1.general block diagram
1.general block diagram
 

Destacado

Princípios de liderança bíblica em elias 5
Princípios de liderança bíblica em elias   5Princípios de liderança bíblica em elias   5
Princípios de liderança bíblica em elias 5
Vilmar Nascimento
 
Isha Arogya Information
Isha Arogya InformationIsha Arogya Information
Isha Arogya Information
Isha Outreach
 

Destacado (19)

Ajuda ao apocalipse
Ajuda ao apocalipseAjuda ao apocalipse
Ajuda ao apocalipse
 
Princípios de liderança bíblica em elias 5
Princípios de liderança bíblica em elias   5Princípios de liderança bíblica em elias   5
Princípios de liderança bíblica em elias 5
 
diplome du bachelor
diplome du bachelordiplome du bachelor
diplome du bachelor
 
Como se Beneficiar dos Resultados Locais do Google
Como se Beneficiar dos Resultados Locais do GoogleComo se Beneficiar dos Resultados Locais do Google
Como se Beneficiar dos Resultados Locais do Google
 
131101 basis netwerkbijeenkomst presentatie
131101 basis netwerkbijeenkomst presentatie131101 basis netwerkbijeenkomst presentatie
131101 basis netwerkbijeenkomst presentatie
 
Demonstrate Your Value and Get Paid for It - Marketwerks
Demonstrate Your Value and Get Paid for It   - MarketwerksDemonstrate Your Value and Get Paid for It   - Marketwerks
Demonstrate Your Value and Get Paid for It - Marketwerks
 
Select brands
Select brandsSelect brands
Select brands
 
Liberalismo 3.0: o terceiro ciclo de descentralização da humanidade
Liberalismo 3.0:  o terceiro ciclo de descentralização da humanidadeLiberalismo 3.0:  o terceiro ciclo de descentralização da humanidade
Liberalismo 3.0: o terceiro ciclo de descentralização da humanidade
 
Palestra: Treinamento Google Analytics
Palestra: Treinamento Google AnalyticsPalestra: Treinamento Google Analytics
Palestra: Treinamento Google Analytics
 
Investment Funds Regime in Guernsey 21 July 2016
Investment Funds Regime in Guernsey 21 July 2016Investment Funds Regime in Guernsey 21 July 2016
Investment Funds Regime in Guernsey 21 July 2016
 
Customer or Product? ownership and control of personal data
Customer or Product? ownership and control of personal dataCustomer or Product? ownership and control of personal data
Customer or Product? ownership and control of personal data
 
Isha Arogya Information
Isha Arogya InformationIsha Arogya Information
Isha Arogya Information
 
Xo Overview Jason 7.21.11
Xo Overview Jason 7.21.11Xo Overview Jason 7.21.11
Xo Overview Jason 7.21.11
 
Scooby Doo
Scooby DooScooby Doo
Scooby Doo
 
Guernsey CPD Company Law and Registry Update 14 September 16
Guernsey CPD Company Law and Registry Update 14 September 16Guernsey CPD Company Law and Registry Update 14 September 16
Guernsey CPD Company Law and Registry Update 14 September 16
 
Apresentacao Comite de Metricas IAB - Maio/2012
Apresentacao Comite de Metricas IAB - Maio/2012Apresentacao Comite de Metricas IAB - Maio/2012
Apresentacao Comite de Metricas IAB - Maio/2012
 
Nobel piece prize
Nobel piece prizeNobel piece prize
Nobel piece prize
 
Framework GSM para Pruebas Automatizadas
Framework GSM para Pruebas AutomatizadasFramework GSM para Pruebas Automatizadas
Framework GSM para Pruebas Automatizadas
 
Curso: Redes y telecomunicaciones: 06 Protocolo IPv4
Curso: Redes y telecomunicaciones: 06 Protocolo IPv4Curso: Redes y telecomunicaciones: 06 Protocolo IPv4
Curso: Redes y telecomunicaciones: 06 Protocolo IPv4
 

Similar a Machine response

Welcome to International Journal of Engineering Research and Development (IJERD)
Welcome to International Journal of Engineering Research and Development (IJERD)Welcome to International Journal of Engineering Research and Development (IJERD)
Welcome to International Journal of Engineering Research and Development (IJERD)
IJERD Editor
 
Presentazione Luce Sul Blackout Inglese
Presentazione Luce Sul Blackout InglesePresentazione Luce Sul Blackout Inglese
Presentazione Luce Sul Blackout Inglese
5a.blackout
 

Similar a Machine response (20)

M0104198105
M0104198105M0104198105
M0104198105
 
Yasser.pptx
Yasser.pptxYasser.pptx
Yasser.pptx
 
LOAD FREQUENCY CONTROL USING ELECTRIC VEICHLE SYSTEM IN INTERCONNECTED POWER ...
LOAD FREQUENCY CONTROL USING ELECTRIC VEICHLE SYSTEM IN INTERCONNECTED POWER ...LOAD FREQUENCY CONTROL USING ELECTRIC VEICHLE SYSTEM IN INTERCONNECTED POWER ...
LOAD FREQUENCY CONTROL USING ELECTRIC VEICHLE SYSTEM IN INTERCONNECTED POWER ...
 
SPEED GOVERNOR SYSYTEM AND ITS DERIVATIONS
SPEED GOVERNOR SYSYTEM AND ITS DERIVATIONSSPEED GOVERNOR SYSYTEM AND ITS DERIVATIONS
SPEED GOVERNOR SYSYTEM AND ITS DERIVATIONS
 
Control of active power &amp; reactive power
Control of active power &amp; reactive powerControl of active power &amp; reactive power
Control of active power &amp; reactive power
 
Power System Frequency
Power System Frequency Power System Frequency
Power System Frequency
 
Aa4103156160
Aa4103156160Aa4103156160
Aa4103156160
 
L01_EEE_4243.pptx
L01_EEE_4243.pptxL01_EEE_4243.pptx
L01_EEE_4243.pptx
 
H1101046875
H1101046875H1101046875
H1101046875
 
CONTROL MATLAB1.pptx
CONTROL MATLAB1.pptxCONTROL MATLAB1.pptx
CONTROL MATLAB1.pptx
 
A voltage sensitivity index application for power system load shedding consid...
A voltage sensitivity index application for power system load shedding consid...A voltage sensitivity index application for power system load shedding consid...
A voltage sensitivity index application for power system load shedding consid...
 
Load shedding in power system considering the generator control and AHP algor...
Load shedding in power system considering the generator control and AHP algor...Load shedding in power system considering the generator control and AHP algor...
Load shedding in power system considering the generator control and AHP algor...
 
Welcome to International Journal of Engineering Research and Development (IJERD)
Welcome to International Journal of Engineering Research and Development (IJERD)Welcome to International Journal of Engineering Research and Development (IJERD)
Welcome to International Journal of Engineering Research and Development (IJERD)
 
Presentazione Luce Sul Blackout Inglese
Presentazione Luce Sul Blackout InglesePresentazione Luce Sul Blackout Inglese
Presentazione Luce Sul Blackout Inglese
 
Comprehensive Approach Towards Modelling and Simulation of Single Area Power...
Comprehensive Approach Towards Modelling and Simulation of  Single Area Power...Comprehensive Approach Towards Modelling and Simulation of  Single Area Power...
Comprehensive Approach Towards Modelling and Simulation of Single Area Power...
 
Swing equation
Swing equationSwing equation
Swing equation
 
Automatic Load Frequency Control ppt.pdf
Automatic Load Frequency Control ppt.pdfAutomatic Load Frequency Control ppt.pdf
Automatic Load Frequency Control ppt.pdf
 
Transient enhancement technique
Transient enhancement techniqueTransient enhancement technique
Transient enhancement technique
 
1 power system dyn (2)we
1 power system dyn  (2)we1 power system dyn  (2)we
1 power system dyn (2)we
 
Automatic Generation Control
Automatic Generation ControlAutomatic Generation Control
Automatic Generation Control
 

Más de Private Consultants

Más de Private Consultants (20)

GIS BASED SUITABLE SITE SELECTION FOR FLOATING SOLAR POWER PLANT CASE STUDY;...
GIS BASED SUITABLE SITE SELECTION FOR FLOATING SOLAR  POWER PLANT CASE STUDY;...GIS BASED SUITABLE SITE SELECTION FOR FLOATING SOLAR  POWER PLANT CASE STUDY;...
GIS BASED SUITABLE SITE SELECTION FOR FLOATING SOLAR POWER PLANT CASE STUDY;...
 
Sri-Lanka-Energy-Program-EPRI-Energy-Storage-Webinar-Series-Session-4.pdf
Sri-Lanka-Energy-Program-EPRI-Energy-Storage-Webinar-Series-Session-4.pdfSri-Lanka-Energy-Program-EPRI-Energy-Storage-Webinar-Series-Session-4.pdf
Sri-Lanka-Energy-Program-EPRI-Energy-Storage-Webinar-Series-Session-4.pdf
 
Mobilizing Renewable Energy to Overcome the Energy and Financial Crisis: The ...
Mobilizing Renewable Energy to Overcome the Energy and Financial Crisis: The ...Mobilizing Renewable Energy to Overcome the Energy and Financial Crisis: The ...
Mobilizing Renewable Energy to Overcome the Energy and Financial Crisis: The ...
 
Beautiful.pps
Beautiful.ppsBeautiful.pps
Beautiful.pps
 
ACHIEVING THE VISION OF 80 PERCENT RENEWABLES BY 2030 SRILANKA
ACHIEVING THE VISION OF 80 PERCENT RENEWABLES BY 2030 SRILANKAACHIEVING THE VISION OF 80 PERCENT RENEWABLES BY 2030 SRILANKA
ACHIEVING THE VISION OF 80 PERCENT RENEWABLES BY 2030 SRILANKA
 
Solar Power Technology in India by S Kumar
Solar Power Technology in India by S Kumar Solar Power Technology in India by S Kumar
Solar Power Technology in India by S Kumar
 
Report of the committee appointed to investigate the Electricity Supply Inter...
Report of the committee appointed to investigate the Electricity Supply Inter...Report of the committee appointed to investigate the Electricity Supply Inter...
Report of the committee appointed to investigate the Electricity Supply Inter...
 
Life Four Elements. New Year wish
Life Four Elements. New Year wish Life Four Elements. New Year wish
Life Four Elements. New Year wish
 
NDC of sri lanka
NDC of sri lankaNDC of sri lanka
NDC of sri lanka
 
Powering sri lanka towards sustainability (Cabraal 03 Apr17)
Powering sri lanka towards sustainability (Cabraal 03 Apr17)Powering sri lanka towards sustainability (Cabraal 03 Apr17)
Powering sri lanka towards sustainability (Cabraal 03 Apr17)
 
December 2016 bio gas+ newsletter
December 2016 bio gas+ newsletterDecember 2016 bio gas+ newsletter
December 2016 bio gas+ newsletter
 
Conversion of Seawater and Carbon Dioxide into Biofuel/Food and Sweet Water, ...
Conversion of Seawater and Carbon Dioxide into Biofuel/Food and Sweet Water, ...Conversion of Seawater and Carbon Dioxide into Biofuel/Food and Sweet Water, ...
Conversion of Seawater and Carbon Dioxide into Biofuel/Food and Sweet Water, ...
 
Net energy metering manual for three schemes
Net energy metering manual for three schemesNet energy metering manual for three schemes
Net energy metering manual for three schemes
 
Agreements for Net metering, Net accounting, Net plus
Agreements for Net metering, Net accounting, Net plusAgreements for Net metering, Net accounting, Net plus
Agreements for Net metering, Net accounting, Net plus
 
Ceylon Electricity Board Statistical Digest 2015
Ceylon Electricity Board Statistical Digest 2015Ceylon Electricity Board Statistical Digest 2015
Ceylon Electricity Board Statistical Digest 2015
 
Toward a Sustainable Energy Future for All
Toward a Sustainable Energy Future for AllToward a Sustainable Energy Future for All
Toward a Sustainable Energy Future for All
 
Value of solar report
Value of solar reportValue of solar report
Value of solar report
 
Utility-Scale Solar Photovoltaic Power Plants - A Project Developer’s Guide
Utility-Scale Solar Photovoltaic Power Plants - A Project Developer’s GuideUtility-Scale Solar Photovoltaic Power Plants - A Project Developer’s Guide
Utility-Scale Solar Photovoltaic Power Plants - A Project Developer’s Guide
 
A renewables-based South African energy system?
A renewables-based South African energy system?A renewables-based South African energy system?
A renewables-based South African energy system?
 
World Energy Resources Report 2016, E-storage: Shifting from cost to value 20...
World Energy Resources Report 2016, E-storage: Shifting from cost to value 20...World Energy Resources Report 2016, E-storage: Shifting from cost to value 20...
World Energy Resources Report 2016, E-storage: Shifting from cost to value 20...
 

Último

result management system report for college project
result management system report for college projectresult management system report for college project
result management system report for college project
Tonystark477637
 
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar ≼🔝 Delhi door step de...
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar  ≼🔝 Delhi door step de...Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar  ≼🔝 Delhi door step de...
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar ≼🔝 Delhi door step de...
9953056974 Low Rate Call Girls In Saket, Delhi NCR
 
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
dollysharma2066
 

Último (20)

UNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular ConduitsUNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular Conduits
 
Unit 1 - Soil Classification and Compaction.pdf
Unit 1 - Soil Classification and Compaction.pdfUnit 1 - Soil Classification and Compaction.pdf
Unit 1 - Soil Classification and Compaction.pdf
 
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdfONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
 
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
 
result management system report for college project
result management system report for college projectresult management system report for college project
result management system report for college project
 
(INDIRA) Call Girl Bhosari Call Now 8617697112 Bhosari Escorts 24x7
(INDIRA) Call Girl Bhosari Call Now 8617697112 Bhosari Escorts 24x7(INDIRA) Call Girl Bhosari Call Now 8617697112 Bhosari Escorts 24x7
(INDIRA) Call Girl Bhosari Call Now 8617697112 Bhosari Escorts 24x7
 
University management System project report..pdf
University management System project report..pdfUniversity management System project report..pdf
University management System project report..pdf
 
Roadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and RoutesRoadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and Routes
 
chapter 5.pptx: drainage and irrigation engineering
chapter 5.pptx: drainage and irrigation engineeringchapter 5.pptx: drainage and irrigation engineering
chapter 5.pptx: drainage and irrigation engineering
 
Thermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - VThermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - V
 
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
 
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar ≼🔝 Delhi door step de...
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar  ≼🔝 Delhi door step de...Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar  ≼🔝 Delhi door step de...
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar ≼🔝 Delhi door step de...
 
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
 
UNIT-IFLUID PROPERTIES & FLOW CHARACTERISTICS
UNIT-IFLUID PROPERTIES & FLOW CHARACTERISTICSUNIT-IFLUID PROPERTIES & FLOW CHARACTERISTICS
UNIT-IFLUID PROPERTIES & FLOW CHARACTERISTICS
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptx
 
data_management_and _data_science_cheat_sheet.pdf
data_management_and _data_science_cheat_sheet.pdfdata_management_and _data_science_cheat_sheet.pdf
data_management_and _data_science_cheat_sheet.pdf
 
PVC VS. FIBERGLASS (FRP) GRAVITY SEWER - UNI BELL
PVC VS. FIBERGLASS (FRP) GRAVITY SEWER - UNI BELLPVC VS. FIBERGLASS (FRP) GRAVITY SEWER - UNI BELL
PVC VS. FIBERGLASS (FRP) GRAVITY SEWER - UNI BELL
 
Extrusion Processes and Their Limitations
Extrusion Processes and Their LimitationsExtrusion Processes and Their Limitations
Extrusion Processes and Their Limitations
 
BSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptx
BSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptxBSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptx
BSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptx
 
Online banking management system project.pdf
Online banking management system project.pdfOnline banking management system project.pdf
Online banking management system project.pdf
 

Machine response

  • 1. Machine Response During System Disturbances (By Sarath Chandrasiri) 1. System Disturbances: A system disturbance can be defined as any event that causes the frequency and/or voltage of the system to deviate from the normal range of operation. These are caused by incidents such as occurrence of short circuits, generator trips, feeder trips, sudden increase of power output of a generator due to a defect in its control system. The responses of the healthy machines for such events should be so as to return the system to the normal status as quickly as possible and with as little manual intervention as possible. Therefore, the response of machines is of utmost importance from the point of view of system security and reliability. Machine response to system disturbances: The response of machines should be considered from two main aspects. 1. Load- frequency response (Governor response) 2. MVAR – Voltage response (AVR response) Only the first will be considered below. 2. Load- frequency response (Governor response) The frequency and load response of a machine that remains connected to the system during the event is shown below: fdev_dyn= Dynamic frequency deviation Δf = Quasi steady state frequency deviation Machine Load t Page 1 f1 fdev_dyn 0 t1 t2 t3 t4 Δf t f B A
  • 2. Fig 1 – Frequency variation of a machine after disturbance The response can be considered to be in 4 stages. i. Initial response ii. Primary response iii. Secondary response iv. Final stage due to manual action or automatic action through a power system controller. These will now be considered in detail. 3. Initial Response (period from t=0 to t=t1 sec) The initial response of the machine lasts between 0.5 to a few seconds depending on the speed of response of the machine governors and the system involved. In the case of the Bahrain system the initial response time duration is between 0.5 and 1 sec. This period occurs immediately after the incident and the response comes due to the kinetic energy of the GT rotor (GT + generator). The governor has not started responding yet. Since any governor, however fast, has a mechanical device (fuel control valve) as the final element, the response will be delayed due to the inertia of the mechanical parts. If the incident is due to a generation loss then the rest of the machines in the system make a contribution to compensate for the short fall. As given before, the governor has no time to respond and the opening of the fuel control valve remains unchanged during this period. Then from where does the energy required for the increased output of the generators come? It comes from the kinetic energy stored in the generator rotors. A contribution also comes from the rotating loads such as induction motors which is produced as a result a decrease in the KE stored in their rotors. The frequency of the system falls linearly during the period as the stored kinetic energy is converted to electrical energy. Telec = Opposing Torque of Generator Mover Tmech = Mechanical Torque of Prime Mover Mover SHAFT of Moment of Inertia I Page 2
  • 3. FIG-2 To analyze the situation consider Fig-2, which gives the torques acting on the Machine shaft. Tnett =Tmech – Telec = I dω/dt where ωis the shaft angular speed in radians/sec. Under normal system conditions, Tnett = 0 as Tmech = Telec. Therefore, ω remains constant and consequently, the kinetic energy of the rotor remains constant. Before analyzing the behavior of the generator after the disturbance, occurs it is useful to consider some basic ideas. For ease of analysis, it is useful to consider the process to be consisting of 2 different periods: 1. Pre fault period (t<0) 2. Post fault period (t>0) The disturbance is considered to occur at the instant t = 0. Certain physical quantities remain constant as the pre-fault stage ends and the post fault stage begins while other quantities undergo an abrupt change (step change) at t=0. Physical quantities that do not undergo any step change at t=0: These are associated with energy. It is a physical principle that the energy of a system cannot be changed abruptly as this would mean that dE/dt (Power) is infinite. Thus the following quantities do not undergo step changes at t=0. a) Kinetic energy of the rotor b) Speed (and hence system frequency) c) The nett magnetic flux in the direct axis of the generator d) Mechanical torque produced by the GT. Physical quantities that undergo a step change at t=0: Some of these are as follows: a) Electrical power output of the generator b) Reverse torque generated by the generator. c) Generator terminal voltage and current Page 3
  • 4. During this period Tnett < 0 as Tmech < Telec. Thus ω decreases linearly as shown below. is negative but constant. Tnett = I dω/dt dω/dt = Tnett/I (a constant) The shaft decelerates from a speed corresponding to the rated frequency of f Hz to one corresponding to f1 Hz. Storage of Kinetic Energy in the Rotor Due to its moment of inertia the rotor stores kinetic energy. KE energy stored in the rotor (EKE) = ½ I ω2 X 10-6 (MJ) The power available from the shaft can be obtained by differentiating the above. Rotor Power (EKE) = I ω . dω/dt X 10-6 MW As shown in the diagram below this power can flow both ways. • When the speed is decreasing the KE is converted to Electrical Power. • When the speed is increasing the Mechanical Power is converted to KE. When the system is considered as a whole the recovery process depends on the Kinetic energy of the Generating sets and the Motors connected as loads. Page 4 FIG-3
  • 5. 4. The H-Constant It is useful to define a quantity called H which is directly proportional to the Moment of Inertia I of the rotor. If the f0 is the rated frequency in Hz (50 Hz) Pn the Rated Load in MW KE0 the Kinetic Energy of the rotor in MWs Then H=( KE0 / Pn) The advantage of using the H constant is that it is essentially independent of the generator size. Typical values of H lie in the range 2 to 8 sec. Initial rate of decrease of frequency = (df/dt)0 = ΔPf0/2H Thus the rate of drop of frequency will increase with decreasing H and increasing ΔP (pu). Therefore, it is advantageous to have a high H. 5. Primary Response (period from t= t1 to t=t3 sec) At the beginning of this period the fuel control valve starts to move, increasing its opening in response to the output signal from the governor (PRIMARY CONTROLLER), which increases in response to the drop in frequency. With the increased flow of fuel, the Mechanical Torque of the GT (Tmech) starts to increase and at point B on the graph in Fig -1 it Tmech becomes equal to Telec . Therefore at this point deceleration of the shaft ceases. The controller continues to increase its output signal and the shaft accelerates back to a speed corresponding to a freq of f2 Hz. However, the controller cannot bring the frequency back to f due to the droop of the control system, which is explained in the next section. During this period the primary controllers alter the power delivered by the generators until a balance is re-established between the load power and the generated power. The period is characterized by oscillatory phenomena due to the dynamic response of the controllers and the process. Dynamic Frequency Deviation (fdev_dyn): The magnitude of this (See Fig-1) depends on the following: • The magnitude of the disturbance Page 5
  • 6. • KE of rotating machines in the system • The primary controller reserve of all generators • Dynamic characteristics of the machines (including controllers) • Dynamic characteristics of the loads, particularly the self regulating effect loads. Quasi Steady State Frequency Deviation (Δf): The magnitude of this (See Fig-1) depends on the following: The magnitude of the disturbance Power – frequency characteristic of the system 6. Secondary Response (period from to t=t3 to t4 sec) During this period, the generator operates at a steady frequency of f2 Hz, which is less than the rated frequency Δf = (f-f2) H z. The magnitude of Δf depends on the Speed Droop of the governor. Speed Droop: The steady state Load vs. frequency characteristic of the governor system has a drooping characteristic, which is built in to achieve stable operation of the generators ting in parallel. FIG-4 The interpretation of the above speed droops is as follows: Page 6
  • 7. If the machine is operating initially at 50% load and a frequency of 50 Hz and a disturbance occurs, which causes a steady state drop of frequency by 0.5 % (0.25 Hz), then the steady state load rise would be, • 10% if the droop was 5% and • 25% if the droop was 2%. In general the droop SG of a generator is defined as follows: Under steady state (secondary response) conditions, Δ PG = The change in load due to Primary Control action PGn = Rated Load Δf = The change in frequency that is necessary for the Primary Controller to produce the above load change f0= Rated frequency Then, SG = (-Δf / f0) / (Δ PG / PGn) in % The – sign takes care of the fact that a negative Δf produces a positive Δ PG and vice versa, provided the Primary Control Reserve has not been completely used up (see below). FIG-5 The contribution of a generator to a system disturbance depends mainly upon • The Droop • The Primary Control Reserve Referring to FIG-5, in case of a minor disturbance (frequency offset < ΔfB ) the contribution of generator a (which has the controller with a smaller droop) will be greater than that of generator b which has the controller with the smaller droop. Page 7 fA fB fN PMAX fN = Rated Freq
  • 8. In case of a major disturbance (frequency offset > ΔfB ), the contributions of both generators to PRIMARY CONTROL under quasi – steady-state conditions will be equal. The operation of the system though stable in terms of frequency and voltage is not acceptable for an extended period as the above parameters would be out of their normal range. It is also undesirable from the point of view of power flow in the tie lines (if there are any) as the actual active and reactive power flows are different from the specified levels. Furthermore, since the system frequency and voltage are lower than rated there is a possibility that those of the system stability will be lost if another disturbance occurs. Due to these reasons it is necessary to restore the frequency and voltage to rated levels as soon as possible. This can be done manually or through a power system controller. In the secondary response period the governor load set points are adjusted by the operators to bring the system frequency back to normal. Final Response: 7. Dead Band: Usually there is a provision in the governor control system to introduce a dead band. The dead band makes the controller insensitive to small band of frequency changes (Ex 0.1 Hz) around the rated frequency. The dead band serves the following purposes: • Immunity to power system noise: If the GT is is only to play a stabilizing role when large frequency deviations occur, the dead band can be switched on to obtain some insensitivity to frequency. The governor would not react to frequency deviations adjustable over a range of ±0.5 Hz from the set point frequency. The dead band functions only when the machine is on load. • In interconnected systems, where a stable system frequency with very narrow tolerances (± 0.05 Hz) and closely defined cross border tie line power between subsystems are required the dead band merely suppresses the power system noise. • Lower thermal loading of the turbine blades: Turbine blades are highly susceptible to temperature gradients. Therefore, the dead band provides a way of suppressing constant changes of turbine inlet temperature to some extent. This prolongs the life of the blades. • Compressor surges: The dead band also has the effect of keeping the operating point away from the point at which the compressor surge protection starts to operate. Page 8
  • 9. Prepared by K. A. Chandrasiri Senior General Engineer Office of the Director of Electricity Production Page 9
  • 10. References: Electrical Energy Systems Theory by Olle L. Elgerd Transient Processes in Electrical Systems by V. Venikov Page 10