2. OBJETIVO:
El objetivo de esta presentación es mostrar la
configuración, funcionamiento y características del panel
de control cp – i v.
3. INTRODUCCIÓN:
EL PANEL DE CONTROL MYPRO CP-IV PROVEE UN CONTROL AUTOMÁTICO Y DE
MONITOREO, TANTO PARA LOS DIFERENTES MODELOS DE COMPRESOR
TORNILLO COMO PARA DIFERENTES APLICACIONES QUE IMPLIQUEN
CONDENSADORES, ENFRIADORES, ETC.
EL CPU (UNIDAD CENTRAL DE PROCESAMIENTO) REALIZA TODOS LOS
CALCULOS REQUERIDOS, PARA ARRANCAR UN COMPRESOR CON DATOS
CARGADOS EN UN MODULO DE MEMORIA RAM RESPALDADO POR UNA PILA DE
LITIO ESTANDAR.
EL PANEL DE CONTROL DE LA SERIE CP-IV PUEDE OPERAR SOLO Ó PUEDE
CONECTARSE A OTRO CONTROLADOR DE LA SERIE CP-IV PARA FORMAR UNA
RED INTEGRADA.
EL PANEL DE CONTROL DE LA SERIE CP-IV TAMBIÉN PUEDE ENLAZARSE CON
CONTROLADORES LÓGICOS PROGRAMABLES (PLC´S) POR MEDIO DE
COMUNICACIÓN MODBUS.
4. CARACTERÍTICAS:
Pantalla de cristal líquido a color (LCD) capaz de
desplegar 80 digitos alpha-numericos por 30 renglones.
Teclas númericas + Teclas de función+ Teclas de
operación (Para un Total de 33 teclas).
Tarjetas de entradas y salidas digitales de 16 puntos con
contactos secos y relevadores de estado sólido para
salidas de voltaje.
Tarjetas de entradas analógicas de 16 puntos para
señales de 4~20mA, DC 1~5V, or 1kΩ para potenciometro.
5. CARACTERÍTICAS:
Un puerto de comunicación serie RS-232C.
Un puerto de comunicación RS-485 compatible para
comunicación Modbus.
23. AL ENERGIZAR EL PANEL DE CONTROL MYPRO CP-IV, SE DESPLEGARÁ LA SIGUIENTE
PANTALLA Y POSTERIORMENTE SE MOSTRARÁ LA PANTALLA GENERAL DEL
COMPRESOR.
24. PANTALLA GENERAL DEL COMPRESOR DONDE SE MUESTRAN LAS VARIABLES DEL
MISMO.
Titulo
Precaución
Fecha
Bat. baja
Lecturas
De compresor
Alarma
Funciones
Hodómetros
25. SI AL ESTAR EN LA PANTALLA ANTERIOR SE OPRIME LA TECLA [TAB] SE DESPLEGARÁ
LA SIGUIENTE PANTALLA QUE MUESTRA ADEMÁS DE LAS LECTURAS DEL
COMPRESOR, EL ESTADO Y MODO DE OPERACIÓN, ASÍ COMO LAS PROTECCIONES.
Titulo
Precaución
Fecha
Bat. baja
Lecturas
De compresor
Control de
capacidad
Modo de
operación
Alarma
Funciones
Comunicación
26. F1 F2 F3 F4 F5 F6 F7
SETPOINTS CONTROLLER LIMITS LOGS ADJUSTMENT SETUP DIAGNOSTIC
Los menús son accesados con la tecla de función azul localizada
Arriba de la barra de menú
Barra de menú
Teclas de función
28. Configuración ESPECIAL
SI SE REQUIERE CAMBIAR LA CONFIGURACIÓN DE LA CAJA MYPRO SE OPRIMEN EL
CONJUNTO DE TECLAS [SHIFT] + [ALT] + [DELETE] PARA ENTRAR AL MODO DE
CONFIGURACIÓN, AL ENTRAR SE REPITE EL CONJUNTO DE TECLAS ANTES DE QUE
TERMINE EL CONTEO MOSTRADO EN LA SIGUIENTE PANTALLA:
29. ANTES DE ENTRAR AL MODO DE CONFIGURACIÓN SE NOS SOLICITARÁ INICIALIZAR
LAS FUNCIONES DE LA CONFIGURACIÓN, ESTO SE HACE OPRIMIENDO LA TECLA DEL
NÚMERO INDICADO. NORMALMENTE SE OPRIME LA TECLA [ESC].
30. CUANDO EL EQUIPO SE ENCUENTRA EN MODO CONFIGURACIÓN SE DESPLIEGA EL
MENSAJE EN LA PARTE INFERIOR DE “CONTROL PROGRAM HAS BEEN STOPPED BY
SPECIAL BOOT” COMO SE MUESTRA EN LA SIGUIENTE FIGURA:
31. [Método de opción múltiple]
Los espacios en blanco, como los de arriba, son
las áreas de opción múltiple.
1. Mueva el cursor con la tecla [TAB] hacia la
ventana que incluye el ítem deseado.
2. Mueva el cursor con las teclas de flecha
hacia el ítem deseado.
3. Presione [ENTER] para desplegar una
lista.
4. Seleccione un ítem de la lista con la tecla
de flecha.
5. Presione [ENTER] para establecer como
configuración.
(Las letras aparecerán en blanco.)
(Las letras aparecerán en rojo.)
(El cursor se desplazará al siguiente ítem.)
6. Presione [SAVE] para guardar la
configuración.
CONFIGURACION
32. 1. OPERATION MODE
2.D/O TEST OPERATION
3.SETPOINTS
4.SCHEDULER
5.OTHER SETPOINTS
6.AUTO-Vi
7.AUTO-STAGE
SYSTEM START
SYSTEM START DELAY [5] SEG
MISCELANEUS
CUT-IN DELAY [30] SEG
CUT-OUT DELAY [60] SEG
CUT-OUT LSV% [05] %
OIL P. START DELAY [00] SEG
COMP. START DELAY [15] SEG
COMP. RE-START DELAY [30] SEG
OIL FEED OFF DELAY [10] SEG
PUMP OUT
CAPACITY 0% STOP NO
MINIMUM DELAY [0] SEG
MAXIMUN DELAY [1] SEG
PUMP OUT PRESS [1.02] kgf
LSV% [100.0]%
STOP LSV% [ 10.0]%
SET POINTS
COMM SETPT#1 SETPT#2 SETPT#3 SETPT#4
CUT-IN SETPOINT [3.01] kgf [2.8] kgf [2.8] kgf [2.8] kgf [2.8] kgf
CONTROL PRESS. [2.01] kgf [1.9] kgf [1.9] kgf [1.9] kgf [1.9] kgf
CUT-OUT SETPOINT [1.01] kgf [0.9] kgf [0.9] kgf [0.9] kgf [0.9] kgf
3.
SET POINTS
33. 1. OPERATION MODE
2.D/O TEST OPERATION
3.SETPOINTS
4.SCHEDULER
5.OTHER SETPOINTS
6.AUTO-Vi
7.AUTO-STAGE
5.
ANTI CYCLE OIL HEATER
ANTI CYCLE TIME [900] SEG HEATER ON OS [25.0]º C
INTERVAL TIME [900] SEG HEATER OFF OS [30.0]º C
OIL DRAIN SV
SV OFF DELAY [60] SEG
OTHER SET POINTS
34. CAPACITY CONTROL
1. CAPACITY CONTROL
2. VDF COMPRESSOR CONTROL
3. HIGH STAGE CAPACITY CONTROL
4. EXPANSION VALVE (SH) CONTROL
5. EXPANSION VALVE (SP) CONTROL
6. EXPANSION VALVE (LB) CONTROL
7. ECONOMIZER
8. LIQUID INYECTION OIL COOLING
CAPACITY CONTROL (MONITOR)
CONTROL TARGET 2.00 kgf
CONTROL SETPOINT [1.9] kgf
PID OUT (MV)% 90.10%
L. SLIDE VALVE 100.00%
OPERATION AUTO
[MANUAL LOAD] [MANUAL UNLOAD]
CAPACITY CONTROLS (SETPOINTS)
PROPORTIONAL BAND [ 10.0] kgf
INTEGARL TIME [ 8] SEC
DERIVATIVE TIME [ 0] SEC
MANUAL RESET [ 50.0] %
d MV LIMIT [ 5] %/SEC
HI MA UNLOAD [300] A CAPACITY RAMP CONTROL
HI MA UNLOAD FORBID [290] A MVL % [ 0.0] %
HI DP UNLOAD [ 13.5] kgf STEP-1 [ 15] SEC [ 12.5] %
HI DP UNLOAD FORBID [ 13.2] kgf STEP-2 [ 15] SEC [ 25.0] %
STEP-3 [ 15] SEC [ 37.5] %
STEP-4 [ 15] SEC [ 50.0] %
HI SP UNLOAD [ 1.6] kgf STEP-5 [ 15] SEC [ 62.5] %
HI SP UNLOAD FORBID [ 1.8] kgf STEP-6 [ 15] SEC [ 75.0] %
STEP-7 [ 15] SEC [ 87.5] %
CONTROL START DELAY [ 10] SEC STEP-8 [ 15] SEC [ 100.0] %
MV(LSV) DEAD BAND [ 2.0] %
FORCE FULL LOAD [ 2.0] %/SEC REMOTE MVH % [ 100.0] %
MVL%/MVH% BY COM DISABLE
35. ALARM / FAIRULE & OEM LIMITS
ALARM FAIRULE OEM LIMITS
LOW SP [ 0.80] kgf [ 0.70] kgf [ -1.00] kgf
ALARM DELAY [ 5] SEC [ 1] SEC
MASK TIME [ 1] MIN
HIGH DP [ 14.0] kgf [ 14.5] kgf [ 15.0] kgf
LOW OP [ 1.0] kgf [ 0.8] kgf [ 0.5] kgf
HIGH OF [ 1.4] kgf [ 1.4] kgf
ALARM DELAY [ 15] SEC
HIGH MA [ 305] A [ 310] A [ 325] A
HIGH DT [ 95.0] ºC [ 97.0] ºC [ 97.0] ºC
HIGH OT [ 65.0] ºC [ 68.0] ºC [ 68.0] ºC
LOW SSH [ 4.0] ºC
RE-START / TIME OUT [ 60] SEC
LOW d P [ 0.3] kgf [ 0.3] kgf [ 0.3] kgf
MASK TIME [ 600] SEC
LOW OS [ 10.0] ºC [ 10.0] ºC
ALARM FAIRULES
36. TREND LOG
1. TREND LOG
2. ALARM LOG
3. EVENT LOG
4. DEVICE COUNTER MONITOR
5. DEVICE COUNTER SET
TREND LOG
[<] [>] AI 1 AI 2 AI 3 AI 4 AI 5 AI 6 AI 7 AI 8
[^] SP DP OP AFP ST DT OT OS
NO. 1430:THU.08/08/2006 16:19:00 2.11 11.8 14.6 10.8 4.4 77.4 47.9 78.1
[ ]
1.
CANAL
LECTURA
DDD.MM/DD/YYYY
HORA
37. ALARM LOG
1. TREND LOG
2. ALARM LOG
3. EVENT LOG
4. DEVICE COUNTER MONITOR
5. DEVICE COUNTER SET
2.
ALARMA Ó FALLA
DDD.MM/DD/YYYY
HORA
ALARM LOG
[^]
No. 24:THU.08/08/2006 13:39 CAPACITY NO DOWN ALARM
[ ]
39. DEVICE COUNTER MONITOR
DEVICE COUNTER SET
1. TREND LOG
2. ALARM LOG
3. EVENT LOG
4. DEVICE COUNTER MONITOR
5. DEVICE COUNTER SET
4.
COUNTER (MONITOR)
COMPRESOR START / STOP) [ 3] HOURS
COMPRESOR RUN TIME [ 10]
COUNTER (SET)
COMPRESOR START / STOP) [ 3] HOURS
COMPRESOR RUN TIME [ 10]
5.
40. SET TIME
2.
1. SLIDE VALVE SETUP
2. SET TIME
3. PASSWORD
4. ANALOG INPUT ADJUSTMENT
5. ANALOG OUTPUT ADJUSTMENT
6. ANALOG OUTPUT ASSIGNMENT
7. AUXILIARY INPUT TIMER
8. COMMUNICATION SETUP
SET TIME
30SEC [ ADJUST ]
WEEK THURSDAY
MONTH [ 8 ]
DAY [ 3 ]
YEAR [ 2006 ]
HOUR [ 16 ]
MINUTE [ 47 ]
SECOND [ 47 ]
DISPLAY TIMER
CLOSE MENU [ 8 ] MIN
BACK LIGHT OFF [ 10 ] MIN
PASSWORD LIFE [ 30 ] MIN
OTHER TIME
TREND LOG [ 60 ] SEC
41. PASSWORD
3.
1. SLIDE VALVE SETUP
2. SET TIME
3. PASSWORD
4. ANALOG INPUT ADJUSTMENT
5. ANALOG OUTPUT ADJUSTMENT
6. ANALOG OUTPUT ASSIGNMENT
7. AUXILIARY INPUT TIMER
8. COMMUNICATION SETUP
PASSWORD
OLD NEW
LEVEL-1 PASSWORD [ X] [ X]
LEVEL-2 PASSWORD [ X] [ X]
LEVEL-3 PASSWORD [ X] [ X]
42. ANALOG INPUT ADJUSTMENT
4.
1. SLIDE VALVE SETUP
2. SET TIME
3. PASSWORD
4. ANALOG INPUT ADJUSTMENT
5. ANALOG OUTPUT ADJUSTMENT
6. ANALOG OUTPUT ASSIGNMENT
7. AUXILIARY INPUT TIMER
8. COMMUNICATION SETUP
ANALOG INPUT ADJUSTMENT
OFFSET FILTER PROCESS
CH. DESCRIPTION LOW HIGH COEFICIENT VALUE
1.SUCCTION PRESSURE [ 0.0]: [ 0.0] kgf [ 0.60 ] 0.0 kgf
2.DISCHARGE PRESSURE [ 0.0]: [ 0.0] kgf [ 0.60 ] 0.0 kgf
3.OIL SUPPLY PRESSURE [ 0.0]: [ 0.0] kgf [ 0.60 ] 0.0 kgf
4.AFTER FILTER PRESSURE [ 0.0]: [ 0.0] kgf [ 0.60 ] 0.0 kgf
5.SUCCTION TEMPERATURE [ 0.0]: [ 0.0] º C [ 0.60 ] 0.0 º C
6.DISCHARGE TEMPERATURE [ 0.0]: [ 0.0] º C [ 0.60 ] 0.0 º C
7.OIL SUPPLY TEMPERATURE [ 0.0]: [ 0.0] º C [ 0.60 ] 0.0 º C
8.OIL SEPARETER TEMPERATURE [ 0.0]: [ 0.0] º C [ 0.60 ] 0.0 º C
9.INVALID [ 0.0]: [ 0.0] [ 0.60 ] 0
10.INVALID [ 0.0]: [ 0.0] [ 0.60 ] 0
11.INVALID [ 0.0]: [ 0.0] [ 0.60 ] 0
12.COMPRESOR CURRENT MOTOR [ 0.0]: [ 0.0] A [ 0.60 ] 0.0 A
13.INVALID [ 0.0]: [ 0.0] [ 0.60 ] 0
14.INVALID [ 0.0]: [ 0.0] [ 0.60 ] 0
15.LOW STAGE SLIDE VALVE POSITION [ 0.0]: [ 0.0] % [ 0.60 ] 0.00%
16.INVALID [ 0.0]: [ 0.0] [ 0.60 ] 0
CHANNEL SELECT [0 - 15]
43. COMMUNICATION SETUP
8.
1. SLIDE VALVE SETUP
2. SET TIME
3. PASSWORD
4. ANALOG INPUT ADJUSTMENT
5. ANALOG OUTPUT ADJUSTMENT
6. ANALOG OUTPUT ASSIGNMENT
7. AUXILIARY INPUT TIMER
8. COMMUNICATION SETUP
COM1 SETUP
COMMUNICATION RUN
ADDRESS [ 3]
RATE [9600]bps
FORMAT C8 PN S1
PROTOCOL Mod Bus RTU
RESPONCE [ 0] x 10MSEC
44. SHOW DIGITAL I/O STAUS
1. SHOW SYSTEM SET UP
2. SHOW ANALOG INPUT SCALING
3. SHOW OPTIONAL ANALOG INPUT
4. SHOW DIGITAL I / O STATUS
5. SHOW OPTION SETUP 1/2
6. SHOW OPTION SETUP 2/2
7. SHOW PROGRAM VERSION
8. READ REGISTER
9. READ BIT
0. READ TIMER/COUNTER
DIGITAL I/O STATUS
COMP OILP LOAD UNLD Y04 Y05 OILH Y07
Y08 FAIL EMGC RDBK ITL1 ITL2 ITL3 RMTR
4.
SALIDAS
ENTRADAS
45. [Método de ingreso de número]
Los espacios comprendidos entre [ ], como los de arriba, son áreas
para ingresar números.
1. Mueva el cursor con la tecla [TAB] hacia la ventana que incluye
el ítem deseado.
2. Mueva el cursor con las teclas de flecha hacia el ítem deseado.
3. Ingrese un valor usando las teclas numéricas.
Use la tecla del signo menos [-] antes del valor para cambiar psi a
“hg.
4. Presione [ENTER] para establecer como configuración.
(El valor o los valores aparecerán en rojo.)
(El cursor se desplazará al siguiente ítem.)
5. Presione [SAVE] para guardar la configuración.
(El valor o los valores aparecerán en blanco.)