Luca Tagliafico - Università di Genova - POMPE DI CALORE ELIO-ASSISTITE
1. LAST DEVELOPMENTS OF SOLAR ASSISTED HEAT PUMPS IN ITALY
Luca A. Tagliafico, F. Valsuani
University of Genoa
DIME / TEC
Division of Thermal engineering and Environmental
Conditioning
Via all’Opera Pia 15/a – 16145 Genoa Italy
Tel. 010 3532880 – fax 010 311870 – e-mail tgl@ditec.unige
INTRODUCTION
Conventional solar heating panels are a well-established technology, still suffering
however of low efficiencies and rather high investment costs when medium temperature
applications (i.e. space heating purposes) are required. The main reason is that the
working temperature in the solar panel is strictky coupled to that of the water inside the
boiler: this means that high efficiency can be reached only for relatively low working
temperatures (not above 50°C) or for very high solar irradiation G values (above
800W/m2
). These conditions are for instance hardly reached in winter, when the majority of
yearly heating supply (electrical or gas) is required, and the mean coefficient of panel
exploitment over the year is quite low.
The use of solar assisted heat pump (SAHP) systems here presented is based on the
concept that the solar panel can work as the cold-side of an inverse cycle operated as a
heat pump, with the hot side devoted to the heating system. The concept is not new [1, 2]
and has the advantage of decoupling the boiler (that is the condenser-side) temperature
from the solar panel (that is the evaporator-side) temperature. However if conventional on-
off technologies are used to drive the compressor of the plant, not so high coefficients of
performance are reached (in the range 2.5-3.5, which is not particularly favourable if
compared to actual air cooled heat pumps) and several difficulties are still present to adapt
refrigeration capacity to the solar heat rate, which is continuosly changing during the day
and with seasonal climate.
Figure 1. Layout of a DX-SAHP (on the left) and operating prototype (on the right, University of
Genoa) DX-SAHP configuration (small device with 1m2 solar panel and 100W VCC
compressor). The panel can be just for hot water applications or can be also an hybrid panel
(refrigerated PVT panel).
2. In recent years direct-expansion solar assisted heat pumps (DX-SAHPs) [3, 4, 5] have
been deeply analysed, both from steady-state and dynamic point of view. Figure 1 shows
the layout and the prototype developed at the beginning of years 2000 at University of
Genoa.
In DX-SAHPs several difficulties in the development of dedicated variable speed
compressors (VCC) and the need of large panel surfaces when turning towards medium
scale (single building instead of single apartment) applications made the indirect SAHP
configuration, usually with a water-to-water heat pump (W-SAHP), more reliable and
promising.
The simplest reference configuration for a thermal solar water heater is shown in Fig.2,
where the main components are evidenced: the solar panel (be it simply a thermal or an
hybrid PVT panel) at temperature Tp, the boiler and water storage at temperature TH, the
refrigeration system (typically a water-water heat pump) and the user. An auxiliary water
heater (electrical or gas-fired, not shown in the figure) must be used to satisfay correctly
the “useful duty” needed for the user. Furthermore a by-pass can be introduced for further
saving energy purposes, when solar and climate conditions are particularly favourable and
allow the SAHP to work as a traditional solar panel.
The panel efficiency ηp is the ratio between the captured mean thermal energy Qp (given
to the working fluid) and the global radiation heat flux incident on the panel, GA (G solar
insulation, W/m2
and A solar panel surface, m2
):
GA
Q
η up
p
⋅
= (1)
As well known ηp is rougthly a linear decreasing function of the temperature difference
Tp-Ta, and increases with solar insulation G. Introducing the non dimensional parameter δ
we have:
G
)T(TK
δ
δ0.790.86η
ap
p
−⋅
=
⋅−=
(2)
where K, in the range 6I10W/(m2
K), is a global thermal conductance between the solar
panel fluid and the ambient temperature.
As already mentioned, while in traditional solar thermal panels Tp=TH, the working fluid
can give useful heat only for Tp>TH, in SAHPs the Tp value can be regulated at any
desiderated value by the refrigeration system, thus increasing significantly the panel
efficiency (as shown by eq.2 when Tp becomes as low as or even lower than Ta).
The new concept operations can be briefly described as follows: a proper refrigeration
fluid is used to keep the solar panel temperature near to the ambient temperature, giving
maximum ηp and giving maximum regulation flexibility to the TH value, which can be easily
Figure 2. Sketch of the usual solar assisted heat pump (W-SAHP with a Water-water heat pump). The
panel can be just for hot water and heating applications or can be also an hybrid panel
(refrigerated PVT panel).
3. adapted to the user (Tu=TH) needs, thanks to the condenser exploitment.
A similar innovation (Figure 1) has been tested for several years at University of Genoa
(DIME), however heat pump performance coefficients of the order of only 2.6 have been
reached due to the very small size of the plant (1kWT). Despite that, the solution offers
several very important advantages, such as the highest solar panel efficiency, longer
working times of the panel, which could be operated continuously from sun rise to sun set.
Furthermore, much lower panel surfaces are necessary for given heating needs, thus
cutting down the installation and surface costs, with benefits also for the visual impact of
the system. A further advantage is the possibility to use this technology coupled to hybrid
panels, enhancing also the photovoltaic conversion efficiency, thanks to the lower mean-
working temperatures of the PV panel during the day.
These advantages are paid for in terms of electrical energy consumption by the
compressor and assume we are able to regulate quite well the given compressor power,
not only in terms of rotating speed, but also in terms of pressare drops in the expansion
valve. Only in recent years such characteristics have been achieved, making similar
solutions to be envisaged also in the small refrigeration plants.
The development of large solar assisted heat pump systems is becoming more and more
interesting for low temperature applications, such as swimming pool water heating. An
interesting pilot plant was designed and built in Sestri Levante, with quite interesting
expected energy savings.
Figure 3. shows the plant layout of the “bare” panels installed on the roof of the swimming
pool building, with more than 400m2
solar panels deployment and a nominal power of
about 150kWT.
The basic design concept of figure 3 is the same as in figure 2, but all the control and
gas-burner integration devices are shown, including by-pass regulation and auxiliary heat
exchangers.
The plant, which is operating from July 2012, is able to cover almost the 60% of the
winter (from November to March) energy needs of the swimming pool location, covering
the 100% of the needs from April to October (just using the by-pass configuration, with
almost zero primary energy consumption). The mean solar panel efficiency is about 85%
Figure 3. Sketch of the solar assisted heat pump (W-SAHP with a Water-water heat pump) installed
and operating since July 2012 at Sestri Levante (Italy) for swimming pool water heating.
4. and mean heat pump efficiency COP=5.5 can be reached.
Since these quite interesting results were obtained just in a quite favourable location, a
detailed efficiency and energy saving analysis was performed for a lot of locations and
different climate conditions, well described by means of the concept of degree day and
monthly mean ambient temperature and radiation data.
The results of this exhaustive research, with calculations performed over all of the
municipalities in Italy, are reported in figure 4. It is quite evident how the potential energy
savings are well correlated to the degree days and offer, even in a mean annual
calculation based on the mean monthly ambient temperature, potential savings up to 50%
in mild climates and well over 35% in much more cool regions. Indeed, keeping in mind
that in cold regions the heating user loads are quite high and that the installation cost of
bare panels is quite low, the expected economic return of W-SAHPs is quite favourable.
Further advantages are expected when hybrid PVT panels are used coupled to W-
SAHPs. Several applications are available now in northern Italy (more the 1000 small
plants) and a medium size plant is now under construction at University of Genoa (Italy) for
the electrical and thermal energy needs of a Sport building application. The PVT panel
layout is shown in Figure 5 together with the PVT panel solution going to be used, and a
summary of the expected performance and operating data is reported in Table 1.
Figure 4. Energy saving index values (PES), referred to the days degrees (DD) of all the 110 Italian
Municipalities (monthly averaged calculations and yearly-based values). Linear regression and
correlation coefficient are evidenced. Only The cities of Trento and Varese show a strong
departure from mean data.
5. Table 1 – Mean Energy data of the PVT W-SAHP plant at University of Genoa
(Italy) – Yearly expected performance (140m2
panel surface, 20 kWEpeak, 45kWT)
Thermal Energy delivered 95772 kWhter
FV electrical Energy produced 23990 kWhel
Heat pump electrical Energy consumption (mean COP=6.6) 14530 kWhel
Net electrical Energy balance 9460 kWhel
Global primary Energy savings (tep/year) (0.067tep/m2
) 9,34
Annual thermal Energy income 7100 €/y
Annual electrical Energy income 2000 €/y
Total yearly money savings 9100€/y
Cost of the installation (integration burner already available) 250.000€
Regione Liguria contribution 199.000 €
REFERENCES
1. Chaturvedi, D., Chen, T., Kheireddine, A., 1998. Thermal performance of a variable
capacity direct expansion solar-assisted heat pump. Energy Conversion and
Management, 30 (3), 181-191.
2. Çomakly, Ö., Bayramoğlu, M., Kaygusuz, K., 1996. A Thermodynamic model of a
solar assisted heat pump system with energy storage. Solar Energy, 56 (6), 485-492.
3. Gorozabel Chata, F.B., Chaturvedi, S.K., Almogbel A., 2005. Analysis of a direct
expansion solar assisted heat pump using different refrigerants. Energy Conversion
Figure 5. Layout (on the left) of a hybrid PVT plant for electrical and thermal energy needs of the
Sports Building Carmine Romanzi at University of Genoa (Italy). Peak electrical power
20kWE, peak thermal power 45kWT. The hybrid panel is shown on the right.
6. and Management, 46, 2614–2624.
4. Qi Qi, Shiming Deng, 2009. Multivariable control of indoor air temperature and
humidity in a direct expansion (DX) air conditioning (A/C) system, Building and
Environment 44 (8),1659-1667.
5. Scarpa, F., Tagliafico, L.A., Tagliafico, G., 2011. Integrated Solar-Assisted Heat
Pumps for water heating coupled to gas burners; control criteria for dynamic
operation, Applied thermal Engineering 31, 59-68.
6. M.A. Cucumo, U. Marinelli, G. Oliveti: Ingegneria solare – Principi ed applicazioni –
Pitagora editrice 1994
7. D.M. 24 Aprile 2001 Individuazione degli obiettivi quantitativi nazionali di incremento
dell’efficienza energetica negli usi finali – Supp. Ord. 125 G.U. 117, 22 Maggio 2001.
8. B.J.Huang, C.P.Lee. Long-term performance of solar-assisted heat pump water
heater, Renewable Energy, vol. 29: 633-639, 2003.